Professional Documents
Culture Documents
An Overview of Methods To Determine The Harmonics in Three-Phase Systems
An Overview of Methods To Determine The Harmonics in Three-Phase Systems
Abstract--This paper gives an overview of techniques to the harmonics making the source current is sinusoidal. In this
determine the harmonic content of the currents of three-phase case, the active filter current iAF has to be equal to the
power systems. The different methods, such as the Fourier harmonic content of the load current iL. Therefore, depending
transformation, the FBD-method, the instantaneous reactive on the control, the load current iL or the source current iS can
power theory, the dq-transformation and the multiple rotating
be measured and its harmonic content can be calculated. In all
transformation method are described in detail. Advantages and
disadvantages are given and the most favorable methods are
examples in this paper the load current is measured. The
compared. calculated harmonic content is used as the current command
As an example, these methods are used for the control of a signal for the SAPF.
Shunt Active Power Filter to investigate them in detail. For this In this paper, the authors mention that the goal of an active
purpose, the filter is simulated in the PSpice environment. Two filter is to generate sinusoidal source currents. The other
different methods to calculate the harmonic content in three- option is to control the SAPF in a way that the source currents
phase power systems are implemented in a special DSP-model to become proportional to the source voltage, i.e. the filter tries
simulate the time discrete behavior of processors. The simulation to model a resistive load. Opinions vary about which control is
results are presented in this paper.
the preferred one. It is the authors' opinion that from the utility
customers view-point the sinusoidal source current generation
Index Terms - Harmonic Measurement, Harmonics, Active
Filters. is the most favorable because in this case active power is
drawn only from the fundamental voltage.
I. INTRODUCTION
With the increasing use of non-linear loads such as diode-
iS iL
bridge rectifiers, adjustable speed-drives and cycloconverters
the generation of harmonic currents has steadily increased. The iAF
disadvantages [1] of these harmonic currents are well known.
Among others, additional heat in power cables, transformers,
electrical machines and capacitors is generated due to the
increased RMS current. In three-phase four-wire systems, the
triplen harmonics all add up in the neutral conductor which
can lead to an unacceptable high current in this conductor. The
power factor is typically reduced, and harmonics accelerate the
system’s aging process causing extra costs. Fig. 1: Single-phase diagram of the Shunt Active Power Filter installed in a
In the past, different passive, active or a combination of power system.
both, the so-called hybrid filters have been investigated [2, 3].
For the investigations in this paper we assume a three-
Especially the Shunt Active Power Filter (SAPF) has proven to
phase 50 Hz / 400 V voltage source with a source inductance
be very effective and is therefore available on the commercial
of 50 µH. This voltage source feeds a non-linear load which
market and has been installed in industrial power systems.
consists of a B6 diode bridge rectifier with a series connected
The control of these filters requires the calculation of the
harmonic content of the load currents. In this paper different resistor (R = 1 Ω) and inductor (L = 8.3 mH). Capacitive loads
methods such as the Fourier analysis, FBD-Method, multiple are not considered in this paper because it is known that series
rotating transformation method, the instantaneous reactive active filters are better suited for compensating harmonics
power theory, and the dq-transformation are described in detail generated by voltage inducing loads.
and are discussed. Based on this discussion two methods are The SAPF consists of a current controlled three-phase
selected for comparison with the help of the simulation tool IGBT voltage source inverter, filter inductors (Lf = 500 µH) to
PSpice. smooth the inverter's output current and a 800 V dc-link. In the
simulations, the dc-link is assumed to be ideal. The filter
II. SHUNT ACTIVE POWER FILTER current is controlled with a hysteresis controller.
The control (including the calculation of the harmonic
The single phase diagram of a Shunt Active Power Filter is content of the load current) of the SAPF is implemented in a
depicted in Fig. 1. The source supplies a harmonic generating DSP-model to simulate the time discrete behavior of
load. A SAPF is installed in parallel to the load to compensate microprocessors or DSPs [11]. This model allows to write the
complete control algorithm in C-code. The sample frequency harmonic filter products the DFT is not applied due to these
of the controller is fS = 12.8 kHz which results in a number of disadvantages.
