DAIKIN REFRIGERATION MALAYSIA SDN. BHD.

Time Code : 20220412103318


Project Name : HOSPITAL DE CONTINGENCIA
AHU TECHNICAL REPORT AHU No. : UMA-01
Model Name : D DM1-0404B
D for DAIKIN
VRV AHU Model: AHUR16CBLJY2
Software Version : EPOCH 5.0 Patch 4.01 Report Date : 12/4/2022 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 573


Database Version : 2022.04.01 1020 CFM 0.48 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2022.04.01 -
Flow Rate :

Daikin Refrigeration Malaysia Sdn. Bhd is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. The range DMAHU is certified under the
number 09.11.441 and presented on www.eurovent-certification.com.
Certified in accordance with the AHRI Central Station Air-handling Unit Casing Certification Program, which is based on AHRI Standard 1350. Certified units may be found in
the AHRI Directory at www.ahridirectory.org
AHU specified in this report are manufactured by Daikin Refrigeration Malaysia Sdn. Bhd.

AHU Unit Specification


*This symbol is only for DRM internal use.
*Insulation Material
Cross Section (Bottom) : 0.86 m/s : Polyurethane-PU 40 kg/m³ *Delivery Mode : CBU
Air Velocity (Upper) : 0 m/s *Insulation Thickness : 25 mm Unit Orientation : Horizontal
*Inner Skin Thickness 0.5
::0.5 mm *Outer Skin Thickness : 0.5 mm Int Dim (Btm) : 750H x 750W mm
*Inner Skin Material GI
::GI *Outer Skin Material : GI Int Dim (Mid) : - mm
*Inner Surface Painted : No *Outer Surface Painted : Yes Int Dim (Top) : - mm
Recirculation units or units with design inlet temperatures always Design Winter
Application Type (Winter) : : 35 °C
> 9°C Outdoor Temp.
Application Type (Summer) Subgroup[1]
: - according to TCR - ECP-05-2020
Unit Length (Btm) : 5100 mm Unit Height (Btm) : 880 mm Unit Width : 800 mm

*Option Included : 80 mm GI Base Frame, Rubber Cord at Frame,

CAL Class@(+400
Casing Strength Thermal Transmittance Thermal Bridging
Pa/ -400 Pa)
D1(M) >L3(R) / L2(R) T4(M) TB3(M)
Eurovent Energy A+ N ⁽²⁰¹⁶⁾ / Int. Specific Fan Power : - W/(m³/s)
Efficiency Class
(Winter)⁽²⁰¹⁶⁾ /
A+ ⁽²⁰²⁰⁾ ErP Identification Code : NRVU-UVU
(Summer)⁽²⁰²⁰⁾
fs-Pref (Winter / Summer) 0.8 / 0.95
Thermal Transmittance
Casing Deflection CAL Class (+ve/
Class w/leakage / Thermal Bridging
Rating (+ve / -ve) -ve) @ 8''
w/o leakage
CD3 / CD3 CL3 / CL3 CT4 / CT4 CB3
Design dry-bulb temp (ASHRAE 2017 Climatic Design Conditions) 28.8
: °C Country : Peru
Design dew-point temp (ASHRAE 2017 Climatic Design Conditions) 20.3
: °C Place : Lima Callao Intl

Section Weights and Dimension

Section No #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12

Depth mm 3200 1900

Weight kg 392 181

1 EXTERIOR FILTER

*Type Aluminium
: Mesh Grade/Class : ePM Coarse / G3 Filter Face Velocity : 1.36 m/s
*Filter Media Yes
: (Factory Supply) Anodized Aluminium Initial or Clean
Casing Material : 49.18 Pa
*Holding Frame Sliding
: Extrusion Pressure Drop :
Final Pressure Drop :
*Quantity (24'' x 24'') 1: 99.18 Pa
Media : Aluminium Mesh Design Pressure
*Quantity (20'' x 24'') 0: Drop: 74.18 Pa
*Quantity (16'' x 24'') 0: Filter Energy Extra Pressure Drop 0.00
0
: .00 Pa
-
*Quantity (12'' x 24'') 0: Performance :

