Download as pdf
Download as pdf
You are on page 1of 48
SPARTAN CONTROLS LTD. FIELD TROUBLE SHOOTING GUIDE REM Vue?— 500s /PLC Version 1 August 06, 2009 REM Vue"— 500 /PLC FIELD TROUBLE SHOOTING GUIDE, DISCLAIMER This document is designed to provide information regarding the troubleshooting of the REM Vue°— 5005 / PLC Control Systems. Before changing any setpoints or operating parameters consult a Spartan Service Representative or the packager of the unit. Passwords should not be given out without approval from the packager (warranty considerations) or approval from an end user supervisor. REM Vue?— 5008 / PLC FIELD TROUBLE SHOOTING GUIDE TABLE OF CONTENTS TABLE OF CONTENTS ... 4. Control System Electronics ..sssnnnnnnese 4.1 Controller. 14 1.2 VO Module Status... 2, Thermocouples sssnnnne 3. HMI Problem... 3.1 PLC Message...... 3.2 HMI Does Not Come On... 4, Operating Problems .wnmsmnenn 44 Starting 4.2 Loading 4.3 Engine Speed 4.4 Engine Exhaust Temperature(s) 4.5 Engine Can't Take Load 4,6 Overspeed Shutdown. 5, FAQ'S nnn 6. HMI Navigation 6.1 Navigation Chart... 6.2 HMI Screen Snapshots 7. Appendix 1 — Grounding.. 8. Appendix 3 — Alarm Logs, Trends and Data Logs .. 9. Appendix 4— Shutdown/Alarm classes REM Vuc?— 500 / PLC Figo TROUBLE SHOOTING GUIDE REM Vue®— 5008 / PLC FIELD TROUBLE SHOOTING GUIDE 1. Control System Electronics Notes: @- te following covers the REMVue 500 hardware. For PLC consult the PLC hardware manuel. 1.1 Controller Status LED OFF 1 No power; check input voltage and fuse. Status LED OFF after 20s initialization Hardware or software error; try cycling power. Status LED Fast Blink = Controller is being reset; firmware to be downloaded with /O Toolkit software. Status LED Slow or periodic blink —m Clear memory and load project with the 1/0 Toolkit (about 14sec) software. » Internal watchdog has detected problem Communications LEDs & Check wiring, » Send (TD) and Receive (RD) do not Set other device correctly. blink To confirm COM Port operations, use notebook computer with the SIXNET lO’ Toolkit sat to Modbus; use a 422 or 232 convertor (required). 1.2 /O Module Status Status LED OFF '& No power, check connections. Wait until /O Toolkit operation complete, Status LED Long Blink (0.76 on; 0.25 Module has lost communication with controller for on more than 10s, Check ST BUS wiring, & Expected start-up condition — wait a few seconds. Status LED Short Blink (025s on; 0.755 _& Failure of module self-test on start; replace module. on Status LED Winking (10 biinks/s) 1 Occurs during linking operation, If after linking, refer to VO Toolkit for helo. =L1- REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, 2. Thermocouples Failure of thermocouple & Check terminals, » Loose connection F Disconnect thermocouple; chmmeter should show < » Broken 20 ohms for thermocouple. * Short — constant or intermittent & Disconnect thermocouple; meggar or ohmmeter at 40M ohm scale should show isolation from ground Use thermocouple calibrator (ir avavabie) . Wrong Temperature value ® Check for real engine/compressor problem. 7 Mechanical problem J ype is White (+) and Red () > Wrong thermocouele type “ Weng thenmoceu & K type is Yetow (2) and Red () ® Calibrate where possible from end device end. . > Module needs calibrating » Stake-on connectors present Remove stake-on connectors. Temperature erratic » Real engine/oad problem Determine if temperature behaviour is possible due > Splice terminal problem to mechanical fault, & Redo splice ifnot correct. Tighten cold junction terminals. -22- REM Vie"— 500 / PLC FIe> TROUBLE SHOOTING GUIDE 3. HMI Problem 3.1 PLC Message Notes: @ essage appears in the bottom left-hand comer. PLC Not Responding message ® Put cable in place and secure fastening screws. » Communications cable loose or ® Put in correct addressing between HMI and controller; disconnected ‘common values are 1 and 17. » Different baud rates > Controller address has been changed (12. by VO Tooter Controller settings must be 115.2kbaud, N, 8, 1 PLC Disconnected message 1& Make sure the controller is powered up. » Controller off or not running ® Check cable to make sure it did not come loose on » Cable problem the controller or HMI. Repairireplace cable HMI locked-up Cycle power to HMI (can be done when engine is running) with fuse on switch, 3.2 HMI Does Not Come On Voltage out of range Voltage required is 19.2 to 28.8 VDC. Fuse blown © Check for cause and replace fuse. REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, 4. Operating Problems Notes: the olowing covers only the most commonly encountered problems. The REMVue will not cirsetly control the crank, igniton and fuel on 4 Cat ‘engine with an ADEM system or a Waukesha engine with an ESM. The REMVue may not contro! the lube pumps for these units. For more detailed information consult the operating philosophy for that particular panel. 4.1 Starting Alarm/shutdown not cleared Check the first out banner to se what caused the Prelube not clear. » Check shutdown/alarm to see if the engine or compressor permissive is feulted Fail to Crank shutdown Faults when the panel does not ‘see an RPM signal 10 seconds after the crank tums on. Fail to Start > Faults when the engine speed does not go over the RUN PERMIT SPEED before the ENGINE FAILED TO START TIMER expires. initial shutdown. Fix the cause of the shutdown, Acknowledge and clear. Make sure the panel is in LOCAL mode, F If there are class B, b or C shutdowns flagged the ARM CLASS BbC is enabled on the DISCRETE INPUT VERIFY PAGE, tur this off. Check to make sure the prelube pumps are running. If pumps are not running check the signal from the panel to the solenoid (requires voltmeter). If the solenoid is not getting power check the wiring and fuses. Check the supply pressure to the solenoid. If the pumps are running check the engine and compressor oil pressures and make sure they are above the permissive settings (settings in the ‘SEQUENCE PARAMETER PAGES). F Ifthe engine is cranking over make sure the panel is displaying an RPM. Check the manual start valve and make sure it is open. Check the starter supply pressure, consult starter manufacturer manual for correct pressure. Check the starter solenoid to make sure itis tuning fon. If possible check the supply to the starter solenoid and make sure it is opening the starter valve. Verify the engine crank speed is > PURGE PERMIT SPEED (found in SEQUENCE PARAMATER PAGES). If the speed is not over the PURGE PERMIT SPEED the fuel and ignition will not turn on Check the ignition to make sure itis firing. An MPI display will show if the ignition is firing. Other ignition systems may require test equipment to determine ifthe ignition is firing. Verify the fuel shutoff vaive is opening. Check the fuel supply pressure. -44- REM Vie"— 500 / PLC Fie. TROUBLE SHOOTING GUIDE, 4.2 Loading SaaS) “Ready to Load’ does not appear after m Check oil temps; dotermine cause if not OK. ‘engine running and warmed up © Consider reducing engine oil temperature Engine Oil Temp permissive not ermissive met Compressor Oil Temp permissive not met = Consider jermissive lowering compressor oil_ temperature Load started, doss not load & Verify the engine speed is > Minimum Load Speed (found in SEQUENCE PARAMATER PAGES), 1 Check the Capacity Overview to make sure there ate no override conditions. Verify the suction pressure is > suction override setpoint (CAPACITY OVERVIEW or PROCESS CONTROL). Verify the discharge pressure is < discharge override setpoint (CAPACITY OVERVIEW or PROCESS CONTROL). 