Enatel DC System Manual

System Installation Manual


Version 1.2

Model: FLEXICOMPACT 1 to 3 DC Power System

ENTER

OK

energyMANAGER

L1 L2 L3 N

100
1
100
1
100
1
100
1
C32 C32 C32 C32 C32 C32 C32 C32 C32 C32 C32 C32
ACSu rge Prote ctor ACSu rge Prote ctor N C32 C32 C32
PE
2 3 0 /4 0 0 V
DS2 40S -23 0 DS2 40S -23 0
2 2 3 0 /4 0 0 V 2 2 3 0 /4 0 0 V 2 2 3 0 /4 0 0 V 2 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V
IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 Uc 40 0V Uc 40 0V IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2
G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2
6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A In 2 0k A In 2 0k A 6 0 0 0A 6 0 0 0A 6 0 0 0A

Im ax 4 0kA Im ax 4 0kA
Up 2 kV Up 2 kV

T2 C T2 C
CIT EL CIT EL

RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE
2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C

Rectifier Module Rectifier Module Rectifier Module Rectifier Module

RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE
2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C

Rectifier Module Rectifier Module Rectifier Module Rectifier Module

RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE
2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C

Rectifier Module Rectifier Module Rectifier Module Rectifier Module


Warranty
Enatel provides a one year limited warranty, details as stated under the manual section Appendix IV Enatel
Energy Standard Limited Warranty Policy.

System Compliance

Low Voltage Directive (LVD) 2014/35/EU


Electromagnetic Compatibility Directive (EMC) 2014/30/EU
For compliance certifications of individual modules please refer to the relevant manuals.

Copyright © Enatel 2021


All rights reserved.
Release Date: 7 July 2021
Disclaimer: The information in this document may be changed without notice.
Enatel Energy® is a registered trademark of Enatel. All other trademarks are acknowledged as belonging to their respective owners.

Enatel, 66 Treffers Road, Christchurch 8042, New Zealand


Ph: +64 3 366 4550 | Fax: +64 3 366 0884 | Email: sales@enatel.net | http://www.enatel.net
Table of Contents
1 Safety .......................................................................................................................................................... 6
2 Scope .......................................................................................................................................................... 6
3 System Overview ........................................................................................................................................ 6
3.1 Power System ..................................................................................................................................... 7
3.1.1 Standard Features ...................................................................................................................... 7
3.1.2 Current Capacities ...................................................................................................................... 8
3.1.3 Optional Features ....................................................................................................................... 8
3.1.4 Physical Dimensions and Weights .............................................................................................. 8
3.2 Energy Manager ................................................................................................................................. 9
3.3 Rectifier Modules ............................................................................................................................... 9
4 Receiving Instructions............................................................................................................................... 10
4.1 Package Inspection ........................................................................................................................... 10
4.2 Equipment Inspection ...................................................................................................................... 10
4.3 Handling............................................................................................................................................ 11
5 Installation ................................................................................................................................................ 11
5.1 Suitable Racks ................................................................................................................................... 11
5.2 Unpacking ......................................................................................................................................... 11
5.3 Identification Labels ......................................................................................................................... 11
5.4 Installing the flexiCOMPACT System ................................................................................................ 11
STEP 1: Mount the system in the cabinet or rack as appropriate. ................................................ 11
STEP 2: Connect the AC supply...................................................................................................... 11
STEP 3: Mount the AC terminal cover ........................................................................................... 12
STEP 4: Connect the Load .............................................................................................................. 14
STEP 5: Connect the Batteries ....................................................................................................... 15
5.5 Ventilation ........................................................................................................................................ 15
5.6 Supervisory Monitor & IO PCB Alarm Output Configuration ........................................................... 16
5.6.1 SM36 Main PCB Alarm Mappings ............................................................................................. 16
5.6.3 Circuit Breaker Fail Monitoring ................................................................................................ 17
Battery Breaker Monitoring .................................................................................................................. 17
Load Breaker Monitoring....................................................................................................................... 17
5.7 LVD Operation .................................................................................................................................. 18
6 Configuration Utility Software.................................................................................................................. 18
7 ENATEL SYSTEM COMMISSIONING .......................................................................................................... 18
7.1 Essential Field System Set-Up Parameters ....................................................................................... 19
7.1.1 Check/Set Float Voltage ........................................................................................................... 19
7.1.2 Set Battery Temperature Compensation ................................................................................. 19
7.1.3 Set Battery Capacity ................................................................................................................. 20
7.1.4 Set Battery Current Limit .......................................................................................................... 20
7.1.5 Low Voltage Disconnect Settings ............................................................................................. 21

Enatel DC System Manual Page 3 of 4


Model: FLEXICOMPACT 1 to 3 Version 1.2
7.2 Rectifier & Battery Start Up .............................................................................................................. 22
7.2.1 Rectifier Start-up ...................................................................................................................... 22
7.2.2 Battery Start-up ........................................................................................................................ 22
7.3 Load Start-up .................................................................................................................................... 23
7.4 SM36 Digital Inputs .......................................................................................................................... 23
8 DC System Lead Acid Battery Commissioning Check-List ......................................................................... 24
9 PERIODIC MAINTENANCE ROUTINES ....................................................................................................... 28
9.1 System .............................................................................................................................................. 28
9.2 Energy Manager ............................................................................................................................... 28
9.3 Rectifiers ........................................................................................................................................... 28
9.4 Ventilation ........................................................................................................................................ 28
10 Trouble-shooting and Servicing ................................................................................................................ 28
10.1 Rectifiers ........................................................................................................................................... 28
10.2 Servicing............................................................................................................................................ 28
Appendix I System Software ............................................................................................................... 29
I.A Configuration Utility Software.......................................................................................................... 29
I.A.i Installing the Configuration Utility Software ............................................................................ 29
I.A.ii Connecting to the System via USB............................................................................................ 30
I.A.iii Connecting to the System Remotely ........................................................................................ 31
I.A.iv Access Levels ............................................................................................................................ 31
I.B Using the SM3x Web Interface ......................................................................................................... 33
Appendix II Software Upgrading .......................................................................................................... 34
II.A Upgrading the Configuration Utility Software.................................................................................. 34
II.B Upgrading the SM3x Variables File................................................................................................... 34
II.B.i Installation of a .sm3x Variables File ........................................................................................ 34
Appendix III AC Input Transient Protection .......................................................................................... 35
III.A Upstream Over-Current Protection .................................................................................................. 36
III.B Cable Rating ...................................................................................................................................... 37
III.C Discrimination................................................................................................................................... 37
III.D Surge Suppression Device Protection............................................................................................... 37
III.E AC cable installation and surge protection ...................................................................................... 37
Appendix IV Enatel Energy Standard Limited Warranty Policy ............................................................. 38
IV.A Warranty Exclusions and Restrictions .............................................................................................. 38
IV.B Battery Warranty .............................................................................................................................. 38
IV.C Initiating a Warranty Claim............................................................................................................... 39
IV.D Disclaimer ......................................................................................................................................... 39
IV.E Remark.............................................................................................................................................. 39
Appendix V Wiring Schematics ............................................................................................................ 40
TABLE OF F IGURES
Figure 1: FLEXI3 (fully optioned)......................................................................................................................... 7
Figure 2: AC Termination .................................................................................................................................. 12
Figure 3: AC Earth Termination ........................................................................................................................ 12
Figure 4: Mount the AC terminal cover ............................................................................................................ 13

Enatel DC System Manual Page 4 of 5


Model: FLEXICOMPACT 1 to 3 Version 1.2
Figure 5: Lower the AC terminal cover ............................................................................................................. 13
Figure 6: Lock the AC terminal cover................................................................................................................ 14
Figure 7: Load Connections .............................................................................................................................. 15
Figure 8: Battery Connections .......................................................................................................................... 15
Figure 9: SM36 Relay Outputs .......................................................................................................................... 16
LIST OF TABLES
Table 1: flexiCOMPACT dimensions and weights ............................................................................................... 8
Table 2: Main PCB Relay Alarm Assignments ................................................................................................... 17

Enatel DC System Manual Page 5 of 6


Model: FLEXICOMPACT 1 to 3 Version 1.2
1 SAFETY

All installation and maintenance must be carried out by suitably qualified


personnel.

For your protection, the product manual should be read and thoroughly
understood before unpacking, installing and using the equipment.

The system contains static sensitive components that installation or removal of


requires careful handling and the proper precautions to be taken, such as
wearing grounding straps.

