Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

1 2 3 4 5 6 7 8

+401
EXISTING 400kV LINE-1 SLD
MAIN BUS-1
@ABB 2010

A A
400kV BUS-1
MAIN BUS-2
400kV BUS-2
-Q1 -Q2
M M
Q2 Q1 Q2 Q1

-Q51
C:\user data\VR PRO 18.12.2020\3100128876_BALCO_400kV_ CRP for Bypass system ICT & Line_VR\16 - As Manufactured CRP Schemes\1. Native format\1MNS800771-CAAA_400kV ICT_LINE CRP_R4A.e3s

Q51
CT Q51
B Q0 B
-Q0
P Q0
M
CT

Q52 89T CT
P1 7SA522 89TE
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

CORE-1 MAIN-1 DIST PROTN.


Q52
2000-1000/1A 21.1, 67N
FROM LINE PT Q9
CL:PX CORE-1
7SA6
Q9
CORE-2 MAIN-2 DIST PROTN. Q8 52CB
2000-1000/1A 21.2, 67N
CL:PX Q8
METERING 6MD66
C C
EM BCU
CORE-3
CT 2000-1000/1A 315 MVA
CL:0.2s,20VA 7SS523
ICT
400/220/33kV
CORE-4 BUS MAIN-2 DIFF PROTN. 1 BYPASS LINE ICT-1
87.2 2 00ADB08GS031
2000-1000/1A
CL:PX 7SS523 7SS523 3
BUS MAIN-2 DIFF PROTN. BREAKER FAILURE
400kV LINE-1
CORE-5 87.1 (INBUILT 87.1) 00ADB08GS030
2000-1000/1A 89T
CL:PX P2

00ADB08GS032
-Q52
D -Q9 CT D
M

00ADB08GS000

-Q8

00ADB08GS020 00ADB08GS020
INSIDE GIS BUILDING
OUTSIDE GIS BUILDING 220kV BUS-2
400kV 110V 110V 110V /104.A2 TO BYPASS
√3 √3 √3 √3 . LINE 220kV BUS-1
CORE-1 : CL:3P,100VA
E E
CORE-2 : CL:3P,100VA
CORE-3 : CL:0.2,100VA

LA

REF DWG:
(4)G719EA-AG9132-W4R01-C
TO LINE-1 SH-04 OF 41

Based on Prepared 30.06.2020 SHILPA DESAI Title 400kV CONTROL & RELAY PANEL Doc. kind. Circuit diagram Ref.Des. =4R
05 AS MANUFACTURED 31.12.2020 SS Approved 02.07.2020 VIGNESWARAN R 400/220/33kV ICT & LINE DCC
F F
04 AR MODIFICATION 3.11.2020 VR Project 400kV GIS BALCO 1200MW TPP, KORBA PROTECTION SLD Resp. dept. PG-GAS Rev. ind. 05 Language en
Print: 12/31/2020

03 REVISED AS PER CUSTOMER COMMENTS 26.09.2020 SS BITCO LTD. Sheet 103


Rev. Revision note Date Name 3100128876
ABB INDIA LTD
Doc. no. 1MNS800771-CAAA n. sheet 104
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+400kV LINE CUM TRANSFORMER BAY +4RLA
400kV ICT-1 & LINE-1 CRP
400kV INCOMING LINE-1 -FN3
@ABB 2010

A RET670-1/IEC61850/MAIN-1 TRAFO.DIFF. PROTN. A

/103.E3
87T 3Id/I> 49 67 3I> 67N IN> 24-HV U/f> 95DR DR
PDIF PTTR PTOC PIOC PVPH RDRE
FROM EXISTING LV
CT CORE-1

FROM LINE PT
P1 . CORE-2
CORE-1
2000-1000/1A -FN4
C:\user data\VR PRO 18.12.2020\3100128876_BALCO_400kV_ CRP for Bypass system ICT & Line_VR\16 - As Manufactured CRP Schemes\1. Native format\1MNS800771-CAAA_400kV ICT_LINE CRP_R4A.e3s

CL:PX RET670-2/IEC61850/MAIN-2 TRAFO.DIFF. PROTN.