1 Check the suction valve control. Make sure the suction valve setpoint is > suction override setpoint Suction Valve control problems 1 Check to make sure the suction valve is in Auto (SUCTION VALVE CONTROL PAGE). Make sure the suction pressure is not within the deadband © Make sure there are no overrides on the suction control that could be causing the suction valve nat control (most common is discharge override) & Place the suction vaive into Manual. Try making a small increase or decrease to the suction vaive ‘output. Remember to return the control back to Ato I the suction valve does not move in manual check the supply pressure to the IP or positioner. If possible check the analog output signal from the panel. Check the wiring between the panel and the suction valve contra a45- REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, Ea Bypass Valve control problems ® Check to make sure the bypass is in Auto (CAPACITY CONTROL PAGE) Check the CAPACITY OVERVIEW PAGE to see what the Low Select PID output is at. The Low Select PID output has to be > lower split range value in order for the bypass output to increase. As an example: Bypass split range 20 - 80%. The bypass valve will start to close when the Low Select PID output is >20%. The bypass valve will be closed when the Low Select PID output is at 80%. Place the bypass valve in Manual (CAPACITY CONTROL PAGE). Try increasing or decreasing the bypass control. Remember to return the control back to Auto. If the bypass valve does not respond check the supply pressure to the IP or positioner. If possible check the analog output signal from the panel. Check the wiring between the panel and the bypass valve control. 4.3 Engine Speed RPM fluctuates ® Check the load on the unit to make sure it is not fluctuating and causing the speed swings. B Check the fuel pressure to make sure it is not fluctuating, & Check the engine exhaust temperatures and ignition system to make sure a cylinder is not misfiring, E If the governor control is using an UP, check the supply and output pressures, F If the governor control is electronic (ie. Cat ADEM ‘or Waukesha ESM) check the wiring and control devices. Check the output on the GOV CONTROL screen or the CAPACITY OVERVIEW screen, verify the ‘output from the panel is stable. Cylinder performance erratic Watch cylinder exhaust temperatures (see Section 4.4 Engine Exhaust Temperature(s) on page 4-7). Check ignition system (diagnostics if applicable), -4-6- REM Vie" — 500 / PLC Fie. TROUBLE SHOOTING GUIDE Ree Seo ‘Speed not controlling to setpoint. ® Check the GOV CONTROL screen and make sure the ‘speed is not within the deadband. 1 Check the GOV CONTROL screen to see if the ‘output is at 0% or 100% limit © If there is an UP being used check the supply and output pressures. If there is an electronic governor the problem may not be with the REMVue control. Verify the output signal is getting to the electronic governor. If the signal is okay the problem is with the electronic governor system. '& Check the wiring and fuse for the output 4.4 Engine Exhaust Temperature(s) Thermocouple problem See Section 2 Thermocouples on page 2-2 Nats Peace we cae — en estat hemocaile ‘can be changed with engine running. Ignition component problems & View exhaust temperature differences; typically will » Plug — shorted or gap too large affect individual cylinders. » Secondary lead & Check ignition system diagnostics. Exhaust vaive leak I just one cylinder is high, it could be a mechanical problem, Engine overload 1 Check load. If overload, reduce load. 4.5 Engine Can't Take Load Sao Low fuel pressure © The fuel pressure may have to be increased at the regulator before fuel valve. Compressor bypass/suction changes too ® The loading parameters or PID parameters may have sudden to be adjusted. 