SDM230 Service Manual
SDM230 Service Manual
*For SDM230-Mbus:
1 Total kWh→ Import kWh→Export kWh→ Resettable kWh→
Total kVArh→Import kVArh→ Export kVArh→ Resettable kVArh
→ Max. Power Demand→ Voltage →Current→W→ Var →VA Active power
→ Power Factor → Frequency →Pulse Constant→ 16 Example: 4700W
8 7 Mbus Primary Address→Mbus Secondary Address→
UserManual V1.6 Baud Rate→Continuous Running Time
Display No:1,4~7,10~24.
Warnings
Important Safety Information is contained in the 9 10 11 12 13 Reactive power
Maintenance section. Familiarize yourself with this *For SDM230-Std: 17 Example: 1030Var
information before attempting installation or other
procedures. Total kWh→ Import kWh→Export kWh→ Resettable kWh→
Total kVArh→Import kVArh→ Export kVArh→ Resettable kVArh
Risk of Danger: These instructions contain → Pulse Constant→ Modbus ID→ Baud Rate →
! important safety information. Read them before NO. Descriptions Continuous Running Time
starting installation or servicing of the equipment. 1 7 digits used to display measured values Display No:1,4~7,10~12, 21~24.
Caution: Risk of Electric Shock 2 Total value
Apparent power
3 Tariff information 18 Example: 4811VA
4 Import information, Export information
5 Max. Demand for Power or Current.
1.Introduction 6 Pulse output 1and Pulse output2
7 Measurement units
Total active energy
This document provides operating, maintenance and 8 PF = power factor Hz = frequency 1 Power factor
Example:70.00kWh 19
installation instructions of SDM230 series made by Example: 1.000
9 Bar display of Power
Eastron Electronic Co., Ltd. The SDM230 series
10 Communication indicatior
measure and display the characteristics of single phase
two wire (1p2w) network. The SDM230 series covers 5 13 Lock symbol
models:SDM230-Modbus,SDM230-Pulse,SDM230-
Mbus,
. SDM230-2T and SDM230-Std. T1 active energy
The bi-directional measurement makes the meter 2 Example: 10.00kWh Frequency
(for SDM230-2T only) 20 Example: 49.99Hz
suitable for active and reactive energy and power 2.2 Initialization Display
monitoring applications, and also perfect for solar PV
measurements. With RS485 Modbus and M-bus port,
the meter is easy to remote communication with other
AMR/SCADA systems.
All display segments light up, T2 active energy
3 Example: 10.00kWh Pulse 2 constant
display check. 21
(for SDM230-2T only) Example: 1000
Communi- Multi
Model Measurements cation Pulse Outputs Tariffs
U, I, P, Q, S, PF, Hz, 1:
SDM230- Dmd, kWh, kVArh, RS485 configurable
NO Software version (please check
Modbus Import, Export Modbus 2: Modbus address
1000imp/kwh the real software version on the Import(input) active energy Example: 001
4 Example: 50.00kWh 22
product as the final). Mbus primary address
1: Example:001
U, I, P, Q, S, PF, Hz,
SDM230- Dmd, kWh, kVArh, M-bus configurable
EN13757-3 2: NO
Mbus Import, Export
1000imp/kwh
1:
U, I, P, Q, S, PF, Hz,
SDM230- configurable Export(output) active energy
Dmd, kWh, kVArh, NO NO Modbus ID or Mbus Primary Address 5 High and Low bit of MBUS
Pulse 2: Example: 20.00kWh
Import, Export Secondary address
1000imp/kwh
(Default 00 00 00 01)
Example: if the Secondary
1: address high bit is 0000,
U, I, P, Q, S, PF, Hz, 22-1
SDM230- RS485 configurable 2 Tariffs low bit is 0001,that means
Dmd, kWh, kVArh,
2T Modbus 2: (time relay)
Import, Export the integral Secondary
1000imp/kwh
address is 00 00 00 01
(for SDM230-Mbus only)
1: Mbus Secondary Address (High) 6 Resettable total energy
SDM230- kWh, kVArh, RS485 configurable (for SDM230-Mbus only)
Import, Export 2: NO
Std Modbus
1000imp/kwh
Press the “Enter” button, the red part flash. 3.7 Mechanics
Press the “Scroll” button to change the option.
