DOCUMENT NUMBER FIRE FIGHTING SYSTEM HYDRAULIC Page 1 of 131

OSP054-PR-REP-14606 CALCULATION REPORT OTEC PROJECT NO.: OSP054

WASTANI PETROLEUM COMPANY (WASCO)

THE ENGINEERING OF FIRE FIGHTING NETWORK EXTENSION

7 01.04.2020 CTR-005 - Issued for Design M Hamed A A Tawab A S/A E


6 16.02.2020 CTR-005 - Issued for Client Approval M Hamed I Abdallah A S/A E

5 08.01.2020 CTR-005 - Issued for Client Review M Hamed I Abdallah A S/A E


4 21.05.2019 Re-Issued for Client Approval M. Hamed A. Saleh A. Fawzi
3 05.03.2019 Re-Issued for Client Approval M. Hamed A. Saleh A. Fawzi
2 20.12.2018 Issued for Client Approval M. Hamed A. Saleh A. Fawzi
1 25.11.2018 Issued for Client Approval M. Hamed A. Saleh A. Fawzi
0 27.05.2018 Issued for Client Review M. Hamed A. Gamal A. Fawzi
Rev Date Issuance Purpose Prep’d Chk’d App’d
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network Extension
Fire Fighting System Hydraulic Calculation Report

Changes List
Date
Rev. prepared Prepared by Description
(DD.MM.YYYY)
1 25.11.2018 M Hamed According to the new firefighting philosophy

2 20.12.2018 M Hamed New condensate tanks dike- foam case added


New scope of work according to var. order No. OSP054-
3 05.03.2019 M Hamed
CTR-004-Rev.1
4 21.05.2019 M Hamed Updated as per client comments
New scope of work according to var. order No. OSP-054-
5 08.01.2020 M Hamed
CTR-005-Rev.3
6 16.02.2020 M Hamed Updated as per client comments

7 01.04.2020 A. A.Tawab CTR-5-Issued for Design

Page 2 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

Table of Contents
1 INTRODUCTION .............................................................................................................. 4
1.1 References.............................................................................................................................. 4
1.2 Units of Measurement ............................................................................................................ 5
1.3 Codes and Standards ............................................................................................................. 5
1.4 Abbreviations .......................................................................................................................... 6
2 PROJECT OBJECTIVES AND SOW ............................................................................... 6
3 HYDRUALIC CALCULATIONS ........................................................................................ 8
3.1.1 Formulae ......................................................................................................................... 8
3.1.2 Equivalent Pipe Lengths of Valves and Fittings ............................................................. 9
3.1.3 Pipe friction Loss ........................................................................................................... 10
3.2 Hydraulic Calculation Procedures ........................................................................................ 11
3.3 Hydraulic Calculation Working sheets .................................................................................. 11
4 CONCLUSION................................................................................................................ 12
Annex A: Pump Head calc for FH-19 ............................................................................... 13
Annex B: Area-34 Case ..................................................................................................... 33
Annex C: Condensate tanks Case ................................................................................... 50
Annex D: Condensate tank dike -foam case ................................................................... 90

Page 3 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

1 INTRODUCTION

El Wastani Petroleum company (WASCO) owns and operates a network of wells and a gathering
system in Egypt. El Wastani facility is located at EW-1 well location at Damietta.
The original facility is composed of primary separation of gas and liquids. The original design was for
35 MMSCFD of a raw gas. More drilling and outstanding well performances prompted for upgrades
and modifications to the facility to handle an increased gas and liquids production.

1.1 References

1013-73-06-DR-028 Fire water system PID

1013-73-06-DR-029 Fire water ring main and hydrant monitor placement

1013-95-05-DR-04-01 Fire water layout ring main

2185-EW-1-ESB-R30 As built survey of EW-1 well site

1013-96-06-DS-013-001 Data sheets for pumps (Fire Water)

1013-95-05-SP-002 Specification for piping and valve material

3398-210-10-RT-004-Rev.3 Fire & Explosion consequence study

3398-210-10-RT-005-Rev.2 Fire & Gas Detection & Protection Adequacy Study

OSP054-PR-REP-14602 OTEC Water Demand Calculations

Page 4 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

1.2 Units of Measurement


In general SI system of metric units will be used for this project.

1.3 Codes and Standards

• The Egyptian code


• American Petroleum Institute (API):

API RP 2021 Management of atmospheric storage tank fires


API RP 2030 Application of fixed water spray systems for fire protection in the petroleum and
petrochemical industries
API RP 2216 Ignition Risk of Hydrocarbon Liquids and Vapours by Hot Surfaces in the Open Air

• National Fire Protection Association (NFPA)

NFPA 10 Portable Fire Extinguishers


NFPA 11 Standard for Low, Medium and High Expansion Foam.
NFPA 12 Standard on Carbon Dioxide Extinguishing system
NFPA 13 Installation of Sprinkles Systems.
NFPA 14 Standard for the Installation of Standpipe and Hose Systems
NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection.
NFPA 16 Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray
Systems
NFPA20 Standard for the Installation of Stationary Pumps for Fire Protection.
NFPA22 Standard for Water Tanks for Private Fire Protection
NFPA24 Standard for the Installation of Private Fire Service Mains and their
Appurtenances
NFPA25 Water based fire protection systems
NFPA30 Flammable and Combustible Liquids Code
NFPA37 Standard for the Installation and Use of Stationary Combustion Engines and Gas
Turbines
NFPA54 National Fuel Gas Code
NFPA 70 National Electric code
NFPA 72 National Fire Alarm Code
NFPA 75 Protections of Electronic Computer / Data Processing Equipment
NFPA 850 Recommended Practice for Fire Protection for Electric Generating Plants and
High Voltage Direct Current Converter Stations
NFPA 1901 Standard for Automotive Fire Apparatus.
NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems

• British Standards (BS) and (BS EN).

Page 5 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

BS EN 3 Portable fire extinguishers


BS EN 54-1 Components of Automatic Fire Detection Systems

1.4 Abbreviations

Client El Wastani Petroleum company (WASCO)


OTEC OnSpec Tawakol for Engineering and Contracting
SOW Scope of Work
EWP EW-1 well site Plant
FWT Fire water tank
HMD Hydraulically most demanding
U/G Under ground
MSDS Material safety data sheet
GPM Gallon per minute
WCS Worst case scenario

2 PROJECT OBJECTIVES AND SOW


This report presents and illustrates the plant firefighting system water demand calculations; the plant

consists of three main areas described below

1- Process area.
2- Accommodation area.
3- Warehouses and storage areas.

Process area is covered by an existing firefighting system with U/G fire water network loop of 6"
Carbon Steel pipes with FWT of capacity 1500 m³, four pumps; two jockey pumps and two diesel
pumps of 1000 GPM flow rate.
Accommodation & Warehouses and storage areas area are isolated by fences and not covered by
the existing firefighting system.
The scope of work of the project is basic and detailed engineering of the firefighting system for the
plant as described below:

1- Original scope: is to perform the engineering for the Extension of the Existing Fire Water
Manual Network only which consists of water loop and manual hydrants outside the
equipment skids.
2- New scope: is reference to variation order no. OSP054-CTR-001-Rev.0 and it is based on
the recommendations and output of ENPPI Fire Adequacy Report No. (3398-210-10-RT-
005 Rev.2).
3- New scope: is reference to variation order No. (OSP054-CTR-004-Rev.1) and Fire
Consequence Study Modelling report for area 34 No. (OSP054-PR-REP-14613-Rev.1).
4- New scope: is reference to variation order No. (OSP-054-CTR-005-Rev.3)

OTEC extra scope of work is to cover the below listed 48 equipment at the process area by designing
Fixed Firefighting and Cooling system. The execution of the new design shall consider the following

Page 6 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

as per ENPPI Fire Adequacy Report No. (3398-210-10-RT-005 Rev.2) and Fire Consequence Study
Modelling report for area 34 No. (OSP054-PR-REP-14613-Rev.1).
Fire control and/or extinguishment.
1- Cooling fire engulfed equipment exposed to thermal radiation.
2- Prevention of fire escalation.

Page 7 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

3 HYDRUALIC CALCULATIONS

3.1.1 Formulae

3.1.1.1 Friction Loss Formula


Pipe friction losses is determined on the basis of the Hazen and Williams formula,

where:
p = frictional resistance in psi per foot of pipe
Q = flow in gpm
d = actual internal diameter of pipe in inches
C = friction loss coefficient
or in SI units,

where:
Pm = frictional resistance in bars per meter of pipe
Qm = flow in L/min
dm = actual internal diameter in mm
C = friction loss coefficient

3.1.1.2 Velocity pressure Formula


The velocity pressure is determined on the basis of the formula,

where:
Pv = velocity pressure in psi
Q = flow in gpm
D = inside diameter in inches

Page 8 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

3.1.1.3 Normal pressure Formula


Normal pressure is determined on the basis of the formula,

where:
Pn = normal pressure in bar (psi)
Pt = total pressure in bar (psi)
Pv = velocity pressure in bar (psi)

3.1.1.4 Nozzle Discharge Formula


The discharge of a nozzle is calculated by the formula,

where:
Q = gpm flowing from the nozzle
K = nozzle K-factor
P = total pressure in psi at the flow Q
or in SI units,

where:
Qm = flow in L/min
Km = nozzle K-factor (where Km equals 14.4 K)
Pm = total pressure in bars at the flow Qm

3.1.2 Equivalent Pipe Lengths of Valves and Fittings


Equivalent pipe lengths of valves and fittings is calculated according to below table 8.5.2.1 in NFPA

15.

Page 9 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

3.1.3 Pipe friction Loss


Pipe friction loss is calculated in accordance with the Hazen and Williams formula, using C=120
according to the below table 8.5.3.10 in NFPA 15.

Page 10 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

3.2 Hydraulic Calculation Procedures


Hydraulic calculations are performed in accordance with NFPA 15.

1- Calculating pump pressure at FH-19:


o The system is designed so that the pressure at each firewater hydrant / monitor is not
less than 100 psi (6.9 bar).
o The calculated pump pressure is 106 psi (7.3 bar) at FH-19, the required pump pressure
is 145 psi (10 bar).
2- Hydraulic calculations are performed for Three fire scenarios:
o The fire is in process area 34 (WCS).
• The total flow rate required is 2500 GPM and the calculated is 2500 GPM.
• The pressure at HMD is 119.2 psi (8.2 bar).
o The fire is inside condensate tank (Tank T3100B).
• The total flow rate required is 2690.3 GPM and the calculated is 2692 GPM.
• The pressure at HMD is 118.2 psi (8.2 bar).
• The total number of water spray nozzles is 108 with K-factor (1.2).
• The pressure at mushroom nozzle of tank T3100B is 112.6 psi (7.8 bar).
• Assume that the pressure loss from foam bladder foam tank is 21.75 psi (1.5 bar).
• The pressure at foam box of tank T3100B is 91 psi (6.3 bar) and K-factor is (21).
o The fire is inside dike of condensate tanks (Tank T3100A/B).
• The total flow rate required is 2641.5 GPM and the calculated is 2697.3 GPM.
• Assume that the pressure loss from foam bladder foam tank is 21.75 psi (1.5 bar).
• The pressure of foam maker at HMD is 107.6 psi (7.4 bar).
• The total number of foam maker for dike of condensate tanks (Tank T3100A/B) is
26 with K-factor (10).

3.3 Hydraulic Calculation Working sheets


- For detailed hydraulic calculation sheets, see Annex-A/B/C/D

Page 11 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

4 CONCLUSION
Hydraulic calculations are performed in accordance with NFPA 15.
1- The required pump pressure is 145 psi with 3000 GPM.
2- Hydraulic calculations are performed for three fire scenarios showing in the following table:

Condensate tank Dike of condensate


Fire scenarios Area (34)
(Tank T3100B) tanks (Tank T3100A/B)

Total required flow rate (GPM) 2250 2643.7 2641.5

Total calculated flow rate (GPM) 2250 2690.3 2697.3


The required density rate
- 2.7 1.1
(GPM/m2)
The calculated density rate
- 2.71 : 2.77 1.13
(GPM/m2)

Pressure at HMD (bar) 8.2 8.2 7.4

Total no. of water spray nozzles/


- 108 26
foam maker
K-factor of water spray nozzles/
- 1.2 10
foam maker

Page 12 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

Annex A: Pump Head calc for FH-19

Page 13 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

55

====================================================================================================
====================

PIPENET SPRAY/SPRINKLER MODULE

====================================================================================================
====================

VERSION 1.8

====================================================================================================
====================

Results for : Firefighting Hydraulic Calculation for WASCO EW PLANT


Firefighting Pump head Calculations at FH-19
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
====================

Page 14 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

11:52 on 15-Feb-2020
1

LIST OF CONTENTS
================

Page
----

Control Information......................................... 1

Fluid System................................................ 1

Design Information.......................................... 2

Pipe Configuration.......................................... 4

Nozzle Configuration........................................ 8

Designed Diameters & Flowrates.............................. 9

Flow in Pipes............................................... 12

Flow through Nozzles........................................ 14

Flow at Inlets.............................................. 15

Materials Take Off.......................................... 16

Important Notice............................................ 19

Comments.................................................... 20

Page 15 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 1 OF 20
---------------------------------------------------------------------------------------------------
--------------------

CONTROL INFORMATION
-------------------
Convergence accuracy = 1.00E-03
Maximum no. of iterations = 50
Elevation Check Tolerance = 0.50 metres
Warnings Control Option = 0
****** Diagnostic level = 2

FLUID SYSTEM
------------

Fluid Class = 1 (Liquid )


Density = 998.2 kg/cu.m
Viscosity = 2.419 lb/ft hr
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 2 OF 20
---------------------------------------------------------------------------------------------------
--------------------

DESIGN INFORMATION
------------------

Waterspray System

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Schedule Not Lined
10 -- HDPE Not Lined

Design to NFPA 2013 Rules


Using the Hazen-Williams Equation

Velocity Pressure Model: NFPA formula

Pressure loss at entrance: Ignore

Pressure loss at exit: Ignore

Page 16 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 3 OF 20
---------------------------------------------------------------------------------------------------
--------------------

AVAILABLE PIPE SIZES AND MAXIMUM VELOCITIES USED FOR PIPE SIZING
----------------------------------------------------------------

ANSI B36.10 Sch.40 ANSI B36.10 Schedule HDPE


Not lined Not lined Not lined

Nom.Bore Act.Diam Max.Vel. Nom.Bore Act.Diam Max.Vel. Nom.Bore


Act.Diam Max.Vel.
(inches ) (inches ) (m/sec ) (inches ) (inches ) (m/sec ) (inches )
(inches ) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------

0.6250 0.6220 6.0000 0.6250 Not acceptable 0.6250 Not


acceptable
0.7500 0.8240 6.0000 0.7500 Not acceptable 0.7500 Not
acceptable
1.0000 1.0490 6.0000 1.0000 Not acceptable 1.0000 Not
acceptable
1.2500 1.3800 6.0000 1.2500 Not acceptable 1.2500 Not
acceptable
1.5000 1.6100 6.0000 1.5000 Not acceptable 1.5000 Not
acceptable
2.0000 2.0670 6.0000 2.0000 Not acceptable 2.0000 Not
acceptable
2.5000 2.4690 6.0000 2.5000 Not acceptable 2.5000 Not
acceptable
3.0000 3.0680 6.0000 3.0000 Not acceptable 3.0000 Not
acceptable
3.5000 3.5480 6.0000 3.5000 Not acceptable 3.5000 Not
acceptable
4.0000 4.0260 6.0000 4.0000 Not acceptable 4.0000 Not
acceptable
5.0000 5.0470 6.0000 5.0000 Not acceptable 5.0000 Not
acceptable
6.0000 6.0650 6.0000 6.0000 Not acceptable 6.0000
5.1000 3.0000
8.0000 7.9810 6.0000 8.0000 8.1250 6.0000 8.0000
6.4000 3.0000
10.0000 10.0200 6.0000 10.0000 10.2500 6.0000 10.0000
8.0000 3.0000
12.0000 11.9380 6.0000 12.0000 12.2500 6.0000 12.0000
10.4000 3.0000
14.0000 13.1240 6.0000 14.0000 13.3760 6.0000 13.9999 Not
acceptable
16.0000 15.0000 6.0000 16.0000 15.3760 6.0000 16.0000 Not
acceptable
18.0000 16.8760 6.0000 18.0000 17.3760 6.0000 18.0000 Not
acceptable
20.0000 18.8120 6.0000 20.0000 Not acceptable 20.0000 Not
acceptable
24.0000 22.6240 6.0000 23.9999 Not acceptable 23.9999 Not
acceptable

Page 17 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 4 OF 20
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
1 35 1 6.000 4.000 0.000 150.0
3.367
2 1 2 6.000 2.500 2.500 120.0
3.048
9 21 13 6.000 21.20 0.000 120.0
19.20
10 13 14 6.000 122.0 0.000 120.0
37.19
11 15 14 6.000 122.5 0.000 120.0
37.49
12 27 28 6.000 111.3 0.000 120.0
37.49
13 15 31 6.000 27.00 0.000 120.0
4.267
14 14 12 6.000 121.0 0.000 120.0
60.05
15 13 17 6.000 101.3 0.000 120.0
94.18
16 48 12 6.000 119.0 0.000 120.0
22.56
22 16 24 6.000 24.00 0.000 120.0
9.144
23 24 25 6.000 45.20 0.000 120.0
26.82
24 25 26 6.000 63.00 0.000 120.0
18.29
25 26 27 6.000 100.00 0.000 120.0
27.74
26 21 28 6.000 73.50 0.000 120.0
37.49
27 28 16 6.000 54.80 0.000 120.0
18.29
28 29 14 6.000 141.0 0.000 120.0
28.35
29 66 30 12.00 109.0 0.000 120.0
18.29
30 31 16 6.000 113.0 0.000 120.0
55.78
31 30 15 6.000 141.0 0.000 120.0
37.49
32 66 29 6.000 13.50 0.000 120.0
27.43
33 26 33 6.000 63.00 0.000 150.0
9.309
34 33 34 6.000 66.30 0.000 150.0
18.42
35 34 35 6.000 78.00 0.000 150.0
12.08
36 33 36 6.000 100.00 0.000 150.0
13.07
37 27 36 6.000 63.00 0.000 150.0
6.536
38 36 37 6.000 5.500 0.000 150.0
6.536
39 35 38 6.000 159.0 0.000 150.0
24.36
40 38 37 6.000 79.50 0.000 150.0
11.88
50 17 50 6.000 2.500 0.000 120.0

Page 18 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

9.144
51 50 48 6.000 9.500 0.000 120.0
10.06
55 87 88 12.00 9.000 0.000 150.0
14.12
56 53 80 12.00 21.50 0.000 150.0
14.12
57 54 55 12.00 78.90 0.000 150.0
15.53
58 55 75 12.00 56.20 0.000 150.0
43.76
59 56 57 12.00 1.0000 -1.0000 150.0
6.117
60 58 57 12.00 1.0000 0.000 150.0
0.000
61 59 58 12.00 1.0000 -1.0000 150.0
6.117
62 60 59 12.00 6.500 0.000 150.0
14.12
63 52 83 12.00 11.20 0.000 150.0
19.06
64 61 62 12.00 1.0000 -1.0000 150.0
6.117
65 62 63 12.00 1.0000 0.000 150.0
0.000
66 63 64 12.00 1.0000 1.0000 150.0
6.117

Page 19 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 5 OF 20
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
67 64 65 12.00 6.500 0.000 150.0
15.53
73 65 70 12.00 40.30 0.000 150.0
14.12
74 70 60 12.00 60.30 0.000 150.0
15.53
75 32 87 12.00 34.30 0.000 150.0
56.47
76 71 72 12.00 1.0000 -1.0000 150.0
6.117
77 72 73 12.00 1.0000 0.000 150.0
0.000
78 73 74 12.00 1.0000 1.0000 150.0
6.117
79 56 75 12.00 52.50 0.000 150.0
31.06
80 74 75 12.00 6.700 0.000 150.0
0.000
81 83 77 12.00 11.30 0.000 150.0
0.000
82 77 53 12.00 21.50 0.000 150.0
29.65
83 78 52 12.00 12.60 0.000 150.0
14.12
84 97 78 12.00 25.50 0.000 150.0
0.000
85 97 61 12.00 33.00 0.000 150.0
14.12
90 3 6 12.00 1.0000 0.000 120.0
37.48
91 6 8 12.00 1.0000 1.0000 120.0
9.331
92 88 93 12.00 9.000 0.000 150.0
14.12
93 93 94 12.00 10.000 0.000 150.0
14.12
94 8 18 12.00 3.000 0.000 120.0
9.331
95 18 23 12.00 0.5000 0.000 150.0
3.059
96 23 39 12.00 43.70 -2.500 150.0
3.059
97 39 76 12.00 5.600 0.000 150.0
0.000
98 94 95 12.00 9.000 0.000 150.0
14.12
99 95 96 12.00 24.40 0.000 150.0
42.35
100 96 71 12.00 45.00 0.000 150.0
0.000
101 40 41 12.00 4.000 0.000 150.0
3.059
102 80 54 12.00 78.90 0.000 150.0
15.53
103 41 68 12.00 3.000 -1.0000 150.0
3.059
104 68 69 12.00 2.000 0.000 150.0
3.059
105 69 32 12.00 3.000 1.0000 150.0

Page 20 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

3.059
106 76 40 12.00 39.00 0.000 150.0
6.353
107 76 66 6.000 4.000 0.000 150.0
0.000

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
1 1 x 2 2.773 1 x 5 0.5942
2 1 x 9 3.048
9 2 x 4 9.144 1 x 5 0.9144

Page 21 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 6 OF 20
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
10 4 x 2 4.267 2 x 4 9.144 2 x 5 0.9144
11 4 x 4 9.144 1 x 5 0.9144
12 4 x 4 9.144 1 x 5 0.9144
13 1 x 2 4.267
14 2 x 1 2.134 6 x 4 9.144 1 x 5 0.9144
15 10 x 4 9.144 3 x 5 0.9144
16 2 x 1 2.134 2 x 4 9.144
22 1 x 4 9.144
23 2 x 2 4.267 2 x 4 9.144
24 2 x 4 9.144
25 2 x 2 4.267 2 x 4 9.144 1 x 5 0.9144
26 4 x 4 9.144 1 x 5 0.9144
27 2 x 4 9.144
28 3 x 4 9.144 1 x 5 0.9144
29 1 x 4 18.29
30 6 x 4 9.144 1 x 5 0.9144
31 4 x 4 9.144 1 x 5 0.9144
32 3 x 4 9.144
33 1 x 2 2.773 1 x 4 5.942 1 x 5 0.5942
34 3 x 4 5.942 1 x 5 0.5942
35 2 x 2 2.773 1 x 4 5.942 1 x 5 0.5942
36 2 x 4 5.942 2 x 5 0.5942
37 1 x 4 5.942 1 x 5 0.5942
38 1 x 4 5.942 1 x 5 0.5942
39 4 x 4 5.942 1 x 5 0.5942
40 2 x 4 5.942
50 1 x 4 9.144
51 1 x 4 9.144 1 x 5 0.9144
55 1 x 4 14.12
56 1 x 4 14.12
57 1 x 4 14.12 1 x 5 1.412
58 3 x 4 14.12 1 x 5 1.412
59 2 x 1 3.059
61 2 x 1 3.059
62 1 x 4 14.12
63 1 x 4 14.12 1 x 9 4.941
64 2 x 1 3.059
66 2 x 1 3.059
67 1 x 4 14.12 1 x 5 1.412
73 1 x 4 14.12
74 1 x 4 14.12 1 x 5 1.412
75 4 x 4 14.12
76 2 x 1 3.059

Page 22 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 7 OF 20
-------------------------------------------------------------------------------------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
-------------------------------------------------------------------------------------------------
78 2 x 1 3.059
79 2 x 4 14.12 2 x 5 1.412
82 2 x 4 14.12 1 x 5 1.412
83 1 x 4 14.12
85 1 x 4 14.12
90 1 x 2 9.331 1 x 5 2.074 1 x 7 26.08
91 1 x 2 9.331
92 1 x 4 14.12
93 1 x 4 14.12
94 1 x 2 9.331
95 1 x 1 3.059
96 1 x 1 3.059
98 1 x 4 14.12
99 3 x 4 14.12
101 1 x 1 3.059
102 1 x 4 14.12 1 x 5 1.412
103 1 x 1 3.059
104 1 x 1 3.059
105 1 x 1 3.059
106 1 x 2 6.353

Fitting types are :


