Z.CHELLI1
1
Department of Electrical Engineering, University of Mohamed-Cherif Messaadia ,Souk Ahras, ALGERIA.
1
LEER Laboratory University of Mohamed-Cherif Messaadia ,Souk Ahras, ALGERIA;
Abstract: The railways are the most important and transportation because of high efficiency, heavy
modern means of transportation are used to transport a ridership and fast transportation of series DC motor
large number of people, and also used in the industrial (high initial torque) , and we note that DC train
field to transport heavy weight and raw materials for very consumes less energy compared to alternating
long distances. Direct current (DC) electrified railway
current (AC) unit for operating same service
systems show many power quality problems such as
harmonic, reactive power, unbalanced and low power conditions [2-3].
factor. Our study concentrated on the propagation of However, the DC electrified railways cause a lot
currents harmonics in the electric network and their of problems for the power quality such as injecting
filtering solutions. In this article we made a model in harmonics (high THD); reactive power , and low
Matlab/Simulink of a real DC traction substation which is power factor issue [4-5]. In this paper we
located in the mineral line Tebessa - Annaba (in east of concentrated on filtering of currents harmonics
Algeria), this line transport raw materials such as iron generated by the DC electric traction units in a
and phosphate. We present in this work to mitigate railway system by using passive filter which
harmonic currents the passive filtering, using filters installed on different locations of transformer
(tuned at frequencies 11 and 13) at two different locations
feeding (before , after ).
before and after the transformer which freedies the DC
traction substation. The results of simulations with the These solutions are cheap, economy and work in
proposed solution give the best results with minimum the middle and high voltage, eliminate negative
values of total harmonic distortion (THD) in both cases. sequence current, and also participate in the
compensation of the reactive power deficit thus
Keywords –Electrification, DC Traction Substation, improving the power factor of the power networks
Filtering Harmonics, Power Quality, Passive filter, [5, 6].
Railway System.
1
Journal of Electrical Engineering
www.jee.ro
The schematic diagram of the system studied is 3.1. Principle of passive filtering
shown in Figure 1. The single tuned filter connected to the network is
This series connection of two 6-pulse converter represented in Figure 2.
bridges requires two three-phase systems feed by a
Lr
three winding transformers with star/star/triangle
connections (Y/Y/∆) which are spaced from one Ir Ih
another by 30 electrical degrees, that is to say form a
2
Journal of Electrical Engineering
www.jee.ro
Filter h Filter h’
3500
Voltage
Current
3000
connected 2000
Current (A) /Voltage (V)
1500
[7]:
500
X Cf − h
h =
2
(11) 0
X Lf − h -500
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
Time (s)
X Cf − h '
h 2' = (12) Fig. 4. Waveform of the Voltage & Current at the output
X Lf − h ' of group rectifier
V2 V2
+ =Q (13)
X Cf − h − X Lf − h X Cf − h ' − X Lf − h '
h'
Z f −h ' = .Z f − h (14)
h
3
Journal of Electrical Engineering
www.jee.ro
2000
Voltage(V)
100
Current(A)
1500
90
1000 80
70
500
Current (A) / Voltage (V)
60
Amplitude [%]
0
50
-500 40
30
-1000
20
-1500
10
-2000 0
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 2 4 6 8 10 12 14 16 18
Time (s) Order of Harmonic
Fig. 5. Waveform of the voltage /current absorbed of Fig. 9. Harmonic Spectrum of current harmonic injected
rectifier (Y/Y)
2000
Voltage(V)
In figure 7, we see that the current harmonics that
1500
Current(A)
exist are of the form 6k ± 1 (with k integer) , so we
1000
can see the existence of 5, 7, 11,13, ..., since the
load of pollution is a three-phase rectifier and also
marks a high value of THD = 26.31%.
500
Current (A) / Voltage (V)
0
From the figure 9 we see the elimination of
-500
harmonic of the 5th and 7th order and it returns to the
-1000 advantage is the use of transformers with three
-1500 connections Y / Y / ∆ (formation of a 12 pulse
-2000
rectifier), the remaining harmonics are the form
12k ± 1 (with integer k) ie, 11,13, ..., the value of
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
Time(s)
Fig. 6. Waveform of the voltage /current absorbed of THD = 10.38% is still higher than the standard, it is
rectifier (Y/∆) for this reason we think of the passive filtering
solution with implementations of tuned filters in 11th
and 13th before and after the power transformer.
