DC Values and Circuit Diagrams For 3VA1 Molded Case Circuit Breaker
DC Values and Circuit Diagrams For 3VA1 Molded Case Circuit Breaker
DC Values and Circuit Diagrams For 3VA1 Molded Case Circuit Breaker
circuit breaker
DC values and circuit diagrams for 3VA1 molded
case circuit breaker
DC single-pole Hints:
3VA10 3VA11 3VA12 3VA13 3VA14 3VA15 DC all-pole disconnection
disconnection
Applies to molded case circuit
100 A 160 A 250 A 400 A 630 A 1,000 A
grounded *) grounded *) isolated breakers and load break switches in
(16 - 100 A) (16 - 160 A) (160 - 250 A) (320 - 400 A) (500 - 630 A) (630 – 1,000 A) line protection applications, if
protected by a appropriated overload
DC breaking capacity acc. IEC 60947 ICU = ICS in kA
protection device.
B N S N S M H S M H S M H C S M H C M H C
In an ungrounded/isolated system,
always all poles must be switched off.
125 V 125 V 125 V 125 V 125 V 250 V The grounded pole must always be
assigned to the individual current
path so that in case of an ground
16 25 30 16 25 30 30 55 85 100 8 16 25 25 8 16 25 25 35 50 100 fault at least...
- 2 contacts within a 3-pole breaker
or
250 V 250 V 250 V 250 V 250 V 500 V
- 3 contacts within a 4-pole breaker
…in series can take over the
25 36 55 36 55 85 100 55 85 100 8 16 25 25 8 16 25 25 35 50 100 interruption
750 V
8 16 25 16 25 36 55 25 36 55 8 16 25 25 8 16 25 25 25 35 50