Prosedur pengoperasian WW 505

A Start up
1. Klik first out reset di DCS
2. Klik start permissive di DCS
3. Klik remote speed set point Enable di DCS
4. Putar on switch ETS di panel ETS
5. Tekan button ETS di panel ETS
6. Putar switch interlock ETS ‘ Turbine lube oil press LL’
7. Tekan Reset di ww 505
8. Tekan Run di ww 505
9. Layar pindah ke Speed
10. "MvG to idle “ speed 500 rpm
11. Tekan enter – masukan set point speed ( 1000 rpm) – tekan enter
12. Tekan enter – masukan set point speed ( 1500 rpm) – tekan enter
13. Tekan enter – masukan set point speed ( 3000 rpm) – tekan enter
B Hot start tidak melalui idle
1. Klik first out reset di DCS
2. Klik start permissive di DCS
3. Klik remote speed set point Enable di DCS
4. Putar on switch ETS di panel ETS
5. Tekan button ETS di panel ETS
6. Putar switch interlock ETS ‘ Turbine lube oil press LL’
7. Tekan reset di ww 505
8. Tekan run di ww 505
9. Layar pindah ke speed
10. Pilih ‘idle /rated stopped’
11. Saat speed mulai naik ke 1000 rpm ,tekan enter – masukan set point (1500
rpm) – enter
12. Speed idle di 1500 rpm
13. Tekan enter- masukan set point ( 3000 rpm) – enter.
C Critical speed turbin 1700 rpm – 2750 rpm
D Critical speed generator 1100 rpm – 1400 rpm