1 -- 45 Deg Elbow
2 -- 90 Deg Standard Elbow
3 -- 90 Deg Long Radius Elbow
4 -- Tee or Cross (Flow Turned Thro 90 Deg)
5 -- Gate Valve
6 -- Swing Check Valve
7 -- Non-Return Valve
8 -- Ball Valve
9 -- Butterfly Valve
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 8 OF 20
-------------------------------------------------------------------------------------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (bar G ) (bar G )
---------------------------------------------------------------------------------------------------
FH-19/0 2 1 94.5000 250.0000 0.69000E+01 0.12000E+02

Nozzle types are :


1 -- User Defined

Page 23 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 9 OF 20
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
1 35 1 250.0005 10 5.1000 6.0000 *
2 1 2 250.0006 3 6.0650 6.0000 *
9 21 13 -121.0997 3 6.0650 6.0000 *
10 13 14 -80.0800 3 6.0650 6.0000 *
11 15 14 0.7490 3 6.0650 6.0000 *
12 27 28 -132.3196 3 6.0650 6.0000 *
13 15 31 128.9009 3 6.0650 6.0000 *
14 14 12 41.0197 3 6.0650 6.0000 *
15 13 17 -41.0197 3 6.0650 6.0000 *
16 48 12 -41.0197 3 6.0650 6.0000 *
22 16 24 117.6810 3 6.0650 6.0000 *
23 24 25 117.6810 3 6.0650 6.0000 *
24 25 26 117.6810 3 6.0650 6.0000 *
25 26 27 -7.0448 3 6.0650 6.0000 *
26 21 28 121.0997 3 6.0650 6.0000 *
27 28 16 -11.2198 3 6.0650 6.0000 *
28 29 14 120.3507 3 6.0650 6.0000 *
29 66 30 129.6498 3 11.9380 12.0000 *
30 31 16 128.9009 3 6.0650 6.0000 *
31 30 15 129.6498 3 6.0650 6.0000 *
32 66 29 120.3507 3 6.0650 6.0000 *
33 26 33 124.7478 10 5.1000 6.0000 *
34 33 34 141.2177 10 5.1000 6.0000 *
35 34 35 141.2177 10 5.1000 6.0000 *
36 33 36 -16.4699 10 5.1000 6.0000 *
37 27 36 125.2528 10 5.1000 6.0000 *
38 36 37 108.7829 10 5.1000 6.0000 *
39 35 38 -108.7829 10 5.1000 6.0000 *
40 38 37 -108.7829 10 5.1000 6.0000 *
50 17 50 -41.0197 3 6.0650 6.0000 *
51 50 48 -41.0197 3 6.0650 6.0000 *
55 87 88 0.0000 10 10.4000 12.0000 *
56 53 80 0.0035 10 10.4000 12.0000 *
57 54 55 0.0035 10 10.4000 12.0000 *
58 55 75 0.0035 10 10.4000 12.0000 *
59 56 57 0.0035 10 10.4000 12.0000 *
60 58 57 -0.0035 10 10.4000 12.0000 *
61 59 58 -0.0035 10 10.4000 12.0000 *
62 60 59 -0.0035 10 10.4000 12.0000 *

Page 24 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 10 OF 20
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
63 52 83 0.0035 10 10.4000 12.0000 *
64 61 62 -0.0035 10 10.4000 12.0000 *
65 62 63 -0.0035 10 10.4000 12.0000 *
66 63 64 -0.0035 10 10.4000 12.0000 *
67 64 65 -0.0035 10 10.4000 12.0000 *
73 65 70 -0.0035 10 10.4000 12.0000 *
74 70 60 -0.0035 10 10.4000 12.0000 *
75 32 87 0.0000 10 10.4000 12.0000 *
76 71 72 0.0000 10 10.4000 12.0000 *
77 72 73 0.0000 10 10.4000 12.0000 *
78 73 74 0.0000 10 10.4000 12.0000 *
79 56 75 -0.0035 10 10.4000 12.0000 *
80 74 75 0.0000 10 10.4000 12.0000 *
81 83 77 0.0035 10 10.4000 12.0000 *
82 77 53 0.0035 10 10.4000 12.0000 *
83 78 52 0.0035 10 10.4000 12.0000 *
84 97 78 0.0035 10 10.4000 12.0000 *
85 97 61 -0.0035 10 10.4000 12.0000 *
90 3 6 250.0005 9 12.2500 12.0000 *
91 6 8 250.0005 9 12.2500 12.0000 *
92 88 93 0.0000 10 10.4000 12.0000 *
93 93 94 0.0000 10 10.4000 12.0000 *
94 8 18 250.0005 9 12.2500 12.0000 *
95 18 23 250.0005 10 10.4000 12.0000 *
96 23 39 250.0005 10 10.4000 12.0000 *
97 39 76 250.0005 10 10.4000 12.0000 *
98 94 95 0.0000 10 10.4000 12.0000 *
99 95 96 0.0000 10 10.4000 12.0000 *
100 96 71 0.0000 10 10.4000 12.0000 *
101 40 41 0.0000 10 10.4000 12.0000 *
102 80 54 0.0035 10 10.4000 12.0000 *
103 41 68 0.0000 10 10.4000 12.0000 *
104 68 69 0.0000 10 10.4000 12.0000 *
105 69 32 0.0000 10 10.4000 12.0000 *
106 76 40 0.0000 10 10.4000 12.0000 *
107 76 66 250.0005 10 5.1000 6.0000 *

A * indicates that this is a SET diameter

Page 25 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 11 OF 20
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Schedule Not Lined
10 -- HDPE Not Lined
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 12 OF 20
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (bar G ) (bar G ) (bar ) (bar )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
1 35 1 6.00 7.254 7.247 6.9423E-03 6.9423E-03
250.0 1.197
2 1 2 6.00 7.247 6.999 0.2481 3.3970E-03
250.0 0.8462
9 21 13 6.00 7.376 7.382 -6.4726E-03 6.4726E-03 -
121.1 -0.4099
10 13 14 6.00 7.382 7.394 -1.1868E-02 1.1868E-02 -
80.08 -0.2711
11 15 14 6.00 7.394 7.394 2.3842E-06 0.000
0.7490 2.5352E-03
12 27 28 6.00 7.330 7.358 -2.8082E-02 2.8082E-02 -
132.3 -0.4479
13 15 31 6.00 7.394 7.389 5.6224E-03 5.6224E-03
128.9 0.4363
14 14 12 6.00 7.394 7.390 3.9124E-03 3.9124E-03
41.02 0.1388
15 13 17 6.00 7.382 7.387 -4.2224E-03 4.2224E-03 -
41.02 -0.1388
16 48 12 6.00 7.387 7.390 -3.0575E-03 3.0575E-03 -
41.02 -0.1388
22 16 24 6.00 7.358 7.353 5.0349E-03 5.0349E-03
117.7 0.3983
23 24 25 6.00 7.353 7.342 1.0945E-02 1.0945E-02
117.7 0.3983
24 25 26 6.00 7.342 7.330 1.2350E-02 1.2350E-02
117.7 0.3983
25 26 27 6.00 7.330 7.330 -1.0490E-04 1.0490E-04 -
7.045 -2.3846E-02
26 21 28 6.00 7.376 7.358 1.7777E-02 1.7777E-02
121.1 0.4099
27 28 16 6.00 7.358 7.358 -1.4257E-04 1.4257E-04 -
11.22 -3.7978E-02
28 29 14 6.00 7.421 7.394 2.6817E-02 2.6817E-02
120.4 0.4074
29 66 30 12.00 7.427 7.427 8.5497E-04 8.5497E-04
129.6 0.1133
30 31 16 6.00 7.389 7.358 3.0355E-02 3.0355E-02
128.9 0.4363
31 30 15 6.00 7.427 7.394 3.2443E-02 3.2443E-02

Page 26 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

129.6 0.4389
32 66 29 6.00 7.427 7.421 6.4826E-03 6.4826E-03
120.4 0.4074
33 26 33 6.00 7.330 7.311 1.8835E-02 1.8835E-02
124.7 0.5972
34 33 34 6.00 7.311 7.283 2.7760E-02 2.7760E-02
141.2 0.6760
35 34 35 6.00 7.283 7.254 2.9518E-02 2.9518E-02
141.2 0.6760
36 33 36 6.00 7.311 7.312 -6.9475E-04 6.9475E-04 -
16.47 -7.8841E-02
37 27 36 6.00 7.330 7.312 1.8245E-02 1.8245E-02
125.3 0.5996
38 36 37 6.00 7.312 7.309 2.4323E-03 2.4323E-03
108.8 0.5207
39 35 38 6.00 7.254 7.291 -3.7067E-02 3.7067E-02 -
108.8 -0.5207
40 38 37 6.00 7.291 7.309 -1.8473E-02 1.8473E-02 -
108.8 -0.5207
50 17 50 6.00 7.387 7.387 -2.5272E-04 2.5272E-04 -
41.02 -0.1388
51 50 48 6.00 7.387 7.387 -4.2248E-04 4.2248E-04 -
41.02 -0.1388
55 87 88 12.00 7.431 7.431 0.000 0.000
0.000 0.000
56 53 80 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
57 54 55 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
58 55 75 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
59 56 57 12.00 7.431 7.529 -9.7895E-02 0.000
3.5107E-03 4.0414E-06
60 58 57 12.00 7.529 7.529 0.000 0.000 -
3.5107E-03 -4.0414E-06
61 59 58 12.00 7.431 7.529 -9.7895E-02 0.000 -
3.5107E-03 -4.0414E-06
62 60 59 12.00 7.431 7.431 0.000 0.000 -
3.5107E-03 -4.0414E-06
63 52 83 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
64 61 62 12.00 7.431 7.529 -9.7895E-02 0.000 -
3.5107E-03 -4.0414E-06

Page 27 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 13 OF 20
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (bar G ) (bar G ) (bar ) (bar )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
65 62 63 12.00 7.529 7.529 0.000 0.000 -
3.5107E-03 -4.0414E-06
66 63 64 12.00 7.529 7.431 9.7895E-02 0.000 -
3.5107E-03 -4.0414E-06
67 64 65 12.00 7.431 7.431 0.000 0.000 -
3.5107E-03 -4.0414E-06
73 65 70 12.00 7.431 7.431 0.000 0.000 -
3.5107E-03 -4.0414E-06
74 70 60 12.00 7.431 7.431 0.000 0.000 -
3.5107E-03 -4.0414E-06
75 32 87 12.00 7.431 7.431 0.000 0.000
0.000 0.000
76 71 72 12.00 7.431 7.529 -9.7895E-02 0.000
0.000 0.000
77 72 73 12.00 7.529 7.529 0.000 0.000
0.000 0.000
78 73 74 12.00 7.529 7.431 9.7895E-02 0.000
0.000 0.000
79 56 75 12.00 7.431 7.431 0.000 0.000 -
3.5107E-03 -4.0414E-06
80 74 75 12.00 7.431 7.431 0.000 0.000
0.000 0.000
81 83 77 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
82 77 53 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
83 78 52 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
84 97 78 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06
85 97 61 12.00 7.431 7.431 0.000 0.000 -
3.5107E-03 -4.0414E-06
90 3 6 12.00 7.287 7.286 7.6723E-04 7.6723E-04
250.0 0.2074
91 6 8 12.00 7.286 7.188 9.8100E-02 2.0690E-04
250.0 0.2074
92 88 93 12.00 7.431 7.431 0.000 0.000
0.000 0.000
93 93 94 12.00 7.431 7.431 0.000 0.000
0.000 0.000
94 8 18 12.00 7.188 7.188 2.4509E-04 2.4509E-04
250.0 0.2074
95 18 23 12.00 7.188 7.188 1.0490E-04 1.0490E-04
250.0 0.2878
96 23 39 12.00 7.188 7.431 -0.2434 1.3708E-03
250.0 0.2878
97 39 76 12.00 7.431 7.431 1.6499E-04 1.6499E-04
250.0 0.2878
98 94 95 12.00 7.431 7.431 0.000 0.000
0.000 0.000
99 95 96 12.00 7.431 7.431 0.000 0.000
0.000 0.000
100 96 71 12.00 7.431 7.431 0.000 0.000
0.000 0.000
101 40 41 12.00 7.431 7.431 0.000 0.000
0.000 0.000
102 80 54 12.00 7.431 7.431 0.000 0.000
3.5107E-03 4.0414E-06

Page 28 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

103 41 68 12.00 7.431 7.529 -9.7895E-02 0.000


0.000 0.000
104 68 69 12.00 7.529 7.529 0.000 0.000
0.000 0.000
105 69 32 12.00 7.529 7.431 9.7895E-02 0.000
0.000 0.000
106 76 40 12.00 7.431 7.431 0.000 0.000
0.000 0.000
107 76 66 6.00 7.431 7.427 3.7699E-03 3.7699E-03
250.0 1.197
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 14 OF 20
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (bar G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
FH-19/0 2 0.69987E+01 250.0000 250.0000 * 0.00

Note: A * after a value indicates that this is a specification


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 15 OF 20
---------------------------------------------------------------------------------------------------
--------------------

FLOW AT INLETS
--------------

Inlet Node Pressure Flowrate Equivalent K-factor


(bar G ) (US.g/min) (US.g/min , bar G )
------------------------------------------------------------
3 7.287 250.0 92.610

Note: A * after a value indicates that this is a specification

Page 29 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 16 OF 20
---------------------------------------------------------------------------------------------------
--------------------

Materials Take-off
------------------
Pipe lengths
------------

ANSI B36.10 Sch.40 HDPE ANSI B36.10 Schedule

Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length
Nom. Size Tot. Length
(inches ) (metres ) (inches ) (metres ) (inches ) (metres ) (inches ) (metres )
(inches ) (metres )
-------------------------------------------------------------------------------------------------
6.000 1529. 6.000 622.3 12.000 5.000
12.000 109.0 12.000 773.9
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 17 OF 20
-------------------------------------------------------------------------------------------------

Materials Take-off
------------------
Nozzles
-------
Type K-Factor Number
---- -------- ------
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 18 OF 20
-------------------------------------------------------------------------------------------------

Materials Take Off


------------------
Fittings
--------

Fitting
Nominal
Size Fitting Type
(inches ) 1 2 3 4 5 6 7 8 9
-------------------------------------------------------------------------

6.000 4 13 0 76 24 0 0 0 1
12.000 18 4 0 29 9 0 1 0 1

Fitting Types are :


1 -- 45 Deg Elbow 4 -- Tee or Cross 7 -- Non-Return Valve
2 -- 90 Deg Standard Elbow 5 -- Gate Valve 8 -- Ball Valve
3 -- 90 Deg Long Radius Elbow 6 -- Swing Check Valve 9 -- Butterfly Valve

All fittings are as specified by user - no additional fittings have been generated automatically.

The supply demand graph is not available for the network without pump

Page 30 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 19 OF 20
---------------------------------------------------------------------------------------------------
--------------------

IMPORTANT NOTICE
----------------

Your attention is drawn to the need to maintain adequate standards. SUNRISE SYSTEMS Ltd
has itself taken steps to ensure that this program produces valid results when properly
used. Users are reminded of their responsibilities in the application of program results
and, in particular, you should ensure that pertinent output documents are examined and
approved by qualified staff prior to use.

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 20 OF 20
---------------------------------------------------------------------------------------------------
--------------------

COMMENTS
--------

Analysis Converged in 6 Iterations


1

====================================================================================================
====================

Firefighting Hydraulic Calculation for WASCO EW PLANT


Firefighting Pump head Calculations at FH-19
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
===================

Page 31 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

Page 32 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

Annex B: Area-34 Case

Page 33 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

55

====================================================================================================
====================

PIPENET SPRAY/SPRINKLER MODULE

====================================================================================================
====================

VERSION 1.8

====================================================================================================
====================

Results for : Firefighting Hydraulic Calculation for WASCO EW PLANT


Area-34 Case
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
====================

Page 34 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

13:59 on 15-Feb-2020
1

LIST OF CONTENTS
================

Page
----

Control Information......................................... 1

Fluid System................................................ 1

Design Information.......................................... 2

Pipe Configuration.......................................... 4

Designed Diameters & Flowrates.............................. 8

Flow in Pipes............................................... 11

Flow at Inlets.............................................. 13

Flow at Outlets............................................. 14

Materials Take Off.......................................... 15

Important Notice............................................ 17

Comments.................................................... 18

Page 35 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 1 OF 18
---------------------------------------------------------------------------------------------------
--------------------

CONTROL INFORMATION
-------------------
Convergence accuracy = 1.00E-03
Maximum no. of iterations = 50
Elevation Check Tolerance = 0.50 metres
Warnings Control Option = 0
****** Diagnostic level = 2

FLUID SYSTEM
------------

Fluid Class = 1 (Liquid )


Density = 998.2 kg/cu.m
Viscosity = 2.419 lb/ft hr
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 2 OF 18
---------------------------------------------------------------------------------------------------
--------------------

DESIGN INFORMATION
------------------

Waterspray System

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Sch.20 Not Lined
10 -- HDPE Not Lined

Design to NFPA 2013 Rules


Using the Hazen-Williams Equation

Velocity Pressure Model: NFPA formula

Pressure loss at entrance: Ignore

Pressure loss at exit: Ignore

Page 36 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 3 OF 18
---------------------------------------------------------------------------------------------------
--------------------

AVAILABLE PIPE SIZES AND MAXIMUM VELOCITIES USED FOR PIPE SIZING
----------------------------------------------------------------

ANSI B36.10 Sch.40 ANSI B36.10 Sch.20 HDPE


Not lined Not lined Not lined

Nom.Bore Act.Diam Max.Vel. Nom.Bore Act.Diam Max.Vel. Nom.Bore


Act.Diam Max.Vel.
(inches ) (inches ) (m/sec ) (inches ) (inches ) (m/sec ) (inches )
(inches ) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------

0.6250 0.6220 6.0000 0.6250 Not acceptable 0.6250 Not


acceptable
0.7500 0.8240 6.0000 0.7500 Not acceptable 0.7500 Not
acceptable
1.0000 1.0490 6.0000 1.0000 Not acceptable 1.0000 Not
acceptable
1.2500 1.3800 6.0000 1.2500 Not acceptable 1.2500 Not
acceptable
1.5000 1.6100 6.0000 1.5000 Not acceptable 1.5000 Not
acceptable
2.0000 2.0670 6.0000 2.0000 Not acceptable 2.0000 Not
acceptable
2.5000 2.4690 6.0000 2.5000 Not acceptable 2.5000 Not
acceptable
3.0000 3.0680 6.0000 3.0000 Not acceptable 3.0000 Not
acceptable
3.5000 3.5480 6.0000 3.5000 Not acceptable 3.5000 Not
acceptable
4.0000 4.0260 6.0000 4.0000 Not acceptable 4.0000 Not
acceptable
5.0000 5.0470 6.0000 5.0000 Not acceptable 5.0000 Not
acceptable
6.0000 6.0650 6.0000 6.0000 Not acceptable 6.0000
5.1000 6.0000
8.0000 7.9810 6.0000 8.0000 8.1250 3.0000 8.0000
6.4000 6.0000
10.0000 10.0200 6.0000 10.0000 10.2500 3.0000 10.0000
8.0000 6.0000
12.0000 11.9380 6.0000 12.0000 12.2500 3.0000 12.0000
10.4000 6.0000
14.0000 13.1240 6.0000 14.0000 13.3760 3.0000 13.9999 Not
acceptable
16.0000 15.0000 6.0000 16.0000 15.3760 3.0000 16.0000 Not
acceptable
18.0000 16.8760 6.0000 18.0000 17.3760 3.0000 18.0000 Not
acceptable
20.0000 18.8120 6.0000 20.0000 19.2500 3.0000 20.0000 Not
acceptable
24.0000 22.6240 6.0000 24.0000 23.2500 3.0000 23.9999 Not
acceptable

Page 37 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 4 OF 18
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
2 9 13 12.00 0.5000 0.000 120.0
0.000
3 11 2 12.00 1.0000 1.0000 120.0
0.000
4 2 9 12.00 3.000 0.000 120.0
0.000
5 13 3 12.00 43.70 -2.500 150.0
0.000
6 3 18 12.00 5.600 0.000 150.0
0.000
7 10 11 12.00 1.0000 0.000 120.0
0.000
8 4 7 12.00 4.000 0.000 150.0
0.000
10 21 14 6.000 122.0 0.000 120.0
37.19
11 15 14 6.000 122.5 0.000 120.0
37.49
12 27 28 6.000 111.3 0.000 120.0
37.49
13 15 31 6.000 27.00 0.000 120.0
4.267
14 14 12 6.000 121.0 0.000 120.0
60.05
15 21 17 6.000 101.3 0.000 120.0
94.18
16 48 12 6.000 119.0 0.000 120.0
22.56
17 7 44 12.00 3.000 -1.0000 150.0
0.000
18 18 4 12.00 39.00 0.000 150.0
0.000
19 18 41 6.000 4.000 0.000 150.0
0.000
21 77 6 6.000 10.000 0.000 150.0
2.773
22 16 24 6.000 24.00 0.000 120.0
9.144
23 24 25 6.000 45.20 0.000 120.0
26.82
24 25 26 6.000 63.00 0.000 120.0
18.29
25 26 27 6.000 100.00 0.000 120.0
27.74
26 21 28 6.000 95.00 0.000 120.0
0.000
27 28 16 6.000 54.80 0.000 120.0
18.29
28 29 14 6.000 141.0 0.000 120.0
28.35
29 41 30 12.00 109.0 0.000 120.0
18.29
30 31 16 6.000 113.0 0.000 120.0
55.78
31 30 15 6.000 141.0 0.000 120.0
37.49
32 41 29 6.000 13.50 0.000 120.0
27.43
33 26 33 6.000 63.00 0.000 150.0

Page 38 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

9.309
34 33 34 6.000 66.30 0.000 150.0
18.42
35 34 35 6.000 78.00 0.000 150.0
12.08
36 33 36 6.000 100.00 0.000 150.0
13.07
37 27 36 6.000 63.00 0.000 150.0
6.536
38 36 37 6.000 5.500 0.000 150.0
6.536
39 35 38 6.000 159.0 0.000 150.0
24.36
40 38 37 6.000 79.50 0.000 150.0
11.88
41 6 FM-21/0 6.000 7.500 7.500 120.0
3.048
42 83 FH-42/0 6.000 2.500 2.500 120.0
3.048
43 52 23 6.000 10.000 0.000 150.0
2.773
44 23 FM-22/0 6.000 7.500 7.500 120.0
3.048
45 85 FM-32/0 6.000 7.500 7.500 120.0
3.048
50 17 50 6.000 2.500 0.000 120.0
9.144
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 5 OF 18
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
51 50 48 6.000 9.500 0.000 120.0
10.06
55 87 88 12.00 9.000 0.000 150.0
14.12
56 53 80 12.00 21.50 0.000 150.0
14.12
57 54 55 12.00 78.90 0.000 150.0
15.53
58 55 75 12.00 56.20 0.000 150.0
43.76
59 56 57 12.00 1.0000 -1.0000 150.0
6.117
60 58 57 12.00 1.0000 0.000 150.0
0.000
61 59 58 12.00 1.0000 -1.0000 150.0
6.117
62 60 59 12.00 6.500 0.000 150.0
14.12
63 52 83 12.00 11.20 0.000 150.0
19.06
64 61 62 12.00 1.0000 -1.0000 150.0
6.117
65 62 63 12.00 1.0000 0.000 150.0
0.000
66 63 64 12.00 1.0000 1.0000 150.0
6.117
67 64 65 12.00 6.500 0.000 150.0
15.53
68 85 54 6.000 11.50 0.000 150.0
1.981
70 44 46 12.00 2.000 0.000 150.0
0.000

