GE Mark VIVIe HMI and Software Questions

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 42

Hello,

I am a controls system engineer and I am rather new to turbine controls,


particularly the GE Mark VI and VIe DCS software. I am studying this
system for future work on a company client's system and am using a
VMWare image to train with on the software. I have gleaned over a
number of the manuals pertaining to the various features of the system
and have gone over a number of topics already on this website over the
system, and while I like to say I have a decent rudimentary
understanding of the architecture and functionality of the system, there
are still some areas I would like information on (made blatantly aware
by my boss's thorough questioning). My questions on the Mark VI and
VIe are as listed:

1) I understand that the controllers communicate through the EGD


Network and that the HMI reads data via UDP and sends commands via
CMP through the EGD. Is the EGD Network supported on the EGD
Server on the OPC DA Server for both VIe and VI or just VIe? If not
how do they differ?

2) Is CIMPLICITY the only GE supplied HMI? If so how does it relate


to the graphics editing functionality on Toolbox for Mark VI? (I do not
have CIMPLICITY on the VMWare image I possess.)
3) Is the HMI built from a singular data source or do all operator
workstations require to have the same HMI graphics individually
installed? If the former, how is this done?

4) Is WorkstationST and ToolboxST separate applications or is


WorkstationST nested in ToolboxST? (I cannot access ToolboxST as I
do not have the USB dongle.)

5) Is OPC necessary for multiple operator workstations? Can the


operator HMIs simply interface with just the EGD?

I'm sure I'll come up with more questions, but for now these are what I
have. I appreciate any time being taken to answer these.

Thanks.
 
Like Reply
Report

CSA
Jul 9, 2014

 #2

Kevin,

Welcome to the world of Speedtronic turbine control systems in the age


of Mark VI and Mark VIe. Good on you for reading the available
documentation as you begin your learning.

It's not really clear what your job will be working with the Mark
VI/Mark VIe....

1) I'm not quite sure I understand this statement, or what you're trying to
ascertain. In my understanding, "controllers" refers to the controllers in
the turbine control panel--usually called <R>, <S> and <T> (in a TMR
control system). I tend to disassociate the HMI from the controllers for a
couple of reasons. The HMI is first and foremost a device that is not
supposed to perform any turbine control or protection functions. It's
primarily a way for humans to send commands to a turbine control,
graphically view operation, and manage alarms. GE chooses to put
Toolbox (or ToolboxST) on the HMI, and Toolbox can be used to
configure the turbine control panel and for more detailed troubleshooting
and data-gathering (using Trend Recorder, Dynamic Data Recorders,
Watch Windows, and dynamic "rung" display). The HMI, in its current
form, can be used with Mark V, Mark VI and Mark VIe. (There were
some HMIs which were used with some Mark IV turbine control panels,
but GE doesn't really support--nor do they want to support--them.)

There were some Mark V operator interfaces which actually did some
control of multiple turbines (load control) but that was rare and really
was a special case, again, because the operator interface ("HMI") isn't
supposed to perform any control or protection functions (in the GE way
of controlling turbines)--and sending commands isn't really considered
"control." Commands could be sent by discrete and/or analog inputs, so
the HMI could be "bypassed" (though it would be difficult).

The designated controller (usually <R> in a healthy TMR control panel)


broadcasts information onto the UDH Unit Data Highway), which is
then picked up by appropriately configured HMIs, also on the UDH, and
displays that data (or alarms). It's my understanding that both the Mark
VI and the Mark VIe must have any data points to be displayed via
CIMPLICITY (including commands) configured on one or more EGD
"pages", and then TCI (for a Mark VI HMI) or WorkstationST (for a
Mark VIe HMI) can then make the information available to
CIMPLICITY (via a CIMPLICITY Project for Mark VI HMIs, and via
OPC for Mark VIe HMIs).
As for how the controllers communicate between themselves--that's
some version of an Ethernet-based network, called the IONET. The HMI
does not have access to the IONET (directly), and must make requests
for information of the designated controller via EGD over the UDH. I'm
not sure if UDP is the method by which information is transferred
between the HMIs and the designated controller (for sending commands
and managing alarms and viewing data); that's generally all background
stuff (for me, anyway).