The equipment is intended only for use in a restricted access area. This
equipment is not suitable for use in locations where children are likely to be
present.

2 SCOPE
This manual covers essential information for the installing and commissioning of the Enatel DC System
flexiCOMPACT 1 to 3 where the significant difference between the systems is the number of rectifier shelves.

3 SYSTEM OVERVIEW
The flexi compact range is designed to allow a customised DC power solution with all of the benefits of a
standard “off the shelf” system.
The system is intended to be a complete power system in a box with no connections needed to be made
internally. The system is designed to be extremely simple to install and set up.
All the AC and DC connections are made from the front of the unit. Alarm connections are also accessible
from the front by opening the hinged front cover.
By adding smart distribution modules, the system can be customised to suit most requirements whilst
maintaining a robust and smart user experience.
NOTE: the system is supplied with the AC and DC earths connected. The standard system output has the DC
Common in the positive side of the circuit (+ve earth system).

Enatel DC System Manual Page 6 of 7


Model: FLEXICOMPACT 1 to 3 Version 1.2
ENTER

OK

energyMANAGER

8x M8, 16x M6 PEMs for Load & Battery Common Terminals

L1 L2 L3 N

100
1
100
1
100
1
100
1
C32 C32 C32 C32 C32 C32 C32 C32 C32 C32 C32 C32
ACSu rge Prote ctor ACSu rge Prote ctor N C32 C32 C32
PE
2 3 0 /4 0 0 V
DS2 40S -23 0 DS2 40S -23 0
2 2 3 0 /4 0 0 V 2 2 3 0 /4 0 0 V 2 2 3 0 /4 0 0 V 2 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V 2 3 0 /4 0 0 V
IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2 Uc 40 0V Uc 40 0V IEC 60 9 4 7-2 IEC 60 9 4 7-2 IEC 60 9 4 7-2
G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2 G B1 4 04 8 .2
6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A 6 0 0 0A In 2 0k A In 2 0k A 6 0 0 0A 6 0 0 0A 6 0 0 0A

Im ax 4 0kA Im ax 4 0kA
Up 2 kV Up 2 kV

T2 C T2 C
CIT EL CIT EL

4x Battery Breakers 12x Load Breakers AC Input Breakers


Surge Diverters

RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE
2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C

Rectifier Module Rectifier Module Rectifier Module Rectifier Module

RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE
2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C

Rectifier Module Rectifier Module Rectifier Module Rectifier Module

RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE RM 2 0 4 8 HE
2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C 2 .0 kW 4 8 V D C

Rectifier Module Rectifier Module Rectifier Module Rectifier Module

Figure 1: FLEXI3 (fully optioned)

3.1 Power System


3.1.1 Standard Features
The base unit is supplied with the following standard options:
• AC Input:
◦ Single Phase:
 Ph-Ph 220V
 Ph-N 220V
◦ Three Phase:
 Y 3Ph+N
 Ph-N 220V
 Ph-Ph 380-400V
 ∆ 3Ph Ph-Ph 220V
• DC Output: Nominal voltage: 48V DC (contact Enatel for other voltage options)
• SM36 supervisory module (fully integrated in the system) with Network card NT2
• Battery Low Voltage Disconnect (300A, 500A and 800A rating)
• CTO (configurable to order) Options:
◦ AC input MCB with surge protection device, type 2
◦ 2 or 4 x DIN style 27mm battery MCBs
◦ Max of 15 x DIN style 18mm load MCBs (max 12 when fitted with 4 battery breakers)

Enatel DC System Manual Page 7 of 8


Model: FLEXICOMPACT 1 to 3 Version 1.2
◦ Low voltage battery disconnect (LVBD) and low voltage load disconnect (LVLD) options
3.1.2 Current Capacities
• flexi1 system capacity is up to 240A with a maximum of 4x RM3048HE power modules
• flexi2 system capacity is up to 480A with a maximum of 8x RM3048HE power modules
• flexi3 system capacity is up to 720A with a maximum of 12x RM3048HE power modules
3.1.3 Optional Features
Additional options that can be specified at the time of order:
• AC input MCB with surge protection device, type 2
• 2 or 4 x DIN style 27mm battery MCBs
• Max. of 15 x DIN style 18mm load MCBs (max. 12 when fitted with 4 battery breakers).
• 300A or 500A load low voltage disconnect for Non-Priority Load
• I/O board
• AC monitoring including voltage, frequency and current
• Fan control
• Battery control monitoring
• Battery fuse fail
• Site monitoring
• Additional I/O support
NOTE: additional options can be added at a later date but installation outside of the factory is beyond the
contents of this manual. Please consult your sales representative for more details
3.1.4 Physical Dimensions and Weights
Table 1: flexiCOMPACT dimensions and weights
Model flexi 1 flexi 2 flexi 3
Depth (Total) 380mm 380mm 380mm
Width (Total) 483mm (19” mount) 483mm (19” mount) 483mm (19” mount)
Height 178mm (4U) 222mm (5U) 267mm (6U)
Weight without rectifiers 18.3kg* 20.5kg* 22.7kg*
Weight with max. rectifiers 23.5kg* 30.9kg* 38.3kg*
* Maximum weights are indicated approximated based all possible configuration options included, subject to
change.

Enatel DC System Manual Page 8 of 9


Model: FLEXICOMPACT 1 to 3 Version 1.2
3.2 Energy Manager
For full SM3x functionality and operation information of the Energy Manager, refer to the SM35/36 Manual.
3.2.1 Energy Manager Screen and Buttons
LCD Screen Status LEDs Menu Buttons

USB Connector

The controller includes:


1. A large backlit LCD screen which displays the system parameters and warnings.
2. Three Alarm LEDs on the front panel which indicate system operational status –
Red LED Urgent alarm state.
Yellow LED Non-Urgent alarm.
Green LED DC power is connected to the unit; monitor is functioning.
Note: The LED mapping can be user modified.
3. Menu tactile buttons to navigate through the controller menu. Local adjustments to operating
parameters and alarm functions can be made using the menu options.
4. USB Connector: A PC or laptop is connected via USB to the controller (the cable required is USB–mini
USB: not supplied with power system). Control parameters are set using a configuration firmware
file loaded through this interface. The system is supplied preconfigured with a default configuration
file. A backup of this file is included on the supplied CD.

3.3 Rectifier Modules


Fan Cooled

Unlock Button

RM3048HE
3.0kW 48V DC
Status LEDs

The RM3048HE is a telecommunications grade rectifier with the following features:


• High Efficiency

Enatel DC System Manual Page 9 of 10


Model: FLEXICOMPACT 1 to 3 Version 1.2
• Hot Pluggable
• Forced Air Cooled
• Thermally Protected
• Power Factor Corrected
• Wide input AC Voltage
• Constant Power Output Limit
• Input/Output Voltage and Current Protected
• Active Load Sharing
• Serial alarm and control interface
• Microprocessor controlled
There are 3 LED indicators on the front panel which indicate the operational state of the rectifier:
Red LED Urgent alarm state.
Yellow LED Non-Urgent alarm.
Green LED DC power is connected to the unit.
This LED flashes during power save mode.

4 RECEIVING INSTRUCTIONS
Enatel provides all equipment to the delivering carrier securely packed and in perfect condition. Upon
acceptance of the goods from us, the delivering carrier assumes responsibility for its safe arrival to you. On
receipt of the equipment, check the unit and report to Enatel any issues found. It is your responsibility to
document any damage the carrier may have caused then to file your claim promptly and accurately.

4.1 Package Inspection


Examine the shipping crate or carton for any visible damage: punctures, dents and other signs of possible
internal damage.
Should there be any damage to the carton, check to see if the carton has a Shock Watch:
If the carton has a Shock Watch:
• Please follow the instructions as per the label.
• Notify Enatel within 48 hours if the Shock Watch is red and goods are damaged.
• send photos of damaged product and the Shock Watch to support your claim
If the carton DOES NOT have a Shock Watch:
• record any damage or shortage on the receiving documents
• have the carrier sign their full name on the documents

4.2 Equipment Inspection


Within fifteen days of receipt, open the crate or carton and inspect the contents for damage. While
unpacking, be careful not to discard any equipment, parts or manuals. If any damage is detected call the
delivering carrier to determine the appropriate action. They may require an inspection.
NOTE: SAVE ALL THE SHIPPING MATERIALS FOR THE INSPECTOR TO SEE!
After inspection, if damage has been found please contact the Enatel Service Desk on +64 3366 4550. We
will determine if the equipment should be returned to our plant for repair or if some other method would be

Enatel DC System Manual Page 10 of 11


Model: FLEXICOMPACT 1 to 3 Version 1.2
more expeditious. If it is determined that the equipment should be returned to us, ask the delivering carrier
to send the packages back at the delivering carrier’s expense.
If repair is necessary, we will invoice you for the repair so that you may submit the bill to the delivering
carrier with your claim forms.
It is your responsibility to file a claim with the delivering carrier. Failure to properly file a claim for shipping
damages may void warranty service for any physical damages later reported for repair.

