Professional Documents
Culture Documents
Fault Location
Fault Location
1. 1 TAGAKY Method
The general expression of the impedance seen by a relay for the six conventional
impedance loops is for a single-line power network
VR Rf K R
ZR = = m ZL1 +
IR KI (1.1)
KI is the ratio of the current at the relay over the change of the current due to the fault:
IR
KI =
I R (1.2)
and KR a factor depending upon the fault location and the network constants as shown in
Table I. Equation (1.1) can be expressed as:
VR = m ZL1 I R + Rf K R I R
(1.3)
or:
VR = m ZL1 I R + Rf K R (I R – I LD)
(1.4)
where ILD is the pre-fault or load current.
or:
____________________________________________________________________
Principle of single and double-ended data fault location
1
VR conj( I R I LD ) m ZL1 I R conj( I R I LD ) R f K R abs( I R I LD ) 2
(1.6)
For single-phase-to-ground faults, if the system is homogenous, i.e. the phase angles of
all the impedances in the single line network are equal and K R will be areal number if:
imag R f K R abs( I R I LD )2 0
(1.8)
and equation (1.6) can be expressed as:
In Table I, we have:
ZL0 ZL1
K0 L
ZL1 (1.11)
I 1R I 2R ZR1 + (1 – m) ZL1
C1 = C2 = = =
I 1F I 2F ZL1 + ZS1 + ZR1 (1.12)
_____________________________________________________________________
Principle of single and double-ended data fault location
2
numbers. If the angles are not absolutely equal, then C1 and C2 will be close to a real
number. How close they are to a real number is what we call the degree of homogeneity.
Table I Expression of KR
Fault Type KR
A-to-G 3
KR
2 C1 C0 ( 1 K 0 L )
B-to-G 3
KR
2 C1 C0 ( 1 K 0 L )
C-to-G 3
KR
2 C1 C0 ( 1 K 0 L )
A-B, A-B-G 1
2 C1
B-C, B-C-G 1
2 C1
C-A, C-A-G 1
2 C1
I 2R
VA m ZL1 I R R f 3 I 1F m ZL1 I R R f 3
C2 (1.16)
where the current IR supplied for this impedance loop is:
_____________________________________________________________________
Principle of single and double-ended data fault location
3
I R IA K0 L I 0R
(1.17)
Remember that for a phase-A-to-ground fault, we have at the fault point:
I 0F I 2F I 2F
(1.18)
Let us multiply both terms of equation (1.16) by the conjugate of the negative sequence
current:
I 2R conj( I 2R )
VA conj( I 2R ) m ZL1 I R conj( I 2R ) R f 3
C2 (1.19)
We end up with:
abs( I 2R )2
VA conj( I 2R ) m ZL1 I R conj( I 2R ) R f 3
C2 (1.20)
If the system is homogenous, C2 is a real number and we will have:
abs( I 2R )2
imag R f 3 0
C2 (1.21)
Equation (1.20) can be re-written as:
imagVA conj( I 2R )
m
imagZL1 I R conj( I 2R ) (1.23)
Replacing IR by its value, we finally get:
imagVA conj( I 2 R )
m
imagZL1 ( IA K0 L I 0R ) conj( I 2R ) (1.24)
In equation (1.24), all variables are readily available at the relay and the distance to the
fault can be computed.
Remembering that for a phase-B-to-ground fault, we have:
I 0F I 2F 120 I 1F 120
(1.23)
_____________________________________________________________________
Principle of single and double-ended data fault location
4
the same rational that led to equation (1.24) can be applied to phase-B-to-ground faults:
I 0F I 2F 120 I 1F 120
(1.27)
so that we get for a phase-C-to-ground faults:
I 0R
VA m ZL1 I R R f 3 I 0F m ZL1 I R R f 3
C0 (1.29)
Following the same rational and assuming that the zero sequence network is
homogeneous or C0 is a real number, we end up with:
imagVA conj( I 0R )
m
imag ZL1* ( IA K0 L I 0R )* conj( I 0R ) (1.30)
En consequently for phase-B-to-ground faults:
imagVB conj( I 0R )
m
imagZL1* ( IB K0 L I 0R )* conj( I 0R ) (1.31)
And finally, for phase-C-to-ground faults:
m
imag VC conj( I 0R )
imag ZL1* ( IC K0 L I 0R )* conj( I 0R ) (1.32)
The best solution depends then upon the more homogenous of the two sequence
networks, the negative or zero sequence networks.
The modified Tagaky can be applied to single-phase-to ground faults and double-phase
faults. Additional assumptions are required for double-phase-to-ground faults.
The viability and accuracy of the single-ended fault location depends essentially upon
two factors:
1. The value of the fault resistance and the degree of homogeneity.
_____________________________________________________________________
Principle of single and double-ended data fault location
5
2. The presence of a parallel line. Because of the zero sequence coupling, the fault
location equation is no longer valid.
NEG. SEQ.