A Mark VI HMI uses a proprietary MS-Windows service, TCI, to allow


communication over the UDH with Mark VI turbine controls
(specifically, the designated controller). A Mark VIe HMI uses
WorkstationST (also proprietary) to allow communication over the UDH
with Mark VIe turbine controls (again, via the designated controller). In
my opinion, this is done to prevent third-party controls from directly
communicating with Mark VI controllers. GE doesn't want to have to
test and qualify and certify a multitude of control systems and methods--
one can only imagine how expensive that would be, because every
person believes their method would be best for their application and it
would just be a never-ending job. (It would be easier if GE had a
published standard they adhered to, but, then that would make their
system "open" and they really don't want others to supplant their HMIs).
Now, a LOT of people are reading this and saying, "BUT!!! But,"
because they are going to confuse how Toolbox and ToolboxST
communicate with the Mark VI controllers with how the HMI (TCI or
WorkstationST) communicate with controllers. While both (HMI and
Toolbox/ToolboxST) communicate over the UDH, they are not the same
methods of communicating. When Toolbox/ToolboxST are on line with
a Mark VI, they are not using EGD--they are communicating at a more
direct ("lower") level.

So, I hope you are getting the idea now--it's a very tangled and intricate
network and there's not a single answer. And, to complicate matters even
further, there are some early Mark VIe HMIs that a mix of TCI and
WorkstationST--sort of a "hybrid" HMI, if you will. Makes for a lot of
fun for Customers and field service personnel.

The good news is: Once it's all set up and communicating correctly
(sometimes easier said than done), it all works--and works very well. It's
usually humans that screw up the works!

And here's another CRITICALLY important fact you need to know:


Alarms and Events are handled by TCI for Mark VI HMIs, and by
WorkstationST for Mark VIe HMIs. So, if you're thinking you can
implement EGD on some control platform/equipment and communicate
with the designated controller of a Mark VI or Mark VIe--you can,
<b>BUT</b> you can't get Alarms and Events because they are NOT
handled via EGD. (Isn't this fun?)

2) If we're talking about heavy duty gas turbines and steam turbines--
yes, the only HMIs GE supplies are those with CIMPLICITY. Again,
because data has to be transmitted via EGD between the designated
Mark VI controller and the HMI (for TCI or WorkstationST to then pass
to the CIMPLICITY Project (for Mark VI) or CIMPLICITY Viewer (via
OPC for Mark VIe), data points and commands for CIMPLICITY have
to be handled through EGD. Toolbox's graphics capability is entirely
different from CIMPLICITY, because Toolbox communicates more
directly with the Mark VI than via EGD. I'm not sure of the graphics
capability of ToolboxST these days; a lot was intended to be done with
graphics capabilities in ToolboxST, but it never seemed to come to
fruition.

3) This is one of the HUGE problems with GE HMIs using


CIMPLICITY: each HMI has its own display files, and changes made on
any HMI have to be manually transferred to other HMIs. I have been to
sites where every display on every HMI is different--because people
mistakenly thought that a change on one HMI would automatically be
"populated" to every other HMI--and as implemented on Speedtronic
HMIs CIMPLICITY doesn't do that. It can really be quite a mess.

4) WorkstationST and ToolboxST are two separate applications. An


HMI can have only WorkstationST and CIMPLICITY installed on it and
can be used to operate a turbine and auxiliaries. A properly configured
PC can only have ToolboxST installed on it and be capable of
communicating via the UDH with Mark VI controllers--without
WorkstationST.

5) Not quite sure I understand your question, or the intent of the


question. GE supplies HMIs that are either "servers" or "viewers". And
then there's the whole OPC thing, and again, for me anyway, that's all
background stuff. GE seems to be using OPC for Mark VIe HMIs
because they don't have to pay for a "full" license of CIMPLICITY,
using just the "viewer" option via OPC. I have heard that some sites
actually have other control systems capable of getting data via OPC
from the Mark VIe HMI running WorkstationST--but the data points
have to be configured in ToolboxST to be on the EGD pages for
WorkstationST to pass to OPC. (Again, isn't this fun?)

Myself, I consider GE HMIs to be a necessary EVIL (in cap's). They are


<b>HORRIBLY</b>, horribly documented, and the methods by which
they can be modified (points added) have changed multiple times
without any documentation--ever. Also, there is usually a hodge-podge
of different types of command types on any CIMPLICITY display, from
SRTP pushbuttons to SmartObjects to scripts--and it can be absolutely
maddening trying to figure out how to make them work (because many
times they come from the factory improperly configured). In my career
with GE I spent more time (by several multiples) trying to fix non-
working HMIs than I ever spent fixing broken or incorrect turbine
control logic or parameters. They look "cool", but they are a mess, pure
and simple.