4.3 Handling
Handle the equipment with care. Do not drop or lean on the front panel or connectors. Keep the
equipment away from moisture.

5 INSTALLATION

WARNING All upstream AC and Load breakers must be switched OFF prior to
installation. The system must be completely de-powered.
All circuit breakers in the COMPACT DC System must be in their OFF position
prior to installation.

CAUTION Avoid resting cables on sharp edges

5.1 Suitable Racks


Recommended rack size is 19” and minimum 600mm deep.

5.2 Unpacking
Upon unpacking, check that the unit is not damaged, and that you have the required number of modules and
blank panels (if and as appropriate for your system).
NOTE: Do not fit rectifier modules until the Flexi compact system has been installed into the rack.

5.3 Identification Labels


Model and serial numbers are marked on all equipment. Please refer to these numbers in all
correspondence with Enatel.

5.4 Installing the flexiCOMPACT System


NOTE: the following is for a standard -48V system.
STEP 1: Mount the system in the cabinet or rack as appropriate.
STEP 2: Connect the AC supply.
Undo the front thumb screws of the front panel of the flexiCOMPACT system and fold down to allow
unrestricted access to the AC breakers.
Terminate the cables to the input circuit breakers and the terminal blocks for Earth and Neutral.
NOTE: the AC terminals accept up to 16mm2 cables.

Enatel DC System Manual Page 11 of 12


Model: FLEXICOMPACT 1 to 3 Version 1.2
N L1 L2 L3 E

Figure 2: AC Termination
NOTE: the AC earth terminal is connected directly to the system chassis.

AC Earth

Chassis Earth Stud

Figure 3: AC Earth Termination


NOTE: AC and DC EARTHING - This system has a built-in AC to DC earth connection. No extra AC to DC earth
link cable is required. Should this link be removed the warranty will be voided. Please check with Enatel
should this link be required to be removed.
NOTE: if optioned the earthing cable from the chassis earth stud to the cabinet should now be installed.
STEP 3: Mount the AC terminal cover
Mount the AC terminal cover to protect against contact with the incoming AC voltages.

Enatel DC System Manual Page 12 of 13


Model: FLEXICOMPACT 1 to 3 Version 1.2
1. Insert the AC terminal cover into the slots provided in system top cover.

Figure 4: Mount the AC terminal cover


2. Lower the terminal cover into position.
NOTE: check the washer provided is between the securing nut and the plastic cover.

Figure 5: Lower the AC terminal cover

Enatel DC System Manual Page 13 of 14


Model: FLEXICOMPACT 1 to 3 Version 1.2
3. Tighten the securing nut to lock the cover into position.

Tighten Nut

Figure 6: Lock the AC terminal cover


NOTE: the incoming AC cable can be secured to the top cover by cable tie to provide strain relief.
STEP 4: Connect the Load
Load Common (+ve): all load common connections are made to the connectors placed behind the circuit
breakers. 2 sizes of common terminals are available, up to 16mm2 and 35mm2.
NOTE: cables smaller than 6mm2 should be terminated to the 16mm2 connectors to make sure of adequate
clamping force.
Load Live (-ve): Load Live cables are connected directly to the terminals at the top of the circuit breakers.
Load breaker terminals are sized to accept cables up to 16mm2.
Load distributions that include a secondary load LVD (LLVD) are split into 2 sections to allow prioritisation of
the connected loads. Non-priority loads are removed from circuit prior to the primary battery LVD operation
to extend the time of operation of the priority loads. Load distributions in systems without the secondary
LLVD are all removed from circuit together at the battery LVD disconnect point.
Please refer to the specification of the system to determine which breakers are priority and non-priority
loads (if optioned).
NOTE: make sure all incoming cables have adequate strain relief.

Enatel DC System Manual Page 14 of 15


Model: FLEXICOMPACT 1 to 3 Version 1.2
Load and Battery Common (+ve)

Load Live(-ve)

Figure 7: Load Connections

STEP 5: Connect the Batteries


Battery Common (+ve): All Battery Common connections are made to the connectors placed behind the
Circuit breakers. 2 sizes of common terminals are available to accept cables up to 16mm2 and 35mm2.
Battery Live (-ve): Battery Live cables are connected directly to the terminals at the top of the circuit
breakers. Battery breaker terminals are sized to accept cables up to 35mm2.
NOTE: make sure all incoming cables have adequate strain relief.

Load and Battery Common (+ve)

Battery Live(-ve)

Figure 8: Battery Connections

5.5 Ventilation
The performance of the rectifier can be limited if the ventilation is restricted. The rectifier is cooled by
drawing air into the front of the unit with a single fan. This air passes through the rectifier cooling the
electronics and exiting the rectifier at the rear. For efficient airflow:

Enatel DC System Manual Page 15 of 16


Model: FLEXICOMPACT 1 to 3 Version 1.2
• Check the air at the front of the rack is at ambient temperature and not being heated by other
equipment.
• That the rectifier shelf has at least 75mm clear horizontal space behind it. This space must be clear
of cables and any other components that may restrict air movement.
NOTE: if multiple rectifier shelves are installed then there should be at least 75mm clear horizontal
space per shelf.
• Check the free space in the rack continues vertically to the exhaust point at the top of the rack,
without impediment.
• Check the hot exhaust air does not re-circulate to the front of the rack as this will be drawn into the
rectifiers again, in effect raising the apparent ambient temperature.
• Check the operating environment is low dust and fibre.
Pay particular attention to the quality of rectifier air intake. Insects, sand, and other
extraneous matter ingress seriously impacts the performance of the rectifiers.

5.6 Supervisory Monitor & IO PCB Alarm Output Configuration


For full SM3x functionality and operation information, refer to the SM35/36 Manual.
Access to the power system monitor is made by undoing the thumb screws securing the front panel of the
flexiCOMPACT system and folding it down to a level sufficient to give clear and unrestricted access to the
terminals.
Alarm and communication cables terminate directly into the SM36 Supervisory Module. Alarm cables can be
made to enter/exit through either side of the front cover or fed through and out the top or rear of the
system. When routing the cables, ensure they are kept away from the AC and DC power cables when
possible and adequate strain relief is made.
5.6.1 SM36 Main PCB Alarm Mappings
Alarms can be mapped to any of the voltage free output relays fitted to the SM36 supervisory module.
Output states of either Normally Open or Normally Closed can be selected (NO and NC states are for the de-
energised relay). A jumper is fitted to nominate the required output state, ensure the jumper is placed in the
correct configuration for installation requirements.
If an alarm is programmed for the relay to be normally energised (such as a low voltage alarm where loss of
power will put the alarm into its “active” state), then be sure to connect the remote wiring appropriately.
The following Table 2: Main PCB Relay Alarm Assignments lists the default alarm assignment for the SM36
controller as matches the relay outputs shown in Figure 9: SM36 Relay Outputs.