4.6 Overspeed Shutdown Load reduced too quickly Reduce rate of fiow change with compressor suction/ bypass valve(s) Ignition system problems ® Check the ignition system to make sure all cylinders. are firing. The exhaust temperatures may also help determine if there is an ignition problem, REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, 5. FAQ’s » There is 2 shutdown/alarm that i Make sure the panel is in LOCAL. will not reset. Check to see if the shutdownlalarm condition is lear. If itis a discrete input make sure the switch is closed (or open if set to normally open), this can be checked on the VERIFY Dl PAGE. For analogs or temperatures make sure the process variable is not within the shutdown/alarm limits, this canbe checked on the ANALOG/THERMOCOUPLE INPUT READINGS PAGES. Verify the ARM CLASS BOC is not enabled on the VERIFY DI PAGE. > The engine will not start E Make sure the engine is cranking over and the panel is showing an RPM Verify the engine speed is > PURGE PERMIT SPEED, this setting is in the SEQUENCE PARAMATER PAGES. Make sure the fuel shutoff valve is opening. Verify there is sufficient fuel pressure. Check the ignition to make sure itis fring » The unit will not load, panel shows Make sure controls are in AUTO. loading initiated. & Check the engine speed to make sure it is at the MINIMUM LOAD SPEED, this setting is found in the ‘SEQUENCE PARAMTER PAGES, Check the CAPACITY OVERVIEW PAGE to see if what contol is active and make sure itis not in an ‘override condition (typically suction or discharge). > The unit keeps going down on — & Check to see if the load is changing and stalling the underspeed, low compressor oi engine, the DATA LOG can be used to track pressure or low engine oi! —_pressules. pressure. Check the fuel system to make sure itis not causing the engine to quit Check the ignition system. REM Vie"— 500 / PLC Fie. TROUBLE SHOOTING GUIDE, 6. HMI Navigation 6.1 Navigation Chart The navigation chart references the standard program. Some sites may have custom screen layouts. Blocks highlighted in grey are password protected by the OPERATOR PASSWORD. Blocks highlighted in yellow are password protected by the OPERATOR PASSWORD but also allow a view only that does not require a password. (—»| LOCALIREMOTE MODE SELECTOR SD MAIN | STARTISTOP AND LOADIUNLOAD L_,| SD OVERVIEW -6.9- REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, SD OVERVIEW ‘AVTEMP INPUTS |__4 ANALOG INPUT READINGS |__| tcirrp iNpuT READINGS [|__| PERFORMANCE [4] sucionvatve crrL [|__4] capacity contro [+] PROCESS CONTROL, a} CAPACITY OVERVIEW VIEWENTER SETPOINT SHUTDOWN BYPASS PROCESS READINGS CAPACITY! PROCESS CONTROL -6-10- | EXHAUST CYLINDER ‘TEMPERATURES PERFORMANCE >| EXHAUST CYLINDER, DELTA TEMPERATURES, TUNING SCHEDULE [>| ENABLEDISABLE a] TUNING scHEDULE SETUP SUCTION VALVE CTRL DISCH OVRD ON SP ENABLE/DISABLE [4] suction vae ‘OVERRIDE Ly Pip SETUP capacity |__| Governor contRoL CONTROL, —>| sucT PID TUNING PROCESS CONTROL L_4| piscH pip TUNING REM Vie"— 500 / PLC FIe> TROUBLE SHOOTING GUIDE DISCRETES | — FORCE DO | |__| VERIFY DO |__| VERIFY 01 spoveaview |. [| PANEL CONTROL |__,| — oPeraToRLos: L_,| vataLossine 6-11 Vue. Fiep TROUBLE SHOOTING GUIDE 6.2 HMI Screen Snapshots have customized screens. For PLC screens consult the PLC operation manual. The SD MAIN screen gives a quick overview of some of the operating readings. This page allows the starting, stopping, loading and unloading of the unit. You can also select LOCAL or REMOTE mode for the panel. From this screen you can go to the SD OVERVIEW screen which allows access to all other pages for the shutdown portion of the panel. Number displays that are in yellow can be edited numbers in white are read only. eal mm/dd/yy hh:mm | CU at oe Lae EY ceed P) ele ENGINE SPEED ENGINE OIL SUCTION % OPEN Nn z mo eee -123 Mr mec n4 Wear ve -6-2- Vine FieLo TROUBLE SHOOTING GUIDE The SD OVERVIEW screen is used to navigate to all other screens. Note that some screens have a number display under them, these screens have password protected settings in them. To edit password protected settings touch on the yellow numbers and the password screen will pop up and the correct password will have to be entered. If you want to just view screens without entering the password touch on