And, all the background stuff is just that--background stuff. If I


understand the gist of your questions it sounds like you or somebody
wants to try to integrate Mark VI and/or Mark VIe control systems into
some other plant control network--or some other HMI
application/software. And, that, my friend, is not as easy as it seems. Not
at all. There are a couple of OPC companies who advertise they can
communicate with Mark V, Mark VI and Mark VIe--but I don't think
any of them can handle Alarms and Events. And there is only one
company I know of that can fully replace the functionality of a GE Mark
V HMI/<I> (an <I> is the command-line driven operator interface
provided with early Mark V turbine control systems) without using
CIMPLICITY, and also handle Alarms and Events from Mark IV, Mark
V, and Mark VI (soon, also, Mark VIe): CSE Engineering, Inc.
(www.itc-info-us) Again, there are several vendors who can display
information and provide command capability, but only one that can do it
without CIMPLICITY.

So, if you have more questions along these lines ("background stuff")
please try to be more specific about what you are wanting or intending to
do and perhaps we can provide some suggestions, or experience. To my
way of thinking, as "important" as HMIs are--they don't do anything to
control or protect the turbine, which is another reason I think they aren't
very well documented or supported by GE. They are just a necessary
EVIL, with the real "work" done by the Mark VI/Mark VIe. And from
personal experience, I can tell you: A <b>LOT</b> of people have spent
a great deal of time and money trying to "bypass" GE HMIs with
varying degrees of success, and a lot of failure--because a lot of reverse
engineering has to be done. And, there's really only one company that's
done that and stands behind their product (and I'm referring to being able
to completely supplant/replace a GE Mark V HMI/<I>--not just display
data and provide a command interface).
 
Like Reply
Report

Kevin
Jul 9, 2014

 #3

CSA,

Thanks for answering my questions with such depth. I've noted your
presence on this subject prior and am glad to have your attention. I can
definitely use guidance as I venture into this system.

Frankly I do not specifically know what I myself will be involved with


on the Mark VI/VIe, but I do know that my company will be involved on
programming a BMS and performing alarm management for a combined
cycle plant. From what I am aware, we are not trying to integrate the
Mark VI/VIe control system with a third-party HMI application. What I
hope to learn is the architecture and structure of a GE Mark VI/VIe
control system and how it works within the intended scope of its design.
(Basically, a diagram and description of a Mark VI/VIe control system
layout would most likely answer most of my questions.)

Your answers to my questions lights up some areas but it also presents


more questions. Note that I have neither TCI nor WorkstationST on my
image so I have no tangible feel to them, so forgive me if I seem to have
the wrong understanding of their function.
1) So TCI and WorkstationST (which are separate applications) are the
services that relay the commands and inputs to and from the TMR
controllers via EGD over the UDH (from what I read using UDP and
CMP for reading and writing, respectively). However, alarms are not
transmitted likewise. Are they transmitted on the same UDH just without
EGD?

2) Is TCI and WorkstationST a part of the CIMPLICITY HMI? Where


would alarms typically be displayed?

3) I have a project file from the plant that shows all alarm points being
defined on the EGD. What would be the reason for this if EGD is not
used for transmitting alarms to TCI/WorkstationST?

4) Does it matter to CIMPLICITY whether the Alarm check box is


checked for alarms? Or is it merely useful for referencing?

5) Am I correct in saying that communication over the IONet is


performed with EGD?

6) I understand for Mark VIe, you can have viewers on multiple operator
workstations that communicate via OPC to WorkstationST. Does that
mean in this setup you can just have an OPC client and the viewer HMI
(CIMPLICITY?) on an operator workstation, and WorkstationST and
OPC server on a server?

7) Is it possible for the HMI graphics to be located on a server and all


other operator workstations access the same graphic files via TCP/IP?
That way any changes made can be translated to all workstations.

8) Is there an intermediary module/server between the TMR controllers


and the TCIs/WorkstationSTs that data must flow through? From
reading the documentation on OPC DA Server, it appeared as if there
was an EGD Server that the Mark VIe and any OPC client (e.g. HMI)
communicated with on a WorkstationST computer. Also, whether or not
OPC is used, is there a EGD server/service on every TCI/WorkstationST
computer?

Again, thank you for your previous answers and for the time you take to
answer all these.
 