Page 1/6 Printed On 12/04/2022 10:35 AM


DAIKIN REFRIGERATION MALAYSIA SDN. BHD.Time Code : 20220412103318
Project Name : HOSPITAL DE CONTINGENCIA
AHU TECHNICAL REPORT AHU No. : UMA-01
Model Name : D DM1-0404B
D for DAIKIN
VRV AHU Model: AHUR16CBLJY2
Software Version : EPOCH 5.0 Patch 4.01 Report Date : 12/4/2022 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 573


Database Version : 2022.04.01 1020 CFM 0.48 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2022.04.01 -
Flow Rate :

*Spare Filter Qty (set) 0: *Door Type :- *Door Handle Type ::--
2 DX COIL (couple with VRV)

GENERAL FIN TUBE


*Coil Model : 2004-E1008R *Material : Aluminium Material : Copper
*Coil Medium : R410A *Fin Protection : None *OD : 9.53 mm
*Rows/Fin per Inch : 8 / 10 Type : Corrugated *Thickness : 0.350 mm
Coil Layers : 1 Thickness : 0.115 mm Tube Height : 20
*Circuits per Coil : 15 *Height : 508 mm Pattern : 25.4 x 22.0
Total Int. Volume : 5.75 dm³ *Length : 509 mm *Moisture Eliminator : None
Face Velocity : 1.86 m/s *Width : 176 mm ME Pressure Drop : 0.00 Pa
Heat Pump Mode : No
*Split Type : Face Split COOLING HEATING
FRAME / OTHERS AIR SIDE AIR SIDE
*Frame Material : GI EDB / EWB : 35.00 / 32.00 °C EDB / EWB : - °C
*Drain Pan Material : SSTL 304 LDB / LWB : 13.83 / 13.65 °C LDB / LWB : - °C
*Header Material : Copper ERH / LRH : 81.1 / 98.1 % ERH / LRH : - %
*Connection Joint : Brazed Pressure Drop (Wet): 126.86 Pa Pressure Drop : - Pa
Header Location : Right Pressure Drop (Dry) : 87.08 Pa Mass Flow Rate : - kg/h
Drain Pipe Location : Right Mass Flow Rate : 2079.59 kg/h ERH = Entering Air Relative Humidity
Drain Pan Type : Standard Extra Pressure Drop: 0.00 Pa LRH = Leaving Air Relative Humidity
VRV KIT REFRIGERANT SIDE REFRIGERANT SIDE
Controller Entering Liquid : 43.00 °C Cond. Temp : - °C
*EKEQMCBA : 0 Saturated Suction : 6.00 °C Subcooling Temp : - °C
*EKEQFCBA : 1 Suction Superheat : 5.00 °C Hotgas Superheat : - °C
*MicroTech III : 1 Flow Rate : 963.80 kg/h Flow Rate : - kg/h
EXV Kit Pressure Drop : 25.84 kPa Pressure Drop : - kPa
*EKEXV 140 : 0 Temperature Drop : 0.90 °C Temperature Drop : - °C
*EKEXV 200 : 0 Capacity / Circuit : 2.74 kw/cc Capacity / Circuit : - kw/cc
*EKEXV 250 : 0 *Total Capacity : 41.04 kW *Total Capacity : - kW
*EKEXV 400 : 1 *Sensible Capacity : 11.72 kW *Sensible Capacity -: kW
*EKEXV 500 : 0
*Suction Pipe Size : 28.6
*Liquid Pipe Size : 12.7
3 UVC Lamp

Quantity UVC Lamps / Row


*UVC Lamp Length (mm) and
1554mm 1148mm 843mm 436mm
Watts
155W 120W 87W 48W
*Quantity Lamps / Row 0 0 0 1
*No. of Row(s) : 2
Incident Light Intensity (μw/cm2)
UVC Lamp Type : High Output

Page 2/6 Printed On 12/04/2022 10:35 AM


DAIKIN REFRIGERATION MALAYSIA SDN. BHD.Time Code : 20220412103318
Project Name : HOSPITAL DE CONTINGENCIA
AHU TECHNICAL REPORT AHU No. : UMA-01
Model Name : D DM1-0404B
D for DAIKIN
VRV AHU Model: AHUR16CBLJY2
Software Version : EPOCH 5.0 Patch 4.01 Report Date : 12/4/2022 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 573


Database Version : 2022.04.01 1020 CFM 0.48 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2022.04.01 -
Flow Rate :

Electrical Connection : 120-277VAC, 1ph, 50/60Hz


Min 1274
Total Elec. Load (Watts) : 96
UVP/Row (Watts) @12deg 13
:
Max 3685
Ballast Type : Electronic
Mounting Frame : Aluminium and Stainless Steel Components
*Monitoring System : No
Extra Pressure Drop : 0.00 Pa

# Factory default will install micro switch on 1 door nearest to the UV light. If more microswitch option on others door is required, please select it in other component's accessory
option.