the text portion OVERVIEW UNIT #4 SHUTDOWN malty th SYSTEM a My V ms VOLTAGE iL. 0) Masala A tee le ig aed ANALOG INPUT | _TC/RTD READINGS | READINGS Peete Baten cascreTe wpurs. | rTeMPinpurs N CT CAPACITY/PROCESS CONTROL Pt Pally ae pts ee rorce [verry VERIFY ora mec oe 30 a eee -6-13- Vine’. FIELD TROUBLE SHOOTING GUIDE The support screen shows the software versions as well as the panel number. The heartbeat monitor light is also on this page. Ae, 3 SPARTAN CONTROLS >. UPPORT (403) 207-0700 ~6-14- REM 500 / PLC Fie. TROUBLE SHOOTING GUIDE The analog input setpoints page shows the low and high alarm/shutdown settings. The values in yellow (alarms) can be edited without entering the password. The values in blue (shutdowns) can only be edited by entering the password. The input description numbers will actually show the text of the input on the HMI. You can go to the analog input class setup and ranges from the setpoints pages. ANALOG INPUT SETPOINTS Page 1 of2 En) NENT ~6-15— 10 / PLC Frew TROUBLE SHOOTING GUIDE The analog input class shows what type the shutdown is. Go to the help page to view more information on the class types. The class can only be changed by entering the password ANALOG INPUT CLASS Page 1 of 2 LOW AL/SD SETPOINT CLASS HIGH AL/SO SETPOINT CLA cLass a EEE: -6-16- Vine FieLo TROUBLE SHOOTING GUIDE BNETOS INO CONGIGURATION HELP TO aos Pence [olay SS OCI ny eT} ed until end of Cl re ea Pa mena ON Dene No a Cmca eee eee mee) SRO ea oC ause an alarm only. ace Pe ee ee me] failure al : -6-17- REM Vue°— 500 / PLC Fie. TROUBLE SHOOTING GUIDE The Al transmitter ranges, filtering and zero/span adjustments can be made from this page. Requires @ password to allow editing. See the calibrate help for more information Al TRANSMITTER RANGES _ Page 1of2 ALIBRATION PAR an (eT DESCRIPTION VALUE UNITS MINIMUM MAXIMUM FILT d rari AE it ra rT | - 6-18 REM Vne"— 500 / PLC Flew TROUBLE SHOOTING GUIDE TRANSMITTER CALIBRATION HELP SCREEN SM dae ee ne eg eee eee Ce) [Use eee Peso UR SONS 0) ee Ree ne. ec ee eee Se transmitter drift, NOTE - Set Al FILT value to B prior to calibration, eae er ei aes CURE DRTC ere ea in the RAW indicator for t er cai Cee CR Oe eee St TCC eee wiring, a faulty transmit -6-19- 10 / PLC Frew TROUBLE SHOOTING GUIDE The TC/RTD input setpoints page shows the low and high alarm/shutdown settings. The values in yellow (alarms) can be edited without entering the password. The values in blue (shutdowns) can only be edited by entering the password. The input description numbers will actually show the text of the input on the HMI. You can go to the TC/RTD input class setup from the setpoints pages. TC / RTD INPUT SETPOINTS INPUT eG a oT ee ce Tic) RIPTION COOLDOWN VALUE _UNITS SHU. ALARM ALARM SHUTDOL ae Care TPA l ae roe ey ~6-20- REM Vne"— 500 / PLC Flew TROUBLE SHOOTING GUIDE The TC/RTD input class shows what type the shutdown is. Go to the help page to view more information on the class types. The class can only be changed by entering the password, TC / RTD INPUT CLASS Page 1 of 4 T ETPOINT CLAGS HIGH AL/SO SETPOINT CLA I U Nee) | Tear ee ear cLass A cLass A oe cLass Al cLass A tele Lass A cLass A eR EAE A cLass a cLass A PR ee | ~6-21- REM Vue°— 500 / PLC Fie. TROUBLE SHOOTING GUIDE TC /RTD NEU CONFIGURATION EEE See em ge "i eee ee ee) CCE RE AL Cpt} ie ae eas eae? ne lu PCR ae Sine rms 5 os ae See Rees CeCe Pact eis Oe an alarm only, tae ee ee ee mee ne ene wae eT ac Vine FieLo TROUBLE SHOOTING GUIDE The sequence parameter pages show various panel settings. The values in yellow can be edited without entering the password. The values in blue can only be edited by entering the password. SEQUENCE PARAMETER SETPOINTS — Page1of4 COMPRESSOR OIL PRESS GOVERNOR SPLIT RANGE STARTUP PERMISSIVE MAXIMUM VALUE ENGINE OIL PRESSURE ENGINE STARTUP PERMISSIVE IDLE SPEED SETPOINT ENGINE ENGINE PULSES PER REVOLUTION MINIMUM LOAD SETPOINT ENGINE ENGINE