Like Reply
Report
CSA

Jul 11, 2014

 #4

Kevin,

As I've said, I'm not really an expert by any stretch of the imagination on
all the "background" stuff for HMIs. While it can be a real struggle to
get all the communications between HMIs and Mark VIs/Mark VIes
working correctly, when it does work it works very well. I've been to
quite a few sites where it's "just working" but not properly--meaning
some HMIs are properly configured and others are configured
completely differently and both of the experience periods of intermittent
operation, but because there is virtually no written documentation about
how everything should be configured on any given job people are
actually reluctant to make any changes even though they are dissatisfied
with the way things operate! (I know someone or some people are not
pleased when I say these things, but it's sadly true. And, GE should be
held accountable for this--but almost never is. My fervent hope is that
someone in GE will read this and enough people in GE will see this and
things will actually get fixed--a dream, but everyone is allowed to
dream, even if it's a virtual impossibility.)

1) Yes; alarms and events are transmitted via broadcast on the same
UDH (there's only one UDH, though there may be redundant paths
(cables and switches). And, it's my understanding they are NOT
transmitted using EGD.

2) TCI and WorkstationST are separate "applications" (services) which


are installed separately on the HMI, and which are necessary primarily
for alarm/event handling and for passing information from EGD to
CIMPLICITY in the way that GE Salem implements EGD and
CIMPLICITY (which is many times different from the way other
divisions of GE implement CIMPLICITY).

3) The Alarm Window in CIMPLICITY implementations for Mark IV,


Mark V and Mark VI are special CIMPLICITY AMV objects. I believe
that somehow text messages get into the Project file for association with
and display in the Alarm Window and to the alarm printer. Again, it's
one of the background things that works, or it doesn't.

4) Not sure about that, but I believe that's what tells Toolbox how to
associate alarms and text messages. There is another Toolbox "device"
called an HMB device, and somehow alarm and event information gets
into the HMB device (which is for the HMIs) and then it gets pulled into
the CIMPLICITY project. That's my understanding, and it may or may
not be correct.

5) I do NOT believe IONET communication is done using EGD. I


believe it's a proprietary TCP/IP implementation over Ethernet. There's a
LOT that goes on over the IONET, even more on Mark VIes than Mark
VIs. I don't think EGD is sophisticated enough to be able to do that--and
I doubt very seriously that GE would make it that "easy" for others to
see what's going on on the IONET.

6) I believe that's also possible for Mark VI (Viewers using OPC), but,
again, I'm not an expert on HMIs and CIMPLICITY. But I don't think
what you're suggesting with a separate PC running WorkstationST and
an OPC server. I think WorkstationST is an OPC server of sorts for
CIMPLICITY Viewer. And I believe one needs a dongle (UPD) for
WorkstationST.

7) I don't believe CIMPLICITY can work that way. That may be true for
some of the newer versions of CIMPLICITY or PROFICY Machine
Edition, but I've never seen it--and I would have made note of it if I had.
That's one of the most maddening things about CIMPLICITY--every
HMI can have different displays, and while they can be copied between
HMIs, they have to be edited to make them specific to an HMI, and that
can be very difficult since there is/was no standard about how
CIMVIEW display files were made specific to any HMI. There are
multiple ways and even GE engineers in the factory don't know all of the
ways, nor the "proper" way as each version of TCI and WorkstationST
and CIMPLICITY and CIMPLICITY Service Pack is rolled out (and the
"proper" way can change significantly, or minorly, with any of those
programs). If one could go through every display on one HMI and
convert them all to the same configuration for being able to easily make
them specific on any HMI, that would be great. But, from painful
personal experience, that's extremely difficult and time-consuming and
one has to have contacts in GE to help with some of the configurations.

8) No. Again, I believe that is all handled by TCI/CIMPLICITY on


Mark VI, and WorkstationST on Mark VIe. I may be wrong, but that's
my understanding. I believe that CIMPLICITY (on GE Mark VI HMIs)
has a user-configurable OPC server, but I'm not sure if every version of
CIMPLICITY does. I don't know how "open" the OPC server is on
WorkstationST, but I imagine since OPC is supposed to be an open-
source communication means that one could use another OPC "device"
to get/send information to WorkstationST.
Again, I am probably taking some liberties with my understandings here,
but that's how I envision it. I spent a good deal of time avoiding
CIMPLICITY and all of this background stuff--somewhat to my
detriment, but every time I thought I had learned how this or that part of
the HMI and CIMPLICITY worked the next job I went to would be
different--sometimes completely, sometimes only enough to cause fits.
So, I just documented what worked and what didn't, sent the information
back to "the factory" and in a day or so (sometimes sooner) I would get
back a working configuration. Much easier than trying to learn
everything all over again several times a year.

