Material List: Produced On 7/04/2022 With Xpress Selection V9.8.0 - Database DIL 17.2.1

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 9

Produced on 7/04/2022 with Xpress Selection V9.8.0 - database DIL 17.2.

Project name UPSS Farmacia


Project address Peru
Reference PERU
Client name NINA
CATACORA
Revision GCM_01

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Type Model Name Qty Description
Outdoor unit RXQ14AYM 1 Cooling only VRV A(18,20HP single module)
Indoor unit FXHQ63MA 5 VRV H - Unidad suspendida del techo
VE
Branch unit KHRP26A22 2 Refnet branch piping kit
T
KHRP26A33 1 Refnet branch piping kit
T
KHRP26A72 1 Refnet branch piping kit
T
Option or add-on BRC1E63 5 Wired Remote Controller (Navigation Remote
Controller)
Refrigerant R410A 1.7kg Extra refrigerant charge
Copper pipe Piping ø ⅜" 18.7m Copper pipe
Piping ø ½" 5.5m Copper pipe
Piping ø ⅝" 13.7m Copper pipe
Piping ø ¾" 1.7m Copper pipe
Piping ø ⅞" 3.3m Copper pipe
Piping ø 1⅛" 5.5m Copper pipe

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb
temp.)
Rq TC Required total cooling capacity
Max Available total cooling capacity
TC
Rq SC Required sensible cooling capacity
Max Available sensible cooling capacity
SC
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Airflo Supplied airflow
w
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHx WidthxHeightxDepth
D
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
2
2.2. VRV - 1 - RXQ14AYM
Capacity data at conditions and connection ratio (89%) as entered
Name FCU Rq Tmp C
Max Rq Max Teva Tdis Airflo
TC TC SC SC p C w
°C BTU/ BTU/h BTU/ BTU/h °C °C cfm
h h
UEST- FXHQ63MA 27.0 / 19.5 n/a 24397 n/a 17027 Auto 13.1 618
04 VE
UEST- FXHQ63MA 27.0 / 19.5 n/a 24397 n/a 17027 Auto 13.1 618
05 VE
UEST- FXHQ63MA 27.0 / 19.5 n/a 24397 n/a 17027 Auto 13.1 618
06 VE
UEST- FXHQ63MA 27.0 / 19.5 n/a 24397 n/a 17027 Auto 13.1 618
07 VE
UEST- FXHQ63MA 27.0 / 19.5 n/a 24397 n/a 17027 Auto 13.1 618
08 VE

Required cooling capacity towards the outdoor unit: 121984BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest temperature in
case of heating mode), assuming the indoor unit is running at full load at the given indoor temperature design conditions. In
practice the discharge temperature will modulate based on actual capacity requirements and during defrost mode (heating
mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a thermal
comfort level.

Name Soun PS MC WxHxD Wgh


d A t
dBA A mm kg
UEST- 34-39 220V 0.9 1160×195×68 28
04 1ph 0
UEST- 34-39 220V 0.9 1160×195×68 28
05 1ph 0
UEST- 34-39 220V 0.9 1160×195×68 28
06 1ph 0
UEST- 34-39 220V 0.9 1160×195×68 28
07 1ph 0
UEST- 34-39 220V 0.9 1160×195×68 28
08 1ph 0

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
3
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Standard factory refrigerant charge (5m actual piping length)
Refr
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHx WidthxHeightxDepth
D
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
4
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp HC Rq
H HC
% °C BTU/h BTU/h °C BTU/ BTU/
h h
VRV - RXQ14AY 89 33.0 137307 121984
1 M
Name Model Pipin Refrigerant
g
m Type Bse Refr Ex Refr
kg kg
VRV - RXQ14AY 19.5 R410A 7.4 1.7
1 M
Name Model PS MC WxHxD Wght
A
A mm kg
VRV - RXQ14AY 380V 3ph 26.9 1240×1657×76 215
1 M 5

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
5
3.2.1. VRV - 1 - RXQ14AYM
Model Type Model Name Qty Description
Outdoor unit RXQ14AYM 1 Cooling only VRV A(18,20HP single module)
Indoor unit FXHQ63MA 5 VRV H - Unidad suspendida del techo
VE
Branch unit KHRP26A22 2 Refnet branch piping kit
T
KHRP26A33 1 Refnet branch piping kit
T
KHRP26A72 1 Refnet branch piping kit
T
Option or add-on BRC1E63 5 Wired Remote Controller (Navigation Remote
Controller)
Refrigerant R410A 1.7kg Extra refrigerant charge
Copper pipe Piping ø ⅜" 18.7m Copper pipe
Piping ø ½" 5.5m Copper pipe
Piping ø ⅝" 13.7m Copper pipe
Piping ø ¾" 1.7m Copper pipe
Piping ø ⅞" 3.3m Copper pipe
Piping ø 1⅛" 5.5m Copper pipe

Standard factory refrigerant charge (5m actual piping length) = 7.4kg


Extra refrigerant charge = 5.5m(ø½") × 0.11 + 18.7m(ø⅜") × 0.057 + A + B = 1.7kg
A [ CR 89%, actual length 17.5m ] = 0.0kg
B [ 14HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
6
4. Piping Diagrams
Pipes marked with a short red stripe in the diagrams must be connected to the device with a reducing joint.

4.1. Piping VRV - 1

VRV - 1
RXQ14AYM

5.5m 1.8m
½"×1⅛" ⅜"×⅝"
KHRP26A72T

UEST-04
FXHQ63MAVE
3.3m 1.8m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T

UEST-05
FXHQ63MAVE
1.7m 3.5m 3.5m
⅜"×¾" ⅜"×⅝" ⅜"×⅝"
KHRP26A22T KHRP26A22T

UEST-06
FXHQ63MAVE
1.0m
⅜"×⅝"

UEST-07
FXHQ63MAVE
2.1m
⅜"×⅝"

UEST-08
FXHQ63MAVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
7
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring VRV - 1

P1,P2
VRV - 1 UEST-04 BRC1E63
RXQ14AYM FXHQ63MAVE
IN F1,F2 F1,F2
L1,L2,L3,N 26.9A 3ph L, N 0.9A 1ph
P1,P2
UEST-05 BRC1E63
FXHQ63MAVE
F1,F2
L, N 0.9A 1ph
P1,P2
UEST-06 BRC1E63
FXHQ63MAVE
F1,F2
L, N 0.9A 1ph
P1,P2
UEST-07 BRC1E63
FXHQ63MAVE
F1,F2
L, N 0.9A 1ph
P1,P2
UEST-08 BRC1E63
FXHQ63MAVE
F1,F2
L, N 0.9A 1ph

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it)
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
8
6. Device Options

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
9

You might also like