2-3 After choosing the new value, the user needs to Din rail dimensions 36x99x63 (WxHxD)
press the “Enter” button to confirm the setting. Clear Max demand of active power
Per DIN 43880 1 2
11-1 Long press “Enter” button to
confirm the operation. Mounting DIN rail 35mm
Baud rate for Modbus Sealing IP51 (indoor)
Default value: 2400bps Material self-extinguishing
Range: 1200, 2400, UL94V-1
4800, 9600bps.
3 Baud rate for Mbus:
Default value: 2400bps
Range:300, 600,1200, 2400, Clear the resettable energy
12 Long press the Enter button
4800, 9600bps.
to confirm the operation. 4.Dimensions
Press the “Enter” button, the
red digit flash.Press the “Scroll”
5 6 7 8 9 10
button to change the value. After
choosing the new baud rate, m
3-1 45m
the user needs to press the
“Enter” button to confirm the
setting.
Password 3 4
13 Default: 1000
L-out N-out
Parity
4 Default: None
Option:None, Even, Odd
63 m m
3.Specifications
Pulse Output 1
SDM230-Modbus/Std
Default: kWh 3.1 General Specifications 5.Installation and sealing
5 Option:kWh / KVArh /
Voltage AC (Un) 230V 5 6 7 8 9 10
Imp. kWh / Exp.kWh /
Imp.kVArh / Exp.kVArh Voltage Range 176~276V AC
Base Current (Ib/Iref) 10A A B GND 1+ COM 2+
3.2 Accuracy
Press the “Enter” button, the
red part flash.Press the “Scroll” Voltage 0.5% of range max.
button to change the option. After Current 0.5% of nominal DIN Rail
choosing the new pulse constant Frequency 0.2% of mid-frequency
6-1 Active power 1% of range maximum
option, the user needs to press
the “Enter” button to confirm Reactive power 1% of range maximum
the setting. Apparent power 1% of range maximum
Active energy Class 1 IEC62053-21
Class B EN50470-3
Reactive energy 1%of range maximum
Pulse duration
7 Default: 100mS
Option: 200 / 100 / 60mS
3.3 Environment
Operating temperature -25 C to +55 C
Press the “Enter” button, the Storage/transportation temperature -40 C to +70 C
red part flash.Press the “Scroll” Reference temperature 23 C ± 2 C
button to change the option. After Relative humidity 0 to 95%,
7-1 choosing the new pulse duration non-condensing
option, the user needs to press Installation category CAT II
the “Enter” button to confirm Mechanical Environment M1
the setting. Electromagnetic environment E2
Degree of pollution 2
*Maximum operating and storage temperatures are in the Declaration of Conformity(for the MID
Demand Integration Time context of typical daily and seasonal variataion. approved version meter only) Zhejiang Eastron Electronic Co.,Ltd.
8 Default: 15 minutes Add: No.1369 , Chengnan Rd. Jiaxing,
Option: off(0) / 5 / 10 /
We Zhejiang Eastron Electronic Co.,Ltd. Zhejiang, China
15 / 30 / 60
3.4 Pulse Output Declare under our sole responsibility as the manufacturer Tel: 86 573 83698881/83698882
that the poly phase multifuntion electrical energy meter Fax: 86 573 83698883
Press the “Enter” button, the The pulse output 1 can be set to generate pulses to represent “SDM230 Series” correspond to the production model Email: sales@eastrongroup.com
red part flash.Press the “Scroll” total kWh, total kVArh,import kWh, export kWh,import kVArh, Web: www.eastrongroup.com
export kVArh. described in the EU-type examination certificate and to
button to change the option.
8-1 After choosing the new DIT option, Constant can be set to 1000/100/10/1 impulse per kWh or KVArh. the requirements of the Directive 2014/32/EU EU type
the user needs to press the Pulse width 200/100/60mS. examination certificate number 0120/SGS0206.
“Enter” button to confirm the
setting.
Identification number of the NB0120
MID