PCB-ESM35-02
COMMS

10 9 8 2 1
+5V

0V

Aug 09
J111
J111

J114

Internal Systems
MCB-COM
MCB1

MCB2

GPIP7

LVD1

LVDCOM

GPIP8

Connections
8 7 4 3 2 1
J112
J112

Temperature Sensors
J103
RLY101

RLY102

RLY103
RLY104

RLY105
RLY106

J101 J102
J104 J108 J113 J115 J106 J117
J110

BUS1 BUS2
J109

NC NO NC NO NC NO NC NO NC NO NC NO

Communications
J107
J105
J100

1 2 3 4 5 6 - + - +
Bus General Purpose Inputs TS1 TS2 S C S C S C S C S C S C
RY1 RY2 RY3 RY4 RY5 RY6 J501

External I/O
Digital I/P 1 - 6 Connections
Relay Outputs 1 - 6

Figure 9: SM36 Relay Outputs

Enatel DC System Manual Page 16 of 17


Model: FLEXICOMPACT 1 to 3 Version 1.2
Table 2: Main PCB Relay Alarm Assignments
Relay Relay Label Associated Assignments
Output (in Enatel Config.)
Relay 1 CPU Fail
Relay 2 Non-Urgent Alarms Orange LED
Relay 3 Urgent Alarms Buzzer and Red LED
Relay 4 Spare
Relay 5 Spare
Relay 6 Spare
Buzzer

NOTE: Relay 1 is hardware set as a “Monitor Fail” alarm. This alarm activates if the monitor has a hardware
fault or if software becomes corrupted.
5.6.2 SM36 Main PCB General Purpose Digital Inputs Alarm Mappings
General purpose inputs allow the flexiCOMPACT system to monitor any external equipment that includes
relay or auxiliary outputs. The GPIP inputs are activated by connecting the system positive (common) to the
input terminal (configuration setup in the SM36 can allow activation by connecting to system live).
General purpose inputs can also be configured as analogue inputs for purposes such as battery midpoint
monitoring and voltage monitoring.
These inputs may be assigned to contribute to alarm states within the monitor. The state mapping is defined
in the monitor configuration file. Alarm mapping should be completed using the SM3x supervisory module
software. Please refer to the SM36 manual for detailed information.
The inputs are normally activated by connecting system positive (usually system common) to the input.
5.6.3 Circuit Breaker Fail Monitoring
Battery Breaker Monitoring
Battery circuit breakers are monitored via a voltage measurement taken across the breaker to detect
tripping (or manually opened). When a battery breaker is open, there may be very little voltage difference
between the rectifier live bus and the battery live terminal, making typical electronic fail detection methods
problematic.
If no battery is connected, an open breaker will still generate a Battery Breaker Fail alarm. The breaker must
be closed to clear a Battery Breaker Fail alarm.
NOTE: the Battery MCB Fail alarm relies on the battery voltage being measurably different to the system bus
voltage. Due to measurement tolerances it may take some time for the alarm threshold to be reached
before the alarm is activated when a battery breaker is physically turned “off” in non-operational test
circumstances. In a true battery breaker trip event, the required current drawn from the battery required to
open the breaker will ensure the battery voltage is sufficiently low.
Load Breaker Monitoring
Load circuit breakers are monitored electronically via a diode to a digital input on the SM3x. The digital
input will trigger an alarm when it is pulled to the system common (positive) rail. The Breaker Fail alarm will
only operate if a load is connected to the output to provide a return circuit for the sense wire. Therefore, for
breakers that do not have a load connected, the breaker can remain in an OFF position without causing a
false alarm.
NOTE: because of the connection with a diode, a small residual voltage can be measured across an open load
termination even when the circuit breaker is turned off (when measured with high sensitivity digital meters).
This voltage is high impedance and does not present a hazard to the user. The voltage is only apparent when
a load is disconnected.

Enatel DC System Manual Page 17 of 18


Model: FLEXICOMPACT 1 to 3 Version 1.2
5.7 LVD Operation
The primary Low Voltage Disconnect contactor is located in the battery side of the DC distribution. A
secondary Load Low Voltage Disconnect can be optionally included in a section of the load side of the DC
distribution.
The LVD contactor is a bi-stable, magnetically latching contactor. This means that failure of power or
removal of the SM36 from a live system will not cause the contactor to change state. Periodic pulsing of the
LVD control signal allows the monitor to ensure the contactor remains in the correct state. The contactor is
monitored by the SM36 to allow an alarm to be generated when the contactor is open.
The SM36 supervisory monitor unit is powered from both the rectifier side of the LVD contactor and direct
from the battery source. Following an extended AC outage and the low output voltage threshold being
reached, the primary LVD disconnects the battery from the system live bus and the SM36 will lose voltage
sense (as voltage sense is measuring system live bus voltage) yet still maintains operation for system
monitoring. The LVD contactor will not re-engage until rectifier input supply is restored (i.e., until the DC bus
voltage is re-established).
LVD adjustments/settings are all made in the supervisory module. Please refer to the SM36 manual for
detailed setup information.

6 CONFIGURATION UTILITY SOFTWARE


NOTE: the system should use at least version 8.24 of the Configuration Utility software with it.
• Check that the laptop or other device communicating with the system has the correct version of the
configuration utility software installed.
The software version can be found on the top left of the Configuration Utility screen:

The latest version Configuration Software is available on the CD provided with the system, or can be
downloaded from the partner portal. Should you not have access to the partner portal, please go to
www.enatelenergy.com and register. If you have any issues or questions please contact your Enatel
representative.
NOTE: the latest version software will co-exist with a previous version, it does not over-write it. Once the new
version is installed it is safe to delete the older version.
NOTE: key system parameters are stored in the system monitor. Upgrading the Configuration Utility software
does not cause loss of custom settings for this or other systems.

7 ENATEL SYSTEM COMMISSIONING


Use the following set of instructions as a guide, unless different procedures are recommended by local
authorities.
Pre-check:
1. No more building work is to be carried out in site to avoid concrete and plaster dust being ingested
into rectifiers and systems.
2. System installation is completed.

Enatel DC System Manual Page 18 of 19


Model: FLEXICOMPACT 1 to 3 Version 1.2
3. Battery and load circuit breakers are turned off, and upstream AC has been turned off (i.e., system is
completely de-powered).
4. Rectifier/Solar modules have been fitted into their shelf positions and pulled forward enough to
disconnect them from the system.
5. Confirm the earthing is correct for your application before connecting the batteries or rectifiers.
NOTE: this system is supplied with the AC and DC earths connected. This system has DC Common in
the Positive side of the circuit (+ve earth system)..
6. Turn on AC upstream and check that voltages from phase to phase & phase to earth are as expected.
PRE-CHECK DONE: ⃣

7.1 Essential Field System Set-Up Parameters


The following steps are system settings that must be checked at the time of commissioning on site for each
system installed. This section can be printed and filled out for each site commissioned.
Failure to correctly follow the items below may cause incorrect system functionality and in some cases ruin
the battery (without the ability to claim battery replacement under warranty).
Note: Any values shown in this section are indicative only. If the values in your system differ from those
shown here, write in the values relevant to your system.
Refer to the SM36 Supervisory Monitor manual for more details.
7.1.1 Check/Set Float Voltage
Consult the battery manufacturer’s data for the proper setting.
The Float voltage is for 25°C reference temperature in Enatel systems.
SM3x Configuration Utility Software Page: Power Module Control
Example:

Site Setting:

Check/Set Float Voltage Done: ⃣


7.1.2 Set Battery Temperature Compensation
You must consult the battery manufacturer’s data to obtain the correct Slope setting. Note that in many
applications where the battery is constantly being cycled, having temperature compensation enabled may
not be necessary as the voltage on the battery is constantly changing anyway.
SM3x Configuration Utility Software Page: Charge
Example:

Enatel DC System Manual Page 19 of 20


Model: FLEXICOMPACT 1 to 3 Version 1.2
Site Settings:

Set Battery Temperature Compensation Done: ⃣


If you choose not to enable Temperature Compensation, then set the Rectifier Float Voltage to that required
by the battery manufacturer for the average long-term temperature you anticipate your system to operate
at.
7.1.3 Set Battery Capacity
Consult the battery manufacturer’s data for correct battery capacity settings.
For the SM3x to set the correct Battery Current Limit current, it is essential that this is filled out correctly.
These figures are also used for estimating the Battery Time Remaining during a discharge.
For Telecom applications, the 10 hour rate is usually the name-plate rating of the battery. However, once
again, check the battery manufacturer’s data sheets as some manufacturers state the 20 hour rate (which is
usually a little more “optimistic”).
The second rate is required specifically for the time-remaining algorithm. A 4 hour rate is usually a good one
to use. This information is available from the battery manufacturer’s data sheet.
SM3x Configuration Utility Software page: Charge
Example:

Site Settings:

Set Battery Capacity Done: ⃣


Note: Both the 10 hour and secondary battery capacity hour rates should be set at the same time. The SM36
compares rates to ensure the battery data is accurate and may not accept the setting if an inaccuracy is
detected.
7.1.4 Set Battery Current Limit
Consult the battery manufacturer’s data for maximum battery recharge current settings.
The Battery Current Limit is set as a percentage of the 10 hour rate entered in step 3.