256 cycles per fundamental period.
B. Fryze-Bucholz-Depenbrock (FBD)-Method
III. HARMONIC CURRENT CALCULATION The FBD-Method [7] tries to shape the source currents iSa,
iSb and iSc in such a way that they become proportional to the
In literature, different methods to calculate the harmonic source voltages eSa, eSb and eSc. Therefore, the source voltages
content of voltages and currents have been presented during and the load currents are measured. With the help of these
the past 25 years [4 - 11]. In this paper the authors will quantities the equivalent conductance can be calculated:
describe the following methods:
• eSi ⋅ iLi
Fourier Transformation (FFT[5], DFT [6]) Gi = , i = a, b or c (5)
• Fryze-Bucholz-Depenbrock (FBD)-Method [7] eSi ⋅ eSi
• Instantaneous Reactive Power Theory [4]
• dq-Transformation [9, 10] The index i indicates the three phases a, b or c. The terms
• Multiple dq-Transformations [8] in the formula can be calculated with
A. Fourier Transformation 1 t
T t ∫−T
The result of a Fourier Transformation is a continuous eSi ⋅ iLi = ⋅ eSi (t ) ⋅ iLi (t )dt = P (6)
frequency spectrum of a function in the time domain. The
discrete equivalent is called the Discrete Fourier
1 t E2
Transformation (DFT). For active filter applications the source eSi ⋅ eSi = ⋅ ∫ eSi (t ) ⋅ eSi (t )dt = (7)
or load currents are measured. The DFT of a time discrete T t −T 2
current i[n] sampled with frequency fs is determined as
This means that the minimum current required by the load
a −1 2 kn
can be determined:
∑ i[n] ⋅ e
−j
I [k ] = N
(1)
n= a − N
iL* ,min,i = Gi ⋅ eSi (t ) (8)
k = 0, 1, 2, ..., N-1 (2) To achieve unity power factor the current difference has to
The spectrum I [k ] represents all harmonic values of the be compensated. Therefore, the active filter has to inject a
current:
fundamental frequency f0 up to (N-1)th. The number of samples
taken during one fundamental period is *
iAF,i
= iL,i (t ) − Gi ⋅ eSi (t ) (9)
fS The advantages of this method are that it is very easy to
N= (3)
f0 implement and that it requires little computing power. This
method can be used in single- as well as in multi-phase
With the Euler-equation we obtain for the spectrum systems. Especially, in stationary systems the damping
a −1
2 kn a −1
2 kn performance is quite good.
I [k ] = ∑ i[n] ⋅ cos
n= a − N N
− j ⋅ ∑ i[n] ⋅ sin
n= a− N N
(4) On the other hand this method can not distinguish between
reactive and distortion power, i.e. it is not possible to
With the help of this equation the harmonics that need to compensate the harmonic load currents only. Single harmonics
be compensated can be determined. The inverse DFT is used such as the 5th and the 7th can not be detected and
to generate the inverter’s reference signals in the time domain. compensated, too. A second disadvantage is that source
An advantage of the DFT is that all harmonics can be voltage harmonics result in proportional source current
identified individually. Hence, harmonics that need to be harmonics, causing additional power flow. Lastly, the
compensated can be selected and compensated. Furthermore, equivalent conductance G is gained with voltage and current
the DFT can be implemented in single-phase systems as well samples of the last fundamental period, which means that this
as multi-phase-systems. method requires one fundamental period to respond to
Mayor disadvantage, however, is that a large amount of transient conditions making the active filter rather slow.
computing power is required. Especially, in multi-phase C. The instantaneous reactive power theory
systems the frequency spectrum has to be calculated for every
The instantaneous reactive power theory [2 - 4] or pq-
phase. On the other hand, if all harmonics need to be
theory (Fig. 2) is already used in a lot of filter applications.
