Ground Mount Dashboard Reference Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Pariyojan Design of Module Mounting Structure

Panels & Frames Design Purlin Rafter Front Column Rear Column Chat Here
Panel Length (mm) 2108 Demand / Capacity 0.264 27.229 0.192 1.207 <<< Final result
Panel Width (mm) 1048 Fy (MPa) 350 450 450 450 See Note 9
Panel Weight (kg) 30 Thickness 3 1.2 1.8 1.8 See Note 9
Panel Tilt (deg) 10 Min Lip (mm) 25 13 16 16
Panel/Base Gap (mm) 20 Lip (mm) 20 15 15 15
Panel Nos 20 Suggested Flange (mm) 75 30 45 45
Frame Nos 4 Flange (mm) 75 50 50 50
Wind Suggested Web (mm) 150 100 100 100
Basic Wind Speed (m/s) 50 Web (mm) 150 100 100 100 See Note 9
Class of Structure General [1] Weight (kg/m) 7.481 2.082 3.061 3.061
Terrain Category 1 [2] Span / Height (mm) 3493 3162 -41 508
Height (m) 12 Effective Length Factor Kx 1.000 1.000 6.256 1.000
Cyclonic Coast Distance [3] >60 km P(D+W) kN 0.217 5.472 -6.936 7.234
Risk Factor k1 1.000 Mxend1(D+W) (kN-m) 0.000 -0.183 0.000 0.000
Terrain/Height Factor k2 1.066 Mxspan(D+W) (kN-m) 0.877 2.712 0.091 1.628
Topography Factor k3 1.000 Mxend2(D+W) (kN-m) -1.125 -3.256 0.183 3.256
Cyclonic Region Factor k4 1.000 Vyend1(D+W) (kN) 1.294 2.484 4.475 6.405
Design Wind Speed Vz (m/s) 53.300 Vyend2(D+W) (kN) 1.937 4.658 -4.475 -6.405
Velocity pressure pz (kN/sqm) 1.705 P(D-W) kN 0.000 -5.511 7.980 -7.521
Directionality Factor Kd 0.900 Mxend1 (D-W) (kN-m) 0.000 0.165 0.000 0.000
Area Averaging Factor Ka 0.874 Mxspan(D-W) (kN-m) -1.007 -3.112 -0.083 -1.911
Design Pressure pd (kN/sqm) 1.341 Mxend2(D-W) (kN-m) 1.291 3.823 -0.165 -3.823
Max Pressure Coeff Cpmax 0.500 Vyend1(D-W) (kN) 1.554 -2.947 -4.047 -7.521
Min Pressure Coeff Cpmin -0.900 Vyend2(D-W) (kN) 2.130 -5.469 4.047 7.521

Mounting Frame Rafter Bending Moment Diagrams

Notes:
1. Wind load and cold-formed steel design conform to Indian Codes IS:875 and IS:801 respectively.
2. Demand / Capacity ratio should be restricted to 0.66 considering 33% permissible increase for dead+wind load combination and increased pressure per Table 8 note.
3. All modifiers Cb, Cm and K are taken as 1 except for Kx for columns which is calculated automatically
4. All members are single lipped channels
5. Enter data in blue cells
6. This design assumes two rows of panels in portrait orientation
7. Results should be rechecked by a proof engineer
8. Please do not resize or relocate the charts
9. IS:801 does not account for distortional buckling and local buckling under stress gradient so avoid high strength steel and large w/t ratios
Pariyojan Design of Module Mounting Structure

https://docs.google.com/spreadsheets/d/1iEuzPiQIIrnuZa5LdQDfyd5z72lEH--7rFH5uXXIaQI/edit#gid=0
X Y X BMD (D-W) BMD (D+W)
0 0 0.0000 -0.17 0.18
0 -41 1.0118 -2.99 2.61
1037.987372 142 2.0869 -1.81 1.59
2075.974743 325 3.1620 3.82 -3.26
3113.962115 508
3113.962115 0
[1] General Buildings

Temporary Sheds

Low Risk farm and residential buildings

High Risk Hospitals and Power Plants

[2] 1. Exposed open with objects <1.5m high

2. Open with well scattered objects 1.5-10m high

3. Numerous closely spaced structures <10m high and isolated towers

4. Numerous high closely spaced structures

[3] Gujarat and East Coast in India