Page 39 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

71 46 32 12.00 3.000 1.0000 150.0


0.000
73 65 70 12.00 40.30 0.000 150.0
14.12
74 70 60 12.00 60.30 0.000 150.0
15.53
75 32 87 12.00 34.30 0.000 150.0
56.47
76 71 72 12.00 1.0000 -1.0000 150.0
6.117
77 72 73 12.00 1.0000 0.000 150.0
0.000
78 73 74 12.00 1.0000 1.0000 150.0
6.117
79 56 75 12.00 52.50 0.000 150.0
31.06
80 74 75 12.00 6.700 0.000 150.0
0.000
81 83 77 12.00 11.30 0.000 150.0
0.000
82 77 53 12.00 21.50 0.000 150.0
29.65
83 78 52 12.00 12.60 0.000 150.0
14.12
84 97 78 12.00 25.50 0.000 150.0
0.000
85 97 61 12.00 33.00 0.000 150.0
14.12
92 88 93 12.00 9.000 0.000 150.0
14.12
93 93 94 12.00 10.000 0.000 150.0
14.12
98 94 95 12.00 9.000 0.000 150.0
14.12
99 95 96 12.00 24.40 0.000 150.0
42.35
100 96 71 12.00 45.00 0.000 150.0
0.000
102 80 54 12.00 78.90 0.000 150.0
15.53
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 6 OF 18
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
10 4 x 2 4.267 2 x 4 9.144 2 x 5 0.9144
11 4 x 4 9.144 1 x 5 0.9144
12 4 x 4 9.144 1 x 5 0.9144
13 1 x 2 4.267
14 2 x 1 2.134 6 x 4 9.144 1 x 5 0.9144
15 10 x 4 9.144 3 x 5 0.9144
16 2 x 1 2.134 2 x 4 9.144
21 1 x 2 2.773
22 1 x 4 9.144
23 2 x 2 4.267 2 x 4 9.144
24 2 x 4 9.144
25 2 x 2 4.267 2 x 4 9.144 1 x 5 0.9144
27 2 x 4 9.144
28 3 x 4 9.144 1 x 5 0.9144
29 1 x 4 18.29
30 6 x 4 9.144 1 x 5 0.9144
31 4 x 4 9.144 1 x 5 0.9144
32 3 x 4 9.144
33 1 x 2 2.773 1 x 4 5.942 1 x 5 0.5942
34 3 x 4 5.942 1 x 5 0.5942
35 2 x 2 2.773 1 x 4 5.942 1 x 5 0.5942

Page 40 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

36 2 x 4 5.942 2 x 5 0.5942
37 1 x 4 5.942 1 x 5 0.5942
38 1 x 4 5.942 1 x 5 0.5942
39 4 x 4 5.942 1 x 5 0.5942
40 2 x 4 5.942
41 1 x 9 3.048
42 1 x 9 3.048
43 1 x 2 2.773
44 1 x 9 3.048
45 1 x 9 3.048
50 1 x 4 9.144
51 1 x 4 9.144 1 x 5 0.9144
55 1 x 4 14.12
56 1 x 4 14.12
57 1 x 4 14.12 1 x 5 1.412
58 3 x 4 14.12 1 x 5 1.412
59 2 x 1 3.059
61 2 x 1 3.059
62 1 x 4 14.12
63 1 x 4 14.12 1 x 9 4.941
64 2 x 1 3.059
66 2 x 1 3.059
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 7 OF 18
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
67 1 x 4 14.12 1 x 5 1.412
68 1 x 1 1.386 1 x 5 0.5942
73 1 x 4 14.12
74 1 x 4 14.12 1 x 5 1.412
75 4 x 4 14.12
76 2 x 1 3.059
78 2 x 1 3.059
79 2 x 4 14.12 2 x 5 1.412
82 2 x 4 14.12 1 x 5 1.412
83 1 x 4 14.12
85 1 x 4 14.12
92 1 x 4 14.12
93 1 x 4 14.12
98 1 x 4 14.12
99 3 x 4 14.12
102 1 x 4 14.12 1 x 5 1.412

Fitting types are :


1 -- 45 Deg Elbow
2 -- 90 Deg Standard Elbow
3 -- 90 Deg Long Radius Elbow
4 -- Tee or Cross (Flow Turned Thro 90 Deg)
5 -- Gate Valve
6 -- Swing Check Valve
7 -- Non-Return Valve
8 -- Ball Valve
9 -- Butterfly Valve

Page 41 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 8 OF 18
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
2 9 13 2500.0059 10 10.4000 12.0000 *
3 11 2 2500.0056 9 12.2500 12.0000 *
4 2 9 2500.0056 9 12.2500 12.0000 *
5 13 3 2500.0059 10 10.4000 12.0000 *
6 3 18 2500.0059 10 10.4000 12.0000 *
7 10 11 2500.0056 9 12.2500 12.0000 *
8 4 7 2500.0059 10 10.4000 12.0000 *
10 21 14 0.0471 3 6.0650 6.0000 *
11 15 14 -0.0276 3 6.0650 6.0000 *
12 27 28 0.2572 3 6.0650 6.0000 *
13 15 31 0.0713 3 6.0650 6.0000 *
14 14 12 -0.0241 3 6.0650 6.0000 *
15 21 17 0.0241 3 6.0650 6.0000 *
16 48 12 0.0241 3 6.0650 6.0000 *
17 7 44 2500.0059 10 10.4000 12.0000 *
18 18 4 2500.0059 10 10.4000 12.0000 *
19 18 41 0.0000 10 5.1000 6.0000 *
21 77 6 750.0017 10 5.1000 6.0000 *
22 16 24 0.2572 3 6.0650 6.0000 *
23 24 25 0.2572 3 6.0650 6.0000 *
24 25 26 0.2572 3 6.0650 6.0000 *
25 26 27 0.1506 3 6.0650 6.0000 *
26 21 28 -0.0713 3 6.0650 6.0000 *
27 28 16 0.1859 3 6.0650 6.0000 *
28 29 14 -0.0437 3 6.0650 6.0000 *
29 41 30 0.0437 3 11.9380 12.0000 *
30 31 16 0.0713 3 6.0650 6.0000 *
31 30 15 0.0437 3 6.0650 6.0000 *
32 41 29 -0.0437 3 6.0650 6.0000 *
33 26 33 0.1066 10 5.1000 6.0000 *
34 33 34 0.0699 10 5.1000 6.0000 *
35 34 35 0.0699 10 5.1000 6.0000 *
36 33 36 0.0367 10 5.1000 6.0000 *
37 27 36 -0.1066 10 5.1000 6.0000 *
38 36 37 -0.0699 10 5.1000 6.0000 *
39 35 38 0.0699 10 5.1000 6.0000 *
40 38 37 0.0699 10 5.1000 6.0000 *
41 6 FM-21/0 750.0017 3 6.0650 6.0000 *
42 83 FH-42/0 250.0006 3 6.0650 6.0000 *

Page 42 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 9 OF 18
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
43 52 23 750.0017 10 5.1000 6.0000 *
44 23 FM-22/0 750.0017 3 6.0650 6.0000 *
45 85 FM-32/0 750.0017 3 6.0650 6.0000 *
50 17 50 0.0241 3 6.0650 6.0000 *
51 50 48 0.0241 3 6.0650 6.0000 *
55 87 88 2500.0059 10 10.4000 12.0000 *
56 53 80 -663.5541 10 10.4000 12.0000 *
57 54 55 -1413.5558 10 10.4000 12.0000 *
58 55 75 -1413.5558 10 10.4000 12.0000 *
59 56 57 1086.4500 10 10.4000 12.0000 *
60 58 57 -1086.4500 10 10.4000 12.0000 *
61 59 58 -1086.4500 10 10.4000 12.0000 *
62 60 59 -1086.4500 10 10.4000 12.0000 *
63 52 83 336.4482 10 10.4000 12.0000 *
64 61 62 -1086.4500 10 10.4000 12.0000 *
65 62 63 -1086.4500 10 10.4000 12.0000 *
66 63 64 -1086.4500 10 10.4000 12.0000 *
67 64 65 -1086.4500 10 10.4000 12.0000 *
68 85 54 -750.0017 10 5.1000 6.0000 *
70 44 46 2500.0059 10 10.4000 12.0000 *
71 46 32 2500.0059 10 10.4000 12.0000 *
73 65 70 -1086.4500 10 10.4000 12.0000 *
74 70 60 -1086.4500 10 10.4000 12.0000 *
75 32 87 2500.0059 10 10.4000 12.0000 *
76 71 72 2500.0059 10 10.4000 12.0000 *
77 72 73 2500.0059 10 10.4000 12.0000 *
78 73 74 2500.0059 10 10.4000 12.0000 *
79 56 75 -1086.4500 10 10.4000 12.0000 *
80 74 75 2500.0059 10 10.4000 12.0000 *
81 83 77 86.4476 10 10.4000 12.0000 *
82 77 53 -663.5541 10 10.4000 12.0000 *
83 78 52 1086.4500 10 10.4000 12.0000 *
84 97 78 1086.4500 10 10.4000 12.0000 *
85 97 61 -1086.4500 10 10.4000 12.0000 *
92 88 93 2500.0059 10 10.4000 12.0000 *
93 93 94 2500.0059 10 10.4000 12.0000 *
98 94 95 2500.0059 10 10.4000 12.0000 *
99 95 96 2500.0059 10 10.4000 12.0000 *
100 96 71 2500.0059 10 10.4000 12.0000 *

Page 43 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 10 OF 18
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
102 80 54 -663.5541 10 10.4000 12.0000 *

A * indicates that this is a SET diameter

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Sch.20 Not Lined
10 -- HDPE Not Lined
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 11 OF 18
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
2 9 13 12.00 143.5 143.5 2.2736E-02 2.2736E-02
2500. 2.878
3 11 2 12.00 145.0 143.5 1.440 2.0501E-02
2500. 2.074
4 2 9 12.00 143.5 143.5 6.1508E-02 6.1508E-02
2500. 2.074
5 13 3 12.00 143.5 145.7 -2.234 1.316
2500. 2.878
6 3 18 12.00 145.7 145.5 0.1686 0.1686
2500. 2.878
7 10 11 12.00 145.0 145.0 2.0493E-02 2.0493E-02
2500. 2.074
8 4 7 12.00 144.3 144.2 0.1204 0.1204
2500. 2.878
10 21 14 6.00 145.5 145.5 0.000 0.000
4.7126E-02 1.5952E-04
11 15 14 6.00 145.5 145.5 0.000 0.000 -
2.7597E-02 -9.3413E-05
12 27 28 6.00 145.5 145.5 0.000 0.000
0.2572 8.7054E-04
13 15 31 6.00 145.5 145.5 0.000 0.000
7.1256E-02 2.4120E-04
14 14 12 6.00 145.5 145.5 0.000 0.000 -
2.4130E-02 -8.1678E-05
15 21 17 6.00 145.5 145.5 0.000 0.000
2.4130E-02 8.1678E-05
16 48 12 6.00 145.5 145.5 0.000 0.000
2.4130E-02 8.1678E-05
17 7 44 12.00 144.2 145.6 -1.329 9.0323E-02
2500. 2.878
18 18 4 12.00 145.5 144.3 1.174 1.174
2500. 2.878

Page 44 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

19 18 41 6.00 145.5 145.5 0.000 0.000


1.5101E-09 7.2288E-12
21 77 6 6.00 131.9 130.6 1.333 1.333
750.0 3.590
22 16 24 6.00 145.5 145.5 0.000 0.000
0.2572 8.7054E-04
23 24 25 6.00 145.5 145.5 0.000 0.000
0.2572 8.7054E-04
24 25 26 6.00 145.5 145.5 0.000 0.000
0.2572 8.7054E-04
25 26 27 6.00 145.5 145.5 0.000 0.000
0.1506 5.0968E-04
26 21 28 6.00 145.5 145.5 0.000 0.000 -
7.1256E-02 -2.4120E-04
27 28 16 6.00 145.5 145.5 0.000 0.000
0.1859 6.2934E-04
28 29 14 6.00 145.5 145.5 0.000 0.000 -
4.3659E-02 -1.4778E-04
29 41 30 12.00 145.5 145.5 0.000 0.000
4.3659E-02 3.8143E-05
30 31 16 6.00 145.5 145.5 0.000 0.000
7.1256E-02 2.4120E-04
31 30 15 6.00 145.5 145.5 0.000 0.000
4.3659E-02 1.4778E-04
32 41 29 6.00 145.5 145.5 0.000 0.000 -
4.3659E-02 -1.4778E-04
33 26 33 6.00 145.5 145.5 0.000 0.000
0.1066 5.1033E-04
34 33 34 6.00 145.5 145.5 0.000 0.000
6.9904E-02 3.3463E-04
35 34 35 6.00 145.5 145.5 0.000 0.000
6.9904E-02 3.3463E-04
36 33 36 6.00 145.5 145.5 0.000 0.000
3.6704E-02 1.7570E-04
37 27 36 6.00 145.5 145.5 0.000 0.000 -
0.1066 -5.1033E-04
38 36 37 6.00 145.5 145.5 0.000 0.000 -
6.9904E-02 -3.3463E-04
39 35 38 6.00 145.5 145.5 0.000 0.000
6.9904E-02 3.3463E-04
40 38 37 6.00 145.5 145.5 0.000 0.000
6.9904E-02 3.3463E-04
41 6 FM-21/0 6.00 130.6 119.2 11.36 0.7151
750.0 2.539
42 83 FH-42/0 6.00 131.9 128.3 3.599 4.9307E-02
250.0 0.8462
43 52 23 6.00 131.9 130.6 1.333 1.333
750.0 3.590
44 23 FM-22/0 6.00 130.6 119.2 11.36 0.7151
750.0 2.539

Page 45 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 12 OF 18
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
45 85 FM-32/0 6.00 131.0 119.6 11.36 0.7151
750.0 2.539
50 17 50 6.00 145.5 145.5 0.000 0.000
2.4130E-02 8.1678E-05
51 50 48 6.00 145.5 145.5 0.000 0.000
2.4130E-02 8.1678E-05
55 87 88 12.00 141.3 140.6 0.6960 0.6960
2500. 2.878
56 53 80 12.00 132.0 132.1 -9.2316E-02 9.2316E-02 -
663.6 -0.7639
57 54 55 12.00 132.4 133.4 -0.9908 0.9908 -
1414. -1.627
58 55 75 12.00 133.4 134.4 -1.049 1.049 -
1414. -1.627
59 56 57 12.00 133.9 135.2 -1.374 4.5813E-02
1086. 1.251
60 58 57 12.00 135.2 135.2 -6.4545E-03 6.4545E-03 -
1086. -1.251
61 59 58 12.00 133.8 135.2 -1.466 4.5816E-02 -
1086. -1.251
62 60 59 12.00 133.6 133.8 -0.1327 0.1327 -
1086. -1.251
63 52 83 12.00 131.9 131.9 2.2232E-02 2.2232E-02
336.4 0.3873
64 61 62 12.00 132.6 134.0 -1.466 4.5831E-02 -
1086. -1.251
65 62 63 12.00 134.0 134.0 -6.4545E-03 6.4545E-03 -
1086. -1.251
66 63 64 12.00 134.0 132.7 1.374 4.5798E-02 -
1086. -1.251
67 64 65 12.00 132.7 132.8 -0.1418 0.1418 -
1086. -1.251
68 85 54 6.00 131.0 132.4 -1.407 1.407 -
750.0 -3.590
70 44 46 12.00 145.6 145.5 6.0196E-02 6.0196E-02
2500. 2.878
71 46 32 12.00 145.5 144.0 1.510 9.0356E-02
2500. 2.878
73 65 70 12.00 132.8 133.2 -0.3503 0.3503 -
1086. -1.251
74 70 60 12.00 133.2 133.6 -0.4881 0.4881 -
1086. -1.251
75 32 87 12.00 144.0 141.3 2.733 2.733
2500. 2.878
76 71 72 12.00 135.1 136.3 -1.206 0.2143
2500. 2.878
77 72 73 12.00 136.3 136.2 3.0090E-02 3.0090E-02
2500. 2.878
78 73 74 12.00 136.2 134.6 1.634 0.2143
2500. 2.878
79 56 75 12.00 133.9 134.4 -0.5379 0.5379 -
1086. -1.251
80 74 75 12.00 134.6 134.4 0.2017 0.2017
2500. 2.878
81 83 77 12.00 131.9 131.9 6.5613E-04 6.5613E-04
86.45 9.9515E-02
82 77 53 12.00 131.9 132.0 -0.1325 0.1325 -
663.6 -0.7639

Page 46 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

83 78 52 12.00 132.1 131.9 0.1720 0.1720


1086. 1.251
84 97 78 12.00 132.3 132.1 0.1641 0.1641
1086. 1.251
85 97 61 12.00 132.3 132.6 -0.3033 0.3033 -
1086. -1.251
92 88 93 12.00 140.6 139.9 0.6960 0.6960
2500. 2.878
93 93 94 12.00 139.9 139.1 0.7261 0.7261
2500. 2.878
98 94 95 12.00 139.1 138.4 0.6960 0.6960
2500. 2.878
99 95 96 12.00 138.4 136.4 2.010 2.010
2500. 2.878
100 96 71 12.00 136.4 135.1 1.355 1.355
2500. 2.878
102 80 54 12.00 132.1 132.4 -0.2448 0.2448 -
663.6 -0.7639
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 13 OF 18
---------------------------------------------------------------------------------------------------
--------------------

FLOW AT INLETS
--------------

Inlet Node Pressure Flowrate Equivalent K-factor


(psi G ) (US.g/min) (US.g/min , psi G )
------------------------------------------------------------
10 145.0 * 2500. 207.61

Note: A * after a value indicates that this is a specification


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 14 OF 18
---------------------------------------------------------------------------------------------------
--------------------

FLOW AT OUTLETS
---------------

Outlet Node Pressure Flowrate Equivalent K-factor


(psi G ) (US.g/min) (US.g/min , psi G )
------------------------------------------------------------
FM-21/0 119.2 750.0 * 68.693
FH-42/0 128.3 250.0 * 22.071
FM-22/0 119.2 750.0 * 68.686
FM-32/0 119.6 750.0 * 68.579

Note: A * after a value indicates that this is a specification

Page 47 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 15 OF 18
---------------------------------------------------------------------------------------------------
--------------------

Materials Take-off
------------------
Pipe lengths
------------

ANSI B36.10 Sch.40 HDPE ANSI B36.10 Sch.20

Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length
Nom. Size Tot. Length
(inches ) (metres ) (inches ) (metres ) (inches ) (metres ) (inches ) (metres )
(inches ) (metres )
---------------------------------------------------------------------------------------------------
-------------------
6.000 1552. 6.000 649.8 12.000 5.000
12.000 109.0 12.000 773.9
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 16 OF 18
---------------------------------------------------------------------------------------------------
--------------------

Materials Take Off


------------------
Fittings
--------

Fitting
Nominal
Size Fitting Type
(inches ) 1 2 3 4 5 6 7 8 9
-------------------------------------------------------------------------

6.000 5 14 0 70 22 0 0 0 4
12.000 12 0 0 29 8 0 0 0 1

Fitting Types are :


1 -- 45 Deg Elbow 4 -- Tee or Cross 7 -- Non-Return Valve
2 -- 90 Deg Standard Elbow 5 -- Gate Valve 8 -- Ball Valve
3 -- 90 Deg Long Radius Elbow 6 -- Swing Check Valve 9 -- Butterfly Valve

All fittings are as specified by user - no additional fittings have been generated automatically.

The supply demand graph is not available for the network without pump
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 17 OF 18
---------------------------------------------------------------------------------------------------
--------------------

IMPORTANT NOTICE
----------------

Your attention is drawn to the need to maintain adequate standards. SUNRISE SYSTEMS Ltd
has itself taken steps to ensure that this program produces valid results when properly
used. Users are reminded of their responsibilities in the application of program results
and, in particular, you should ensure that pertinent output documents are examined and
approved by qualified staff prior to use.

Page 48 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 18 OF 18
---------------------------------------------------------------------------------------------------
--------------------

COMMENTS
--------

Analysis Converged in 4 Iterations


1

====================================================================================================
====================

Firefighting Hydraulic Calculation for WASCO EW PLANT


Area-34 Case
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
====================

Page 49 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

Annex C: Condensate tanks Case

Page 50 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

55

====================================================================================================
====================

PIPENET SPRAY/SPRINKLER MODULE

====================================================================================================
====================

VERSION 1.8

====================================================================================================
====================

Results for : Firefighting Hydraulic Calculation for WASCO EW PLANT


Condensate tanks Case - Scenario 1
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
====================

Page 51 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

14:12 on 15-Feb-2020
1

LIST OF CONTENTS
================

Page
----

Control Information......................................... 1

Fluid System................................................ 1

Design Information.......................................... 2

Pipe Configuration.......................................... 4

Nozzle Configuration........................................ 14

Designed Diameters & Flowrates.............................. 17

Flow in Pipes............................................... 23

Flow through Nozzles........................................ 29

G.P.L.C. Results............................................ 32

Flow at Inlets.............................................. 33

Materials Take Off.......................................... 34

Important Notice............................................ 37

Comments.................................................... 38

Page 52 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 1 OF 38
---------------------------------------------------------------------------------------------------
--------------------

CONTROL INFORMATION
-------------------
Convergence accuracy = 1.00E-03
Maximum no. of iterations = 50
Elevation Check Tolerance = 0.50 metres
Warnings Control Option = 0
****** Diagnostic level = 2

FLUID SYSTEM
------------

Fluid Class = 1 (Liquid )


Density = 998.2 kg/cu.m
Viscosity = 2.419 lb/ft hr
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 2 OF 38
---------------------------------------------------------------------------------------------------
--------------------

DESIGN INFORMATION
------------------

Waterspray System

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Sch.20 Not Lined
10 -- HDPE Not Lined

Design to NFPA 2013 Rules


Using the Hazen-Williams Equation

Velocity Pressure Model: NFPA formula

Pressure loss at entrance: Ignore

Pressure loss at exit: Ignore

Page 53 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 3 OF 38
---------------------------------------------------------------------------------------------------
--------------------

AVAILABLE PIPE SIZES AND MAXIMUM VELOCITIES USED FOR PIPE SIZING
----------------------------------------------------------------

ANSI B36.10 Sch.40 ANSI B36.10 Sch.20 HDPE


Not lined Not lined Not lined

Nom.Bore Act.Diam Max.Vel. Nom.Bore Act.Diam Max.Vel. Nom.Bore


Act.Diam Max.Vel.
(inches ) (inches ) (m/sec ) (inches ) (inches ) (m/sec ) (inches )
(inches ) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------

0.6250 0.6220 6.0000 0.6250 Not acceptable 0.6250 Not


acceptable
0.7500 0.8240 6.0000 0.7500 Not acceptable 0.7500 Not
acceptable
1.0000 1.0490 6.0000 1.0000 Not acceptable 1.0000 Not
acceptable
1.2500 1.3800 6.0000 1.2500 Not acceptable 1.2500 Not
acceptable
1.5000 1.6100 6.0000 1.5000 Not acceptable 1.5000 Not
acceptable
2.0000 2.0670 6.0000 2.0000 Not acceptable 2.0000 Not
acceptable
2.5000 2.4690 6.0000 2.5000 Not acceptable 2.5000 Not
acceptable
3.0000 3.0680 6.0000 3.0000 Not acceptable 3.0000 Not
acceptable
3.5000 3.5480 6.0000 3.5000 Not acceptable 3.5000 Not
acceptable
4.0000 4.0260 6.0000 4.0000 Not acceptable 4.0000 Not
acceptable
5.0000 5.0470 6.0000 5.0000 Not acceptable 5.0000 Not
acceptable
6.0000 6.0650 6.0000 6.0000 Not acceptable 6.0000
5.1000 6.0000
8.0000 7.9810 6.0000 8.0000 8.1250 3.0000 8.0000
6.4000 6.0000
10.0000 10.0200 6.0000 10.0000 10.2500 3.0000 10.0000
8.0000 6.0000
12.0000 11.9380 6.0000 12.0000 12.2500 3.0000 12.0000
10.4000 6.0000
14.0000 13.1240 6.0000 14.0000 13.3760 3.0000 13.9999 Not
acceptable
16.0000 15.0000 6.0000 16.0000 15.3760 3.0000 16.0000 Not
acceptable
18.0000 16.8760 6.0000 18.0000 17.3760 3.0000 18.0000 Not
acceptable
20.0000 18.8120 6.0000 20.0000 19.2500 3.0000 20.0000 Not
acceptable
24.0000 22.6240 6.0000 24.0000 23.2500 3.0000 23.9999 Not
acceptable

Page 54 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 4 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
1 19 32 12.00 3.000 1.0000 150.0
0.000
2 7 4 12.00 0.5000 0.000 120.0
0.000
3 1 20 12.00 1.0000 1.0000 120.0
0.000
4 44 9 12.00 5.600 0.000 150.0
0.000
5 43 19 12.00 2.000 0.000 150.0
0.000
6 27 228 6.000 8.500 8.500 120.0
9.144
7 131 41 4.000 1.800 0.000 120.0
6.096
8 4 44 12.00 43.70 -2.500 150.0
0.000
9 21 13 6.000 21.20 0.000 120.0
19.20
10 13 14 6.000 122.0 0.000 120.0
0.000
11 15 14 6.000 122.5 0.000 120.0
37.49
12 35 28 6.000 111.3 0.000 120.0
37.49
13 15 31 6.000 27.00 0.000 120.0
4.267
14 14 12 6.000 121.0 0.000 120.0
60.05
15 13 17 6.000 101.3 0.000 120.0
94.18
16 48 12 6.000 119.0 0.000 120.0
22.56
17 20 7 12.00 3.000 0.000 120.0
0.000
18 23 43 12.00 3.000 -1.0000 150.0
0.000
19 9 22 12.00 39.00 0.000 150.0
0.000
20 22 23 12.00 4.000 0.000 150.0
0.000
21 9 6 6.000 4.000 0.000 150.0
0.000
22 24 25 6.000 24.00 0.000 120.0
0.000
23 25 26 6.000 45.20 0.000 120.0
0.000
24 26 34 6.000 63.00 0.000 120.0
0.000
25 34 35 6.000 100.00 0.000 120.0
0.000
26 21 28 6.000 73.50 0.000 120.0
37.49
27 28 24 6.000 54.80 0.000 120.0
18.29
28 29 14 6.000 141.0 0.000 120.0
28.35
29 6 136 12.00 109.0 0.000 120.0
0.000
30 31 24 6.000 113.0 0.000 120.0

