ACB LT ROOM

Equipmen
Sr.No. Feeder t Location Qty AMP
1 TOWER-C1 RM ACB Tower C-D 1 1000
2 Capacitor Panel 450 KVAR ACB Tower C-D 1 1000
3 INCOMER-1 TRF-1 (1250 KVA) ACB Tower C-D 1 2000
4 INCOMER-2 DG ACB Tower C-D 1 1600
5 BUS COPLOR ACB Tower C-D 1 2000
6 INCOMER-3 DG ACB Tower C-D 1 1000
7 INCOMER-4 TRF-2 (1250 KVA) ACB Tower C-D 1 2000
8 Capacitor Panel 450 KVAR ACB Tower C-D 1 1000
9 TOWER-C2 RM ACB Tower C-D 1 1000
10 TOWER-D RM ACB Tower C-D 1 1000
11 TOWER-B1 RM ACB Tower A-B 1 1000
12 Capacitor Panel 550 KVAR ACB Tower A-B 1 1250
13 INCOMER-1 TRF-1 (1600 KVA) ACB Tower A-B 1 2500
14 INCOMER-2 DG ACB Tower A-B 1 1600
15 BUS COPLOR ACB Tower A-B 1 2500
16 INCOMER-3 DG ACB Tower A-B 1 1250
17 INCOMER-4 TRF-2 (1600 KVA) ACB Tower A-B 1 2500
18 Capacitor Panel 550 KVAR ACB Tower A-B 1 1250
19 TOWER-B2 RM ACB Tower A-B 1 1000
20 TOWER-A RM ACB Tower A-B 1 1000

CAPACITOR PANEL
Sr.No. Equipment Location Qty KVAR
1 Capacitor panel Tower C-D 1 450
2 Capacitor panel Tower C-D 1 450
3 Capacitor panel Tower A-B 1 550
4 Capacitor panel Tower A-B 1 550

ISOLATOR PANELS
Equipmen
Sr.No. Feeder t Location Qty KVA
1 DG Incomer ACB Tower-B back side GF 1 1250
2 DG Incomer ACB Tower-B back side GF 1 1600
3 LT Panel Isolator Tower- A & B ACB Tower-B back side GF 1 2500
4 LT Panel Isolator Tower- A & B ACB Tower-B back side GF 1 3200
5 LT Panel Isolator Tower- C & D ACB Tower-D back side GF 1 2000

6 LT Panel Isolator Tower- C & D ACB Tower-D back side GF 1 2000


ROOM
Panel
Make Make Status Remarks
OMEGA Advance Operational
OMEGA Advance Not Operational
OMEGA Advance Operational
OMEGA Advance Operational
OMEGA Advance Operational Tripping Issue in breaker
OMEGA Advance Not Operational
OMEGA Advance Not Operational
OMEGA Advance Not Operational
OMEGA Advance Operational
OMEGA Advance Operational
OMEGA Advance Operational
OMEGA Advance Not Operational
OMEGA Advance Operational TNC not working
OMEGA Advance Not Operational
OMEGA Advance Operational
OMEGA Advance Operational Tripping Issue in breaker
OMEGA Advance Not Operational
OMEGA Advance Not Operational
OMEGA Advance Operational
OMEGA Advance Operational

OR PANEL
Panel
Make Status Remarks
Make
Advance Advance Not Operational
Advance Advance Not Operational
Advance Advance Not Operational
Advance Advance Not Operational

R PANELS
Panel
Make Make Status Remarks
OMEGA Advance Operational Handover Pending from Project side
OMEGA Advance Not Operational Handover Pending from Project side
OMEGA Advance Not Operational Handover Pending from Project side
OMEGA Advance Not Operational Handover Pending from Project side
OMEGA Advance Operational Handover Pending from Project side

OMEGA Advance Not Operational Handover Pending from Project side