GENERAL COMPLIANCE

circulation system with a system surge capacity of not 316.5.2 Pump delay. Where required by the manufac-
less than 1 gallon for each square foot (40.7 liters per turer, heaters shall be installed with an automatic device
square meter) of water surface. The capacity of the perim- that will ensure that the pump continues to run after the
eter overflow system and related piping is permitted to be heater shuts off for the time period specified by the
considered as a portion of the surge capacity. manufacturer.
315.5 Equalizers. Equalizers on skimmers shall be 316.6 Solar thermal water heaters. Solar thermal water
prohibited. heating systems utilized for pools and spas shall comply with
315.6 Hazard. Skimming devices shall be designed and Sections 316.6.1 through 316.6.3.
installed so as not to create a hazard to the user. 316.6.1 Installation. Solar thermal water heaters shall be
installed in accordance with the International Mechanical
Code or International Residential Code, as applicable in
SECTION 316 accordance with Section 102.7.1.
HEATERS 316.6.2 Certification of collectors. Solar thermal collec-
316.1 General. The provisions of this section apply to heat- tors shall be listed and labeled in accordance with ICC
ers for pools and spas. 901/SRCC 100 .
Exception: Portable residential spas and portable resi- 316.6.3 Marking of collectors and modules. Solar ther-
dential exercise spas. mal collectors and photovoltaic modules shall be
316.2 Certification. Heaters and hot water storage tanks permanently marked with the manufacturer’s name,
shall be listed and labeled in accordance with the applicable model number, and serial number. Such markings shall be
standard indicated in Table 316.2(1). Hot water heating located on each collector in a position that is readily
systems and components shall comply with the applicable viewable after installation.
standard indicated in Table 316.2(2).
316.3 Sizing. Heaters shall be sized in accordance with the SECTION 317
manufacturer’s specifications. AIR BLOWER AND AIR INDUCTION SYSTEM
316.4 Installation. Heaters shall be installed in accordance 317.1 General. This section applies to devices and systems
with the manufacturer’s specifications and the International that induce or allow air to enter Class A and residential pools
Fuel Gas Code, International Mechanical Code, Interna- and spas either by means of a powered pump or passive
tional Energy Conservation Code, NFPA 70 or International design.
Residential Code, as applicable in accordance with Section
102.7.1. Solar water heating systems shall be installed in 317.2 Backflow prevention. Air blower systems shall be
accordance with Section 316.6. equipped with backflow protection as specified in UL 1563
or CSA C22.2 No. 218.1.
316.4.1 Temperature. A means shall be provided to
monitor water temperature. 317.3 Air intake source. Air intake sources shall not induce
water, dirt or contaminants.
316.4.2 Access prohibited. For public pools and spas,
public access to controls shall be prohibited. 317.4 Sizing. Air induction systems shall be sized in accor-
dance with the manufacturer’s specifications.
316.5 Heater circulation system. Heater circulation
systems shall comply with Sections 316.5.1 and 316.5.2. 317.5 Inspection and service. Air blowers shall be provided
with access for inspection and service.
316.5.1 Water flow. Water flow through the heater
bypass piping, back-siphonage protection, and the use of
heat sinks shall be in accordance with the heater manufac-
turer’s specifications.

TABLE 316.2(1)
WATER HEATERS
DEVICE STANDARD
Electric water heater UL 1261, UL 1563 or CSA C22.2 No. 218.1
Gas-fired water heater ANSI Z21.56/CSA 4.7a
Heat exchanger AHRI 400
Heat pump water heater AHRI 1160 and one of the following: CSA C22.2 No. 236, UL 1995, or UL/CSA 60335-2-40

TABLE 316.2(2)
WATER HEATING SYSTEMS AND COMPONENTS
SYSTEM STANDARD
Solar water heater ICC/APSP 902/SRCC 400

3-10 2021 INTERNATIONAL SWIMMING POOL AND SPA CODE®