Page 55 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

55.78
31 136 15 6.000 141.0 0.000 120.0
37.49
32 6 29 6.000 13.50 0.000 120.0
27.43
33 36 37 6.000 79.50 0.000 150.0
0.000
34 33 38 6.000 78.00 0.000 150.0
0.000
35 34 30 6.000 63.00 0.000 150.0
0.000
36 135 37 6.000 5.500 0.000 150.0
0.000
37 30 135 6.000 100.00 0.000 150.0
0.000
38 30 33 6.000 66.30 0.000 150.0
0.000
39 35 135 6.000 63.00 0.000 150.0
0.000
40 38 36 6.000 159.0 0.000 150.0
0.000
41 42 1 12.00 1.0000 0.000 120.0
0.000
50 17 50 6.000 2.500 0.000 120.0
9.144
51 50 48 6.000 9.500 0.000 120.0
10.06
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 5 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
55 87 27 6.000 30.30 1.0000 120.0
24.08
56 53 80 12.00 21.50 0.000 150.0
14.12
57 54 55 12.00 78.90 0.000 150.0
15.53
58 55 75 12.00 56.20 0.000 150.0
43.76
59 56 57 12.00 1.0000 -1.0000 150.0
6.117
60 58 57 12.00 1.0000 0.000 150.0
0.000
61 59 58 12.00 1.0000 -1.0000 150.0
6.117
62 60 59 12.00 6.500 0.000 150.0
14.12
63 52 83 12.00 11.20 0.000 150.0
19.06
64 61 62 12.00 1.0000 -1.0000 150.0
6.117
65 62 63 12.00 1.0000 0.000 150.0
0.000
66 63 64 12.00 1.0000 1.0000 150.0
6.117
67 64 65 12.00 6.500 0.000 150.0
15.53
73 65 70 12.00 40.30 0.000 150.0
14.12
74 70 60 12.00 60.30 0.000 150.0
15.53
75 87 32 12.00 34.30 0.000 150.0
56.47

Page 56 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

76 72 71 12.00 1.0000 1.0000 150.0


6.117
77 73 72 12.00 1.0000 0.000 150.0
0.000
78 74 73 12.00 1.0000 -1.0000 150.0
6.117
79 56 75 12.00 52.50 0.000 150.0
31.06
80 75 74 12.00 6.700 0.000 150.0
0.000
81 83 77 12.00 11.30 0.000 150.0
0.000
82 77 53 12.00 21.50 0.000 150.0
29.65
83 78 52 12.00 12.60 0.000 150.0
14.12
84 97 78 12.00 25.50 0.000 150.0
0.000
85 97 61 12.00 33.00 0.000 150.0
14.12
92 93 184 12.00 10.000 0.000 150.0
14.12
93 94 93 12.00 10.000 0.000 150.0
0.000
98 95 94 12.00 9.000 0.000 150.0
14.12
99 96 95 12.00 24.40 0.000 150.0
42.35
100 71 96 12.00 45.00 0.000 150.0
0.000
102 80 54 12.00 78.90 0.000 150.0
15.53
121 130 10 4.000 1.800 0.000 120.0
6.096
123 10 132 4.000 1.800 0.000 120.0
6.096
124 184 124 6.000 30.30 2.000 120.0
24.08
125 132 129 4.000 1.800 0.000 120.0
6.096
126 116 117 4.000 1.800 0.000 120.0
6.096
127 115 11 4.000 1.800 0.000 120.0
6.096
128 39 125 4.000 1.800 0.000 120.0
6.096
129 121 39 4.000 0.9000 0.000 120.0
6.096
130 125 113 4.000 1.800 0.000 120.0
6.096
131 11 116 4.000 1.800 0.000 120.0
6.096
132 126 120 4.000 1.800 0.000 120.0
6.096

Page 57 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 6 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
133 228 121 4.000 0.4000 0.000 120.0
0.000
134 121 16 4.000 0.9000 0.000 120.0
6.096
135 127 131 4.000 1.800 0.000 120.0
6.096
136 117 118 4.000 1.800 0.000 120.0
6.096
137 16 127 4.000 1.800 0.000 120.0
6.096
138 183 162 4.000 1.800 0.000 120.0
6.096
139 155 171 4.000 1.800 0.000 120.0
6.096
140 268 174 4.000 0.4000 0.000 120.0
0.000
141 153 183 4.000 1.800 0.000 120.0
6.096
142 174 161 4.000 0.9000 0.000 120.0
6.096
143 41 115 4.000 1.800 0.000 120.0
6.096
144 96 185 12.00 14.50 0.000 150.0
14.12
145 129 126 4.000 1.800 0.000 120.0
6.096
146 93 18 6.000 30.30 1.0000 120.0
24.08
147 113 130 4.000 1.800 0.000 120.0
6.096
148 124 122 6.000 18.00 15.00 120.0
8.534
149 182 166 4.000 1.800 0.000 120.0
6.096
150 171 156 4.000 1.800 0.000 120.0
6.096
151 175 153 4.000 1.800 0.000 120.0
6.096
152 164 165 4.000 1.800 0.000 120.0
6.096
153 163 155 4.000 1.800 0.000 120.0
6.096
154 156 148 4.000 1.800 0.000 120.0
6.096
155 149 163 4.000 1.800 0.000 120.0
6.096
156 162 167 4.000 1.800 0.000 120.0
6.096
157 148 164 4.000 1.800 0.000 120.0
6.096
158 216 195 4.000 1.800 0.000 120.0
6.096
159 229 215 4.000 1.800 0.000 120.0
6.096
160 196 188 4.000 1.800 0.000 120.0
6.096
161 174 149 4.000 0.9000 0.000 120.0
6.096
162 165 172 4.000 1.800 0.000 120.0

Page 58 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

6.096
163 166 175 4.000 1.800 0.000 120.0
6.096
164 167 186 4.000 1.800 0.000 120.0
6.096
165 161 182 4.000 1.800 0.000 120.0
6.096
166 191 214 4.000 0.4000 0.000 120.0
0.000
167 214 213 4.000 0.9000 0.000 120.0
6.096
168 188 229 4.000 1.800 0.000 120.0
6.096
169 228 191 6.000 3.700 3.700 120.0
9.144
170 233 216 4.000 1.800 0.000 120.0
6.096
171 189 226 4.000 1.800 0.000 120.0
6.096
172 230 196 4.000 1.800 0.000 120.0
6.096
173 222 189 4.000 1.800 0.000 120.0
6.096
174 190 233 4.000 1.800 0.000 120.0
6.096
175 226 211 4.000 1.800 0.000 120.0
6.096
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 7 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
176 195 222 4.000 1.800 0.000 120.0
6.096
177 212 230 4.000 1.800 0.000 120.0
6.096
178 213 212 4.000 1.800 0.000 120.0
6.096
179 221 232 4.000 1.800 0.000 120.0
6.096
180 211 231 4.000 1.800 0.000 120.0
6.096
181 214 190 4.000 0.9000 0.000 120.0
6.096
182 235 203 4.000 1.800 0.000 120.0
6.096
183 234 251 4.000 1.800 0.000 120.0
6.096
184 215 221 4.000 1.800 0.000 120.0
6.096
185 202 259 4.000 1.800 0.000 120.0
6.096
186 243 248 4.000 0.9000 0.000 120.0
6.096
187 250 243 4.000 0.4000 0.000 120.0
0.000
188 238 239 4.000 1.800 0.000 120.0
6.096
189 205 238 4.000 1.800 0.000 120.0
6.096
190 259 234 4.000 1.800 0.000 120.0
6.096
191 263 202 4.000 1.800 0.000 120.0
6.096

Page 59 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

192 246 235 4.000 1.800 0.000 120.0


6.096
193 265 205 4.000 1.800 0.000 120.0
6.096
194 251 254 4.000 1.800 0.000 120.0
6.096
195 248 237 4.000 1.800 0.000 120.0
6.096
196 240 263 4.000 1.800 0.000 120.0
6.096
197 243 204 4.000 0.9000 0.000 120.0
6.096
198 237 240 4.000 1.800 0.000 120.0
6.096
199 204 246 4.000 1.800 0.000 120.0
6.096
200 239 252 4.000 1.800 0.000 120.0
6.096
201 203 265 4.000 1.800 0.000 120.0
6.096
202 268 250 6.000 3.700 3.700 120.0
9.144
203 184 87 12.00 9.000 0.000 150.0
0.000
204 18 268 6.000 8.500 8.500 120.0
9.144
205 273 198 4.000 1.800 0.000 120.0
6.096
206 209 207 4.000 1.800 0.000 120.0
6.096
207 217 219 4.000 1.800 0.000 120.0
6.096
208 150 134 4.000 1.800 0.000 120.0
6.096
209 133 264 6.000 8.500 8.500 120.0
9.144
210 147 40 4.000 1.800 0.000 120.0
6.096
211 140 3 4.000 1.800 0.000 120.0
6.096
212 40 160 4.000 1.800 0.000 120.0
6.096
213 160 159 4.000 1.800 0.000 120.0
6.096
214 8 145 4.000 1.800 0.000 120.0
6.096
215 158 8 4.000 0.9000 0.000 120.0
6.096
216 157 150 4.000 1.800 0.000 120.0
6.096
217 264 158 4.000 0.4000 0.000 120.0
0.000
218 141 142 4.000 1.800 0.000 120.0
6.096

Page 60 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 8 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
219 3 141 4.000 1.800 0.000 120.0
6.096
220 145 139 4.000 1.800 0.000 120.0
6.096
221 154 144 4.000 1.800 0.000 120.0
6.096
222 128 157 4.000 1.800 0.000 120.0
6.096
223 159 154 4.000 1.800 0.000 120.0
6.096
224 185 187 12.00 2.500 0.000 150.0
14.12
225 143 151 6.000 18.00 15.00 120.0
8.534
226 158 128 4.000 0.9000 0.000 120.0
6.096
227 142 137 4.000 1.800 0.000 120.0
6.096
228 134 140 4.000 1.800 0.000 120.0
6.096
229 139 147 4.000 1.800 0.000 120.0
6.096
231 244 209 4.000 1.800 0.000 120.0
6.096
232 94 133 6.000 30.30 1.0000 120.0
24.08
233 260 273 4.000 1.800 0.000 120.0
6.096
234 200 241 4.000 1.800 0.000 120.0
6.096
235 201 244 4.000 1.800 0.000 120.0
6.096
236 207 224 4.000 1.800 0.000 120.0
6.096
237 199 257 4.000 0.4000 0.000 120.0
0.000
238 257 261 4.000 0.9000 0.000 120.0
6.096
239 198 217 4.000 1.800 0.000 120.0
6.096
240 264 199 6.000 3.700 3.700 120.0
9.144
241 224 200 4.000 1.800 0.000 120.0
6.096
242 236 266 4.000 1.800 0.000 120.0
6.096
243 208 260 4.000 1.800 0.000 120.0
6.096
244 267 223 4.000 1.800 0.000 120.0
6.096
245 219 236 4.000 1.800 0.000 120.0
6.096
246 261 208 4.000 1.800 0.000 120.0
6.096
247 257 201 4.000 0.9000 0.000 120.0
6.096
248 241 267 3.000 1.800 0.000 120.0
4.572
249 95 143 6.000 30.30 2.000 120.0

Page 61 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

24.08
266 180 179 4.000 18.00 12.00 120.0
0.000
269 187 123 12.00 13.00 0.000 150.0
24.70
270 253 180 4.000 30.30 2.000 120.0
0.000
271 138 253 4.000 55.00 0.000 120.0
12.19

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
6 1 x 4 9.144
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 9 OF 38
---------------------------------------------------------------------------------------------------
-----------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
7 1 x 4 6.096
9 2 x 4 9.144 1 x 5 0.9144
11 4 x 4 9.144 1 x 5 0.9144
12 4 x 4 9.144 1 x 5 0.9144
13 1 x 2 4.267
14 2 x 1 2.134 6 x 4 9.144 1 x 5 0.9144
15 10 x 4 9.144 3 x 5 0.9144
16 2 x 1 2.134 2 x 4 9.144
26 4 x 4 9.144 1 x 5 0.9144
27 2 x 4 9.144
28 3 x 4 9.144 1 x 5 0.9144
30 6 x 4 9.144 1 x 5 0.9144
31 4 x 4 9.144 1 x 5 0.9144
32 3 x 4 9.144
50 1 x 4 9.144
51 1 x 4 9.144 1 x 5 0.9144
55 5 x 2 4.267 3 x 5 0.9144
56 1 x 4 14.12
57 1 x 4 14.12 1 x 5 1.412
58 3 x 4 14.12 1 x 5 1.412
59 2 x 1 3.059
61 2 x 1 3.059
62 1 x 4 14.12
63 1 x 4 14.12 1 x 9 4.941
64 2 x 1 3.059
66 2 x 1 3.059
67 1 x 4 14.12 1 x 5 1.412
73 1 x 4 14.12
74 1 x 4 14.12 1 x 5 1.412
75 4 x 4 14.12
76 2 x 1 3.059
78 2 x 1 3.059
79 2 x 4 14.12 2 x 5 1.412
82 2 x 4 14.12 1 x 5 1.412
83 1 x 4 14.12
85 1 x 4 14.12
92 1 x 4 14.12
98 1 x 4 14.12
99 3 x 4 14.12
102 1 x 4 14.12 1 x 5 1.412
121 1 x 4 6.096
123 1 x 4 6.096
124 5 x 2 4.267 3 x 5 0.9144

Page 62 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 10 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
125 1 x 4 6.096
126 1 x 4 6.096
127 1 x 4 6.096
128 1 x 4 6.096
129 1 x 4 6.096
130 1 x 4 6.096
131 1 x 4 6.096
132 1 x 4 6.096
134 1 x 4 6.096
135 1 x 4 6.096
136 1 x 4 6.096
137 1 x 4 6.096
138 1 x 4 6.096
139 1 x 4 6.096
141 1 x 4 6.096
142 1 x 4 6.096
143 1 x 4 6.096
144 1 x 4 14.12
145 1 x 4 6.096
146 5 x 2 4.267 3 x 5 0.9144
147 1 x 4 6.096
148 2 x 2 4.267
149 1 x 4 6.096
150 1 x 4 6.096
151 1 x 4 6.096
152 1 x 4 6.096
153 1 x 4 6.096
154 1 x 4 6.096
155 1 x 4 6.096
156 1 x 4 6.096
157 1 x 4 6.096
158 1 x 4 6.096
159 1 x 4 6.096
160 1 x 4 6.096
161 1 x 4 6.096
162 1 x 4 6.096
163 1 x 4 6.096
164 1 x 4 6.096
165 1 x 4 6.096
167 1 x 4 6.096
168 1 x 4 6.096
169 1 x 4 9.144
170 1 x 4 6.096

Page 63 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 11 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
171 1 x 4 6.096
172 1 x 4 6.096
173 1 x 4 6.096
174 1 x 4 6.096
175 1 x 4 6.096
176 1 x 4 6.096
177 1 x 4 6.096
178 1 x 4 6.096
179 1 x 4 6.096
180 1 x 4 6.096
181 1 x 4 6.096
182 1 x 4 6.096
183 1 x 4 6.096
184 1 x 4 6.096
185 1 x 4 6.096
186 1 x 4 6.096
188 1 x 4 6.096
189 1 x 4 6.096
190 1 x 4 6.096
191 1 x 4 6.096
192 1 x 4 6.096
193 1 x 4 6.096
194 1 x 4 6.096
195 1 x 4 6.096
196 1 x 4 6.096
197 1 x 4 6.096
198 1 x 4 6.096
199 1 x 4 6.096
200 1 x 4 6.096
201 1 x 4 6.096
202 1 x 4 9.144
204 1 x 4 9.144
205 1 x 4 6.096
206 1 x 4 6.096
207 1 x 4 6.096
208 1 x 4 6.096
209 1 x 4 9.144
210 1 x 4 6.096
211 1 x 4 6.096
212 1 x 4 6.096
213 1 x 4 6.096
214 1 x 4 6.096
215 1 x 4 6.096

Page 64 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 12 OF 38
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
216 1 x 4 6.096
218 1 x 4 6.096
219 1 x 4 6.096
220 1 x 4 6.096
221 1 x 4 6.096
222 1 x 4 6.096
223 1 x 4 6.096
224 1 x 4 14.12
225 2 x 2 4.267
226 1 x 4 6.096
227 1 x 4 6.096
228 1 x 4 6.096
229 1 x 4 6.096
231 1 x 4 6.096
232 5 x 2 4.267 3 x 5 0.9144
233 1 x 4 6.096
234 1 x 4 6.096
235 1 x 4 6.096
236 1 x 4 6.096
238 1 x 4 6.096
239 1 x 4 6.096
240 1 x 4 9.144
241 1 x 4 6.096
242 1 x 4 6.096
243 1 x 4 6.096
244 1 x 4 6.096
245 1 x 4 6.096
246 1 x 4 6.096
247 1 x 4 6.096
248 1 x 4 4.572
249 5 x 2 4.267 3 x 5 0.9144
269 1 x 2 6.353 1 x 4 14.12 3 x 5 1.412
271 2 x 2 3.048 1 x 4 6.096

Fitting types are :


1 -- 45 Deg Elbow
2 -- 90 Deg Standard Elbow
3 -- 90 Deg Long Radius Elbow
4 -- Tee or Cross (Flow Turned Thro 90 Deg)
5 -- Gate Valve
6 -- Swing Check Valve
7 -- Non-Return Valve
8 -- Ball Valve
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 13 OF 38
---------------------------------------------------------------------------------------------------
--------------------
9 -- Butterfly Valve

Page 65 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 14 OF 38
---------------------------------------------------------------------------------------------------
--------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (psi G ) (psi G )
---------------------------------------------------------------------------------------------------
29 10 2 1.2000 12.9600 0.29000E+02 0.17400E+03
30 126 2 1.2000 12.9600 0.29000E+02 0.17400E+03
31 127 2 1.2000 12.9600 0.29000E+02 0.17400E+03
32 132 2 1.2000 12.9600 0.29000E+02 0.17400E+03
33 39 2 1.2000 12.9600 0.29000E+02 0.17400E+03
34 125 2 1.2000 12.9600 0.29000E+02 0.17400E+03
35 130 2 1.2000 12.9600 0.29000E+02 0.17400E+03
36 16 2 1.2000 12.9600 0.29000E+02 0.17400E+03
37 113 2 1.2000 12.9600 0.29000E+02 0.17400E+03
38 129 2 1.2000 12.9600 0.29000E+02 0.17400E+03
39 120 2 1.2000 12.9600 0.29000E+02 0.17400E+03
40 162 2 1.2000 12.9600 0.29000E+02 0.17400E+03
41 116 2 1.2000 12.9600 0.29000E+02 0.17400E+03
42 41 2 1.2000 12.9600 0.29000E+02 0.17400E+03
43 11 2 1.2000 12.9600 0.29000E+02 0.17400E+03
44 117 2 1.2000 12.9600 0.29000E+02 0.17400E+03
45 131 2 1.2000 12.9600 0.29000E+02 0.17400E+03
46 118 2 1.2000 12.9600 0.29000E+02 0.17400E+03
47 115 2 1.2000 12.9600 0.29000E+02 0.17400E+03
48 153 2 1.2000 12.9600 0.29000E+02 0.17400E+03
49 167 2 1.2000 12.9600 0.29000E+02 0.17400E+03
50 166 2 1.2000 12.9600 0.29000E+02 0.17400E+03
51 161 2 1.2000 12.9600 0.29000E+02 0.17400E+03
52 156 2 1.2000 12.9600 0.29000E+02 0.17400E+03
53 165 2 1.2000 12.9600 0.29000E+02 0.17400E+03
54 163 2 1.2000 12.9600 0.29000E+02 0.17400E+03
55 148 2 1.2000 12.9600 0.29000E+02 0.17400E+03
56 149 2 1.2000 12.9600 0.29000E+02 0.17400E+03
57 155 2 1.2000 12.9600 0.29000E+02 0.17400E+03
58 182 2 1.2000 12.9600 0.29000E+02 0.17400E+03
59 175 2 1.2000 12.9600 0.29000E+02 0.17400E+03
60 186 2 1.2000 12.9600 0.29000E+02 0.17400E+03
61 183 2 1.2000 12.9600 0.29000E+02 0.17400E+03
62 172 2 1.2000 12.9600 0.29000E+02 0.17400E+03
63 171 2 1.2000 12.9600 0.29000E+02 0.17400E+03
64 164 2 1.2000 12.9600 0.29000E+02 0.17400E+03
65 222 2 1.2000 12.9600 0.29000E+02 0.17400E+03
66 196 2 1.2000 12.9600 0.29000E+02 0.17400E+03
67 188 2 1.2000 12.9600 0.29000E+02 0.17400E+03
68 215 2 1.2000 12.9600 0.29000E+02 0.17400E+03
69 212 2 1.2000 12.9600 0.29000E+02 0.17400E+03
70 221 2 1.2000 12.9600 0.29000E+02 0.17400E+03

Page 66 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 15 OF 38
---------------------------------------------------------------------------------------------------
--------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (psi G ) (psi G )
---------------------------------------------------------------------------------------------------
71 213 2 1.2000 12.9600 0.29000E+02 0.17400E+03
72 226 2 1.2000 12.9600 0.29000E+02 0.17400E+03
73 190 2 1.2000 12.9600 0.29000E+02 0.17400E+03
74 229 2 1.2000 12.9600 0.29000E+02 0.17400E+03
75 230 2 1.2000 12.9600 0.29000E+02 0.17400E+03
76 216 2 1.2000 12.9600 0.29000E+02 0.17400E+03
77 189 2 1.2000 12.9600 0.29000E+02 0.17400E+03
78 211 2 1.2000 12.9600 0.29000E+02 0.17400E+03
79 195 2 1.2000 12.9600 0.29000E+02 0.17400E+03
80 233 2 1.2000 12.9600 0.29000E+02 0.17400E+03
81 232 2 1.2000 12.9600 0.29000E+02 0.17400E+03
82 240 2 1.2000 12.9600 0.29000E+02 0.17400E+03
83 251 2 1.2000 12.9600 0.29000E+02 0.17400E+03
84 231 2 1.2000 12.9600 0.29000E+02 0.17400E+03
85 246 2 1.2000 12.9600 0.29000E+02 0.17400E+03
86 234 2 1.2000 12.9600 0.29000E+02 0.17400E+03
87 204 2 1.2000 12.9600 0.29000E+02 0.17400E+03
88 237 2 1.2000 12.9600 0.29000E+02 0.17400E+03
89 202 2 1.2000 12.9600 0.29000E+02 0.17400E+03
90 248 2 1.2000 12.9600 0.29000E+02 0.17400E+03
91 263 2 1.2000 12.9600 0.29000E+02 0.17400E+03
92 235 2 1.2000 12.9600 0.29000E+02 0.17400E+03
93 254 2 1.2000 12.9600 0.29000E+02 0.17400E+03
94 259 2 1.2000 12.9600 0.29000E+02 0.17400E+03
95 265 2 1.2000 12.9600 0.29000E+02 0.17400E+03
96 252 2 1.2000 12.9600 0.29000E+02 0.17400E+03
97 238 2 1.2000 12.9600 0.29000E+02 0.17400E+03
98 239 2 1.2000 12.9600 0.29000E+02 0.17400E+03
99 203 2 1.2000 12.9600 0.29000E+02 0.17400E+03
100 205 2 1.2000 12.9600 0.29000E+02 0.17400E+03
101 236 2 1.2000 12.9600 0.29000E+02 0.17400E+03
102 273 2 1.2000 12.9600 0.29000E+02 0.17400E+03
103 224 2 1.2000 12.9600 0.29000E+02 0.17400E+03
104 198 2 1.2000 12.9600 0.29000E+02 0.17400E+03
105 208 2 1.2000 12.9600 0.29000E+02 0.17400E+03
106 219 2 1.2000 12.9600 0.29000E+02 0.17400E+03
107 260 2 1.2000 12.9600 0.29000E+02 0.17400E+03
108 244 2 1.2000 12.9600 0.29000E+02 0.17400E+03
109 207 2 1.2000 12.9600 0.29000E+02 0.17400E+03
110 200 2 1.2000 12.9600 0.29000E+02 0.17400E+03
111 201 2 1.2000 12.9600 0.29000E+02 0.17400E+03
112 266 2 1.2000 12.9600 0.29000E+02 0.17400E+03