100
90
80
70
4.2. Operation with filtering
60
Amplitude[%]
20
10
two tuned filters corresponding to these harmonics
0
0 2 4 6 8 10 12 14 16 18
as shown in the following figure 10.
Order of Harmonic
20
Power Supply ‐ Catenary 3 KV DC
15 Ih
10 +
5 I11 I13
Current (A)
-5
‐
-10
Transformer Rectifier 2
-15 Rail
-20
Filter Filter Traction Substation
-25
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
11 13
Time(s)
Fig. 8. Waveform of the current injected in electric Fig. 10. Systems studied with passive filtering (case 1)
network
4
Journal of Electrical Engineering
www.jee.ro
25 25
20 20
15 15
10 10
5 5
Current (A)
Current (A)
0 0
-5 -5
-10 -10
-15 -15
-20 -20
-25 -25
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
Time(s) Time(s)
Fig. 11. Waveform of the current injected (Ih) in electric Fig. 14. Waveform of the current injected (Ih) in electric
network with passive filter (case 1) network with passive filter (case 2)
100 100
90 90
80 80
70 70
60 60
Amplitude [%]
Amplitude [%]
50 50
40 40
30 30
20 20
10 10
0 0
0 2 4 6 8 10 12 14 16 18 0 2 4 6 8 10 12 14 16 18
Order of Harmonic Order of Harmonic
Fig. 12. Harmonic Spectrum of current harmonic injected Fig. 15. Harmonic Spectrum of current harmonic injected
with filtering (case 1) with filtering (case 2)
5
Journal of Electrical Engineering
www.jee.ro
To achieve this solution in the best way we chose 3. T. Suzuki, H. Hayashiya, T. Yamanoi, and K.
two locations for the installation of these filters Kawahara. : Application examples of energy saving
measures in Japanese DC feeding system . In:
(before, and after the transformer that supplies the Proc.14th International Power Electronics Conf.,
traction station). Hiroshima, Japan, May 2014, p. 1062-1067.
Finally, the simulation results obtained give a
minimum value of the current THD injected into the 4. W-A.Jager, M. Huizer, and E. K. H van der Pols. :
network in the case of filtering after the transformer Implementation of an active regeneration unit in a
(medium voltage) and the filtering before the traction substation . In: Proc.16th European Conf. On
Power Electronics and Applications, Lappeenranta,
transformer (high voltage). Finland, Aug. 2014, p.1-9.
Annex 2: Characteristic of the Rectifier Group 9. M. Brenna, F. Foiadelli. : Analysis of the Filters
Installed in the Interconnection Points Between
Different Railway Supply Systems . In: IEEE
Number of diode in series with the bridge arm. 1 Transactions on Smart Grid, Vol. 3, No. 1, March
Number of parallel diode bridge arms 4+1=5 2012, p. 551-558.
Total number of rectifier diodes 2x30 =
60 10. K.-W. Lao, N. Dai, W.-G. Liu, and M.-C.
Input Rated current (AC side). 577 A Wong. : Hybrid power quality compensator with
Nominal output current (continuous rating) 1000 A minimum DC operation voltage design for high-speed
Actual DC voltage (at the output of the rectifier 3310 V traction power systems . In: IEEE Trans. Power
Electron., Vol. 28, No. 4, 2013, p. 2024 - 2036.
group)
Nominal voltage charge (at the exit of the 3240 V
group)
Current DC front (DC side) 16.7 kA
Losses block transformer - rectifier (charging) 38.24 kw
Rated inductance 0.2 mH
References
1. A. Szeląg, T. Maciołek. : A 3 kV DC electric traction
system modernisation for increased speed and trains
power demand problems of analysis and synthesis. In:
Przegląd Elektrotechniczny, Vol 89, No. 3a, 2013,
p. 21-28.