No. Accessory Name Qty


* Door Micro Switch 1
4 SUPPLY FAN

GENERAL FAN MOTOR


Discharge Arrangement : Front Type : Centrifugal Backward TEFC Squirrel Cage
*Motor Type :
1020.00 CFM Brand : Kruger Induction
*Supply Air Volume
Flow Rate : 0.48 m³/s *Model : BDB250CM *Eff Type : IE2 (High eff)
*Altitude : 0.00 m Fan Size : 250 mm *Brand : TECO
*Air Temperature : 20.00 °C Disch. Open (HxW) : 330x330 mm :1.10
*Motor Output Power :1.10 kW
Air Density : 1.20 kg/m³ At Frequency : 60 hz Frame Size : 90S

Internal Static Max. Fan Speed : 3600 RPM N Voltage : 380 V


794.51 Pa
Pressure : Total Efficiency : 57.7 % N Current : 2.57 A

External Static Static Efficiency : 57.0 % Efficiency : 84 %


249.09 Pa
Pressure : Duct Velocity : - m/s Speed : 1740 RPM

Other Static *Speed : 3113 RPM Fan System Input


9.95 Pa 1.27 kW
Pressure : *Shaft Diameter : 20 mm Power :

Velocity Pressure : 12.90 Pa *Shaft Power : 0.89 kW Service Factor : 20 %


Extra Pressure Drop: 0.00 Pa Shaft Power/mtr eff: 1.06 kW Speed Reserve : 0 %
*Total Pressure : 1066.45 Pa Specific Fan Power : 2.20 kW/(m³/s) Watt / CMH : 0.61
*VPT : No *Standby motor with *Electrical Supply : 380V/3Ph/60Hz
No
*VFD : Yes heater : *Pole : 4

VFD Panel Mounted *Door Type : Hinged *Shaft Diameter : 24 mm


*Electrical Panel :
On AHU *Door Handle Type : Standard *Space Heater : No
*Thermistor : No
# Design based on wet coil condition.

# The fan system effect is taken into account in the fan performance.

Sound Power
Sound Power, Lw 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Total (dBA)
In-duct Outdoor Air dB 93 91 88 82 77 74 71 66 85
In-duct Supply Air dB 97 101 96 88 82 79 74 69 92
Casing Sound Power Level dB 92 95 86 77 68 60 59 38 82

Page 3/6 Printed On 12/04/2022 10:35 AM


DAIKIN REFRIGERATION MALAYSIA SDN. BHD.Time Code : 20220412103318
Project Name : HOSPITAL DE CONTINGENCIA
AHU TECHNICAL REPORT AHU No. : UMA-01
Model Name : D DM1-0404B
D for DAIKIN
VRV AHU Model: AHUR16CBLJY2
Software Version : EPOCH 5.0 Patch 4.01 Report Date : 12/4/2022 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 573


Database Version : 2022.04.01 1020 CFM 0.48 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2022.04.01 -
Flow Rate :

5 DIFFUSER

Diffuser Height : 430 mm Diffuser Width : 430 mm Pressure Drop : 50.00 Pa


Extra Pressure Drop: 0.00 Pa
6 ELECTRIC HEATER

Volume : 0.48 m³/s EDB / EWB : 13.83 / 13.65 °C


*Wiring Connection : 1 Phase LDB / LWB : 18.90 / 20.58 °C Heater Capacity : 3 kW
Power Supply : 220V/1PH/60Hz Air Pressure Drop : 0 Pa
*Heater Voltage : 220V/1Ph *U-Form : 1 KW 2 KW 2.5 KW 3 KW Extra Pressure Drop : 0.00 Pa
*Heater Arrangement: Vertical (STD) *Quantity : 3 0 0 0 *Main Terminal No
::No
*Control Panel Type : Basic *RH Controller : None *Sensor Type : None
*Control Type : 3 Steps
Step 1 : 1 kW Step 2 : 1 kW Step 3 : 1 kW
Step 4 : 0 kW Step 5 : 0 kW Step 6 : 0 kW
7 PRIMARY FILTER