Page 67 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 16 OF 38
---------------------------------------------------------------------------------------------------
--------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (psi G ) (psi G )
---------------------------------------------------------------------------------------------------
113 267 2 1.2000 12.9600 0.29000E+02 0.17400E+03
114 261 2 1.2000 12.9600 0.29000E+02 0.17400E+03
115 241 2 1.2000 12.9600 0.29000E+02 0.17400E+03
116 217 2 1.2000 12.9600 0.29000E+02 0.17400E+03
117 209 2 1.2000 12.9600 0.29000E+02 0.17400E+03
118 223 2 1.2000 12.9600 0.29000E+02 0.17400E+03
119 8 2 1.2000 12.9600 0.29000E+02 0.17400E+03
120 147 2 1.2000 12.9600 0.29000E+02 0.17400E+03
121 159 2 1.2000 12.9600 0.29000E+02 0.17400E+03
122 160 2 1.2000 12.9600 0.29000E+02 0.17400E+03
123 40 2 1.2000 12.9600 0.29000E+02 0.17400E+03
124 128 2 1.2000 12.9600 0.29000E+02 0.17400E+03
125 139 2 1.2000 12.9600 0.29000E+02 0.17400E+03
126 145 2 1.2000 12.9600 0.29000E+02 0.17400E+03
127 157 2 1.2000 12.9600 0.29000E+02 0.17400E+03
128 140 2 1.2000 12.9600 0.29000E+02 0.17400E+03
129 3 2 1.2000 12.9600 0.29000E+02 0.17400E+03
130 142 2 1.2000 12.9600 0.29000E+02 0.17400E+03
131 137 2 1.2000 12.9600 0.29000E+02 0.17400E+03
132 134 2 1.2000 12.9600 0.29000E+02 0.17400E+03
133 150 2 1.2000 12.9600 0.29000E+02 0.17400E+03
134 154 2 1.2000 12.9600 0.29000E+02 0.17400E+03
135 144 2 1.2000 12.9600 0.29000E+02 0.17400E+03
136 141 2 1.2000 12.9600 0.29000E+02 0.17400E+03
149 151 3 50.0000 509.2200 0.29000E+02 0.17400E+03
150 122 3 50.0000 509.2200 0.29000E+02 0.17400E+03
151 179 5 21.0000 196.9920 0.58000E+02 0.17400E+03

Nozzle types are :


2 -- Condensate Tank Nozzle
3 -- Mushroom Nozzle
5 -- Foam Box
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 17 OF 38
---------------------------------------------------------------------------------------------------
--------------------

GENERAL PRESSURE LOSS COMPONENTS


---------------------------------

Label Input node Output node Resistance Factor Resistant Exponent Component
Description
(psi /US.g/min^exp)
---------------------------------------------------------------------------------------------------
-------------------
" 1" " 123" " 138" 5.900066E-04 2.00000 "
Non-Library"

Page 68 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 18 OF 38
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
1 19 32 2690.3088 10 10.4000 12.0000 *
2 7 4 2690.3088 10 10.4000 12.0000 *
3 1 20 2690.3088 9 12.2500 12.0000 *
4 44 9 2690.3088 10 10.4000 12.0000 *
5 43 19 2690.3088 10 10.4000 12.0000 *
6 27 228 476.5714 3 6.0650 6.0000 *
7 131 41 80.2797 3 4.0260 4.0000 *
8 4 44 2690.3088 10 10.4000 12.0000 *
9 21 13 0.0369 3 6.0650 6.0000 *
10 13 14 0.0190 3 6.0650 6.0000 *
11 15 14 0.0026 3 6.0650 6.0000 *
12 35 28 0.2615 3 6.0650 6.0000 *
13 15 31 0.0369 3 6.0650 6.0000 *
14 14 12 -0.0179 3 6.0650 6.0000 *
15 13 17 0.0179 3 6.0650 6.0000 *
16 48 12 0.0179 3 6.0650 6.0000 *
17 20 7 2690.3088 9 12.2500 12.0000 *
18 23 43 2690.3088 10 10.4000 12.0000 *
19 9 22 2690.3088 10 10.4000 12.0000 *
20 22 23 2690.3088 10 10.4000 12.0000 *
21 9 6 0.0000 10 5.1000 6.0000 *
22 24 25 0.2615 3 6.0650 6.0000 *
23 25 26 0.2615 3 6.0650 6.0000 *
24 26 34 0.2615 3 6.0650 6.0000 *
25 34 35 0.1568 3 6.0650 6.0000 *
26 21 28 -0.0369 3 6.0650 6.0000 *
27 28 24 0.2245 3 6.0650 6.0000 *
28 29 14 -0.0396 3 6.0650 6.0000 *
29 6 136 0.0396 3 11.9380 12.0000 *
30 31 24 0.0369 3 6.0650 6.0000 *
31 136 15 0.0396 3 6.0650 6.0000 *
32 6 29 -0.0396 3 6.0650 6.0000 *
33 36 37 0.0709 10 5.1000 6.0000 *
34 33 38 0.0709 10 5.1000 6.0000 *
35 34 30 0.1047 10 5.1000 6.0000 *
36 135 37 -0.0709 10 5.1000 6.0000 *
37 30 135 0.0338 10 5.1000 6.0000 *
38 30 33 0.0709 10 5.1000 6.0000 *
39 35 135 -0.1047 10 5.1000 6.0000 *

Page 69 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 19 OF 38
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
40 38 36 0.0709 10 5.1000 6.0000 *
41 42 1 2690.3088 9 12.2500 12.0000 *
50 17 50 0.0179 3 6.0650 6.0000 *
51 50 48 0.0179 3 6.0650 6.0000 *
55 87 27 476.5714 3 6.0650 6.0000 *
56 53 80 0.0340 10 10.4000 12.0000 *
57 54 55 0.0340 10 10.4000 12.0000 *
58 55 75 0.0340 10 10.4000 12.0000 *
59 56 57 0.0340 10 10.4000 12.0000 *
60 58 57 -0.0340 10 10.4000 12.0000 *
61 59 58 -0.0340 10 10.4000 12.0000 *
62 60 59 -0.0340 10 10.4000 12.0000 *
63 52 83 0.0340 10 10.4000 12.0000 *
64 61 62 -0.0340 10 10.4000 12.0000 *
65 62 63 -0.0340 10 10.4000 12.0000 *
66 63 64 -0.0340 10 10.4000 12.0000 *
67 64 65 -0.0340 10 10.4000 12.0000 *
73 65 70 -0.0340 10 10.4000 12.0000 *
74 70 60 -0.0340 10 10.4000 12.0000 *
75 87 32 -2690.3088 10 10.4000 12.0000 *
76 72 71 0.0000 10 10.4000 12.0000 *
77 73 72 0.0000 10 10.4000 12.0000 *
78 74 73 0.0000 10 10.4000 12.0000 *
79 56 75 -0.0340 10 10.4000 12.0000 *
80 75 74 0.0000 10 10.4000 12.0000 *
81 83 77 0.0340 10 10.4000 12.0000 *
82 77 53 0.0340 10 10.4000 12.0000 *
83 78 52 0.0340 10 10.4000 12.0000 *
84 97 78 0.0340 10 10.4000 12.0000 *
85 97 61 -0.0340 10 10.4000 12.0000 *
92 93 184 -1681.9000 10 10.4000 12.0000 *
93 94 93 -1206.4154 10 10.4000 12.0000 *
98 95 94 -731.0833 10 10.4000 12.0000 *
99 96 95 -200.3917 10 10.4000 12.0000 *
100 71 96 0.0000 10 10.4000 12.0000 *
102 80 54 0.0340 10 10.4000 12.0000 *
121 130 10 66.8969 3 4.0260 4.0000 *
123 10 132 53.5160 3 4.0260 4.0000 *
124 184 124 531.8374 3 6.0650 6.0000 *

Page 70 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 20 OF 38
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
125 132 129 40.1364 3 4.0260 4.0000 *
126 116 117 26.7575 3 4.0260 4.0000 *
127 115 11 53.5160 3 4.0260 4.0000 *
128 39 125 107.0549 3 4.0260 4.0000 *
129 121 39 120.4496 3 4.0260 4.0000 *
130 125 113 93.6654 3 4.0260 4.0000 *
131 11 116 40.1364 3 4.0260 4.0000 *
132 126 120 13.3788 3 4.0260 4.0000 *
133 228 121 240.8991 3 4.0260 4.0000 *
134 121 16 120.4496 3 4.0260 4.0000 *
135 127 131 93.6654 3 4.0260 4.0000 *
136 117 118 13.3788 3 4.0260 4.0000 *
137 16 127 107.0549 3 4.0260 4.0000 *
138 183 162 40.0469 3 4.0260 4.0000 *
139 155 171 80.1005 3 4.0260 4.0000 *
140 268 174 240.3616 3 4.0260 4.0000 *
141 153 183 53.3966 3 4.0260 4.0000 *
142 174 161 120.1808 3 4.0260 4.0000 *
143 41 115 66.8969 3 4.0260 4.0000 *
144 96 185 200.3917 10 10.4000 12.0000 *
145 129 126 26.7575 3 4.0260 4.0000 *
146 93 18 475.4847 3 6.0650 6.0000 *
147 113 130 80.2797 3 4.0260 4.0000 *
148 124 122 531.8374 3 6.0650 6.0000 *
149 182 166 93.4563 3 4.0260 4.0000 *
150 171 156 66.7476 3 4.0260 4.0000 *
151 175 153 66.7476 3 4.0260 4.0000 *
152 164 165 26.6978 3 4.0260 4.0000 *
153 163 155 93.4563 3 4.0260 4.0000 *
154 156 148 53.3966 3 4.0260 4.0000 *
155 149 163 106.8160 3 4.0260 4.0000 *
156 162 167 26.6978 3 4.0260 4.0000 *
157 148 164 40.0469 3 4.0260 4.0000 *
158 216 195 78.5378 3 4.0260 4.0000 *
159 229 215 39.2655 3 4.0260 4.0000 *
160 196 188 65.4453 3 4.0260 4.0000 *
161 174 149 120.1808 3 4.0260 4.0000 *
162 165 172 13.3489 3 4.0260 4.0000 *
163 166 175 80.1005 3 4.0260 4.0000 *

Page 71 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 21 OF 38
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
164 167 186 13.3489 3 4.0260 4.0000 *
165 161 182 106.8160 3 4.0260 4.0000 *
166 191 214 235.6722 3 4.0260 4.0000 *
167 214 213 117.8361 3 4.0260 4.0000 *
168 188 229 52.3548 3 4.0260 4.0000 *
169 228 191 235.6723 3 6.0650 6.0000 *
170 233 216 91.6330 3 4.0260 4.0000 *
171 189 226 39.2655 3 4.0260 4.0000 *
172 230 196 78.5378 3 4.0260 4.0000 *
173 222 189 52.3548 3 4.0260 4.0000 *
174 190 233 104.7321 3 4.0260 4.0000 *
175 226 211 26.1769 3 4.0260 4.0000 *
176 195 222 65.4453 3 4.0260 4.0000 *
177 212 230 91.6330 3 4.0260 4.0000 *
178 213 212 104.7321 3 4.0260 4.0000 *
179 221 232 13.0885 3 4.0260 4.0000 *
180 211 231 13.0885 3 4.0260 4.0000 *
181 214 190 117.8361 3 4.0260 4.0000 *
182 235 203 78.3548 3 4.0260 4.0000 *
183 234 251 26.1159 3 4.0260 4.0000 *
184 215 221 26.1769 3 4.0260 4.0000 *
185 202 259 52.2328 3 4.0260 4.0000 *
186 243 248 117.5616 3 4.0260 4.0000 *
187 250 243 235.1231 3 4.0260 4.0000 *
188 238 239 26.1159 3 4.0260 4.0000 *
189 205 238 39.1740 3 4.0260 4.0000 *
190 259 234 39.1740 3 4.0260 4.0000 *
191 263 202 65.2928 3 4.0260 4.0000 *
192 246 235 91.4195 3 4.0260 4.0000 *
193 265 205 52.2328 3 4.0260 4.0000 *
194 251 254 13.0580 3 4.0260 4.0000 *
195 248 237 104.4880 3 4.0260 4.0000 *
196 240 263 78.3548 3 4.0260 4.0000 *
197 243 204 117.5616 3 4.0260 4.0000 *
198 237 240 91.4195 3 4.0260 4.0000 *
199 204 246 104.4880 3 4.0260 4.0000 *
200 239 252 13.0580 3 4.0260 4.0000 *
201 203 265 65.2928 3 4.0260 4.0000 *
202 268 250 235.1232 3 6.0650 6.0000 *

Page 72 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 22 OF 38
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
203 184 87 -2213.7378 10 10.4000 12.0000 *
204 18 268 475.4847 3 6.0650 6.0000 *
205 273 198 65.2717 3 4.0260 4.0000 *
206 209 207 78.3273 3 4.0260 4.0000 *
207 217 219 39.1614 3 4.0260 4.0000 *
208 150 134 80.0757 3 4.0260 4.0000 *
209 133 264 475.3321 3 6.0650 6.0000 *
210 147 40 66.7269 3 4.0260 4.0000 *
211 140 3 53.3801 3 4.0260 4.0000 *
212 40 160 53.3801 3 4.0260 4.0000 *
213 160 159 40.0344 3 4.0260 4.0000 *
214 8 145 106.7829 3 4.0260 4.0000 *
215 158 8 120.1435 3 4.0260 4.0000 *
216 157 150 93.4274 3 4.0260 4.0000 *
217 264 158 240.2871 3 4.0260 4.0000 *
218 141 142 26.6895 3 4.0260 4.0000 *
219 3 141 40.0344 3 4.0260 4.0000 *
220 145 139 93.4274 3 4.0260 4.0000 *
221 154 144 13.3448 3 4.0260 4.0000 *
222 128 157 106.7829 3 4.0260 4.0000 *
223 159 154 26.6895 3 4.0260 4.0000 *
224 185 187 200.3917 10 10.4000 12.0000 *
225 143 151 530.6916 3 6.0650 6.0000 *
226 158 128 120.1435 3 4.0260 4.0000 *
227 142 137 13.3448 3 4.0260 4.0000 *
228 134 140 66.7269 3 4.0260 4.0000 *
229 139 147 80.0757 3 4.0260 4.0000 *
231 244 209 91.3878 3 4.0260 4.0000 *
232 94 133 475.3321 3 6.0650 6.0000 *
233 260 273 78.3294 3 4.0260 4.0000 *
234 200 241 39.1593 3 4.0260 4.0000 *
235 201 244 104.4522 3 4.0260 4.0000 *
236 207 224 65.2696 3 4.0260 4.0000 *
237 199 257 235.0450 3 4.0260 4.0000 *
238 257 261 117.5235 3 4.0260 4.0000 *
239 198 217 52.2159 3 4.0260 4.0000 *
240 264 199 235.0450 3 6.0650 6.0000 *
241 224 200 52.2138 3 4.0260 4.0000 *
242 236 266 13.0537 3 4.0260 4.0000 *

Page 73 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 23 OF 38
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
243 208 260 91.3899 3 4.0260 4.0000 *
244 267 223 13.0528 3 4.0260 4.0000 *
245 219 236 26.1074 3 4.0260 4.0000 *
246 261 208 104.4542 3 4.0260 4.0000 *
247 257 201 117.5215 3 4.0260 4.0000 *
248 241 267 26.1053 3 3.0680 3.0000 *
249 95 143 530.6916 3 6.0650 6.0000 *
266 180 179 200.3917 3 4.0260 4.0000 *
269 187 123 200.3917 10 10.4000 12.0000 *
270 253 180 200.3917 3 4.0260 4.0000 *
271 138 253 200.3917 3 4.0260 4.0000 *

A * indicates that this is a SET diameter

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Sch.20 Not Lined
10 -- HDPE Not Lined

Page 74 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 24 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
1 19 32 12.00 145.1 143.5 1.523 0.1034
2690. 3.097
2 7 4 12.00 143.5 143.4 2.6047E-02 2.6047E-02
2690. 3.097
3 1 20 12.00 145.0 143.5 1.443 2.3477E-02
2690. 2.232
4 44 9 12.00 145.5 145.3 0.1931 0.1931
2690. 3.097
5 43 19 12.00 145.1 145.1 6.8954E-02 6.8954E-02
2690. 3.097
6 27 228 6.00 137.4 124.8 12.59 0.5170
476.6 1.613
7 131 41 4.00 124.5 124.4 6.3087E-02 6.3087E-02
80.28 0.6167
8 4 44 12.00 143.4 145.5 -2.043 1.507
2690. 3.097
9 21 13 6.00 145.3 145.3 0.000 0.000
3.6928E-02 1.2500E-04
10 13 14 6.00 145.3 145.3 0.000 0.000
1.9003E-02 6.4324E-05
11 15 14 6.00 145.3 145.3 0.000 0.000
2.6419E-03 8.9426E-06
12 35 28 6.00 145.3 145.3 0.000 0.000
0.2615 8.8508E-04
13 15 31 6.00 145.3 145.3 0.000 0.000
3.6928E-02 1.2500E-04
14 14 12 6.00 145.3 145.3 0.000 0.000 -
1.7925E-02 -6.0674E-05
15 13 17 6.00 145.3 145.3 0.000 0.000
1.7925E-02 6.0674E-05
16 48 12 6.00 145.3 145.3 0.000 0.000
1.7925E-02 6.0674E-05
17 20 7 12.00 143.5 143.5 7.0450E-02 7.0450E-02
2690. 2.232
18 23 43 12.00 143.8 145.1 -1.316 0.1035
2690. 3.097
19 9 22 12.00 145.3 143.9 1.345 1.345
2690. 3.097
20 22 23 12.00 143.9 143.8 0.1379 0.1379
2690. 3.097
21 9 6 6.00 145.3 145.3 0.000 0.000
2.8787E-09 1.3780E-11
22 24 25 6.00 145.3 145.3 0.000 0.000
0.2615 8.8508E-04
23 25 26 6.00 145.3 145.3 0.000 0.000
0.2615 8.8508E-04
24 26 34 6.00 145.3 145.3 0.000 0.000
0.2615 8.8508E-04
25 34 35 6.00 145.3 145.3 0.000 0.000
0.1568 5.3066E-04
26 21 28 6.00 145.3 145.3 0.000 0.000 -
3.6928E-02 -1.2500E-04
27 28 24 6.00 145.3 145.3 0.000 0.000
0.2245 7.6008E-04
28 29 14 6.00 145.3 145.3 0.000 0.000 -
3.9570E-02 -1.3394E-04
29 6 136 12.00 145.3 145.3 0.000 0.000
3.9570E-02 3.4571E-05

Page 75 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

30 31 24 6.00 145.3 145.3 0.000 0.000


3.6928E-02 1.2500E-04
31 136 15 6.00 145.3 145.3 0.000 0.000
3.9570E-02 1.3394E-04
32 6 29 6.00 145.3 145.3 0.000 0.000 -
3.9570E-02 -1.3394E-04
33 36 37 6.00 145.3 145.3 0.000 0.000
7.0863E-02 3.3922E-04
34 33 38 6.00 145.3 145.3 0.000 0.000
7.0863E-02 3.3922E-04
35 34 30 6.00 145.3 145.3 0.000 0.000
0.1047 5.0123E-04
36 135 37 6.00 145.3 145.3 0.000 0.000 -
7.0863E-02 -3.3922E-04
37 30 135 6.00 145.3 145.3 0.000 0.000
3.3842E-02 1.6200E-04
38 30 33 6.00 145.3 145.3 0.000 0.000
7.0863E-02 3.3922E-04
39 35 135 6.00 145.3 145.3 0.000 0.000 -
0.1047 -5.0123E-04
40 38 36 6.00 145.3 145.3 0.000 0.000
7.0863E-02 3.3922E-04
41 42 1 12.00 145.0 145.0 2.3468E-02 2.3468E-02
2690. 2.232
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 25 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
50 17 50 6.00 145.3 145.3 0.000 0.000
1.7925E-02 6.0674E-05
51 50 48 6.00 145.3 145.3 0.000 0.000
1.7925E-02 6.0674E-05
55 87 27 6.00 140.4 137.4 3.013 1.593
476.6 1.613
56 53 80 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
57 54 55 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
58 55 75 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
59 56 57 12.00 139.7 141.1 -1.420 0.000
3.3960E-02 3.9094E-05
60 58 57 12.00 141.1 141.1 0.000 0.000 -
3.3960E-02 -3.9094E-05
61 59 58 12.00 139.7 141.1 -1.420 0.000 -
3.3960E-02 -3.9094E-05
62 60 59 12.00 139.7 139.7 0.000 0.000 -
3.3960E-02 -3.9094E-05
63 52 83 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
64 61 62 12.00 139.7 141.1 -1.420 0.000 -
3.3960E-02 -3.9094E-05
65 62 63 12.00 141.1 141.1 0.000 0.000 -
3.3960E-02 -3.9094E-05
66 63 64 12.00 141.1 139.7 1.420 0.000 -
3.3960E-02 -3.9094E-05
67 64 65 12.00 139.7 139.7 0.000 0.000 -
3.3960E-02 -3.9094E-05
73 65 70 12.00 139.7 139.7 0.000 0.000 -
3.3960E-02 -3.9094E-05
74 70 60 12.00 139.7 139.7 0.000 0.000 -
3.3960E-02 -3.9094E-05

Page 76 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

75 87 32 12.00 140.4 143.5 -3.130 3.130 -


2690. -3.097
76 72 71 12.00 141.1 139.7 1.420 0.000
0.000 0.000
77 73 72 12.00 141.1 141.1 0.000 0.000
0.000 0.000
78 74 73 12.00 139.7 141.1 -1.420 0.000
0.000 0.000
79 56 75 12.00 139.7 139.7 0.000 0.000 -
3.3960E-02 -3.9094E-05
80 75 74 12.00 139.7 139.7 0.000 0.000
0.000 0.000
81 83 77 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
82 77 53 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
83 78 52 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
84 97 78 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
85 97 61 12.00 139.7 139.7 0.000 0.000 -
3.3960E-02 -3.9094E-05
92 93 184 12.00 139.8 140.2 -0.3488 0.3488 -
1682. -1.936
93 94 93 12.00 139.8 139.8 -7.8201E-02 7.8201E-02 -
1206. -1.389
98 95 94 12.00 139.7 139.8 -7.1579E-02 7.1579E-02 -
731.1 -0.8416
99 96 95 12.00 139.7 139.7 -1.8860E-02 1.8860E-02 -
200.4 -0.2307
100 71 96 12.00 139.7 139.7 0.000 0.000
0.000 0.000
102 80 54 12.00 139.7 139.7 0.000 0.000
3.3960E-02 3.9094E-05
121 130 10 4.00 124.4 124.4 4.5036E-02 4.5036E-02
66.90 0.5139
123 10 132 4.00 124.4 124.3 2.9770E-02 2.9770E-02
53.52 0.4111
124 184 124 6.00 140.2 135.4 4.792 1.952
531.8 1.800
125 132 129 4.00 124.3 124.3 1.7509E-02 1.7509E-02
40.14 0.3083
126 116 117 4.00 124.3 124.3 8.2703E-03 8.2703E-03
26.76 0.2055
127 115 11 4.00 124.4 124.3 2.9770E-02 2.9770E-02
53.52 0.4111
128 39 125 4.00 124.7 124.5 0.1074 0.1074
107.1 0.8224