Z1S Z1R
V2L V2R
I2L I2R
For short and medium length lines, the fault location can be determined using the
property that at the fault point, the voltage drop from either extremity is equal, so that we
have (see Fig. 2.1):
V 2 L V 2 R ZL1 I 2 R
m (2.2)
ZL1 ( I 2 L I 2 R )
Since m is a real number and the outcome of equation (2.2) could have a small imaginary
part, we have to take the real part of equation (2.2):
V 2 L V 2 R ZL1 I 2 R
m real (2.3)
ZL1 ( I 2 L I 2 R )
The advantage of equation (2.3) is that any effect from the fault resistance has been
eliminated.
A major advantage of the two-ended fault location using the negative sequence network
is that it is immune to zero sequence coupling: a parallel line does not have any impact
on the fault location.
_____________________________________________________________________
Principle of single and double-ended data fault location
6
A major shortcoming of the negative sequence network method is that it does not work
for tri-phase fault. One could resort then to the positive sequence network as shown in
figure 2.2.
POS. SEQ.
Z1S Z1R
V1L V1R
I1L-ILDS I1R-ILDR
Fault location formulas using the positive sequence network are similar to the ones used
with the negative sequence network. The difference is that the pre-fault current has to be
subtracted from the calculated positive sequence current at the relay location.
Equation (2.2) used in the case of the negative sequence network becomes when applied
to the positive sequence network:
As for equation (2.2), we take the real part to get a real distance m:
_____________________________________________________________________
Principle of single and double-ended data fault location
7
3. Example of application
We have a 400 kV transmission line with a phase-A-to-ground fault at 33% of the line
length from the left side. The fault resistance is 8.75 Ohms primary. The line secondary
parameters are:
Z1= 2.3019 +j 32.9193 Ohms
Z0=34.164+j 127.50 Ohms
The next secondary voltages and currents are recorded during the fault on the left hand
side line extremity
VAL =69.9450 – j 19.5875
VBL =62.1958 – j 67.68521
ICL =-0.1185 – j 0.1016
IAL =0.5715 – j 2.8522
IBL = 0.0891 – j 0.1472
ICL = -0.1185 – j 0.1016
The next secondary voltages and currents are recorded during the fault on the right-hand
side line extremity
VAR =77.8525 –j 19.4403
VBR =-61.4240 –j 67.6931
ICR =-0.1210 + j 0.0032
IAR =0.3292 – j 1.6383
IBR =0.08653 – j 0.0423
ICR =-0.1210 + j 0.0032
Based on this the next sequence quantities can be calculated for the left-hand side:
V2L =-6.4091 – j 0.0171
I2L =0.1823 – j 0.9692
V1L =83.1743 – j 19.6387
I1L =0.2086 – j 0.8493
I0L =0.1807 – j 1.03368
V2R =-3.9518 + j 0.0562
I2R =0.1024 – j 0.5995
V1R =85.4949 –j 19.5298
I1R =0.1286 – j 0.4797
I0R =0.0983 – j 0.5592
The load current can be obtained simply by subtracting the negative sequence current
from the positive sequence current. That provides the pre-fault current at both
extremities:
IALLD= I1L-I2L= 0.02633 + j 0.1199
IARLD= I1R-I2R= 0.02627 + j 0.1198
_____________________________________________________________________
Principle of single and double-ended data fault location
8
Using the Tagaki method from the left-hand side, we get for the distance using equation
(1.8):
m=0.3476
Using the Tagaki method from the right-hand side, we get for the distance using equation
(1.8):
m= 0.6953
Using the modified Tagaki from the left-hand side and using negative sequence
polarization according to equation (1.24), we get:
imagVAL conj( I 2 L )
m =0.3345
imagZL1 ( IAL K0 L I 0 L ) conj( I 2 L )
Using the modified Tagaki from the right-hand side and using negative sequence
polarization according to the same equation, we get:
imagVAL conj( I 2 L )
m =0.6747
imagZL1 ( IAL K0 L I 0 L ) conj( I 2 L )
Using the modified Tagaki from the left-hand side and using the zero sequence
polarization according to equation (1.30), we get:
imagVAL conj( I 0 L )
m =0.3358
imagZL1 ( IAL K0 L I 0 L ) conj( I 0 L )
Using the modified Tagaki from the right-hand side and using the zero sequence
polarization according to the same equation, we get:
imagVAR conj( I 2 R )
m =0.6739
imagZL1 ( IAR K0 L I 0 R ) conj( I 2 R )
Using data from both extremities and using the negative sequence network, we get from
equation (2.3):
V 2 L V 2 R ZL1 I 2 R
m real =0.3349
ZL1 ( I 2 L I 2 R )
Using data from both extremities and using the positive sequence network, we get from
equation (2.4):
_____________________________________________________________________
Principle of single and double-ended data fault location
9
V 1L V 1R ZL1 ( I 1R I 1R pre _ flt )
m real =0.3373
ZL1 ( I 1L I 1L )
pre flt I 1R I 1R pre _ flt
It appears that the modified Tagaki with negative sequence polarization or using data
from both extremities with either the negative or the positive sequence network provide
the best results.
Reference
Lecture notes, Gabriel Benmouyal, Schweitzer Electric
_____________________________________________________________________
Principle of single and double-ended data fault location
10