DC Values and Circuit Diagrams For 3VA1 Molded Case Circuit Breaker

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

3VA molded case

circuit breaker
DC values and circuit diagrams for 3VA1 molded
case circuit breaker

Unrestricted | © Siemens 2020 | 2020-10-23


3VA1 molded case circuit breaker
Breaking capacity classes DC

DC single-pole Hints:
3VA10 3VA11 3VA12 3VA13 3VA14 3VA15 DC all-pole disconnection
disconnection
Applies to molded case circuit
100 A 160 A 250 A 400 A 630 A 1,000 A
grounded *) grounded *) isolated breakers and load break switches in
(16 - 100 A) (16 - 160 A) (160 - 250 A) (320 - 400 A) (500 - 630 A) (630 – 1,000 A) line protection applications, if
protected by a appropriated overload
DC breaking capacity acc. IEC 60947 ICU = ICS in kA
protection device.
B N S N S M H S M H S M H C S M H C M H C
In an ungrounded/isolated system,
always all poles must be switched off.
125 V 125 V 125 V 125 V 125 V 250 V The grounded pole must always be
assigned to the individual current
path so that in case of an ground
16 25 30 16 25 30 30 55 85 100 8 16 25 25 8 16 25 25 35 50 100 fault at least...
- 2 contacts within a 3-pole breaker
or
250 V 250 V 250 V 250 V 250 V 500 V
- 3 contacts within a 4-pole breaker
…in series can take over the
25 36 55 36 55 85 100 55 85 100 8 16 25 25 8 16 25 25 35 50 100 interruption

Circuit breaker suitable for pollution


degree 3.
500 V 500 V 500 V 500 V 500 V 750 V
From 800 V pollution degree 2.

Further wirings are available on


25 36 55 36 55 85 100 55 85 100 8 16 25 25 8 16 25 25 35 50 100 request.

750 V

600 V 600 V 600 V 600 V 600 V 35 50 100 GF = ground fault monitoring


- *) Minus pole grounded
1,000 V**) **) only for In = 630 A / 800 A

8 16 25 16 25 36 55 25 36 55 8 16 25 25 8 16 25 25 25 35 50

Page 2 Unrestricted | © Siemens 2020 | 2020-10-23