B B
CORE-2 87T 3Id/I> 49 24-LV U/f> 95DR DR
2000-1000/1A PDIF PTTR PVPH RDRE
CL:PX FROM EXISTING LV
CT CORE-1
FROM 220kV
CORE-3 SEL BUS PT
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

CT 2000-1000/1A
CL:0.2,20VA
CORE-4
2000-1000/1A -FN2
CL:PX REL670/IEC61850/MAIN-1 DIST. PROTN.

CORE-5
21 Z< 60 67 3I> 67N IN> 50BF 95DR DR
2000-1000/1A
C PDIS ZCVPSOF RFUF PTOC PTOC BF RDRE C
CL:PX
P2
FROM LINE PT
CORE-1

-Q9 M

-KF1
MAKE:SECURE REC650/IEC61850/BAY CONTROL UNIT/DC1/DC2
MODEL:PREMEIR 300
-Q51
P,Q,S, I U 25 SC/VC 79 52 89T 95DR DR
TVM I,U,f
CVMMXN CMMXU VMMXU SESRSYN SMBRREC CSWI CSWI RDRE

D D
FROM LINE PT
-Q0 P
CORE-3 LV SEL BUS PT CORE-1
M
R-Y PH ONLY

-FN5
P444/IEC61850/MAIN-2 DIST. PROTN.

21 Z< 60 67 3I> 67N IN> 50BF 95DR DR


PDIS ZCVPSOF RFUF PTOC PTOC BF RDRE
/106.A3

FROM LINE PT
E CORE-2
E
TO ICT-1

NOTE:- WIRING PROVISION ARE GIVEN. IED(FN4,FN5) &


AUX.RELAYS & TEST SW. & CSS-2 SW. REMOVED

Based on Prepared 30.06.2020 SHILPA DESAI Title 400kV CONTROL & RELAY PANEL Doc. kind. Circuit diagram Ref.Des. =4R
05 AS MANUFACTURED 31.12.2020 SS Approved 02.07.2020 VIGNESWARAN R 400/220/33kV ICT & LINE DCC
F F
04 AR MODIFICATION 3.11.2020 VR Project 400kV GIS BALCO 1200MW TPP, KORBA PROTECTION SLD Resp. dept. PG-GAS Rev. ind. 05 Language en
Print: 12/31/2020

03 REVISED AS PER CUSTOMER COMMENTS 26.09.2020 SS BITCO LTD. Sheet 104


Rev. Revision note Date Name 3100128876
ABB INDIA LTD
Doc. no. 1MNS800771-CAAA n. sheet 105
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+402
EXISTING 400kV ICT-1 BAY
MAIN BUS-1
@ABB 2010

A A
MAIN BUS-2

+4RLA
-Q1 -Q2 400kV ICT-1 & LINE-1 CRP
M M
C:\user data\VR PRO 18.12.2020\3100128876_BALCO_400kV_ CRP for Bypass system ICT & Line_VR\16 - As Manufactured CRP Schemes\1. Native format\1MNS800771-CAAA_400kV ICT_LINE CRP_R4A.e3s

-Q51
B -Q0 B
/106.E3 FROM LV SIDE
P
CT:T1 CORE-1
M

-FN4
7UT613 6MD66 RET670-2/IEC61850/TRAFO.DIFF. PROTN.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

CORE-1 MAIN-1 DIFF PROTN. O/C & E/F PROTN


2000-1000/1A 87.1R 67.2 HV 64R IN>>
64R
CL:PX PIOC
7UT613
CORE-2 DIFF +REF PROTN FROM BCT CT-1
87.2R+64.2R /106.B3
2000-1000/1A 64R
CL:PX
C C
CORE-3 SPARE
/106.D3 FROM LV SIDE
CT 2000-1000/1A CT:T1 CORE-2
CL:0.2s,20VA 7SS523
CORE-4 BUS MAIN-2 DIFF PROTN.
2000-1000/1A 87.2
CL:PX 7SS523 7SS523
BUS MAIN-2 DIFF PROTN. BREAKER FAILURE
CORE-5 87.1 (INBUILT 87.1)
2000-1000/1A
CL:PX P2
-Q52