I would be much more comfortable answering questions about Mark VI


or Mark VIe than about HMIs--which, again, I deem a necessary EVIL.
I'm probably only about two-thirds right with some of the low-level
details, but I'm hoping that someone will correct me--and help you (and
others!). There seems to be a GE employee or two lurking here from
time to time who offers useful information and corrections.
 
Like Reply
Report

Demigrog
Aug 26, 2014

 #5

Hello,

CSA covered a lot of ground, I’ll just fill in a few gaps and correct a few
details. I highly recommend joining the GE Connect website as soon as
you can; there is a lot more detail on there.

1) EGD is a UDP based protocol that is used for controller to controller,


controller to HMI, and controller to distributed I/O communications on
the Mark VI and Mark VIe. It is actually an open protocol, though only
GE and partners generally use it—it is available on Mark VI, Mark VIe,
GE PLCs, and a number of Drives products. EGD sends data at a set
rate, so network traffic is predictable and consistent. Since it is a
sessionless protocol that is broadcast or multicast, it can be very efficient
for fanning data out to multiple clients. The EGD spec also defines the
concept of an EGD Configuration Server (included in WorkstationST for
the Mark VIe) that contains the definition of all of the EGD produced
and consumed in the system; this allows consumers of data (ie HMIs) to
know when the server changes (ie someone added a point to a Mark
VIe), and potentially do dynamic binding and use the changes
immediately. CMP is a separate UDP protocol for sending commands
(with replication for redundancy) and is layered on top of the EGD
exchanges. The EGD protocol is also used for Mark VIe
communications to its I/O packs, but with hard-coded exchanges
specific to the pack type. From the Controller configuration in
ToolboxST, it is easy to setup EGD data; usually you just select a
variable and in its properties set its EGD Page. (Pages are simply
collections of points with a particular update rate and multicast address.)
Consuming an EGD point simply requires “referencing” a device in
ToolboxST, after which its EGD points are simply available.

2) CIMPLICITY is the official HMI for many of the products based on


the Mark VIe, including all of the heavy duty turbine products. Some
GE businesses use iFIX, and a few like Wind have their own SCADA
system. All of them communicate with the Mark VI/VIe control system
through an aggregating layer, either TCI or WorkstationST. Since
WorkstationST provides OPC DA, OPC UA, and OPC AE support, third
party HMIs are not uncommon for DCS systems, though rarely for
turbine control. The OPC AE protocol does allow third parties to access
alarm data, albeit in an imperfect way, as there is no open protocol for
alarms that is fully featured enough to implement, say, the ISA 18.2
alarm standard. CIMPLICITY has its pros and cons, and a lot of the
issues have more to do with how the screens were developed. For
example, most of the DCS screens for Mark VIe use lots of scripts to
automatically configure screen objects when the screens open. This
makes it easier to produce standard screens quickly, but complicates
customization—there is a lot of tribal knowledge involved.

3) As CSA mentioned, there is a lot of variability from site to site,


particularly retrofit sites (new units are a lot more consistent). I’ve seen
networked file shares as the source of a common configuration, but at
this point the best solution (IMO) is to use GE’s Configuration
Management Server and the WorkstationST HMI feature. The CMS
server (part of ControlST) handles version control and provides the
“master copy”, while the HMI feature automatically keeps HMI screens
on all workstations up to date.

4) ControlST is the name of the whole package, of which ToolboxST


and WorkstationST are components. WorkstationST is a management
platform for a collection of Windows Services performing a bunch of
different jobs. ToolboxST is the engineering and configuration tool for
the Mark VIe, but also is used to configure specific instances of
WorkstationST running on PCs in the control system. Not all
WorkstationST instances are HMIs, though every HMI must have a local
instance of WorkstationST. For example, you might have a PC with a
time card setup running WorkstationST as an NTP server. There are a lot
of features of WorkstationST that can be turned on for any particular
server, like protocol gateways, alarm scanners, HMI screen
synchronization, etc. WorkstationST also includes the Alarm Viewer

tool, which it sounds like you will probably know very well soon.