Enatel DC System Manual Page 20 of 21


Model: FLEXICOMPACT 1 to 3 Version 1.2
It is recommended this value is set at the highest rate allowable to ensure the battery is recharged as fast as
possible.
In some systems, especially larger systems, this may require limiting further because of the number of
rectifiers available, rather than the maximum setting.
SM3x Configuration Utility Software Page: Control
Example:

Site Settings:

Set Battery Current Limit Done: ⃣

For telecom settings, this limit is often set to 10% (or 0.1C10, i.e. a 10A current limit for a 100Ahr battery).
This is more typical of a design parameter than the need for the setting to be at this level but a setting higher
than this level should be considered to enable the fastest recharge possible without exceeding the battery
manufacturer’s maximum value.
Ensure sufficient rectifier capacity is available to cover battery recharge and load requirements.
7.1.5 Low Voltage Disconnect Settings
The LVD disconnect set points are usually a customer generated setting.
As the discharge time increases, the higher the end voltage should be set. For a discharge of <1hr, this may
be as low as 1.75Vpc (42.0V for a “48V” battery), or for an 8 hour discharge, it may be 1.85Vpc (44.4V for a
“48V” battery).
Note that if only one LVD is fitted, LVD2 and LVD3 thresholds are set outside of possible tripping voltages.
This avoids any confusion over which LVD signal is being used by the SM3x monitor.
SM3x Configuration Utility Software Page: Alarms (Levels)
Example:

Enatel DC System Manual Page 21 of 22


Model: FLEXICOMPACT 1 to 3 Version 1.2
Site Settings:

Low Voltage Disconnect Settings Done: ⃣

7.2 Rectifier & Battery Start Up


7.2.1 Rectifier Start-up
1. Turn the upstream AC circuits on.
2. Fully insert first rectifier, wait for the rectifier to start and its power on LED to remain green.
3. Check the SM3x powers up and indicates the system default float voltage (approx. 54V on its
display). If the audible alarm activates, press any SM3x button to silence it.
4. If a different system float voltage has been specified, set this at this time using the procedure
specified in the SM3x Manual (either from the front panel or connected computer).
5. Fully insert the rest of the rectifiers checking they power up with only their green “power on” LED
illuminated.
6. Check that the load and battery currents on the SM3x are 0 amps (+/- 1 or 2 amps).
7. Check that all SM3x configuration settings are correct (as per customer specification) with respect
to:
◦ Voltage levels
◦ Alarm settings
◦ Alarm mappings to the volts-free relays
Refer to the SM3x manual for information on how to check these via the front panel or locally connected
computer.
7.2.2 Battery Start-up
Note: It is preferable that battery circuit breaker connections should be made when the rectifiers are
turned on and the system is “live”. This is because the system voltage and battery voltages will be similar,
thus minimising any arcing during connection. This also prevents high current arcing due to the charging of
the rectifier output capacitors.
1. Power up only one rectifier initially (to limit any damage if any connections are incorrect).
2. Measure the voltage across each battery string at the terminals of the Compact System. Ensure that
the reading from the DC Common bus to the Battery Live Terminals is -48V as per System
specification.
3. Turn on battery circuit breaker measuring the battery voltage. Ensure that the voltage increases
slightly to the system Float Voltage (typically the voltage will increase from 2 to 3V below float to
float voltage. At this point the batteries will be drawing some current to bring them to a full state of
charge.
Rectifier and Battery Start-Up Done: ⃣

Enatel DC System Manual Page 22 of 23


Model: FLEXICOMPACT 1 to 3 Version 1.2
7.3 Load Start-up
1. Check downstream load connections have been made and there are no loose/floating load cables.
2. Turn ON the load circuit breaker.
3. Check that the downstream equipment is being powered up as expected.
4. Check the system float voltage on the SM3x is at the level previously noted.
5. Check the load current is at a level expected (it could be zero if loads downstream have not been
connected).
Note: If the audible alarm activates, press any SM3x keypad button to silence it.
Refer to the SM3x manual for information on how to check these via the front panel or locally connected
computer.
Load Start-Up Done: ⃣

Note: Prior to leaving the system after it has been commissioned, ensure all AC, DC and battery circuits are
OFF. If it is required that the system is to be left on (to power load equipment) ensure rectifiers are left in
their powered up state, and batteries are in circuit. This prevents anyone leaving the batteries only
powering the load (in which case the batteries would go flat).

7.4 SM36 Digital Inputs


1. SM36 Digital Inputs:
i. GPIP 7 (Load MCB Open)
To check Load MCB Open alarm, connect a load, but with no load turned on. Then switch the
breaker to its OFF position and turn on some load (any amount will do). This triggers a Load
MCB Open alarm. Turn ON the MCB to clear the alarm.
Note: It is recommended to have Battery breakers OFF once the Grid or any of the phase contactors are
closed during this test.
ii. GPIP8 (Battery LVD Open)
To check Battery LVD Open functionality:
a. Turn the battery breakers OFF.
b. Set the LVD Disconnect Point at a value higher than the bus voltage. See 7.1.5 Low Voltage
Disconnect Settings on page 21.
c. The Battery LVD opens and the alarm triggered.
Note: Make sure to reset the LVD disconnect point to the correct value after the test is done then turn ON
the battery breakers.
2. SM36 Battery Temperature Alarm
Temperature alarm tests are performed by heating up (using a heat gun or other source) and cooling down
(using an aerosol can of freeze, or a tub of ice) the temperature sensor.

SM36 Digital Inputs Done: ⃣

Enatel DC System Manual Page 23 of 24


Model: FLEXICOMPACT 1 to 3 Version 1.2
8 DC SYSTEM LEAD ACID BATTERY COMMISSIONING CHECK-LIST
This section is for a more detailed commissioning process than the Essential Set-up Parameters. It may be
printed out separately and filed for record keeping.
DC System Lead Acid Battery Commissioning Check-List
Site Date:____________________
Name:_____________________________________________________ _______
_____________
Tests Without Batteries Connected Value Results
Check Float Voltage Meter:______ __________ V /
Check Load Current Meter:______ __________ A /
Alarms
Voltage thresholds can either be checked using an external power supply, or by
adjusting the EM4x float voltage 0.1V above (or below for the low voltage alarms).
It is recommended to have the batteries disconnected.
1. Adjust the supply/float voltage to 55.7V & observe the “High Float” alarm.
2. Adjust the supply/float voltage to 57.7V & observe the “High Load” alarm.
3. Adjust the supply/float voltage to 52.7V & observe the “Low Float” alarm.
4. Adjust the supply/float voltage to 46.9V & observe the “Low Load” alarm.
High Load Volts (urgent) 57.6V __________ V /
High Float Volts (non-urgent) 55.6V __________ V /
Low Float Volts (non-urgent) 52.8V __________ V /
Low Load Volts (urgent) 47.0V __________ V /
Depending on the test load available, it may be necessary to adjust the High
Load Current alarm threshold down to suit. For example, with 40A test load,
adjust the Load Current High Setpoint threshold (Web UI page Alarm
Configuration>System Alarms) to 35A. Then simply apply the 40A load and
observe the alarm change state.
Once the test is complete, be sure to rest the Load Current High Setpoint to its
previous value (or check with the customer for the correct value they require).
Load Current High Setpoint __________ A /
Temperature alarm tests are performed by heating up (using a heat gun or other
source) and cooling down (using an aerosol can of freeze, or a tub of ice) the
temperature sensors.
Battery Temperature High (urgent) __________°C /
Battery Temperature Low (non-urgent) __________°C /
Room Temperature High (non-urgent) __________°C /
Room Temperature Low (non-urgent) __________°C /
When an AC Monitoring PCB is not fitted at system level (as in most cases), the
AC Fail alarm is generated from the rectifiers. The rectifiers sense if AC is
present, and extend an AC fail alarm to the EM4x. Therefore, to test this
alarm, simply turn off the rectifier AC breakers. To allow the controller to

