ELECTRICAL POWER REQUIREMENT FOR DAIKIN VRV X OUTDOOR UNITS

RECOMMONDED POWER SUPPLY IS 3PH + N, 380 – 415 VAC, 50Hz. WITH EARTHING.
EARTH LEAKAGE CKT. BRAKER 300mA FOR EACH ODU IS MANDATORY.
Nominal size of Cu
MCB (Amp) ELCB (Amp) conductor, 4core XLPE
SR. NO. MODEL
POWER CONSUMPTION (kw) RLA MFA TOCA MCA
4 Pole
Qty (300mA,4-Pole) insulated armoured
cables
130% 120% 110% 100% Amps. Amps. Amps. Amps. Amps. Amps. SQ. MM.
1 RXQ18ARY6 15.5 15.4 15.4 15.3 23.6 35 37.8 30.2 40 2 40 10
1 RXQ20ARY6 17.9 17.8 17.8 17.7 26.4 45 41.7 38.9 63 2 63 10

NOTE:-
1. RLA is based on Indore temp. 27ºc and outdoor temp. 35ºc
2. Max. aloowable voltage variation between phase is 2%
3. Select wire size based on the larger value of MCA or TOCA
4. MFA is used to select circuit breaker and the ground fault circuit interrupter(ELCB)
SYMBOLS:-
MCA:- Min. circuit amps.
TOCA:- Total over current amps.
MFA:- Max. fused amps.
RLA:- Rated load amps.
Safety Measures
1) Time delay of atleast 20 seconds is required in between power switchovers. In case time delay is not possible reverse phase protection is required
2) Auto phase change over switch should be installed in main panel to automatically change the phase sequence and
to avoid tripping of outdoor units in case of power switchovers