Page 77 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 26 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
129 121 39 4.00 124.8 124.7 0.1184 0.1184
120.4 0.9253
130 125 113 4.00 124.5 124.5 8.3908E-02 8.3908E-02
93.67 0.7195
131 11 116 4.00 124.3 124.3 1.7509E-02 1.7509E-02
40.14 0.3083
132 126 120 4.00 124.3 124.3 2.2812E-03 2.2812E-03
13.38 0.1028
133 228 121 4.00 124.8 124.8 2.4399E-02 2.4399E-02
240.9 1.851
134 121 16 4.00 124.8 124.7 0.1184 0.1184
120.4 0.9253
135 127 131 4.00 124.5 124.5 8.3908E-02 8.3908E-02
93.67 0.7195
136 117 118 4.00 124.3 124.3 2.2812E-03 2.2812E-03
13.38 0.1028
137 16 127 4.00 124.7 124.5 0.1074 0.1074
107.1 0.8224
138 183 162 4.00 123.8 123.8 1.7441E-02 1.7441E-02
40.05 0.3076
139 155 171 4.00 123.9 123.8 6.2836E-02 6.2836E-02
80.10 0.6153
140 268 174 4.00 124.2 124.2 2.4292E-02 2.4292E-02
240.4 1.846
141 153 183 4.00 123.8 123.8 2.9663E-02 2.9663E-02
53.40 0.4102
142 174 161 4.00 124.2 124.1 0.1179 0.1179
120.2 0.9232
143 41 115 4.00 124.4 124.4 4.5036E-02 4.5036E-02
66.90 0.5139
144 96 185 12.00 139.7 139.7 8.0872E-03 8.0872E-03
200.4 0.2307
145 129 126 4.00 124.3 124.3 8.2703E-03 8.2703E-03
26.76 0.2055
146 93 18 6.00 139.8 136.8 3.006 1.587
475.5 1.609
147 113 130 4.00 124.5 124.4 6.3087E-02 6.3087E-02
80.28 0.6167
148 124 122 6.00 135.4 113.1 22.25 0.9524
531.8 1.800
149 182 166 4.00 124.0 123.9 8.3580E-02 8.3580E-02
93.46 0.7179
150 171 156 4.00 123.8 123.8 4.4815E-02 4.4815E-02
66.75 0.5127
151 175 153 4.00 123.8 123.8 4.4815E-02 4.4815E-02
66.75 0.5127
152 164 165 4.00 123.8 123.7 8.2321E-03 8.2321E-03
26.70 0.2051
153 163 155 4.00 124.0 123.9 8.3580E-02 8.3580E-02
93.46 0.7179
154 156 148 4.00 123.8 123.8 2.9663E-02 2.9663E-02
53.40 0.4102
155 149 163 4.00 124.1 124.0 0.1070 0.1070
106.8 0.8205
156 162 167 4.00 123.8 123.7 8.2321E-03 8.2321E-03
26.70 0.2051
157 148 164 4.00 123.8 123.8 1.7441E-02 1.7441E-02
40.05 0.3076

Page 78 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

158 216 195 4.00 119.1 119.1 6.0585E-02 6.0585E-02


78.54 0.6033
159 229 215 4.00 119.0 119.0 1.6792E-02 1.6792E-02
39.27 0.3016
160 196 188 4.00 119.1 119.0 4.3221E-02 4.3221E-02
65.45 0.5027
161 174 149 4.00 124.2 124.1 0.1179 0.1179
120.2 0.9232
162 165 172 4.00 123.7 123.7 2.2812E-03 2.2812E-03
13.35 0.1025
163 166 175 4.00 123.9 123.8 6.2836E-02 6.2836E-02
80.10 0.6153
164 167 186 4.00 123.7 123.7 2.2812E-03 2.2812E-03
13.35 0.1025
165 161 182 4.00 124.1 124.0 0.1070 0.1070
106.8 0.8205
166 191 214 4.00 119.4 119.4 2.3422E-02 2.3422E-02
235.7 1.810
167 214 213 4.00 119.4 119.3 0.1137 0.1137
117.8 0.9052
168 188 229 4.00 119.0 119.0 2.8610E-02 2.8610E-02
52.35 0.4022
169 228 191 6.00 124.8 119.4 5.356 0.1023
235.7 0.7977
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 27 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
170 233 216 4.00 119.2 119.1 8.0566E-02 8.0566E-02
91.63 0.7039
171 189 226 4.00 119.0 119.0 1.6792E-02 1.6792E-02
39.27 0.3016
172 230 196 4.00 119.1 119.1 6.0585E-02 6.0585E-02
78.54 0.6033
173 222 189 4.00 119.0 119.0 2.8610E-02 2.8610E-02
52.35 0.4022
174 190 233 4.00 119.3 119.2 0.1032 0.1032
104.7 0.8045
175 226 211 4.00 119.0 119.0 7.9422E-03 7.9422E-03
26.18 0.2011
176 195 222 4.00 119.1 119.0 4.3221E-02 4.3221E-02
65.45 0.5027
177 212 230 4.00 119.2 119.1 8.0566E-02 8.0566E-02
91.63 0.7039
178 213 212 4.00 119.3 119.2 0.1032 0.1032
104.7 0.8045
179 221 232 4.00 119.0 119.0 2.2049E-03 2.2049E-03
13.09 0.1005
180 211 231 4.00 119.0 119.0 2.2049E-03 2.2049E-03
13.09 0.1005
181 214 190 4.00 119.4 119.3 0.1137 0.1137
117.8 0.9052
182 235 203 4.00 118.6 118.5 6.0333E-02 6.0333E-02
78.35 0.6019
183 234 251 4.00 118.4 118.4 7.9041E-03 7.9041E-03
26.12 0.2006
184 215 221 4.00 119.0 119.0 7.9422E-03 7.9422E-03
26.18 0.2011
185 202 259 4.00 118.5 118.4 2.8458E-02 2.8458E-02
52.23 0.4012
186 243 248 4.00 118.9 118.8 0.1132 0.1132
117.6 0.9031

Page 79 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

187 250 243 4.00 118.9 118.9 2.3315E-02 2.3315E-02


235.1 1.806
188 238 239 4.00 118.4 118.4 7.9041E-03 7.9041E-03
26.12 0.2006
189 205 238 4.00 118.4 118.4 1.6754E-02 1.6754E-02
39.17 0.3009
190 259 234 4.00 118.4 118.4 1.6754E-02 1.6754E-02
39.17 0.3009
191 263 202 4.00 118.5 118.5 4.3045E-02 4.3045E-02
65.29 0.5016
192 246 235 4.00 118.6 118.6 8.0208E-02 8.0208E-02
91.42 0.7023
193 265 205 4.00 118.5 118.4 2.8458E-02 2.8458E-02
52.23 0.4012
194 251 254 4.00 118.4 118.4 2.1744E-03 2.1744E-03
13.06 0.1003
195 248 237 4.00 118.8 118.6 0.1027 0.1027
104.5 0.8026
196 240 263 4.00 118.6 118.5 6.0333E-02 6.0333E-02
78.35 0.6019
197 243 204 4.00 118.9 118.8 0.1132 0.1132
117.6 0.9031
198 237 240 4.00 118.6 118.6 8.0208E-02 8.0208E-02
91.42 0.7023
199 204 246 4.00 118.8 118.6 0.1027 0.1027
104.5 0.8026
200 239 252 4.00 118.4 118.4 2.1744E-03 2.1744E-03
13.06 0.1003
201 203 265 4.00 118.5 118.5 4.3045E-02 4.3045E-02
65.29 0.5016
202 268 250 6.00 124.2 118.9 5.355 0.1019
235.1 0.7959
203 184 87 12.00 140.2 140.4 -0.2164 0.2164 -
2214. -2.548
204 18 268 6.00 136.8 124.2 12.58 0.5148
475.5 1.609
205 273 198 4.00 118.4 118.4 4.3045E-02 4.3045E-02
65.27 0.5014
206 209 207 4.00 118.5 118.4 6.0265E-02 6.0265E-02
78.33 0.6017
207 217 219 4.00 118.4 118.3 1.6716E-02 1.6716E-02
39.16 0.3008
208 150 134 4.00 123.8 123.8 6.2798E-02 6.2798E-02
80.08 0.6151
209 133 264 6.00 136.7 124.2 12.58 0.5145
475.3 1.609
210 147 40 4.00 123.8 123.7 4.4823E-02 4.4823E-02
66.73 0.5126

Page 80 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 28 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
211 140 3 4.00 123.7 123.7 2.9625E-02 2.9625E-02
53.38 0.4101
212 40 160 4.00 123.7 123.7 2.9625E-02 2.9625E-02
53.38 0.4101
213 160 159 4.00 123.7 123.7 1.7441E-02 1.7441E-02
40.03 0.3075
214 8 145 4.00 124.0 123.9 0.1069 0.1069
106.8 0.8203
215 158 8 4.00 124.1 124.0 0.1178 0.1178
120.1 0.9229
216 157 150 4.00 123.9 123.8 8.3504E-02 8.3504E-02
93.43 0.7177
217 264 158 4.00 124.2 124.1 2.4292E-02 2.4292E-02
240.3 1.846
218 141 142 4.00 123.7 123.7 8.1940E-03 8.1940E-03
26.69 0.2050
219 3 141 4.00 123.7 123.7 1.7441E-02 1.7441E-02
40.03 0.3075
220 145 139 4.00 123.9 123.8 8.3504E-02 8.3504E-02
93.43 0.7177
221 154 144 4.00 123.7 123.7 2.2812E-03 2.2812E-03
13.34 0.1025
222 128 157 4.00 124.0 123.9 0.1069 0.1069
106.8 0.8203
223 159 154 4.00 123.7 123.7 8.1940E-03 8.1940E-03
26.69 0.2050
224 185 187 12.00 139.7 139.7 4.7150E-03 4.7150E-03
200.4 0.2307
225 143 151 6.00 134.9 112.7 22.25 0.9487
530.7 1.796
226 158 128 4.00 124.1 124.0 0.1178 0.1178
120.1 0.9229
227 142 137 4.00 123.7 123.7 2.2812E-03 2.2812E-03
13.34 0.1025
228 134 140 4.00 123.8 123.7 4.4823E-02 4.4823E-02
66.73 0.5126
229 139 147 4.00 123.8 123.8 6.2798E-02 6.2798E-02
80.08 0.6151
231 244 209 4.00 118.6 118.5 8.0200E-02 8.0200E-02
91.39 0.7020
232 94 133 6.00 139.8 136.7 3.006 1.586
475.3 1.609
233 260 273 4.00 118.5 118.4 6.0265E-02 6.0265E-02
78.33 0.6017
234 200 241 4.00 118.4 118.3 1.6716E-02 1.6716E-02
39.16 0.3008
235 201 244 4.00 118.7 118.6 0.1027 0.1027
104.5 0.8024
236 207 224 4.00 118.4 118.4 4.3007E-02 4.3007E-02
65.27 0.5014
237 199 257 4.00 118.8 118.8 2.3315E-02 2.3315E-02
235.0 1.806
238 257 261 4.00 118.8 118.7 0.1131 0.1131
117.5 0.9028
239 198 217 4.00 118.4 118.4 2.8458E-02 2.8458E-02
52.22 0.4011
240 264 199 6.00 124.2 118.8 5.355 0.1018
235.0 0.7956

Page 81 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

241 224 200 4.00 118.4 118.4 2.8465E-02 2.8465E-02


52.21 0.4011
242 236 266 4.00 118.3 118.3 2.2125E-03 2.2125E-03
13.05 0.1003
243 208 260 4.00 118.6 118.5 8.0170E-02 8.0170E-02
91.39 0.7020
244 267 223 4.00 118.3 118.3 2.2125E-03 2.2125E-03
13.05 0.1003
245 219 236 4.00 118.3 118.3 7.8735E-03 7.8735E-03
26.11 0.2006
246 261 208 4.00 118.7 118.6 0.1027 0.1027
104.5 0.8024
247 257 201 4.00 118.8 118.7 0.1131 0.1131
117.5 0.9028
248 241 267 3.00 118.3 118.3 2.3926E-02 2.3926E-02
26.11 0.3453
249 95 143 6.00 139.7 134.9 4.784 1.944
530.7 1.796
266 180 179 4.00 108.9 91.06 17.82 0.7811
200.4 1.539
269 187 123 12.00 139.7 139.6 1.0620E-02 1.0620E-02
200.4 0.2307
270 253 180 4.00 113.0 108.9 4.155 1.315
200.4 1.539
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 29 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
271 138 253 4.00 115.9 113.0 2.916 2.916
200.4 1.539

Page 82 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 30 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (psi G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
29 10 0.12434E+03 12.9600 13.3808 3.25 0.2700E+01
0.2788E+01
30 126 0.12430E+03 12.9600 13.3787 3.23 0.2700E+01
0.2787E+01
31 127 0.12450E+03 12.9600 13.3895 3.31 0.2700E+01
0.2789E+01
32 132 0.12431E+03 12.9600 13.3796 3.24 0.2700E+01
0.2787E+01
33 39 0.12459E+03 12.9600 13.3946 3.35 0.2700E+01
0.2791E+01
34 125 0.12450E+03 12.9600 13.3895 3.31 0.2700E+01
0.2789E+01
35 130 0.12437E+03 12.9600 13.3828 3.26 0.2700E+01
0.2788E+01
36 16 0.12459E+03 12.9600 13.3946 3.35 0.2700E+01
0.2791E+01
37 113 0.12443E+03 12.9600 13.3856 3.28 0.2700E+01
0.2789E+01
38 129 0.12430E+03 12.9600 13.3789 3.23 0.2700E+01
0.2787E+01
39 120 0.12430E+03 12.9600 13.3787 3.23 0.2700E+01
0.2787E+01
40 162 0.12375E+03 12.9600 13.3491 3.00 0.2700E+01
0.2781E+01
41 116 0.12430E+03 12.9600 13.3789 3.23 0.2700E+01
0.2787E+01
42 41 0.12437E+03 12.9600 13.3828 3.26 0.2700E+01
0.2788E+01
43 11 0.12431E+03 12.9600 13.3796 3.24 0.2700E+01
0.2787E+01
44 117 0.12430E+03 12.9600 13.3787 3.23 0.2700E+01
0.2787E+01
45 131 0.12443E+03 12.9600 13.3856 3.28 0.2700E+01
0.2789E+01
46 118 0.12430E+03 12.9600 13.3787 3.23 0.2700E+01
0.2787E+01
47 115 0.12434E+03 12.9600 13.3808 3.25 0.2700E+01
0.2788E+01
48 153 0.12378E+03 12.9600 13.3510 3.02 0.2700E+01
0.2781E+01
49 167 0.12374E+03 12.9600 13.3488 3.00 0.2700E+01
0.2781E+01
50 166 0.12387E+03 12.9600 13.3558 3.05 0.2700E+01
0.2782E+01
51 161 0.12404E+03 12.9600 13.3647 3.12 0.2700E+01
0.2784E+01
52 156 0.12378E+03 12.9600 13.3510 3.02 0.2700E+01
0.2781E+01
53 165 0.12374E+03 12.9600 13.3488 3.00 0.2700E+01
0.2781E+01
54 163 0.12394E+03 12.9600 13.3597 3.08 0.2700E+01
0.2783E+01
55 148 0.12376E+03 12.9600 13.3497 3.01 0.2700E+01
0.2781E+01
56 149 0.12404E+03 12.9600 13.3647 3.12 0.2700E+01
0.2784E+01
57 155 0.12387E+03 12.9600 13.3558 3.05 0.2700E+01
0.2782E+01

Page 83 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

58 182 0.12394E+03 12.9600 13.3597 3.08 0.2700E+01


0.2783E+01
59 175 0.12382E+03 12.9600 13.3529 3.03 0.2700E+01
0.2782E+01
60 186 0.12374E+03 12.9600 13.3489 3.00 0.2700E+01
0.2781E+01
61 183 0.12376E+03 12.9600 13.3497 3.01 0.2700E+01
0.2781E+01
62 172 0.12374E+03 12.9600 13.3489 3.00 0.2700E+01
0.2781E+01
63 171 0.12382E+03 12.9600 13.3529 3.03 0.2700E+01
0.2782E+01
64 164 0.12375E+03 12.9600 13.3491 3.00 0.2700E+01
0.2781E+01
65 222 0.11900E+03 12.9600 13.0905 1.01 0.2700E+01
0.2727E+01
66 196 0.11904E+03 12.9600 13.0924 1.02 0.2700E+01
0.2728E+01
67 188 0.11900E+03 12.9600 13.0905 1.01 0.2700E+01
0.2727E+01
68 215 0.11897E+03 12.9600 13.0886 0.99 0.2700E+01
0.2727E+01
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 31 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (psi G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
69 212 0.11916E+03 12.9600 13.0990 1.07 0.2700E+01
0.2729E+01
70 221 0.11896E+03 12.9600 13.0884 0.99 0.2700E+01
0.2727E+01
71 213 0.11925E+03 12.9600 13.1040 1.11 0.2700E+01
0.2730E+01
72 226 0.11897E+03 12.9600 13.0886 0.99 0.2700E+01
0.2727E+01
73 190 0.11925E+03 12.9600 13.1040 1.11 0.2700E+01
0.2730E+01
74 229 0.11898E+03 12.9600 13.0893 1.00 0.2700E+01
0.2727E+01
75 230 0.11909E+03 12.9600 13.0952 1.04 0.2700E+01
0.2728E+01
76 216 0.11909E+03 12.9600 13.0952 1.04 0.2700E+01
0.2728E+01
77 189 0.11898E+03 12.9600 13.0893 1.00 0.2700E+01
0.2727E+01
78 211 0.11896E+03 12.9600 13.0884 0.99 0.2700E+01
0.2727E+01
79 195 0.11904E+03 12.9600 13.0924 1.02 0.2700E+01
0.2728E+01
80 233 0.11916E+03 12.9600 13.0990 1.07 0.2700E+01
0.2729E+01
81 232 0.11896E+03 12.9600 13.0884 0.99 0.2700E+01
0.2727E+01
82 240 0.11853E+03 12.9600 13.0647 0.81 0.2700E+01
0.2722E+01
83 251 0.11841E+03 12.9600 13.0579 0.76 0.2700E+01
0.2720E+01
84 231 0.11896E+03 12.9600 13.0884 0.99 0.2700E+01
0.2727E+01
85 246 0.11860E+03 12.9600 13.0685 0.84 0.2700E+01
0.2723E+01
86 234 0.11841E+03 12.9600 13.0581 0.76 0.2700E+01
0.2720E+01

Page 84 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

87 204 0.11869E+03 12.9600 13.0735 0.88 0.2700E+01


0.2724E+01
88 237 0.11860E+03 12.9600 13.0685 0.84 0.2700E+01
0.2723E+01
89 202 0.11845E+03 12.9600 13.0600 0.77 0.2700E+01
0.2721E+01
90 248 0.11869E+03 12.9600 13.0735 0.88 0.2700E+01
0.2724E+01
91 263 0.11848E+03 12.9600 13.0619 0.79 0.2700E+01
0.2721E+01
92 235 0.11853E+03 12.9600 13.0647 0.81 0.2700E+01
0.2722E+01
93 254 0.11841E+03 12.9600 13.0579 0.76 0.2700E+01
0.2720E+01
94 259 0.11842E+03 12.9600 13.0588 0.76 0.2700E+01
0.2721E+01
95 265 0.11845E+03 12.9600 13.0600 0.77 0.2700E+01
0.2721E+01
96 252 0.11841E+03 12.9600 13.0579 0.76 0.2700E+01
0.2720E+01
97 238 0.11841E+03 12.9600 13.0581 0.76 0.2700E+01
0.2720E+01
98 239 0.11841E+03 12.9600 13.0579 0.76 0.2700E+01
0.2720E+01
99 203 0.11848E+03 12.9600 13.0619 0.79 0.2700E+01
0.2721E+01
100 205 0.11842E+03 12.9600 13.0588 0.76 0.2700E+01
0.2721E+01
101 236 0.11833E+03 12.9600 13.0537 0.72 0.2700E+01
0.2720E+01
102 273 0.11840E+03 12.9600 13.0577 0.75 0.2700E+01
0.2720E+01
103 224 0.11837E+03 12.9600 13.0557 0.74 0.2700E+01
0.2720E+01
104 198 0.11837E+03 12.9600 13.0557 0.74 0.2700E+01
0.2720E+01
105 208 0.11852E+03 12.9600 13.0643 0.80 0.2700E+01
0.2722E+01
106 219 0.11834E+03 12.9600 13.0539 0.72 0.2700E+01
0.2720E+01
107 260 0.11846E+03 12.9600 13.0605 0.78 0.2700E+01
0.2721E+01
108 244 0.11852E+03 12.9600 13.0643 0.80 0.2700E+01
0.2722E+01

Page 85 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 32 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (psi G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
109 207 0.11840E+03 12.9600 13.0577 0.75 0.2700E+01
0.2720E+01
110 200 0.11835E+03 12.9600 13.0545 0.73 0.2700E+01
0.2720E+01
111 201 0.11862E+03 12.9600 13.0693 0.84 0.2700E+01
0.2723E+01
112 266 0.11833E+03 12.9600 13.0537 0.72 0.2700E+01
0.2720E+01
113 267 0.11831E+03 12.9600 13.0525 0.71 0.2700E+01
0.2719E+01
114 261 0.11862E+03 12.9600 13.0693 0.84 0.2700E+01
0.2723E+01
115 241 0.11834E+03 12.9600 13.0539 0.72 0.2700E+01
0.2720E+01
116 217 0.11835E+03 12.9600 13.0545 0.73 0.2700E+01
0.2720E+01
117 209 0.11846E+03 12.9600 13.0605 0.78 0.2700E+01
0.2721E+01
118 223 0.11832E+03 12.9600 13.0528 0.72 0.2700E+01
0.2719E+01
119 8 0.12396E+03 12.9600 13.3606 3.09 0.2700E+01
0.2783E+01
120 147 0.12374E+03 12.9600 13.3488 3.00 0.2700E+01
0.2781E+01
121 159 0.12367E+03 12.9600 13.3449 2.97 0.2700E+01
0.2780E+01
122 160 0.12368E+03 12.9600 13.3456 2.98 0.2700E+01
0.2780E+01
123 40 0.12371E+03 12.9600 13.3468 2.98 0.2700E+01
0.2781E+01
124 128 0.12396E+03 12.9600 13.3606 3.09 0.2700E+01
0.2783E+01
125 139 0.12380E+03 12.9600 13.3516 3.02 0.2700E+01
0.2782E+01
126 145 0.12387E+03 12.9600 13.3555 3.05 0.2700E+01
0.2782E+01
127 157 0.12387E+03 12.9600 13.3555 3.05 0.2700E+01
0.2782E+01
128 140 0.12371E+03 12.9600 13.3468 2.98 0.2700E+01
0.2781E+01
129 3 0.12368E+03 12.9600 13.3456 2.98 0.2700E+01
0.2780E+01
130 142 0.12367E+03 12.9600 13.3447 2.97 0.2700E+01
0.2780E+01
131 137 0.12367E+03 12.9600 13.3447 2.97 0.2700E+01
0.2780E+01
132 134 0.12374E+03 12.9600 13.3488 3.00 0.2700E+01
0.2781E+01
133 150 0.12380E+03 12.9600 13.3516 3.02 0.2700E+01
0.2782E+01
134 154 0.12367E+03 12.9600 13.3447 2.97 0.2700E+01
0.2780E+01
135 144 0.12367E+03 12.9600 13.3447 2.97 0.2700E+01
0.2780E+01
136 141 0.12367E+03 12.9600 13.3449 2.97 0.2700E+01
0.2780E+01
149 151 0.11265E+03 509.2200 530.6904 4.22 0.2700E+01
0.2814E+01

Page 86 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

150 122 0.11314E+03 509.2200 531.8362 4.44 0.2700E+01


0.2820E+01
151 179 0.91058E+02 196.9920 200.3912 1.73 0.1080E+01
0.1099E+01

Note: A * after a value indicates that this is a specification


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 33 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW AT INLETS
--------------

Inlet Node Pressure Flowrate Equivalent K-factor


(psi G ) (US.g/min) (US.g/min , psi G )
------------------------------------------------------------
42 145.0 * 2690. 223.42

Note: A * after a value indicates that this is a specification


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 34 OF 38
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH GENERAL PRESSURE LOSS COMPONENT


---------------------------------------------

GPL Component Inlet Pressure Outlet Pressure Pressure Drop Flow rate
Label (psi G ) (psi G ) (psi ) (US.g/min)
--------------------------------------------------------------------------------------
1 139.640 115.948 23.6927 200.391
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 35 OF 38
---------------------------------------------------------------------------------------------------
--------------------

Materials Take-off
------------------
Pipe lengths
------------

ANSI B36.10 Sch.40 HDPE ANSI B36.10 Sch.20

Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length
Nom. Size Tot. Length
(inches ) (metres ) (inches ) (metres ) (inches ) (metres ) (inches ) (metres )
(inches ) (metres )
---------------------------------------------------------------------------------------------------
-------------------
3.000 1.800 6.000 618.3 12.000 5.000
4.000 287.5 12.000 804.9
6.000 1750.
12.000 109.0

Page 87 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 36 OF 38
---------------------------------------------------------------------------------------------------
--------------------

Materials Take-off
------------------
Nozzles
-------

Type K-Factor Number


---- -------- ------
Condensate Tank Nozzle 1.2000 108
Mushroom Nozzle 50.0000 2
Foam Box 21.0000 1
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 37 OF 38
---------------------------------------------------------------------------------------------------
--------------------

Materials Take Off


------------------
Fittings
--------

Fitting
Nominal
Size Fitting Type
(inches ) 1 2 3 4 5 6 7 8 9
-------------------------------------------------------------------------

3.000 0 0 0 1 0 0 0 0 0
4.000 0 2 0 108 0 0 0 0 0
6.000 4 30 0 58 27 0 0 0 0
12.000 12 1 0 29 11 0 0 0 1

Fitting Types are :


1 -- 45 Deg Elbow 4 -- Tee or Cross 7 -- Non-Return Valve
2 -- 90 Deg Standard Elbow 5 -- Gate Valve 8 -- Ball Valve
3 -- 90 Deg Long Radius Elbow 6 -- Swing Check Valve 9 -- Butterfly Valve

All fittings are as specified by user - no additional fittings have been generated automatically.