Enatel DC System Manual Page 24 of 25


Model: FLEXICOMPACT 1 to 3 Version 1.2
continue to read alarms there must be DC present on the output of the
system.
As this causes the rectifier output to cease, a Rectifier Fail alarm is also
generated. To generate the Urgent Rectifier Fail, turn off the required number
to make this occur (usually set to 2, but check via the EM4x Web UI for the
setting (Control page>Rectifier Urgent Fail Threshold).
AC Fail (urgent) Urgent /
Rectifier Fail (non-urgent) Non-urgent /
Urgent Rectifier Fail (urgent) No. /
Modules:____
To check Load MCB fail, connect a load, but with no load turned on. Then
switch the breaker to its off position, and turn on some load (any amount will
do). This will cause the alarm to occur as the load side to the circuit will be
taken to system common voltage. Turn off the load, and then return the
breaker to its on position.
Load MCB Fail (urgent) /
Tests with Batteries
• Turn off Battery Breaker/s
• Connect battery/batteries
• Check the correct Battery Capacity (Ahrs) has been entered (EM4x Web UI
Battery>Battery Settings). This is the total capacity, so for example 100Ahr
strings in parallel, this should be 200.
• Go to EM4x Web UI Battery>Battery Settings>Battery Charge Current Limit.
Check Battery Charge Current Limit (BCL) is set to desired level (usually
0.25C10, (25%)). This means that for a single 100Ahr battery, the BCL will be
25A, or if two 100Ahr batteries are connected in parallel, the BCL will be
50A.
• Connect load (but turn off).
• Check Vf is set to 54.0V. (Web UI Control>Float Voltage)
• Turn on Battery Breaker/s
Check Battery current is positive if charging /
For systems fitted with Battery Monitoring (BCM) cards:
Go to EM4x Web UI Battery>Battery Status. Check cell voltages are approximately /
the same, at about 2.25V (or 13.5V for 12V monoblocs).
If any are out by a large amount, then check the BCM sense wiring is correct.
Set load to required level (e.g., 30A), Check operates /
Initiate a Battery Test.
Click the Start Battery Test button on EM4x Web UI Charge
page.
Check Battery Current is negative (discharging). Note the /
overview data in the header of the Web UI.
Check Battery Current Meter:______ __________ A /
After several minutes, or until the battery voltage has dropped
below approx. 47V,

Enatel DC System Manual Page 25 of 26


Model: FLEXICOMPACT 1 to 3 Version 1.2
click the Stop button at the top of the Web UI Charge page.
During this time the Battery Condition Monitor (if fitted) is
logging.
Battery Current Limit (BCL)
Check that the battery recharge current is limited to the Battery BCL functions /
Current Limit level (usually 0.25C10, (25%)). See Web UI Battery
Settings>Calculated Charge Current Limit for Amp value. _______%
Note: as the BCL is based on fine voltage control of the system
bus, the BCL make take one or two minutes to “settle”, i.e., you
may observe a brief excursion of the battery recharge current
beyond the BCL setting.
Check Manual Equalise (if configured). Click the Start Manual Equalise button on the /
Charge page to initiate a battery equalisation. Click the Stop button at the top of the
Charge page to end.
A Battery MCB Fail alarm is generated from the voltage measured across the battery
MCB.
Therefore, to check a Battery MCB Fail alarm, simply open one of the battery MCB’s.
If batteries are connected to the system at this time, the alarm may take a few
moments to activate. Once test is complete, turn breaker back on.
Battery MCB Fail (urgent) /
Temperature Compensation
Check Temperature Compensation is enabled. /
Web UI Battery>Battery Settings>Rectifier Compensation>On.
Apply heat or cold to the Battery Temperature Sensor/s. Check /
the float voltage moves up or down as expected.
If actual measurement is required, apply a known heat or cold Temp.______°C
to the sensor. Allow it to fully come to temperature and record
the amount of voltage movement. Voltage offset:
________ V OK? /
Check Alarm Relay Contacts
To generate these alarms, refer to the procedures described earlier in the
Commissioning Check-list.
Spare relays will not be able to be tested unless an alarm is mapped to them. As
these are tested in the factory, it is not essential to test them at time of
commissioning.
On main EM4x PCB
Relay 1 (Monitor Fail) /
(pull out the RJ45 lead connecting the monitor to the system rectifier shelf –
this simply de-powers the monitor)
Relay 2 (Summary Non-urgent) /
Relay 3 (Summary Urgent) /
Relay 4 (Spare) /
Relay 5 (Spare) /

Enatel DC System Manual Page 26 of 27


Model: FLEXICOMPACT 1 to 3 Version 1.2
Relay 6 (Spare) /

Note: Prior to leaving the system after it has been commissioned, check all AC, DC and battery circuits are
off. If it is required that the system is to be left on (to power load equipment, ensure rectifiers are left in their
powered up state, and batteries are in circuit. This will prevent anyone leaving the batteries only powering
the load (in which case the batteries go flat).

Enatel DC System Manual Page 27 of 28


Model: FLEXICOMPACT 1 to 3 Version 1.2
9 PERIODIC MAINTENANCE ROUTINES
As ENATEL Power Systems are state of the art electronic systems, very little routine maintenance relative to
past equipment is required.

9.1 System
• During normal operation the cable entries to the MCB’s may loosen over time due to movement in
the cable strands.
• To avoid damage to the MCB’s and cable entries due to heat build-up and arching, it is
recommended that the retaining torque is periodically checked at least annually.
• MCB’s should be maintained at a torque of 2Nm.
• All other connections should also be checked at this time.
• Inspect all cabling for signs of wear.

9.2 Energy Manager


• The Energy Manager can give a good indication of the condition of the system. Alarm logs can show
issues with the system and rectifiers and should be regularly checked.
• As a minimum, check that the float voltage and load current is as expected.

9.3 Rectifiers
• During normal operation some dust will build-up on the front of the rectifiers. This should be kept to
a minimum by regularly wiping the rectifiers to avoid accumulation within the rectifiers and blocking
the airflow to the units. The positioning of the system and surroundings will determine the regularity
of this requirement.
• In extremely dusty positions it is recommended that the units are removed and cleaned with
compressed air to prevent airflow blockages.
• Rectifier intakes should be inspected for any intakes of contaminants that may affect system
performance.

9.4 Ventilation
• Check that there has been no change in the required airflow space or environment that impacts the
ventilation. Refer to 5.5 Ventilation for the required details.

10 TROUBLE-SHOOTING AND SERVICING


10.1 Rectifiers
If the red LED is alight:
• Unplug the rectifier and re-engage.
• Check AC power to the rectifier.
• Check for rectifier alarms in the monitor Urgent Alarm list.
• If symptoms persist, contact a service agent.
If the yellow LED is alight:
• Check the monitor Non-Urgent Alarm list.

10.2 Servicing

Enatel DC System Manual Page 28 of 29


Model: FLEXICOMPACT 1 to 3 Version 1.2
DANGER Do not operate the rectifier if the covers are damaged or removed in any way.

WARNING The rectifier contains voltages that may be lethal even after the input supply
has been removed.

WARNING The rectifier contains components at high temperature that may burn if
touched

To isolate the rectifier from the power supply, unplug it from the shelf.
This rectifier contains no user serviceable components. Do not disassemble the rectifier.
If the rectifier develops an operational fault or is damaged in any way, an authorised service centre should
service it immediately.

Appendix I SYSTEM SOFTWARE


There are three key items of software related to the functionality of the system:
1. The Configuration Utility software (also referred to as the Craft Tool): which manages the
functionality and settings of the system. It is hosted on the laptop, tablet or other device
communicating to the system.
2. The Variables file: specific system configurable options, parameters and logic ladders. These are pre-
loaded prior to shipment into the SM3x and is user adjustable via the Configuration Utility software.
3. The SM3x firmware: typically for the SM3x main microprocessor and the network microprocessor.
Where the SM3x webpage also needs updating in conjunction with firmware bootload.
NOTE: Upgrades to each of the software items may be provided. To install new versions of the Configuration
Utility software and the Variables file refer to Appendix II Software Upgrading. To upgrade the SM3x
firmware refer to the SM3x manual for instructions.

I.A Configuration Utility Software


The system is managed via the Configuration Utility software. The latest version Configuration Software is
available on the CD provided with the system or can be downloaded from the partner portal. Should you not
have access to the partner portal, please go to www.enatelenergy.com and register. If you have any issues or
questions please contact your Enatel representative.
NOTE: EXTENSIVE CONTEXT-SENSITIVE ONLINE HELP FILES ARE EMBEDDED IN THE CONFIGURATION UTILITY SOFTWARE.
ACCESS THESE BY PLACING THE CURSOR IN A DIALOG BOX AND PRESSING F1.
I.A.i Installing the Configuration Utility Software
1. Save the complete Configuration Utility software directory to the required location on your
communicating device.

Enatel DC System Manual Page 29 of 30


Model: FLEXICOMPACT 1 to 3 Version 1.2
2. Read the Readme.txt.

3. Double-click on the SM3X Configuration.exe file to install the software.

I.A.ii Connecting to the System via USB


1. Connect to the system from your communicating device via the mini-USB port on the front of the
SM3x.
2. Open the Configuration Utility software (SM3x Configuration.exe).
3. Select the connection as established in Step 1 above the Direct USB Connection.