5) CIMPLICITY comes in two flavors at the moment: project based, and


advanced viewer. Since about 2008, GE’s HMIs use advanced viewer,
because it uses OPC DA to collect data, which has advantages in that
there is no “import” step for getting points into CIMPLICITY. Project
mode has a “DevCOM” that lets CIMPLICITY’s point manager natively
read EGD data. Other HMIs could potentially read EGD directly (the old
“COI” for Mark VI/EX2100 did that), but there is a big advantage to
using an aggregator like WorkstationST or CIMPLICITY’s point
manager: it can combine data from multiple sources, and abstracts the
details of the communications interfaces.

1A) Alarms are transmitted from the Mark VIe to the Alarm Server
component of WorkstationST via a proprietary TCP/IP protocol.
Because it is a Session based protocol, it uses up a little CPU on the
controller per client, which is one of the reasons for having an
aggregating layer like WorkstationST’s alarm server rather than a
connection from each HMI to the controller. The Mark VI was a little
different; it had another UDP based protocol for alarms, but the alarm
server on TCI or WorkstationST is still the aggregator.
2B) Alarms in a Mark VIe are best displayed in the stand along Alarm
Viewer tool. However, there is also an ActiveX control version of it that
is sometimes embedded into CIMPLICITY screens. Generally,
CIMPLICITY’s native alarm viewer isn’t used with the Mark VIe, as it
doesn’t support some of the features needed for standards like ISA 18.2.

3B) It isn’t uncommon for alarms to also be EGD points, largely to drive
indicators on HMI screens. Not a requirement, however.

Hope that helps. This is a very deep topic.


 
Like Reply
Report

junaidkhan

Mar 23, 2015

 #6

Hello Dear,

I'm Student of Electrical Engineering, Just reached on the end of our


course. I want to work on GE Mark VIe ICS. Can you provide me the
GE Mark VIe installed on VMware Machine or on VirtualBox Image?
I'll be really thankful to you, in this manner I can do some practice.
My Email is junaid.khan.sadozai@gmail.com

Thanks
 
Like Reply
Report

CSA

Mar 24, 2015

 #7

ToolboxST requires a UPD (USB Protective Device). Without a UPD


you can't open the Mark VIe configuration application. The only way I
know of to get a dongle is to buy a copy of ToolboxST from GE or one
of its packagers.

People need to remember that just because something can be transmitted


electronically doesn't mean it's not protected by copyright laws and IP
(Intellectual Property) laws. GE employees earn a living by writing
software for GE. They have families and lives they support by writing
software and that software is protected property which is illegal to pirate
or steal--even for academic purposes.

How would you feel if an application you wrote, invested your time,
knowledge and creative talents that you were using to support your
family, pay for food, housing, clothing and savings, was made available
for free by others just because they thought it should be freely
available--or, more likely, "just because they could distribute it freely"?
 
Like Reply
Report

Jeffery Johnston

Apr 16, 2015

 #8

Kevin,

You seem very proficient in the GE world of turbine controls and i'm a
new controls engineer with a lot to learn. i'm hoping you might be able
to help with a project i'm working on. We are attempting to connect a
Fogg skid (Allen Bradley PLC) to the HMI using a MVI69-EGD card
and having much difficulty. Would you happen to have any experience
with connecting a 3rd party controller not to the Mark VI but to the
toolbox?
 
Like Reply
Report

five

Aug 13, 2015

 #9

I sell USB dongles for markVie HMI. cost is 1000 USD.

please let me know if anybody require it


 
Like Reply
Report

CSA
Aug 17, 2015

 #10

Hi, five,

Can you post your contact information:

email address

phone number

Do these dongles work with Mark V and Mark VI, also?

Thanks!!!
 
Like Reply
Report

Bob johnston

Aug 17, 2015

 #11

Do you have MKVI dongles. Can you post your contact details please.
 
Like Reply
Report

glenmorangie

Aug 23, 2015

 #12

Can you please reply with some contact details?


 
Like Reply
Report

Javier Salas

Sep 30, 2016

 #13

Do you have available this Dongle? I need one


 
Like Reply
Report

listm

Oct 1, 2016

 #14

>I sell USB dongles for markVie HMI. cost is 1000 USD.
>please let me know if anybody require it

I just want to point out Control.com's policy on buying and selling in the
forum. On http://control.com/guidelns.php, item 4, it says the following:

"Currently, Control.com doesn't allow buying and selling items via our
forum. If you are looking for something in particular, such as an item of
used equipment, you might word your post to ask for recommendations
on reputable vendors of such items."