The supply demand graph is not available for the network without pump
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 38 OF 38
---------------------------------------------------------------------------------------------------
--------------------

IMPORTANT NOTICE
----------------

Your attention is drawn to the need to maintain adequate standards. SUNRISE SYSTEMS Ltd
has itself taken steps to ensure that this program produces valid results when properly
used. Users are reminded of their responsibilities in the application of program results
and, in particular, you should ensure that pertinent output documents are examined and
approved by qualified staff prior to use.

Page 88 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 39 OF 38
---------------------------------------------------------------------------------------------------
--------------------

COMMENTS
--------

Analysis Converged in 4 Iterations


1

====================================================================================================
====================

Firefighting Hydraulic Calculation for WASCO EW PLANT


Condensate tanks Case - Scenario 1
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
====================

Page 89 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

Annex D: Condensate tank dike -foam case

Page 90 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

55

====================================================================================================
====================

PIPENET SPRAY/SPRINKLER MODULE

====================================================================================================
====================

VERSION 1.8

====================================================================================================
====================

Results for : Firefighting Hydraulic Calculation for WASCO EW PLANT


Condensate tanks dike foam Case - Scenario 2
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
====================

Page 91 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

14:19 on 15-Feb-2020
1

LIST OF CONTENTS
================

Page
----

Control Information......................................... 1

Fluid System................................................ 1

Design Information.......................................... 2

Pipe Configuration.......................................... 4

Nozzle Configuration........................................ 14

Orifice Plates.............................................. 18

Designed Diameters & Flowrates.............................. 19

Flow in Pipes............................................... 26

Flow through Nozzles........................................ 32

Orifice Plate Results....................................... 36

Flow at Inlets.............................................. 37

Materials Take Off.......................................... 38

Important Notice............................................ 41

Comments.................................................... 42

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 1 OF 42
---------------------------------------------------------------------------------------------------
--------------------

CONTROL INFORMATION
-------------------
Convergence accuracy = 1.00E-03
Maximum no. of iterations = 50
Elevation Check Tolerance = 0.50 metres
Warnings Control Option = 0
****** Diagnostic level = 2

FLUID SYSTEM
------------

Fluid Class = 1 (Liquid )


Density = 998.2 kg/cu.m
Viscosity = 2.419 lb/ft hr

Page 92 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 2 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGN INFORMATION
------------------

Waterspray System

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Sch.20 Not Lined
10 -- HDPE Not Lined

Design to NFPA 2013 Rules


Using the Hazen-Williams Equation

Velocity Pressure Model: NFPA formula

Pressure loss at entrance: Ignore

Pressure loss at exit: Ignore


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 3 OF 42
---------------------------------------------------------------------------------------------------
--------------------

AVAILABLE PIPE SIZES AND MAXIMUM VELOCITIES USED FOR PIPE SIZING
----------------------------------------------------------------

ANSI B36.10 Sch.40 ANSI B36.10 Sch.20 HDPE


Not lined Not lined Not lined

Nom.Bore Act.Diam Max.Vel. Nom.Bore Act.Diam Max.Vel. Nom.Bore


Act.Diam Max.Vel.
(inches ) (inches ) (m/sec ) (inches ) (inches ) (m/sec ) (inches )
(inches ) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------

0.6250 0.6220 6.0000 0.6250 Not acceptable 0.6250 Not


acceptable
0.7500 0.8240 6.0000 0.7500 Not acceptable 0.7500 Not
acceptable
1.0000 1.0490 6.0000 1.0000 Not acceptable 1.0000 Not
acceptable
1.2500 1.3800 6.0000 1.2500 Not acceptable 1.2500 Not
acceptable
1.5000 1.6100 6.0000 1.5000 Not acceptable 1.5000 Not
acceptable
2.0000 2.0670 6.0000 2.0000 Not acceptable 2.0000 Not
acceptable
2.5000 2.4690 6.0000 2.5000 Not acceptable 2.5000 Not
acceptable
3.0000 3.0680 6.0000 3.0000 Not acceptable 3.0000 Not
acceptable
3.5000 3.5480 6.0000 3.5000 Not acceptable 3.5000 Not
acceptable
4.0000 4.0260 6.0000 4.0000 Not acceptable 4.0000 Not
acceptable
5.0000 5.0470 6.0000 5.0000 Not acceptable 5.0000 Not
acceptable
6.0000 6.0650 6.0000 6.0000 Not acceptable 6.0000
5.1000 6.0000

Page 93 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

8.0000 7.9810 6.0000 8.0000 8.1250 6.0000 8.0000


6.4000 6.0000
10.0000 10.0200 6.0000 10.0000 10.2500 6.0000 10.0000
8.0000 6.0000
12.0000 11.9380 6.0000 12.0000 12.2500 6.0000 12.0000
10.4000 6.0000
14.0000 13.1240 6.0000 14.0000 13.3760 6.0000 13.9999 Not
acceptable
16.0000 15.0000 6.0000 16.0000 15.3760 6.0000 16.0000 Not
acceptable
18.0000 16.8760 6.0000 18.0000 17.3760 6.0000 18.0000 Not
acceptable
20.0000 18.8120 6.0000 20.0000 19.2500 6.0000 20.0000 Not
acceptable
24.0000 22.6240 6.0000 24.0000 23.2500 6.0000 23.9999 Not
acceptable
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 4 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
2 43 5 12.00 2.000 0.000 150.0
0.000
3 19 9 12.00 0.5000 0.000 120.0
0.000
4 5 32 12.00 3.000 1.0000 150.0
0.000
5 23 7 12.00 1.0000 1.0000 120.0
0.000
6 27 228 6.000 8.500 8.000 120.0
9.144
7 131 41 3.000 1.800 0.000 120.0
4.572
8 4 20 12.00 5.600 0.000 150.0
0.000
9 21 13 6.000 21.20 0.000 120.0
0.000
10 13 14 6.000 122.0 0.000 120.0
37.19
11 15 14 6.000 122.5 0.000 120.0
37.49
12 35 28 6.000 111.3 0.000 120.0
37.49
13 15 31 6.000 27.00 0.000 120.0
4.267
14 14 12 6.000 121.0 0.000 120.0
60.05
15 13 17 6.000 101.3 0.000 120.0
94.18
16 48 12 6.000 119.0 0.000 120.0
22.56
17 22 42 12.00 4.000 0.000 150.0
0.000
18 9 4 12.00 43.70 -2.500 150.0
0.000
19 42 43 12.00 3.000 -1.0000 150.0
0.000
20 29 6 6.000 13.50 0.000 120.0
0.000
21 7 19 12.00 3.000 0.000 120.0
0.000
22 24 25 6.000 24.00 0.000 120.0
0.000
23 25 26 6.000 45.20 0.000 120.0

Page 94 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

0.000
24 26 34 6.000 63.00 0.000 120.0
0.000
25 34 35 6.000 100.00 0.000 120.0
0.000
26 21 28 6.000 73.50 0.000 120.0
0.000
27 28 24 6.000 54.80 0.000 120.0
18.29
28 29 14 6.000 141.0 0.000 120.0
28.35
29 6 136 12.00 109.0 0.000 120.0
18.29
30 31 24 6.000 113.0 0.000 120.0
55.78
31 136 15 6.000 141.0 0.000 120.0
37.49
33 36 37 6.000 79.50 0.000 150.0
0.000
34 33 38 6.000 78.00 0.000 150.0
0.000
35 34 30 6.000 63.00 0.000 150.0
0.000
36 135 37 6.000 5.500 0.000 150.0
0.000
37 30 135 6.000 100.00 0.000 150.0
0.000
38 30 33 6.000 66.30 0.000 150.0
0.000
39 35 135 6.000 63.00 0.000 150.0
0.000
40 38 36 6.000 159.0 0.000 150.0
0.000
41 20 22 12.00 39.00 0.000 150.0
0.000
42 20 6 6.000 4.000 0.000 150.0
0.000
43 44 23 12.00 1.0000 0.000 120.0
0.000
50 17 50 6.000 2.500 0.000 120.0
9.144
51 50 48 6.000 9.500 0.000 120.0
10.06
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 5 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
55 87 27 6.000 30.30 2.000 120.0
24.08
56 53 80 12.00 21.50 0.000 150.0
14.12
57 54 55 12.00 78.90 0.000 150.0
15.53
58 55 75 12.00 56.20 0.000 150.0
43.76
59 56 57 12.00 1.0000 -1.0000 150.0
6.117
60 58 57 12.00 1.0000 0.000 150.0
0.000
61 59 58 12.00 1.0000 -1.0000 150.0
6.117
62 60 59 12.00 6.500 0.000 150.0
14.12

Page 95 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

63 52 83 12.00 11.20 0.000 150.0


19.06
64 61 62 12.00 1.0000 -1.0000 150.0
6.117
65 62 63 12.00 1.0000 0.000 150.0
0.000
66 63 64 12.00 1.0000 1.0000 150.0
6.117
67 64 65 12.00 6.500 0.000 150.0
15.53
73 65 70 12.00 40.30 0.000 150.0
14.12
74 70 60 12.00 60.30 0.000 150.0
15.53
75 32 87 12.00 34.30 0.000 150.0
56.47
76 71 72 12.00 1.0000 -1.0000 150.0
6.117
77 72 73 12.00 1.0000 0.000 150.0
0.000
78 73 74 12.00 1.0000 1.0000 150.0
6.117
79 56 75 12.00 52.50 0.000 150.0
31.06
80 74 75 12.00 6.700 0.000 150.0
0.000
81 83 77 12.00 11.30 0.000 150.0
0.000
82 77 53 12.00 21.50 0.000 150.0
29.65
83 78 52 12.00 12.60 0.000 150.0
14.12
84 97 78 12.00 25.50 0.000 150.0
0.000
85 97 61 12.00 33.00 0.000 150.0
14.12
92 184 93 12.00 10.000 0.000 150.0
14.12
93 93 94 12.00 10.000 0.000 150.0
14.12
98 94 95 12.00 9.000 0.000 150.0
14.12
99 95 96 12.00 24.40 0.000 150.0
42.35
100 96 71 12.00 45.00 0.000 150.0
0.000
102 80 54 12.00 78.90 0.000 150.0
15.53
121 130 10 3.000 1.800 0.000 120.0
4.572
123 10 132 3.000 1.800 0.000 120.0
4.572
124 184 124 6.000 30.30 2.000 120.0
24.08
125 132 129 3.000 1.800 0.000 120.0
4.572
126 116 117 3.000 1.800 0.000 120.0
4.572
127 115 11 3.000 1.800 0.000 120.0
4.572
128 39 125 3.000 1.800 0.000 120.0
4.572
129 121 39 3.000 0.9000 0.000 120.0
4.572
130 125 113 3.000 1.800 0.000 120.0
4.572
131 11 116 3.000 1.800 0.000 120.0
4.572
132 126 120 3.000 1.800 0.000 120.0
4.572

Page 96 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 6 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
133 228 121 4.000 0.5000 0.000 120.0
0.000
134 121 16 3.000 0.9000 0.000 120.0
4.572
135 127 131 3.000 1.800 0.000 120.0
4.572
136 117 118 3.000 1.800 0.000 120.0
4.572
137 16 127 3.000 1.800 0.000 120.0
4.572
138 183 162 3.000 1.800 0.000 120.0
4.572
139 155 171 3.000 1.800 0.000 120.0
4.572
140 268 174 4.000 0.5000 0.000 120.0
0.000
141 153 183 3.000 1.800 0.000 120.0
4.572
142 174 161 3.000 0.9000 0.000 120.0
4.572
143 41 115 3.000 1.800 0.000 120.0
4.572
144 96 185 12.00 14.50 0.000 150.0
14.12
145 129 126 3.000 1.800 0.000 120.0
4.572
146 93 18 6.000 30.30 2.000 120.0
24.08
147 113 130 3.000 1.800 0.000 120.0
4.572
148 124 122 6.000 18.00 14.50 120.0
8.534
149 182 166 3.000 1.800 0.000 120.0
4.572
150 171 156 3.000 1.800 0.000 120.0
4.572
151 175 153 3.000 1.800 0.000 120.0
4.572
152 164 165 3.000 1.800 0.000 120.0
4.572
153 163 155 3.000 1.800 0.000 120.0
4.572
154 156 148 3.000 1.800 0.000 120.0
4.572
155 149 163 3.000 1.800 0.000 120.0
4.572
156 162 167 3.000 1.800 0.000 120.0
4.572
157 148 164 3.000 1.800 0.000 120.0
4.572
158 216 195 3.000 1.800 0.000 120.0
4.572
159 229 215 3.000 1.800 0.000 120.0
4.572
160 196 188 3.000 1.800 0.000 120.0
4.572
161 174 149 3.000 0.9000 0.000 120.0
4.572
162 165 172 3.000 1.800 0.000 120.0

Page 97 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

4.572
163 166 175 3.000 1.800 0.000 120.0
4.572
164 167 186 3.000 1.800 0.000 120.0
4.572
165 161 182 3.000 1.800 0.000 120.0
4.572
166 191 214 4.000 0.5000 0.000 120.0
0.000
167 214 213 3.000 0.9000 0.000 120.0
4.572
168 188 229 3.000 1.800 0.000 120.0
4.572
169 228 191 6.000 3.700 3.700 120.0
9.144
170 233 216 3.000 1.800 0.000 120.0
4.572
171 189 226 3.000 1.800 0.000 120.0
4.572
172 230 196 3.000 1.800 0.000 120.0
4.572
173 222 189 3.000 1.800 0.000 120.0
4.572
174 190 233 3.000 1.800 0.000 120.0
4.572
175 226 211 3.000 1.800 0.000 120.0
4.572
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 7 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
176 195 222 3.000 1.800 0.000 120.0
4.572
177 212 230 3.000 1.800 0.000 120.0
4.572
178 213 212 3.000 1.800 0.000 120.0
4.572
179 221 232 3.000 1.800 0.000 120.0
4.572
180 211 231 3.000 1.800 0.000 120.0
4.572
181 214 190 3.000 0.9000 0.000 120.0
4.572
182 235 203 3.000 1.800 0.000 120.0
4.572
183 234 251 3.000 1.800 0.000 120.0
4.572
184 215 221 3.000 1.800 0.000 120.0
4.572
185 202 259 3.000 1.800 0.000 120.0
4.572
186 243 248 3.000 0.9000 0.000 120.0
4.572
187 250 243 4.000 0.5000 0.000 120.0
0.000
188 238 239 3.000 1.800 0.000 120.0
4.572
189 205 238 3.000 1.800 0.000 120.0
4.572
190 259 234 3.000 1.800 0.000 120.0
4.572
191 263 202 3.000 1.800 0.000 120.0
4.572

Page 98 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

192 246 235 3.000 1.800 0.000 120.0


4.572
193 265 205 3.000 1.800 0.000 120.0
4.572
194 251 254 3.000 1.800 0.000 120.0
4.572
195 248 237 3.000 1.800 0.000 120.0
4.572
196 240 263 3.000 1.800 0.000 120.0
4.572
197 243 204 3.000 0.9000 0.000 120.0
4.572
198 237 240 3.000 1.800 0.000 120.0
4.572
199 204 246 3.000 1.800 0.000 120.0
4.572
200 239 252 3.000 1.800 0.000 120.0
4.572
201 203 265 3.000 1.800 0.000 120.0
4.572
202 268 250 4.000 3.700 3.700 120.0
6.096
203 87 184 12.00 9.000 0.000 150.0
0.000
204 18 268 6.000 8.500 8.000 120.0
9.144
205 273 198 3.000 1.800 0.000 120.0
4.572
206 209 207 3.000 1.800 0.000 120.0
4.572
207 217 219 3.000 1.800 0.000 120.0
4.572
208 150 134 3.000 1.800 0.000 120.0
4.572
209 133 264 6.000 8.500 8.000 120.0
9.144
210 147 40 3.000 1.800 0.000 120.0
4.572
211 140 3 3.000 1.800 0.000 120.0
4.572
212 40 160 3.000 1.800 0.000 120.0
4.572
213 160 159 3.000 1.800 0.000 120.0
4.572
214 8 145 3.000 1.800 0.000 120.0
4.572
215 158 8 3.000 0.9000 0.000 120.0
4.572
216 157 150 3.000 1.800 0.000 120.0
4.572
217 264 158 4.000 0.5000 0.000 120.0
0.000
218 141 142 3.000 1.800 0.000 120.0
4.572

Page 99 of 131
Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 8 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
219 3 141 3.000 1.800 0.000 120.0
4.572
220 145 139 3.000 1.800 0.000 120.0
4.572
221 154 144 3.000 1.800 0.000 120.0
4.572
222 128 157 3.000 1.800 0.000 120.0
4.572
223 159 154 3.000 1.800 0.000 120.0
4.572
224 185 187 12.00 2.500 2.000 150.0
0.000
225 143 151 6.000 18.00 14.50 120.0
8.534
226 158 128 3.000 0.9000 0.000 120.0
4.572
227 142 137 3.000 1.800 0.000 120.0
4.572
228 134 140 3.000 1.800 0.000 120.0
4.572
229 139 147 3.000 1.800 0.000 120.0
4.572
231 244 209 3.000 1.800 0.000 120.0
4.572
232 94 133 6.000 30.30 2.000 120.0
24.08
233 260 273 3.000 1.800 0.000 120.0
4.572
234 200 241 3.000 1.800 0.000 120.0
4.572
235 201 244 3.000 1.800 0.000 120.0
4.572
236 207 224 3.000 1.800 0.000 120.0
4.572
237 199 257 4.000 0.5000 0.000 120.0
0.000
238 257 261 3.000 0.9000 0.000 120.0
4.572
239 198 217 3.000 1.800 0.000 120.0
4.572
240 264 199 6.000 3.700 3.700 120.0
9.144
241 224 200 3.000 1.800 0.000 120.0
4.572
242 236 266 3.000 1.800 0.000 120.0
4.572
243 208 260 3.000 1.800 0.000 120.0
4.572
244 267 223 3.000 1.800 0.000 120.0
4.572
245 219 236 3.000 1.800 0.000 120.0
4.572
246 261 208 3.000 1.800 0.000 120.0
4.572
247 257 201 3.000 0.9000 0.000 120.0
4.572
248 241 267 3.000 1.800 0.000 120.0
4.572
249 95 143 6.000 30.30 2.000 120.0

Page 100 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

24.08
265 192 88 12.00 20.00 0.000 120.0
43.55
266 88 279 12.00 8.000 0.000 120.0
0.000
267 123 138 12.00 9.000 0.000 120.0
0.000
268 187 192 12.00 10.000 0.000 120.0
0.000
269 138 179 12.00 9.000 0.000 120.0
0.000
270 179 180 12.00 9.000 0.000 120.0
0.000
271 180 181 12.00 9.000 0.000 120.0
0.000
272 181 253 12.00 4.500 0.000 120.0
0.000
273 88 280 12.00 9.000 0.000 120.0
0.000
274 253 256 12.00 9.000 0.000 120.0
0.000
275 256 258 12.00 9.000 0.000 120.0
0.000
276 258 262 12.00 9.000 0.000 120.0
0.000
277 262 269 12.00 9.000 0.000 120.0
0.000
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 9 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE CONFIGURATION
------------------

Pipe Label Input Node Output Node Nom.Bore Length Elevation C


Fitt.eq.lnth
(inches ) (metres ) (metres ) Factor
(metres )
---------------------------------------------------------------------------------------------------
------
278 269 270 12.00 9.000 0.000 120.0
0.000
279 270 271 12.00 9.000 0.000 120.0
0.000
280 271 272 12.00 9.000 0.000 120.0
0.000
281 272 274 12.00 4.500 0.000 120.0
0.000
282 274 275 12.00 9.000 0.000 120.0
0.000
283 275 276 12.00 9.000 0.000 120.0
0.000
284 276 277 12.00 9.000 0.000 120.0
0.000
285 277 278 12.00 9.000 0.000 120.0
0.000
286 278 255 12.00 4.500 0.000 120.0
0.000
287 279 123 12.00 4.500 0.000 120.0
0.000
288 280 281 12.00 9.000 0.000 120.0
0.000
289 281 282 12.00 9.000 0.000 120.0
0.000
290 282 283 12.00 9.000 0.000 120.0
0.000
291 283 285 12.00 9.000 0.000 120.0
0.000
292 284 255 12.00 9.000 0.000 120.0
0.000
293 285 284 12.00 9.000 0.000 120.0
0.000

Page 101 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
6 1 x 4 9.144
7 1 x 4 4.572
10 4 x 2 4.267 2 x 4 9.144 2 x 5 0.9144
11 4 x 4 9.144 1 x 5 0.9144
12 4 x 4 9.144 1 x 5 0.9144
13 1 x 2 4.267
14 2 x 1 2.134 6 x 4 9.144 1 x 5 0.9144
15 10 x 4 9.144 3 x 5 0.9144
16 2 x 1 2.134 2 x 4 9.144
27 2 x 4 9.144
28 3 x 4 9.144 1 x 5 0.9144
29 1 x 4 18.29
30 6 x 4 9.144 1 x 5 0.9144
31 4 x 4 9.144 1 x 5 0.9144
50 1 x 4 9.144
51 1 x 4 9.144 1 x 5 0.9144
55 5 x 2 4.267 3 x 5 0.9144
56 1 x 4 14.12
57 1 x 4 14.12 1 x 5 1.412
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 10 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
58 3 x 4 14.12 1 x 5 1.412
59 2 x 1 3.059
61 2 x 1 3.059
62 1 x 4 14.12
63 1 x 4 14.12 1 x 9 4.941
64 2 x 1 3.059
66 2 x 1 3.059
67 1 x 4 14.12 1 x 5 1.412
73 1 x 4 14.12
74 1 x 4 14.12 1 x 5 1.412
75 4 x 4 14.12
76 2 x 1 3.059
78 2 x 1 3.059
79 2 x 4 14.12 2 x 5 1.412
82 2 x 4 14.12 1 x 5 1.412
83 1 x 4 14.12
85 1 x 4 14.12
92 1 x 4 14.12
93 1 x 4 14.12
98 1 x 4 14.12
99 3 x 4 14.12
102 1 x 4 14.12 1 x 5 1.412
121 1 x 4 4.572
123 1 x 4 4.572
124 5 x 2 4.267 3 x 5 0.9144
125 1 x 4 4.572
126 1 x 4 4.572
127 1 x 4 4.572
128 1 x 4 4.572
129 1 x 4 4.572
130 1 x 4 4.572
131 1 x 4 4.572
132 1 x 4 4.572

Page 102 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

134 1 x 4 4.572
135 1 x 4 4.572
136 1 x 4 4.572
137 1 x 4 4.572
138 1 x 4 4.572
139 1 x 4 4.572
141 1 x 4 4.572
142 1 x 4 4.572
143 1 x 4 4.572
144 1 x 4 14.12
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 11 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
145 1 x 4 4.572
146 5 x 2 4.267 3 x 5 0.9144
147 1 x 4 4.572
148 2 x 2 4.267
149 1 x 4 4.572
150 1 x 4 4.572
151 1 x 4 4.572
152 1 x 4 4.572
153 1 x 4 4.572
154 1 x 4 4.572
155 1 x 4 4.572
156 1 x 4 4.572
157 1 x 4 4.572
158 1 x 4 4.572
159 1 x 4 4.572
160 1 x 4 4.572
161 1 x 4 4.572
162 1 x 4 4.572
163 1 x 4 4.572
164 1 x 4 4.572
165 1 x 4 4.572
167 1 x 4 4.572
168 1 x 4 4.572
169 1 x 4 9.144
170 1 x 4 4.572
171 1 x 4 4.572
172 1 x 4 4.572
173 1 x 4 4.572
174 1 x 4 4.572
175 1 x 4 4.572
176 1 x 4 4.572
177 1 x 4 4.572
178 1 x 4 4.572
179 1 x 4 4.572
180 1 x 4 4.572
181 1 x 4 4.572
182 1 x 4 4.572
183 1 x 4 4.572
184 1 x 4 4.572
185 1 x 4 4.572
186 1 x 4 4.572
188 1 x 4 4.572
189 1 x 4 4.572