CRANK TERMINATE SPEED MAXIMUM LOAD SETPOINT ENGINE ENGINE OIL TEMPERATURE PURGE PERMIT SPEED |) LOAD PERMISSIVE SETPO! ENGINE INITIAL LOAD RATE (1-100) RUNNING SPEED PERMIT HIGHER #= FASTER BYPASS VALVE SPLIT RANG! UNLOAD / COOLDOWN RAMI MINIMUM VALUE DELAY TIMER BYPASS VALVE SPLIT RANG! MAXIMUM VALUE GOVERNOR SPLIT RANGE MINIMUM VALUE UNLOAD / COOLDOWN STEP RAMP RATE Fico TROUBLE SHOOTING GUIDE. Fico TROUBLE SHOOTING GUIDE. REMVie"— 500 / PLC Fico TROUBLE SHOOTING GUIDE This screen allows access to the exhaust differential setup and pressure differential/RPM setpoints. All other setpoints can also be accessed from this page. To edit setpoint values you have to go into the edit password protected screen and enter the password ~6-27— REM Vue°— 500 / PLC Fie. TROUBLE SHOOTING GUIDE The discrete inputs can be bypassed for a short period of time. This screen requires a password. To enable the bypass just touch the NOT BYPASSED button, it will then change to BYPASSED. The BYPASS TIMER will start counting down. DISCRETE INPUT SD BYPASS Page1of3 Carne 56 Te se sta ase ~6-28- REM Vne"— 500 / PLC Flew TROUBLE SHOOTING GUIDE The analogithermocouple inputs can be bypassed for a short period of time. This screen requires a password. To enable the bypass just touch the NOT BYPASSED button, it will then change to BYPASSED. The BYPASS TIMER will start counting down. ANALOG INPUT SD BYPASS _ Page 1of2 REMOVE BYPASS TIME REMAINING: RESET TT eee nd ‘POINTS BYPASSED (4 MAX): ad Teer eae Ey Exar) MAIN eel ~ 6-29 REM Vue°— 500 / PLC Fie. TROUBLE SHOOTING GUIDE The analog input readings show the value as well as the high/low alarms and shutdowns. This is a view only screen. ANALOG INPUT READINGS __ Page1of2 Tae DESCRIPTIO rat CTE -6-30- REM 500 / PLC Fie. TROUBLE SHOOTING GUIDE The tc/rtd input readings show the value as well as the high/low alarms and shutdowns. This is a view only screen, TC / RTD INPUT READINGS _ Page 1of3 Os Mey ance DESCRIPTION VALUE UNITS _ PC -6-31- REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, The performance page allows access to the engine exhaust temperatures and the trending. These are view only pages, The most commonly used screen is the exhaust cylinder temperatures. ~6-32- Vine FieLo TROUBLE SHOOTING GUIDE EXHAUST TEMPERATURES Peay Pere Lg a aL 2 re 2 Ca. a sibel ea ~6-33- 10 / PLC Frew TROUBLE SHOOTING GUIDE Suction valve control page. This is where the suction valve can be changed between auto and manual control. The tuning schedule and discharge override can be enabledidisabled from this page. The user can access the tuning schedule setup, suction valve overrides and PID setup from this, Page. SUCTION VALVE CONTROL SUCTION PRESS SETPOINT Ener] P GAIN 1 GAIN Pleas Ae (RPT/SEC) AUTO DGAIN ee MANUAL (SEC) En er ~6-34- Wine’ FIELD TROUBLE SHOOTING GUIDE The bypass valve and the speed control can be placed in AUTO/MANUAL on this page. Tela em DISABLED Per) ese igen. 6-35 — 10 / PLC Frew TROUBLE SHOOTING GUIDE The GOV CONTROL screen is where the governor can be placed in manual. This shows the output to the interface device for the governor, typically an VP. L J 3 rea SETPOINT row GINGA) = osen| wevcre NGan eee ourPUT rerrsec MEME oee0=00 ERR) sro _| oo DGAIN MANUAL cece!” RIRIRGHED) corer REY) osu | -6-36- Wine’ FIELD TROUBLE SHOOTING GUIDE The PROCESS CONTROL page allows the SUCTION OVERRIDE to be placed in manual, The user can also access the suction and discharge overrides PID pages for the capacity control. i Ca Sao e SETPOINT ADJUST (PSI) ADJUST (PSD ale | Oe Meas Pena = 6-37— REM Vine*— 500 / PLC Fie. TROUBLE SHOOTING GUIDE The capacity overview shows the override outputs and the low select which is then passed into the speed and bypass control. 