*Type AmAir
: 300E Grade/Class : ePM Coarse / G4 Filter Face Velocity : 1.36 m/s
*Filter Media Yes
: (Factory Supply) Moisture Resistant Initial or Clean
Casing Material : 30.79 Pa
*Holding Frame Sliding
: Beverage Board Pressure Drop :
Final Pressure Drop :
*Quantity (24'' x 24'') 1: Non-woven cotton 80.79 Pa
Media : Design Pressure
*Quantity (20'' x 24'') 0: Synthetic Blend 55.79 Pa
Drop:
*Quantity (16'' x 24'') 0: Filter Energy Extra Pressure Drop 0.00
0
: .00 Pa
-
*Quantity (12'' x 24'') 0: Performance :

*Spare Filter Qty (set) 0: *Door Type : Hinged *Door Handle Type Standard
::Standard
7 SECONDARY FILTER

*Type V
VariCel
: ariCel II 80-85%-4" (50%) Grade/Class : ePM1 / F7 Filter Face Velocity : 1.36 m/s
*Filter Media Yes
: (Factory Supply) Moisture resistant Initial or Clean
Casing Material : 44.93 Pa
*Holding Frame Sliding
: Beverage board Pressure Drop :

*Quantity (24'' x 24'') 1: Final Pressure Drop: 134.79 Pa


Media : Ultra-fine Fibre Glass
*Quantity (20'' x 24'') 0: Design Pressure
89.86 Pa
*Quantity (16'' x 24'') 0: Drop:
Filter Energy
D
*Quantity (12'' x 24'') 0: Performance : Extra Pressure Drop : 0.00 Pa
*Spare Filter Qty (set) 0: *Door Type : Hinged *Door Handle Type Standard
::Standard
8 HEPA FILTER

Type AstroCel
: I 99.97% Grade/Class : E12 Filter Face Velocity : 1.29 m/s
*Filter Media Yes
: (Factory Supply) Initial or Clean
*Holding Frame Universal
: 195.65 Pa
Casing Material Galvanized
: Steel Pressure Drop :

*Quantity (24" x24 ") 1


: Ultra-fine retardant Fibre Final Pressure Drop : 600 Pa
Media :
*Quantity (20" x24 ") 0
: Glass
Design Pressure
397.82 Pa
*Quantity (16" x24 ") 0
: Drop:
Filter Energy
-
*Quantity (12" x24 ") 0
: Performance : Extra Pressure Drop : 0.00 Pa

Page 4/6 Printed On 12/04/2022 10:35 AM


DAIKIN REFRIGERATION MALAYSIA SDN. BHD.Time Code : 20220412103318
Project Name : HOSPITAL DE CONTINGENCIA
AHU TECHNICAL REPORT AHU No. : UMA-01
Model Name : D DM1-0404B
D for DAIKIN
VRV AHU Model: AHUR16CBLJY2
Software Version : EPOCH 5.0 Patch 4.01 Report Date : 12/4/2022 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 573


Database Version : 2022.04.01 1020 CFM 0.48 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2022.04.01 -
Flow Rate :

*Spare Filter Qty (set) 0: Door Type Hinged


::Hinged Door Handle Type : Standard

DOOR LOCATION

No Component Name Location No Component Name Location


1 Supply Fan Right 1 Hepa Filter Right
2 Pri + Sec Filter Right

UNIT MODEL REMARK


CUSTOMER :
MANUFACTURER :

SPECIAL REMARK

No Component Name Remark


1. For unit total height exceeded 2550 mm, or section length and width exceeded 2250 mm, it will
be delivered in SKD/CKD with standard container unless specified by customer to be still in CBU
mode and using open-top/flat rack containers.
1 Unit Model
2. Electrical wiring design and installation on the unit are based on factory standard practice. All
installation activities must be carried out by qualified personnel, and shall ensure compliant with
relevant local laws and regulations.

Page 5/6 Printed On 12/04/2022 10:35 AM