compensated only the amplitude of the fundamental has to be
The phase voltages ea, eb, and ec and the load currents iLa,
determined, so saving calculation time. Although reducing the
required computing power drastically the DFT method still iLb and iLc are measured and transformed into α-β orthogonal
requires powerfull processors. Another drawback is that in coordinates.
transient conditions the harmonics can not be accurately ea
detected rapidly, because the spectrum is calculated from the eα 1 − 1
− 1
= ⋅ ⋅
2 2
3
2
eb (10)
3 −
3
samples of the previous fundamental cycle. In commercial e β 0
1 1
2 2
ec
iLa
iLα 1 − 12 − 12
= ⋅ ⋅
3 − 12 3
2
3 i Lb (11)
i Lβ 0
1
2
i Lc
Fig. 4: Multiple dq-transformations The load current iL is depicted in Fig. 5. The filter and source
currents in the case the instantaneous reactive power theory is
used are depicted in Fig. 6. The impact of the source voltage is algorithms, the instantaneous power theory and the dq-
shown very clearly. Because there are no in- and output filters transformation, have been selected for implementation in
used in the simulation. In practice the measured source three-phase power systems.
voltages are filtered at the input. Further, the inverter will have Although the implementation of the instantaneous power
an output LC- or LCL-filter. Fig. 7 shows the results of the dq- theory is more simple because it does not require a PLL the
transformation implementation. Again, no in- and output filters dq-transformation does not require in- and output filters to
are implemented, but with this method the source current generate sinusoidal source currents. In this way the SAPF can
becomes nearly sinusoidal. Only the steep current rise can not be made more cost effective.
be compensated because of the dynamic limits of the SAPF.
For the dq-transformation no in- and output filters are VI. REFERENCES
necessary to obtain sinusoidal source currents. [1] "IEEE recommended practices and requirements for harmonic control in
electrical power systems", IEEE 519-1992
[2] Akagi H.: "Trends in active power line conditioners", IEEE
Transactions on Power Electronics, Vol.9, 1994
[3] Akagi H.: " New trends in active filters for power line conditioning",
IEEE transactions on industry applications Vol. 32, No. 6, 1996
[4] Akagi H., Kanazawa Y., Nabae A, "Instantaneous reactive power
compensators comprising switching devices without energy storage
components", IEEE transactions on industry applications Vol. 20, No. 3,
1984
[5] Zhang F., Geng Z., Yuan W., "The algorithm of interpolating windowed
FFT for harmonic analysis of electric power systems", IEEE transactions
on power delivery Vol. 16, No. 2, 2001
[6] Lev-Ari H., 6WDQNRYLü 0 Lin S., "Application of staggered
undersampling to power quality monitoring", IEEE transactions on
power delivery Vol. 15, No. 3, 2000
[7] Depenbrock M, Skudelny H.-Ch., "Dynamic Compensation of
Nonactive Power Using the FBD-Method. Basic Properties
Demonstration by Benchmark Examples", IEEE Second International
Workshop on Power Definitions and Measurements under Non-
Sinusoidal Conditions, Stresa, Italy, 1993
[8] Bojrup M., Karlsson P., Alaküla M., Gertmar L., "A multiple rotating
integrator controller for active filters", ABB
[9] United States Patent US5,648,894, Jul. 15, 1997, De Doncker R.W.:
"Active filter control"
[10] Jacobs J., Detjen D., De Doncker R. W.: A new hybrid filter versus a
shunt active power filter, EPE 2001, Graz (Austria), 27-29.8.2001
Fig. 7: Filter current iF and source current iS with dq-transformation [11] Detjen D., Schröder S., De Doncker R.W.: "Embedding DSP control
algorithms in PSpice", COMPEL, Blacksburg/Virginia, 2000
V. CONCLUSION
In this paper different algorithms to calculate the reference
signals for SAPF are reviewed. Advantages and disadvantages
are given. Based on these advantages and disadvantages two