Professional Documents
Culture Documents
Experiment - 2
Experiment - 2
ROLL NO.
SUBJECT.
Experiment no: 2
Aim:
Performance test on VCR system with continuous flow condition
Objective:
To find out the COP of vapor compression refrigeration (VCR) system with continuous
flow condition and with water cooled condenser
Theory:
Vapour compression uses circulating liquid refrigerant as the medium which absorbs and
removes heat from the space to be cooled and subsequently rejects that heat elsewhere. All VCR
systems have four components: the compressor, a condenser, an expansion valve and a vapour.
Figure - 1: VCR Cycle on P-h diagram
Circulating refrigerant enters the compressor in the thermodynamic state known as a
saturated vapour and is compressed to a higher pressure, resulting in a higher temperature as
well. The hot, compressed vapour is then in the thermodynamic state known as a superheated
vapour and it is at a temperature and pressure at which it can be condensed with either cooling
water or cooling air flowing across the coil or tubes. This is where the circulating refrigerant
rejects heat from the system and the rejected heat is carried away by either the water or the air.
The saturated liquid after condensing passes through an expansion device resulting in pressure
and temperature drop. This two-phase mixture then passes through the evaporator at a
temperature lower than the ambient. This results in isobaric heat transfer to the refrigerant, thus
providing cooling effect.
As shown in the figure the standard single stage, saturated vapour compression
refrigeration system consists of the following four processes:
Process 1-2: Isobaric heat extraction in the evaporator Process.
Process 2-3: Isentropic compression of superheated vapour in compressor.
Process 3-4: Isobaric heat rejection in condenser.
Process 4-1: Isenthalpic expansion of saturated liquid in expansion device.
Experiment setup
Studying a VCR system requires many data points like temperature, pressure, mass flow
rate etc. Besides VCR cycles come in various forms and different components according to the
application. Studying different types of systems would require building a special test rig. Most
VCR lab equipment come with a chiller box, a capillary and a standard air-cooled condenser.
While existing systems provide temperature scanners and analog pressure gauges, data
acquisition is always an issue. This variable VCR system is designed to be “variable” in true
sense. It consists of a variable speed compressor, two options for cooling load, two types of
condensers and three types of expansion device. This gives a flexibility of operating 12 different
VCR systems in a single setup. It helps is analyzing the VCR system in every possible
configuration. Each of this configuration can be operated at the desired compressor speed.
Data acquisition and controlling is made seamless with the use of HMI. The entire
operation of the VCR system is automated with PLC controls and data logging via USB. The
system can also be remotely operated by an Ethernet connection
Operation Procedure:
1. The selections for VCR cycle can be initiated when the heater time reaches to around
25min.
2. Click on the next Tab on the schematic diagram to jump to the VCR selections page.
3. Expansion device selection: Electronic Expansion Valve (EEV) with 20% opening.
4. Listen for the distinctive sound of a solenoid valve opening. This sound acts a
confirmation that the required VCR line is open.
5. If the sound of a solenoid valve is not heard, try clicking the required expansion device
tab on and off on the HMI screen to hear the sound again.
6. If the sound is not heard even after repeated clicking, contact the maintenance team for
resolving the issue.
7. After successfully selecting the expansion device and hearing the solenoid valve sound,
click next tab.
8. Condenser selection: select air cooled condenser.
9. Listen for the distinctive sound of a solenoid valve opening. This sound acts a
confirmation that the required VCR line is open.
10. If the sound of a solenoid valve is not heard, try clicking the required condenser tab on
and off on the HMI screen to hear the sound again.
11. If the sound is not heard even after repeated clicking, contact the maintenance team for
resolving the issue.
12. Ensure that you have followed the message displayed next to the condenser tabs before
proceeding further.
13. After successfully selecting the condenser and hearing the solenoid valve sound, click
next tab.
14. Water flow selection: Select the required water flow method for the cold-water tank. For
current experiment select live water flow i.e., fresh water will pass through plate heat
exchanger and then leave the system. There is no use of evaporator tank (Coolant tank)
for live system.
15. Ensure that you have followed the message displayed next to the water flow tabs before
proceeding further.
16. There are no solenoid valve sounds in this selection.
17. Enter the compressor frequency.
18. Click finish.
19. Regulate the constant flow rate through the evaporator (Plate heat exchanger)
20. Take reading at an interval of 10 second of the time
21. Change the coolant flow through evaporator (PHE) and Repeat steps 14 to 20
OBSERVATION TABLE
Compressor
Water flow Temperature (C) Pressure (bar)
Power (W)
rate (Lit/min)
T1 T2 T3 T4 T5 T6 T8 T9 P1 P2 Wc
8.7 79.1 29.2 13.1 23.1 23.8 17.5 23.2 43.4 1.6 10.9 1674
9.9 82.1 30.5 14.1 23.1 23.8 17.3 23.1 46.3 1.7 11.7 1730
Shutdown Process
1. Once the VCR cycle is the stopped and the data is logged to USB drive.
2. Shutting down on HMI operation: After stopping the VCR cycle for any reason, the user
must not switch off the system immediately.
3. Allow the solenoid valves to remain open and equalize the refrigerant in the system.
Equalization of refrigerant can be visualized in the rotameter.
4. The user can proceed to switch off the system once the equalization stops.
5. Once the VCR cycle is stopped by the user, he can safely turn off the main switch and
shut down the system after equalization.
6. If in HMI mode the system cuts off on an indication or a warning message, the user can
safely turn off the main switch and shut down the system after equalization.
7. If in HMI mode the system trips on an error message, the user must first resolve the error
and then turn off the main switch.
Calculation:
Result Table:
Refrigerant
Cooling Load COP Heating COP
Sr. No. mass flow rate
(W) (Experimental) (Theoretical)
(kg/s)
Conclusion:
Safety Hazards:
Personal Protective Equipment: Safety Goggles; Standing Shields, Sturdy Shoes.
Personal Care:
Do not wear loose clothing, Neck Ties/Scarves; Jewelry (remove).
Tie back long hair.
Take Care while doing electrical connections, particularly with grounding;
Do not use frayed electrical cords
Clean any spills immediately