4. Check that the SM3x is turned ON.


5. Click the Connect button.

Enatel DC System Manual Page 30 of 31


Model: FLEXICOMPACT 1 to 3 Version 1.2
NOTE: Clicking Quick Connect will automatically connect to the system via USB.
I.A.iii Connecting to the System Remotely
NOTE: Connecting remotely requires an established internet IP address for the SM3x and site connection.
1. Open the Configuration Utility software.
2. Select Remote HTTP Connector or Remote UDP Connection as appropriate.
NOTE: that UDP is the preferred method of remote communication as it is considerably faster and lower
bandwidth than HTTP.
3. Enter the IP address in the URL field.

4. Click on the Connect button.


I.A.iv Access Levels
The Configuration Utility software has different levels of access to the SM3x. The levels are:
Customer
This level allows visibility of configuration parameters but no changes are possible.

Enatel DC System Manual Page 31 of 32


Model: FLEXICOMPACT 1 to 3 Version 1.2
Default Password: customer
Expert
This advanced level allows full change access to configuration parameters and allows access to the
Bootloader, Rectifier Logging and Voltage Mode Switching.
Default Password: expert
Factory
Is a setting used by Enatel staff. Access is not provided by default.
NOTE: The default access level is Customer.
To change the access level:
1. Right-click anywhere in the Page pane area as shown below.

2. Select Log In As to change the access level required.

3. Select the required access level, customer or expert as described above.

Enatel DC System Manual Page 32 of 33


Model: FLEXICOMPACT 1 to 3 Version 1.2
4. Enter the password when prompted, customer or expert as appropriate.
NOTE: The passwords may be changed by the user to preferred values.

I.B Using the SM3x Web Interface


NOTE: an established network with an IP address for the SM3x is required.
1. Enter the IP address of the SM3x in a web browser such as Edge, Chrome, Firefox and so forth. The
SM3x web interface landing page appears.

2. Click on a feature link.


For example:

3. The log-in dialog box appears.

4. Enter in the appropriate fields:


Username = Admin
Password = Admin1

Enatel DC System Manual Page 33 of 34


Model: FLEXICOMPACT 1 to 3 Version 1.2
5. Click OK.

Appendix II SOFTWARE UPGRADING


II.A Upgrading the Configuration Utility Software
NOTE: it is recommended that the latest version of the Configuration Utility software is used with the system.
The software version can be found on the top left of the Configuration Utility screen:

The latest version Configuration Software is available on the CD provided with the system, or can be
downloaded from the partner portal. Should you not have access to the partner portal, please go to
www.enatelenergy.com and register. If you have any issues or questions please contact your Enatel
representative.
NOTE: the latest version software will co-exist with a previous version, it does not over-write it. Once the new
version is installed it is safe to delete the older version.
NOTE: key system parameters are stored in the system monitor. Upgrading the Configuration Utility software
will not cause you to lose custom settings.

II.B Upgrading the SM3x Variables File


An Enatel system is supplied pre-set and is user configurable. Should a new default set of parameters be
required to be installed a *.sm3x file will be made available by your Enatel representative or through the
Partner Portal.
NOTE: This process will over-write existing custom configurations. It is recommended prior to starting a back-
up variables file is made. On the Setup page click on the Save Variables to File (Complete) button.
II.B.i Installation of a .sm3x Variables File
1. Open the Configuration Utility software.
2. Open the Setup page.

Enatel DC System Manual Page 34 of 35


Model: FLEXICOMPACT 1 to 3 Version 1.2
.
3. Click on the Load file into monitor (No network identity) button.
NOTE: the “No network identity” function prevents overwriting of existing network settings needed to
communicate with the system.
4. Navigate to the required variable file and click Open.

Appendix III AC INPUT TRANSIENT PROTECTION


Information to assist the installer for AC input protection is detailed in this section.
Input and output cables
MUST BE SEPARATE
i.e., do NOT run parallel

Distance between
Bunched SPD1 & SPD2
Short Leads (Close should be minimum
coupled) of 10 metres

N Input and output


cables MUST BE
IEC Class I L SEPARATE
(EN Type 1) SPD 1 i.e., do NOT run
(DIN Class B) parallel

Very Short Lead


(preferably <150mm) Earth Bar POWER SYSTEM

E L
Earth Bar

SPD 2 3 metres
IEC Class II
N separation
(EN Type 2)
Alternative SPD to
(DIN Class C) rectifier
Earth Route

AC to DC
No other connections Earth Link
to earth between RECTIFIER
Bunched
earth bar and ground (Close
IEC Class III + - coupled)
(EN Type 3) To Loads
(DIN Class D)
DC Common (+ve)
(Built in to rectifiers)
Busbar

SPD = Surge Protection Device

Illustration A: Surge Protection Installation


Illustration A shows the surge protection installation principles, utilising the 3 stage protection zone concept.

Enatel DC System Manual Page 35 of 36


Model: FLEXICOMPACT 1 to 3 Version 1.2
The Type 1 (SPD1) surge arrester, fitted in the installation's main incoming electrical switchboard, is capable
of diverting the energy of a direct lightning strike. This is the first stage of the electrical network's protection.
It is important that upstream Type 1 protection is provided on site. Although the actual surge capability of
the device used can vary depending on the severity of lightening in any particular installation, the typical
maximum discharge current of a Type 1 surge suppressor will be in the order of 50kA to 100kA (10/350µs
impulse)
The 10/350µs current wave as shown below is the standardized current waveform which passes through
equipment when subjected to an overvoltage due to a direct lightning strike.

Illustration B: Surge Protection Types


A Type 2 surge arrester (SPD2) should be used in coordination with the incoming Type 1 surge arrester. This
is the second stage of protection. The Type 2 Surge arrester is designed to run-off energy caused by an
overvoltage comparable to that of an indirect lightning strike or an operating overvoltage (this is effectively
the “left-over” surge from the Type 1 protection device). To provide sufficient de-coupling between the
Type 1 and Type 2 devices, impedance is required. This is typically stated to be 10m of cable (approximately
10µH). This cable may be looped if the distance available is too short. Alternatively, various manufacturers
have devices which act as filter elements or provide active park ignition for applications where 10m of cable
is not practical (such as outdoor enclosures).
Note: Enatel Rectifiers are compliant with EN61000-4-5, Level 4 without any external/upstream surge
suppression. To maintain a coordinated approach to surge suppression, Type 2 SPD should be installed
upstream if not fitted in the system.

WARNING If these systems are used in outdoor cabinet applications, the fitment of a
Type 2 AC Surge Suppression Device is mandatory.
If a Type 2 SPD is NOT fitted, the warranty is void.

III.A Upstream Over-Current Protection


There are three considerations to take into account when selecting an appropriate fuse/circuit breaker:
- Firstly, the upstream protection should protect the downstream cable from overload situations,
- Secondly, discrimination should be maintained with the downstream device fuses, and
- Thirdly, protection of the surge suppression devices should be taken into account.

Enatel DC System Manual Page 36 of 37


Model: FLEXICOMPACT 1 to 3 Version 1.2
III.B Cable Rating
The maximum current drawn by this DC power system is 18.9Amax at 230V per feed. The upstream
protection device must be able to supply this load under all conditions without tripping. Therefore, typically
at least 20% headroom is allowed for in the protection device, making its minimum rating 50A. As a result,
typically 63A device is used. Therefore, the cable used to supply the system must be rated at the upstream
protection device rating. Please see your local wiring regulations for exact requirements, as cable sizes can
vary depending on these regulations and on the material the cable’s insulation is made from.
Note for rectifier AC feed cable sizes: each rectifier is fed by one set of cables from the AC input terminals.
Although in theory it may appear that this smaller wire is unprotected, in fact it is protected on two
accounts. Firstly, it is protected by the rectifier input fuse (which is only a short distance away). Secondly,
the rectifiers are power-limited on their input. Therefore, they can never be overloaded. As a result, the
wire can never be over-loaded by the rectifier – it can only see fault current.

III.C Discrimination
Discrimination ensures that the upstream circuit breaker or fuse does not blow if a rectifier input is faulty (in
a short circuit manner). Therefore, it is important to ensure the upstream protection discriminates with the
internal fuse of the rectifier. The fuse used in the RM2048 is a slow-blow 15A fuse.