If the poster offering these dongles (Five) is a reputable vendor, he or


she should post contact information.

Regards,
One of the Control.com moderators
 
Like Reply
Report

Jack

Oct 3, 2016

 #15

Provide your e-mail id as well

<i><b>Moderator's note:</b> Just to clarify, it is the <b>vendor</b>


who must provide contact information.</i>
 
Like Reply
Report

CRSwanson

Jan 4, 2017

 #16

CSA,

The Mark VIe is being considered for a combined cycle power plant I
work for. 2 GTs 1 ST and 2 HRSGs. The system would replace our
current plant wide DCS including GTs, ST, HRSGs, switchgear, MCCs,
water treatment, everything. The current system is an old ABB
Procontrol P13 DCS.

1) Have your thoughts and experience with the Mark VIe changed since
2014?

2) Has the HMI improved?

3) Do you think the Mark VIe is a good system for the entire plant or is
it better suited for GT control only?

4) Does the Mark VIe allow online logic or configuration changes?

5) Can equipment be added to the network and displayed on the HMI?


Can this be done online?

6) How difficult is it to configure control logic and the HMI?

Thanks for any information you can give


 
Like Reply
Report
CSA

Jan 5, 2017

 #17

CRSwanson,

1) I believe the Mark VIe is a fine, robust, purpose-built control system


very suitable for turbine control and plant-wide DCS control. The issue
for me is that it's very likely there will be at least two groups that will be
providing equipment--one for the turbines, and one for the balance-of-
plant/DCS. And, sometimes these two groups don't work well together,
which can lead to some small problems which can become big problems.

But that has nothing to do with the Mark VIe--it's the application (the
programming and configuration).

2) Well, yes and no. The method for getting signals/values onto an HMI
display is markedly improved--though it's <b>STILL</b> not properly
documented. The basic CIMPLICITY displays provided with a system
are just that: basic and little more than adequate. There are many things
which can be done to improve the CIMPLICITY graphics, but the
biggest thing which can muck things up is the inconsistent use of button
types for various functions.

The Alarm Window is handled by a separate application running on the


HMI (separate from CIMPLICITY) and it's NOT well integrated into the
HMI. The Alarm Window is VERY powerful and can be very helpful--if
properly configured, and properly used by the operators, technicians and
operations managers.

If you're considering buying a "Historian" think long and hard about that
decision. The "Historians" provided with Mark VIe can be very
powerful, but usually are extremely ... EXTREMELY ... poorly
configured. And, it takes a dedicated person, preferably two, on a site to
get familiar with the "Historian" and properly configure it and be able to
use it when there's a problem and historical data is desired. You have
been warned.

3) The Mark VIe was specifically designed to encompass an entire plant,


including turbines and all associated equipment. This was done for the
H- and HA-class turbines which heavily integrate the HRSG and plant
auxiliaries into the turbine control and protection. There are many I/O
packs and printed circuit cards & terminal boards which were developed
specifically for balance-of-plant I/O.

The fly in the ointment with many Mark VIe systems is that the
packagers of the equipment vastly over-estimated the ambient
temperature ratings of the components. The designer of the equipment
overstated the ambient temperatures in which the equipment could be
operated, and this lead to siting equipment in remote locations without
proper cooling and ventilation. Further, when combining the modules
into systems many times the temperature of modules mounted lower in
the cabinets would contribute to very high temperatures experienced by
modules mounted above them. This has been a real, serious problem for
many sites. (There have been several threads on control.com about this.)
In my experience, a lot of I/O packs have been replaced which were
found to be in fine condition when tested in a laboratory environment,
and if there had been proper ventilation and air circulation in the cabinet
the modules would not have "failed."

4) Yes. Most configuration changes and some simple programming


modifications can be done when the equipment is running. But, some
modifications do require a re-boot, which, on a properly configured
TMR control system, can be done while the equipment is running. (It's
risky, but it has bee done many times.)
5) If by "equipment" you mean can new I/O modules/packs be added on-
line, no. If you mean can spare I/O channels on existing I/O modules be
configured and used and the value of the signal from the new I/O
displayed on an HMI, then, yes, I would say that a good technician could
wire in new I/O, configure spare channels on existing modules, and add
the values to HMI displays without having to shut down the equipment.