6-38 — Wine’ FIELD TROUBLE SHOOTING GUIDE The discrete outputs can be forced on/off. The crank, fuel and ignition can not be tured on at the ‘same time. The unit has to be stopped and no ESD shutdowns flagged. Put the control in MANUAL to toggle the outputs. crm OFF to] | lig rol] OFF ON || OFF = 6-39— REM Vue°— 500 / PLC Fie. TROUBLE SHOOTING GUIDE Verify DO page shows the state of the discrete outputs. VERIFY DISCRETE OUTPUT OUTPUT = OUTPUT OFF ON pire re ca om || fe Bred OFF Co Co -6-40- REM Vine! 500 / PLC Fie. TROUBLE SHOOTING GUIDE Verify DI screen is where you can class 8, b and C shutdowns will trip the ARM CLASS BbC button. If this is turned on all of the jot clear. Push the button to turn it off. VERIFY DISCRETE INPUT Page 1 of 2 ~6-41- REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, 7. Appendix 1 — Grounding The diagram here shows the recommended grounding arrangement to avoid ground loops. Poor grounding or grounding loops can cause many strange electrical and operational problems. ups Ignition Contro! ‘Ground rod (right) required if building \steol isnot implicitly ‘grounded through ‘burial in earth. REM Vie"— 500 / PLC Fie. TROUBLE SHOOTING GUIDE, 8. Appendix 3 — Alarm Logs, Trends and Data Logs Alarm logs, trends and data logs are sometimes very useful in trouble-shooting a problem. The Alarm Log shows the nature of the alarm, when the alarm occurred and if the alarm has been acknowledged. This is supplemented by the historic Shutdown/Alarm Log, The Trend Display shows up to 12 parameters in a trend format. The time base of the trend can be set from 30 minutes and up to 999,999 min (> 1 year). There are 60 samples per trace so a new sample appears every 30 s for the minimum time base of 30 minutes. The engine exhaust temperatures are shown on a separate trend screen, There are two data logs in the REM Vie" system: = HMIDatalog— This is accessible from the OVERVIEW screen and the other is in the controller. The HMI data log screen samples data in a circular buffer for 60 seconds after the engine stops; thus allowing a detailed review from before the engine stopped to after it stopped. Up to 1,000 samples 64 points each can be captured. The sampling frequency is set from a supervisor HMI screen. A review of this data can help determine any recent changes. = Controller Data Log — This data log exists in the controller and is accessible only with the VO Toolkit software. Typically, the sampling period is 15 or 30 minutes allowing data capture for a longer period (1 to 3 months), 9. Appendix 4 — Shutdown/Alarm classes All the input sensors and selected calculated parameters (e.g. torque index) in both the REM Vud"— 500 /A and /S versions can be scaled and have provision for upper and lower alarms and upper and fower shut down limits as appropriate. As well, the alarms and shutdowns can be classified as shown below. The digital, analog, thermocouple and RTD inputs can be configured for different alarm and shutdown classes. B Class A— Alarm/shutdown functions are always enabled. All Class A shutdowns must be cleared before the unit can be started. Examples: engine oil level, compressor cylinder discharge temperature B class B— Alarm/shutdown functions are disabled until the B Timer is started. Class B functions are bypassed until the B Timer expires. Examples: lubricator no flow, engine jacket water temperature, intake manifold temperature Class b— Alarm/shutdown functions are disabled until the b Timer is started. Class functions are bypassed until the b Timer expires. Examples: engine/compressor oil pressures. 9-43 - REM Vue"— 500 /PLC Fie> TROUBLE SHOOTING GUIDE, B Class C— © Class Other — indication — E Disabled — Alarm/shutdown functions are disabled until the unit is running. Class C functions are then individually monitored. When a Class C function becomes healthy it is enabled, and will cause an alarm/shutdown if it then goes unhealthy. Custom logic as required Alarms and shutdowns are disabled. A sensor failure will generate an alarm No alarms, shutdowns or sensor failure alarm. 94d

You might also like