III.D Surge Suppression Device Protection


It is recommended to have Type 2 Surge Protection Devices (s) (as defined by IEC 61643-11) upstream to the
supplied cabinet. These devices are rated for repeated strikes of 20kA (8/20μs waveform), and single shot
protection of 40kA.
It is important that upstream Type 1 protection is also provided on site. To ensure correct operation of the
s, at least 10m of AC feeder cable is fitted between the Type 1 and Type 2 protection. If the distance
between the AC incoming distribution board and the DC Power System is less than 10m, then loop the cable
until at least 10m of cable is used. This ensures correct de-coupling of the devices.

III.E AC cable installation and surge protection


The following precautions MUST be adhered to when installing AC cabling.
1. Avoid running input and output cables from AC Surge Protection Devices together:
Incoming Incoming
AC AC

AC to DC Power
System
AC to DC Power
System

SPD SPD
(Type 1) (Type 1)

Significant coupling
between unprotected and
protected AC line negates Minimal coupling
the effectiveness of SPD between Protected and
Unprotected AC lines

Enatel DC System Manual Page 37 of 38


Model: FLEXICOMPACT 1 to 3 Version 1.2
2. Avoid “T” Connections:

Incoming AC to DC Power Incoming AC to DC Power


AC System AC System

Tee connection introduces SPD


significant impedance to (Type 1)
surge, reducing the
effectiveness of the SPD (by
SPD approx. 0.7 to 0.8V/mm)
(Type 1)

“Tee” connection not “Kelvin” connection


recommended recommended

Appendix IV ENATEL ENERGY STANDARD LIMITED WARRANTY POLICY


Enatel warrants that its products shall be free from defects of material or workmanship under use consistent
with correct installation and commission, normal operation, product specifications, Enatel’s written
instructions, and regional standards compliance, for a period of one (1) year from the start date. The start
date shall be defined as (a) the date the product is shipped from Enatel’s factory; or (b) in the case of resale
by an authorized Enatel reseller, whichever is the lesser of i) the date on the sales invoice or ii) ninety (90)
days after original shipment by Enatel factory.
The warranty provides for repairing or replacing, at Enatel’s sole discretion, those products deemed
defective by Enatel after inspection of its products returned by the customer to the factory or other Enatel
authorized location within the warranty period. Replaced product provided by Enatel under the terms of this
warranty does not extend the original warranty, replacement product assumes the warranty of the original
product. Repaired product or component thereof has a warranty period of ninety (90) days or the remainder
of the unexpired term of the original product warranty, whichever is greater.

IV.A Warranty Exclusions and Restrictions


Products or parts may be excluded from warranty coverage for reasons including, but not limited to: if the
hardware or software has been altered or repaired by an unauthorized party; is defective due to misuse,
negligence, accident, mechanical damage, improper installation or maintenance; inappropriate on-site
conditions such as high humidity, dust, power surges, out-of-range temperatures, animal or insect damage,
water or other liquid damage; where serial numbers or identification marks are removed or defaced in any
way; Force Majeure event; has cosmetic shortcomings which do not affect normal operation; inappropriate
electrical stress; for suspected fraud or abuse of Enatel’s warranty policy; the account has breached or is in
dispute of Enatel’s commercial terms and conditions.
Note Enatel warranty does not cover data loss, regular back-ups to separate storage is required.

IV.B Battery Warranty


Battery warranty is NOT covered under this warranty. Where Enatel supplies batteries a separate warranty
statement shall govern the battery warranty, or where an Enatel battery warranty is not provided the
authorized battery vendor’s warranty shall be assigned to the batteries.
Note that batteries’ operational limits are typically more constrained than Enatel manufactured equipment,
need specific care during storage and maintenance, and requirements typically vary for each battery type
and vendor. Enatel product warranty is voided should improper care of associated batteries be the cause of
product defect.

Enatel DC System Manual Page 38 of 39


Model: FLEXICOMPACT 1 to 3 Version 1.2
Unless stated otherwise in the terms and conditions of sale warranty for peripherals, attachments or
apparatus not manufactured by Enatel shall be excluded from this warranty.

IV.C Initiating a Warranty Claim


To make a warranty claim please complete a Request for RMA Number form:
https://www.enatel.net/support/#rma.
Issuance of a RMA number means your RMA request has been approved and the product or part warranty
claim may now be managed as instructed by Enatel.
Shipping Defective Product to Enatel: All shipments must be shipped prepaid and include proof of the date of
your original purchase along with the RMA number of the approved RMA clearly indicated with the shipment
– see the Request for RMA Number form for further details.
Note Enatel will pay the cost of shipping replacement or repaired units from warranty claims from Enatel
back to the customer, only, unless otherwise approved by Enatel during the RMA Number application
process.

IV.D Disclaimer
Enatel’s warranties and remedies set forth above are exclusive and in lieu of all other warranties, remedies
and conditions, whether oral or written, express or implied. Enatel specifically disclaims any and all implied
warranties, including but not limited to warranties of merchantability and fitness for a particular purpose. In
no event shall Enatel be responsible for indirect or consequential damages or lost profits even in the case of
negligence and if Enatel has been advised of the possibility of such damages. Enatel’s sole obligation shall be
the repair or replacement of a non-conforming product. In no case shall Enatel’s liability under this warranty
exceed the value of the unit provided. If the law prohibits Enatel from disclaiming implied warranties or
warranties of merchantability, all such warranties are limited to the greatest extent permitted by law. Enatel
reserves the right to change the information detailed within this statement without notice.
The benefits conferred by these warranties are in addition to other rights you may have depending on your
country, state or province of residence. Furthermore, some countries, states and provinces do not allow the
exclusion or limitation of incidental or consequential damages or exclusions or limitations on the duration of
implied warranties, so the above limitations or exclusions may not apply to you. If any provision of these
warranties is unlawful, void or unenforceable, that provision shall be deemed severable and shall not affect
any remaining provisions. This warranty shall be governed by and interpreted in accordance with the laws of
New Zealand.

IV.E Remark
Enatel is a registered company name. New Zealand Company Number: 1202388
Enatel Energy® is a registered trademark of Enatel.

Enatel DC System Manual Page 39 of 40


Model: FLEXICOMPACT 1 to 3 Version 1.2
Appendix V WIRING SCHEMATICS
AC Input Terminations Load & Bat tery Common (+ve) Terminations Bat tery Live (-) Terminations Load L ive (-) Terminations
(Dir ect into breakers/ter minals) (Dir ect to Busbar Terminals) (Dir ect into breakers) (Dir ect into breakers)

N L1 L2 L3 E B 1- B 2- B 3- B 4-

AC 4k7

Distribution 4k7
4k7
Whit e
Battery LVD B attery
S hunt P LYS W Fuse Fail
PCB
Red (+ve)

+ 4k 7
- 4k 7
-

+
N L1 L2 L3
12
Red (+ve)
11
V V V
14

GDT
Surge

NC
NC

NC

NC
NC
Diverters
E
A C to DC E art h Link

Earth
Stud

L1 N E L2 N E L3 N E L1 N E

RECT IFI ER 5 RECT IFI ER 6 RECT IFI ER 7 RECT IFI ER 8

J31 EN TER

A C Linking P CB
J29
J30 J33 S erial Comm unication
Connect ion t o S M3x

Orange
Y ellow

Y ellow
B rown

B rown
Green

Green
Whit e

Whit e
V iolet

B lack

B lack
Grey
B lue

Red

Red
J 101

J 111

J 112
L2 N E L3 N E L1 N E L2 N E

Aux Power
GPIP8
LVD Com
LVD1
I1-
I1+
GPIP7
MCB Com
MCB2
MCB1

MCB3
MCB4
GPIP9
GPIP10
I2+
I2-
I3+
I3-
LVD2
LVD Com
BUS1
RECT IFI ER 5 RECT IFI ER 6 RECT IFI ER 7 RECT IFI ER 8

Temp 2

Temp 1
RY1

RY2

RY4

RY5
RY3

RY6
A C Linking P CB

GPIP1
GPIP2
GPIP3
GPIP4
GPIP5
GPIP6
BUS2

+ve

+ve
- ve

- ve
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC
J102 J105 J107 J109 J110 J100

Customer Alarms

Amb. Temp.

Batt. Temp.
(Optional)
L3 N E L1 N E L2 N E L3 N E

RECT IFI ER 9 RECT IFI ER 10 RECT IFI ER 11 RECT IFI ER 12

J32
TITLE 6U up to 12 x Rectifers,-48VDC, 4x Batt, 12x Load, DRAWN
CW
3x AC with SPD REVISION
DRAWING NUMBER SYSTEM NUMBER DATE: 29 Aug 18 1.2
SHEET
140275 FLEXI3-F00 SCALE: NTS 1 of 1