6) That depends on your background, and your tolerance for learning


new things. Every control system has its quirks of programming, but the
application used to make programming changes, ToolboxST, is pretty
powerful. Configuration and troubleshooting--very detailed
troubleshooting involving trends and various data capture methods--can
all be done with a single application, ToolboxST. Is it "user-friendly"?
It's no iPhone or video game controller, but in my personal opinion it is
powerful without being too detailed or obtuse. As with MANY
programming/configuration software tool packages these days, there can
be many nested levels of configuration, but that isn't peculiar to
ToolboxST. The documentation is getting better, but it still has a way to
go--particularly when it comes to the HMI.

Properly configured, properly programmed and properly commissioned


the Mark VIe is a fine control system.
 
Like Reply
Report

CRSwanson

Jan 6, 2017

 #18

CSA... Thank you for your reply.

The question "Can equipment be added to the network and displayed on


the HMI?" was not meant for GE or Mark VIe equipment it was meant
for other manufactures. Example: I have an online DGA monitor that
can provide data via an ethernet connection. I want to put this on the
Mark VIe HMI. Can the monitor be connected to one of the Mark VIe
network switches and the data be displayed on the Mark VIe HMI? If I
can't use the Mark VIe network how can I bring in this data and display
it on the HMI?
 
Like Reply
Report
CSA

Jan 7, 2017

 #19

CRSwanson,

Thanks for the clarification. I don't know what a DGA monitor is and
what communication methods it is capable of (MODBUS; OPC; etc.).
CIMPLICITY (or PROFICY, or whatever they're calling it these days)
has some pretty good native communication capabilities, meaning that it
can talk directly with lots of other devices, including devices capable of
OPC.

I suggest you research CIMPLICITY/PROFICY and learn what it's


communication capabilities are to determine what it can do.

The GE network includes a PDH (Plant Data Highway--see how easy it


is to explain abbreviations to others that probably aren't familiar with
them) which is an Ethernet-based system which is designed to allow
other devices to communicate with HMIs to share data. And, there's
always everyone's favorite, MODBUS, which can even be done using
TCP/IP over Ethernet.
 
Like Reply
Report

Seven

Oct 2, 2017

 #20

Any recommendation where to get the ToolboxST dongle and Visupro


dongle from?

Thanks a lot
 

demigrog2

Oct 6, 2017

 #21

>Any recommendation where to get the ToolboxST dongle and


>Visupro dongle from?
You're talking about the hardware dongle enforcing the product license
for ControlST; logically, you'd order it from GE. Granted finding the
right place can be tricky; fortunately the google search for "GE
ControlST License" came up with the right link on the first result. Minor
miracle, that.

The workflow itself <i>is</i> a little uglier than I'd like, because the
hardware dongles changed for ControlST V5 and later. At least now
there is only one dongle needed for ControlST and CIMPLICITY, plus
GE's Proficy products.

Hope that helps!


 
Like Reply
Report

Jess

Nov 4, 2018

 #22

Hi Kevin.
I'm in the similar situation like you in this case. I was in a Mark VI
training more than 15 years ago and am needing to asist a client that uses
Mark VIe. I would like to review my training previous to assist him, but
I don't have a simulator or something like this in order to review this
control system previously. Could you share with me your VMWare
images just for personal training uses? I will appreciate a lot your
support.

My email: jchacinr70@gmail.com

Thank you very much in advance.


 
Like Reply
Report

ME42

Nov 5, 2018

 #23

SISO Engineering has the contacts with GE to get this software for
folks. Note: You need to be a recognized Mark VIe user/utility
Send them an email @ max@siso-eng.com. They can walk you through
how to get a license for all that software.
 
Like Reply
Report

MUNOZLE

Oct 25, 2019

 #24

Hello,

I am an electrical engineer, and I am quite new to turbine controls,


particularly in GE Mark VIe software. I have a problem with the
ToolboxST GE software and the HMI. This does not allow me to view
the variable data in the HMI (Cimplicity). I have collected several
manuals related to the various system features, and I have reviewed
several issues that are already on this website about the system. I have
managed to resolve the system failure. I appreciate the technical
assistance with the steps to solve the problem. This fault occurred after a
download to the UCES processors (R, S, and T).
 
Like Reply
Report

ME42

Oct 28, 2019

 #25

MUNOZLE,

Can you be more specific on the error? There could be many issues with
controllers or HMIs. If you provide detail on the issues, we can better
help you.
 
Like Reply
Report

You might also like