D -Q9 D
M

REF DWG:
-Q8 (4)G719EA-AG9132-W4R02-C
SH-04 OF 41

INSIDE GIS BUILDING


OUTSIDE GIS BUILDING

E E
/106.A2

TO ICT-1

Based on Prepared 30.06.2020 SHILPA DESAI Title 400kV CONTROL & RELAY PANEL Doc. kind. Circuit diagram Ref.Des. =4R
05 AS MANUFACTURED 31.12.2020 SS Approved 02.07.2020 VIGNESWARAN R 400/220/33kV ICT & LINE DCC
F F
04 AR MODIFICATION 3.11.2020 VR Project 400kV GIS BALCO 1200MW TPP, KORBA PROTECTION SLD Resp. dept. PG-GAS Rev. ind. 05 Language en
Print: 12/31/2020

03 REVISED AS PER CUSTOMER COMMENTS 26.09.2020 SS BITCO LTD. Sheet 105


Rev. Revision note Date Name 3100128876
ABB INDIA LTD
Doc. no. 1MNS800771-CAAA n. sheet 106
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+402RA
EXISTING 400kV ICT-1 BAY
FROM 400kV ICT-1
FROM 400kV BYPASS LINE
@ABB 2010

A A

/105.E2

/104.E2
PART OF ABB

BCT-CT-2 MAKE:SECURE
1000/1A METERING-PREMEIR 300 6MD66
CL:0.2,30VA TVM BCU

FROM LINE PT
CORE-3
C:\user data\VR PRO 18.12.2020\3100128876_BALCO_400kV_ CRP for Bypass system ICT & Line_VR\16 - As Manufactured CRP Schemes\1. Native format\1MNS800771-CAAA_400kV ICT_LINE CRP_R4A.e3s

BCT-CT-1 /105.C4 TO HV CORE-2


1600/1A
B CL:PS B

315 MVA
400/220/33kV
ICT-1 P2 P1
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

CORE-1

CORE-2 SPARE

00ADB08GS031
C 00ADB08GS030 M
C

00ADB08GS032
P2

2X600/1A METERING
CL:0.2S
2X600/1A NCCS
CL:0.5
2X1200/1A
CL:5P30 L80-WLB8000-8

D 2X1200/1A D
CL:TPY GMC 22B-I
CT 2X1200/1A
CL:TPY
CT:T1 CORE-2 GMC 22B-I
2000-1000/1A
CL:PX TO HV SIDE
/105.C3
CT:T1 CORE-1 CORE-2
2000-1000/1A FROM HV SIDE
/105.B4
CL:PX CORE-1
P1
M

00ADB08GS000 P
E E
REF DWG:
(4)G719EA-AG9132-W4R02-C
SH-04 OF 41
00ADB08GS020 M 00ADB08GS020 M

220kV MAIN BUS-2

220kV MAIN BUS-1

Based on Prepared 30.06.2020 SHILPA DESAI Title 400kV CONTROL & RELAY PANEL Doc. kind. Circuit diagram Ref.Des. =4R
05 AS MANUFACTURED 31.12.2020 SS Approved 02.07.2020 VIGNESWARAN R 400/220/33kV ICT & LINE DCC
F F
04 AR MODIFICATION 3.11.2020 VR Project 400kV GIS BALCO 1200MW TPP, KORBA PROTECTION SLD Resp. dept. PG-GAS Rev. ind. 05 Language en
Print: 12/31/2020

03 REVISED AS PER CUSTOMER COMMENTS 26.09.2020 SS BITCO LTD. Sheet 106


Rev. Revision note Date Name 3100128876
ABB INDIA LTD
Doc. no. 1MNS800771-CAAA n. sheet 107
1MYN691003-102(A3)REV01

1 2 3 4 5 6 7 8

You might also like