Lloyds TSB Bank Chessington 001 RA
Lloyds TSB Bank Chessington 001 RA
Chessington
Surrey
FIRE RISK
ASSESSMENT
All employers, managers, occupiers and owners of premises where the main use of the building or
part of the building is an office or shop including:
• Sources of fuel
• Sources of oxygen
2. Identify people at risk
• People in and around the premises
• Fire-fighting
• Escape routes
• Lighting
• Maintenance
4. Record, plan, inform, instruct and train
• Record significant finding and action taken
• Inform and instruct relevant people; co-operate and co-ordinate with others
• Provide training
5. Review
• Keep assessment under review
3. PREMISES DETAILS
28 North Parade
PREMISES ADDRESS Chessington
Surrey
KT9 1QF
0845 3000000
OCCUPIER Lloyds TSB Bank plc
OWNER As Above
DIMENSIONS 15m x 6m
1 floor in height.
No. OF FLOORS IN PREMISES 1
HISTORY
DETAILS None
No persons asleep.
PROVIDE TRAINING:
Ensure all staff receive appropriate training annually on,
DETAILS General fire procedures and fire awareness.
Evacuation procedures,
Recognising dangerous practices,
Activation of alarm,
Alerting other members of staff in case of fire if
necessary,
If required the use of fire fighting equipment.
No comprehensive training programme.
MATTERS OF CONCERN No training records of staff.
None
MATTERS OF CONCERN
During office hours a fire in the kitchen, with the kitchen door in the open position. This
door is on the protected escape route and staff have to pass by this door in order to
escape the premises.
Smoke and products of combustion would prevent use of the rear fire exit and prevent
the cashiers from using either of the fire exits.
Early detection of the fire will not be accomplished due to no installed fire alarm system,
but detection will only be achieved by staff or occupants discovering a fire.
Practiced fire drills where cashiers escape over the counter would enhance any
evacuation, but this procedure is unacceptable under H&S.
ACTION REQUIRED:
While using the kitchen the occupants must not leave the room unattended.
Staff training in the use of fire fighting equipment including fire blankets.
None required
DETAILS
None
MATTERS OF CONCERN
None
ACTION REQUIRED
CONCLUSION:
BS 5839-1:2002 Fire Alarm System type P2/M as stated in Annex A in the code
of practice.
ACTION REQUIRED:
TO BE DATE VERIFIED
COMPLETED COMPLETED BY NAME
DEFICIENCY REMEDIAL ACTION REQUIRED BY DD/MM/YY DD/MM/YY
4. Hazards from sources of ignition When using kitchen equipment personnel must ASAP
stay in attendance
All electrical equipment when not in use to be ASAP
unplugged.
4. Hazards from Oxygen Window and all internal doors kept shut when ASAP
premises not occupied.
4. Hazards from work processes Recommendation of BS 5839 Fire Alarm system PRIORITY
to category P2/M standard.
Door leading from kitchen to be replaced with a PRIORITY
30 minute fire door with fitted intumescent strip
and smoke seals.
This kitchen door to be maintained closed with a
self closing device.
5. Identified people at risk from fire Recommendation of BS 5839 Fire Alarm system PRIORITY
to category P2/M standard.
Door leading from kitchen to be replaced with a PRIORITY
30 minute fire door with fitted intumescent strip
and smoke seals.
This door to be maintained closed with a self
closing device.
An annual staff training programme. PRIORITY
TO BE DATE VERIFIED
COMPLETED COMPLETED BY NAME
DEFICIENCY REMEDIAL ACTION REQUIRED BY DD/MM/YY DD/MM/YY
6. Risk of fire occurring. Recommendation of BS 5839 Fire Alarm system PRIORITY
to category P2/M standard.
Door leading from kitchen to be replaced with a PRIORITY
30 minute fire door with fitted intumescent strip
and smoke seals. This door to be maintained
closed with a self closing device.
An annual staff training programme to include, PRIORITY
• Safe use of fire extinguishers
• Fire Warden training
• Fire Marshalling
• Evacuation procedures in case of fire
• General fire safety awareness
6. Risk to people from fire. As Above PRIORITY
TO BE DATE VERIFIED
COMPLETED COMPLETED BY NAME
DEFICIENCY REMEDIAL ACTION REQUIRED BY DD/MM/YY DD/MM/YY
TO BE DATE VERIFIED
COMPLETED COMPLETED BY NAME
DEFICIENCY REMEDIAL ACTION REQUIRED BY DD/MM/YY DD/MM/YY
12. Means for ensuring escape routes A programme to be formulated for testing the PRIORITY
can be safely used during evacuation. door locking deactivation system opens on
power failure.
13. Emergency action plan. Review staff training programme to highlight PRIORITY
EAP and evacuation details.
14. Reviewing of procedures. A comprehensive testing programme of fire PRIORITY
safety measures.
Risk Assessment update. ASAP
15. Maintenance of preventative & A comprehensive testing programme of fire PRIORITY
protective fire safety measures. safety measures as stated above.