Page 103 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 12 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
190 1 x 4 4.572
191 1 x 4 4.572
192 1 x 4 4.572
193 1 x 4 4.572
194 1 x 4 4.572
195 1 x 4 4.572
196 1 x 4 4.572
197 1 x 4 4.572
198 1 x 4 4.572
199 1 x 4 4.572
200 1 x 4 4.572
201 1 x 4 4.572
202 1 x 4 6.096
204 1 x 4 9.144
205 1 x 4 4.572
206 1 x 4 4.572
207 1 x 4 4.572
208 1 x 4 4.572
209 1 x 4 9.144
210 1 x 4 4.572
211 1 x 4 4.572
212 1 x 4 4.572
213 1 x 4 4.572
214 1 x 4 4.572
215 1 x 4 4.572
216 1 x 4 4.572
218 1 x 4 4.572
219 1 x 4 4.572
220 1 x 4 4.572
221 1 x 4 4.572
222 1 x 4 4.572
223 1 x 4 4.572
225 2 x 2 4.267
226 1 x 4 4.572
227 1 x 4 4.572
228 1 x 4 4.572
229 1 x 4 4.572
231 1 x 4 4.572
232 5 x 2 4.267 3 x 5 0.9144
233 1 x 4 4.572
234 1 x 4 4.572
235 1 x 4 4.572
236 1 x 4 4.572

Page 104 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 13 OF 42
---------------------------------------------------------------------------------------------------
--------------------

PIPE FITTINGS
-------------

Pipe Number x Type Equivalent Length


Label (metres )
---------------------------------------------------------------------------------------------------
-
238 1 x 4 4.572
239 1 x 4 4.572
240 1 x 4 9.144
241 1 x 4 4.572
242 1 x 4 4.572
243 1 x 4 4.572
244 1 x 4 4.572
245 1 x 4 4.572
246 1 x 4 4.572
247 1 x 4 4.572
248 1 x 4 4.572
249 5 x 2 4.267 3 x 5 0.9144
265 4 x 2 9.331 3 x 5 2.074

Fitting types are :


1 -- 45 Deg Elbow
2 -- 90 Deg Standard Elbow
3 -- 90 Deg Long Radius Elbow
4 -- Tee or Cross (Flow Turned Thro 90 Deg)
5 -- Gate Valve
6 -- Swing Check Valve
7 -- Non-Return Valve
8 -- Ball Valve
9 -- Butterfly Valve

Page 105 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 14 OF 42
---------------------------------------------------------------------------------------------------
--------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (psi G ) (psi G )
---------------------------------------------------------------------------------------------------
29 10 2 1.8000 13.2300 0.29000E+02 0.17400E+03
30 126 2 1.8000 13.2300 0.29000E+02 0.17400E+03
31 127 2 1.8000 13.2300 0.29000E+02 0.17400E+03
32 132 2 1.8000 13.2300 0.29000E+02 0.17400E+03
33 39 2 1.8000 13.2300 0.29000E+02 0.17400E+03
34 125 2 1.8000 13.2300 0.29000E+02 0.17400E+03
35 130 2 1.8000 13.2300 0.29000E+02 0.17400E+03
36 16 2 1.8000 13.2300 0.29000E+02 0.17400E+03
37 113 2 1.8000 13.2300 0.29000E+02 0.17400E+03
38 129 2 1.8000 13.2300 0.29000E+02 0.17400E+03
39 120 2 1.8000 13.2300 0.29000E+02 0.17400E+03
40 162 2 1.8000 13.2300 0.29000E+02 0.17400E+03
41 116 2 1.8000 13.2300 0.29000E+02 0.17400E+03
42 41 2 1.8000 13.2300 0.29000E+02 0.17400E+03
43 11 2 1.8000 13.2300 0.29000E+02 0.17400E+03
44 117 2 1.8000 13.2300 0.29000E+02 0.17400E+03
45 131 2 1.8000 13.2300 0.29000E+02 0.17400E+03
46 118 2 1.8000 13.2300 0.29000E+02 0.17400E+03
47 115 2 1.8000 13.2300 0.29000E+02 0.17400E+03
48 153 2 1.8000 13.2300 0.29000E+02 0.17400E+03
49 167 2 1.8000 13.2300 0.29000E+02 0.17400E+03
50 166 2 1.8000 13.2300 0.29000E+02 0.17400E+03
51 161 2 1.8000 13.2300 0.29000E+02 0.17400E+03
52 156 2 1.8000 13.2300 0.29000E+02 0.17400E+03
53 165 2 1.8000 13.2300 0.29000E+02 0.17400E+03
54 163 2 1.8000 13.2300 0.29000E+02 0.17400E+03
55 148 2 1.8000 13.2300 0.29000E+02 0.17400E+03
56 149 2 1.8000 13.2300 0.29000E+02 0.17400E+03
57 155 2 1.8000 13.2300 0.29000E+02 0.17400E+03
58 182 2 1.8000 13.2300 0.29000E+02 0.17400E+03
59 175 2 1.8000 13.2300 0.29000E+02 0.17400E+03
60 186 2 1.8000 13.2300 0.29000E+02 0.17400E+03
61 183 2 1.8000 13.2300 0.29000E+02 0.17400E+03
62 172 2 1.8000 13.2300 0.29000E+02 0.17400E+03
63 171 2 1.8000 13.2300 0.29000E+02 0.17400E+03
64 164 2 1.8000 13.2300 0.29000E+02 0.17400E+03
65 222 2 1.8000 13.2300 0.29000E+02 0.17400E+03
66 196 2 1.8000 13.2300 0.29000E+02 0.17400E+03
67 188 2 1.8000 13.2300 0.29000E+02 0.17400E+03
68 215 2 1.8000 13.2300 0.29000E+02 0.17400E+03
69 212 2 1.8000 13.2300 0.29000E+02 0.17400E+03
70 221 2 1.8000 13.2300 0.29000E+02 0.17400E+03

Page 106 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 15 OF 42
---------------------------------------------------------------------------------------------------
--------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (psi G ) (psi G )
---------------------------------------------------------------------------------------------------
71 213 2 1.8000 13.2300 0.29000E+02 0.17400E+03
72 226 2 1.8000 13.2300 0.29000E+02 0.17400E+03
73 190 2 1.8000 13.2300 0.29000E+02 0.17400E+03
74 229 2 1.8000 13.2300 0.29000E+02 0.17400E+03
75 230 2 1.8000 13.2300 0.29000E+02 0.17400E+03
76 216 2 1.8000 13.2300 0.29000E+02 0.17400E+03
77 189 2 1.8000 13.2300 0.29000E+02 0.17400E+03
78 211 2 1.8000 13.2300 0.29000E+02 0.17400E+03
79 195 2 1.8000 13.2300 0.29000E+02 0.17400E+03
80 233 2 1.8000 13.2300 0.29000E+02 0.17400E+03
81 232 2 1.8000 13.2300 0.29000E+02 0.17400E+03
82 240 2 1.8000 13.2300 0.29000E+02 0.17400E+03
83 251 2 1.8000 13.2300 0.29000E+02 0.17400E+03
84 231 2 1.8000 13.2300 0.29000E+02 0.17400E+03
85 246 2 1.8000 13.2300 0.29000E+02 0.17400E+03
86 234 2 1.8000 13.2300 0.29000E+02 0.17400E+03
87 204 2 1.8000 13.2300 0.29000E+02 0.17400E+03
88 237 2 1.8000 13.2300 0.29000E+02 0.17400E+03
89 202 2 1.8000 13.2300 0.29000E+02 0.17400E+03
90 248 2 1.8000 13.2300 0.29000E+02 0.17400E+03
91 263 2 1.8000 13.2300 0.29000E+02 0.17400E+03
92 235 2 1.8000 13.2300 0.29000E+02 0.17400E+03
93 254 2 1.8000 13.2300 0.29000E+02 0.17400E+03
94 259 2 1.8000 13.2300 0.29000E+02 0.17400E+03
95 265 2 1.8000 13.2300 0.29000E+02 0.17400E+03
96 252 2 1.8000 13.2300 0.29000E+02 0.17400E+03
97 238 2 1.8000 13.2300 0.29000E+02 0.17400E+03
98 239 2 1.8000 13.2300 0.29000E+02 0.17400E+03
99 203 2 1.8000 13.2300 0.29000E+02 0.17400E+03
100 205 2 1.8000 13.2300 0.29000E+02 0.17400E+03
101 236 2 1.8000 13.2300 0.29000E+02 0.17400E+03
102 273 2 1.8000 13.2300 0.29000E+02 0.17400E+03
103 224 2 1.8000 13.2300 0.29000E+02 0.17400E+03
104 198 2 1.8000 13.2300 0.29000E+02 0.17400E+03
105 208 2 1.8000 13.2300 0.29000E+02 0.17400E+03
106 219 2 1.8000 13.2300 0.29000E+02 0.17400E+03
107 260 2 1.8000 13.2300 0.29000E+02 0.17400E+03
108 244 2 1.8000 13.2300 0.29000E+02 0.17400E+03
109 207 2 1.8000 13.2300 0.29000E+02 0.17400E+03
110 200 2 1.8000 13.2300 0.29000E+02 0.17400E+03
111 201 2 1.8000 13.2300 0.29000E+02 0.17400E+03
112 266 2 1.8000 13.2300 0.29000E+02 0.17400E+03

Page 107 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 16 OF 42
---------------------------------------------------------------------------------------------------
--------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (psi G ) (psi G )
---------------------------------------------------------------------------------------------------
113 267 2 1.8000 13.2300 0.29000E+02 0.17400E+03
114 261 2 1.8000 13.2300 0.29000E+02 0.17400E+03
115 241 2 1.8000 13.2300 0.29000E+02 0.17400E+03
116 217 2 1.8000 13.2300 0.29000E+02 0.17400E+03
117 209 2 1.8000 13.2300 0.29000E+02 0.17400E+03
118 223 2 1.8000 13.2300 0.29000E+02 0.17400E+03
119 8 2 1.8000 13.2300 0.29000E+02 0.17400E+03
120 147 2 1.8000 13.2300 0.29000E+02 0.17400E+03
121 159 2 1.8000 13.2300 0.29000E+02 0.17400E+03
122 160 2 1.8000 13.2300 0.29000E+02 0.17400E+03
123 40 2 1.8000 13.2300 0.29000E+02 0.17400E+03
124 128 2 1.8000 13.2300 0.29000E+02 0.17400E+03
125 139 2 1.8000 13.2300 0.29000E+02 0.17400E+03
126 145 2 1.8000 13.2300 0.29000E+02 0.17400E+03
127 157 2 1.8000 13.2300 0.29000E+02 0.17400E+03
128 140 2 1.8000 13.2300 0.29000E+02 0.17400E+03
129 3 2 1.8000 13.2300 0.29000E+02 0.17400E+03
130 142 2 1.8000 13.2300 0.29000E+02 0.17400E+03
131 137 2 1.8000 13.2300 0.29000E+02 0.17400E+03
132 134 2 1.8000 13.2300 0.29000E+02 0.17400E+03
133 150 2 1.8000 13.2300 0.29000E+02 0.17400E+03
134 154 2 1.8000 13.2300 0.29000E+02 0.17400E+03
135 144 2 1.8000 13.2300 0.29000E+02 0.17400E+03
136 141 2 1.8000 13.2300 0.29000E+02 0.17400E+03
149 151 3 48.5000 509.2200 0.29000E+02 0.17400E+03
150 122 3 48.5000 509.2200 0.29000E+02 0.17400E+03
151 123 5 10.0000 103.0700 0.58000E+02 0.17400E+03
152 138 5 10.0000 103.0700 0.58000E+02 0.17400E+03
153 179 5 10.0000 103.0700 0.58000E+02 0.17400E+03
154 180 5 10.0000 103.0700 0.58000E+02 0.17400E+03
155 181 5 10.0000 103.0700 0.58000E+02 0.17400E+03
156 253 5 10.0000 103.0700 0.58000E+02 0.17400E+03
157 256 5 10.0000 103.0700 0.58000E+02 0.17400E+03
158 258 5 10.0000 103.0700 0.58000E+02 0.17400E+03
159 262 5 10.0000 103.0700 0.58000E+02 0.17400E+03
160 269 5 10.0000 103.0700 0.58000E+02 0.17400E+03
161 270 5 10.0000 103.0700 0.58000E+02 0.17400E+03
162 271 5 10.0000 103.0700 0.58000E+02 0.17400E+03
163 272 5 10.0000 103.0700 0.58000E+02 0.17400E+03
164 274 5 10.0000 103.0700 0.58000E+02 0.17400E+03
165 275 5 10.0000 103.0700 0.58000E+02 0.17400E+03
166 276 5 10.0000 103.0700 0.58000E+02 0.17400E+03

Page 108 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 17 OF 42
---------------------------------------------------------------------------------------------------
--------------------

NOZZLE CONFIGURATION
--------------------

Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (US.g/min) (psi G ) (psi G )
---------------------------------------------------------------------------------------------------
167 277 5 10.0000 103.0700 0.58000E+02 0.17400E+03
168 278 5 10.0000 103.0700 0.58000E+02 0.17400E+03
169 255 5 10.0000 103.0700 0.58000E+02 0.17400E+03
170 284 5 10.0000 103.0700 0.58000E+02 0.17400E+03
171 285 5 10.0000 103.0700 0.58000E+02 0.17400E+03
172 283 5 10.0000 103.0700 0.58000E+02 0.17400E+03
173 282 5 10.0000 103.0700 0.58000E+02 0.17400E+03
174 281 5 10.0000 103.0700 0.58000E+02 0.17400E+03
175 280 5 10.0000 103.0700 0.58000E+02 0.17400E+03
176 279 5 10.0000 103.0700 0.58000E+02 0.17400E+03

Nozzle types are :


2 -- Condensate Tank Nozzle
3 -- Mushroom Nozzle
5 -- Foam Maker
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 18 OF 42
---------------------------------------------------------------------------------------------------
--------------------

ORIFICE PLATES
--------------

Plate Pipe Pressure Drop Diameter


Label Label (psi ) (inches )
---------------------------------------------------------------------
X05/0 268 0.21750E+02

Page 109 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 19 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
2 43 5 2697.2761 10 10.4000 12.0000 *
3 19 9 2697.2761 10 10.4000 12.0000 *
4 5 32 2697.2761 10 10.4000 12.0000 *
5 23 7 2697.2759 9 12.2500 12.0000 *
6 27 228 0.0000 3 6.0650 6.0000 *
7 131 41 0.0000 3 3.0680 3.0000 *
8 4 20 2697.2761 10 10.4000 12.0000 *
9 21 13 0.0744 3 6.0650 6.0000 *
10 13 14 0.0494 3 6.0650 6.0000 *
11 15 14 -0.0130 3 6.0650 6.0000 *
12 35 28 0.2597 3 6.0650 6.0000 *
13 15 31 0.0744 3 6.0650 6.0000 *
14 14 12 -0.0250 3 6.0650 6.0000 *
15 13 17 0.0250 3 6.0650 6.0000 *
16 48 12 0.0250 3 6.0650 6.0000 *
17 22 42 2697.2761 10 10.4000 12.0000 *
18 9 4 2697.2761 10 10.4000 12.0000 *
19 42 43 2697.2761 10 10.4000 12.0000 *
20 29 6 0.0614 3 6.0650 6.0000 *
21 7 19 2697.2759 9 12.2500 12.0000 *
22 24 25 0.2597 3 6.0650 6.0000 *
23 25 26 0.2597 3 6.0650 6.0000 *
24 26 34 0.2597 3 6.0650 6.0000 *
25 34 35 0.1553 3 6.0650 6.0000 *
26 21 28 -0.0744 3 6.0650 6.0000 *
27 28 24 0.1853 3 6.0650 6.0000 *
28 29 14 -0.0614 3 6.0650 6.0000 *
29 6 136 0.0614 3 11.9380 12.0000 *
30 31 24 0.0744 3 6.0650 6.0000 *
31 136 15 0.0614 3 6.0650 6.0000 *
33 36 37 0.0709 10 5.1000 6.0000 *
34 33 38 0.0709 10 5.1000 6.0000 *
35 34 30 0.1044 10 5.1000 6.0000 *
36 135 37 -0.0709 10 5.1000 6.0000 *
37 30 135 0.0335 10 5.1000 6.0000 *
38 30 33 0.0709 10 5.1000 6.0000 *
39 35 135 -0.1044 10 5.1000 6.0000 *
40 38 36 0.0709 10 5.1000 6.0000 *
41 20 22 2697.2761 10 10.4000 12.0000 *

Page 110 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 20 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
42 20 6 -0.0000 10 5.1000 6.0000 *
43 44 23 2697.2759 9 12.2500 12.0000 *
50 17 50 0.0250 3 6.0650 6.0000 *
51 50 48 0.0250 3 6.0650 6.0000 *
55 87 27 0.0000 3 6.0650 6.0000 *
56 53 80 0.0340 10 10.4000 12.0000 *
57 54 55 0.0340 10 10.4000 12.0000 *
58 55 75 0.0340 10 10.4000 12.0000 *
59 56 57 0.0340 10 10.4000 12.0000 *
60 58 57 -0.0340 10 10.4000 12.0000 *
61 59 58 -0.0340 10 10.4000 12.0000 *
62 60 59 -0.0340 10 10.4000 12.0000 *
63 52 83 0.0340 10 10.4000 12.0000 *
64 61 62 -0.0340 10 10.4000 12.0000 *
65 62 63 -0.0340 10 10.4000 12.0000 *
66 63 64 -0.0340 10 10.4000 12.0000 *
67 64 65 -0.0340 10 10.4000 12.0000 *
73 65 70 -0.0340 10 10.4000 12.0000 *
74 70 60 -0.0340 10 10.4000 12.0000 *
75 32 87 2697.2761 10 10.4000 12.0000 *
76 71 72 0.0000 10 10.4000 12.0000 *
77 72 73 0.0000 10 10.4000 12.0000 *
78 73 74 0.0000 10 10.4000 12.0000 *
79 56 75 -0.0340 10 10.4000 12.0000 *
80 74 75 0.0000 10 10.4000 12.0000 *
81 83 77 0.0340 10 10.4000 12.0000 *
82 77 53 0.0340 10 10.4000 12.0000 *
83 78 52 0.0340 10 10.4000 12.0000 *
84 97 78 0.0340 10 10.4000 12.0000 *
85 97 61 -0.0340 10 10.4000 12.0000 *
92 184 93 2697.2761 10 10.4000 12.0000 *
93 93 94 2697.2761 10 10.4000 12.0000 *
98 94 95 2697.2761 10 10.4000 12.0000 *
99 95 96 2697.2761 10 10.4000 12.0000 *
100 96 71 0.0000 10 10.4000 12.0000 *
102 80 54 0.0340 10 10.4000 12.0000 *
121 130 10 0.0000 3 3.0680 3.0000 *
123 10 132 0.0000 3 3.0680 3.0000 *
124 184 124 0.0000 3 6.0650 6.0000 *

Page 111 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 21 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
125 132 129 0.0000 3 3.0680 3.0000 *
126 116 117 0.0000 3 3.0680 3.0000 *
127 115 11 0.0000 3 3.0680 3.0000 *
128 39 125 0.0000 3 3.0680 3.0000 *
129 121 39 0.0000 3 3.0680 3.0000 *
130 125 113 0.0000 3 3.0680 3.0000 *
131 11 116 0.0000 3 3.0680 3.0000 *
132 126 120 0.0000 3 3.0680 3.0000 *
133 228 121 0.0000 3 4.0260 4.0000 *
134 121 16 0.0000 3 3.0680 3.0000 *
135 127 131 0.0000 3 3.0680 3.0000 *
136 117 118 0.0000 3 3.0680 3.0000 *
137 16 127 0.0000 3 3.0680 3.0000 *
138 183 162 0.0000 3 3.0680 3.0000 *
139 155 171 0.0000 3 3.0680 3.0000 *
140 268 174 0.0000 3 4.0260 4.0000 *
141 153 183 0.0000 3 3.0680 3.0000 *
142 174 161 0.0000 3 3.0680 3.0000 *
143 41 115 0.0000 3 3.0680 3.0000 *
144 96 185 2697.2761 10 10.4000 12.0000 *
145 129 126 0.0000 3 3.0680 3.0000 *
146 93 18 0.0000 3 6.0650 6.0000 *
147 113 130 0.0000 3 3.0680 3.0000 *
148 124 122 0.0000 3 6.0650 6.0000 *
149 182 166 0.0000 3 3.0680 3.0000 *
150 171 156 0.0000 3 3.0680 3.0000 *
151 175 153 0.0000 3 3.0680 3.0000 *
152 164 165 0.0000 3 3.0680 3.0000 *
153 163 155 0.0000 3 3.0680 3.0000 *
154 156 148 0.0000 3 3.0680 3.0000 *
155 149 163 0.0000 3 3.0680 3.0000 *
156 162 167 0.0000 3 3.0680 3.0000 *
157 148 164 0.0000 3 3.0680 3.0000 *
158 216 195 0.0000 3 3.0680 3.0000 *
159 229 215 0.0000 3 3.0680 3.0000 *
160 196 188 0.0000 3 3.0680 3.0000 *
161 174 149 0.0000 3 3.0680 3.0000 *
162 165 172 0.0000 3 3.0680 3.0000 *
163 166 175 0.0000 3 3.0680 3.0000 *

Page 112 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 22 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
164 167 186 0.0000 3 3.0680 3.0000 *
165 161 182 0.0000 3 3.0680 3.0000 *
166 191 214 0.0000 3 4.0260 4.0000 *
167 214 213 0.0000 3 3.0680 3.0000 *
168 188 229 0.0000 3 3.0680 3.0000 *
169 228 191 0.0000 3 6.0650 6.0000 *
170 233 216 0.0000 3 3.0680 3.0000 *
171 189 226 0.0000 3 3.0680 3.0000 *
172 230 196 0.0000 3 3.0680 3.0000 *
173 222 189 0.0000 3 3.0680 3.0000 *
174 190 233 0.0000 3 3.0680 3.0000 *
175 226 211 0.0000 3 3.0680 3.0000 *
176 195 222 0.0000 3 3.0680 3.0000 *
177 212 230 0.0000 3 3.0680 3.0000 *
178 213 212 0.0000 3 3.0680 3.0000 *
179 221 232 0.0000 3 3.0680 3.0000 *
180 211 231 0.0000 3 3.0680 3.0000 *
181 214 190 0.0000 3 3.0680 3.0000 *
182 235 203 0.0000 3 3.0680 3.0000 *
183 234 251 0.0000 3 3.0680 3.0000 *
184 215 221 0.0000 3 3.0680 3.0000 *
185 202 259 0.0000 3 3.0680 3.0000 *
186 243 248 0.0000 3 3.0680 3.0000 *
187 250 243 0.0000 3 4.0260 4.0000 *
188 238 239 0.0000 3 3.0680 3.0000 *
189 205 238 0.0000 3 3.0680 3.0000 *
190 259 234 0.0000 3 3.0680 3.0000 *
191 263 202 0.0000 3 3.0680 3.0000 *
192 246 235 0.0000 3 3.0680 3.0000 *
193 265 205 0.0000 3 3.0680 3.0000 *
194 251 254 0.0000 3 3.0680 3.0000 *
195 248 237 0.0000 3 3.0680 3.0000 *
196 240 263 0.0000 3 3.0680 3.0000 *
197 243 204 0.0000 3 3.0680 3.0000 *
198 237 240 0.0000 3 3.0680 3.0000 *
199 204 246 0.0000 3 3.0680 3.0000 *
200 239 252 0.0000 3 3.0680 3.0000 *
201 203 265 0.0000 3 3.0680 3.0000 *
202 268 250 0.0000 3 4.0260 4.0000 *

Page 113 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 23 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
203 87 184 2697.2761 10 10.4000 12.0000 *
204 18 268 0.0000 3 6.0650 6.0000 *
205 273 198 0.0000 3 3.0680 3.0000 *
206 209 207 0.0000 3 3.0680 3.0000 *
207 217 219 0.0000 3 3.0680 3.0000 *
208 150 134 0.0000 3 3.0680 3.0000 *
209 133 264 0.0000 3 6.0650 6.0000 *
210 147 40 0.0000 3 3.0680 3.0000 *
211 140 3 0.0000 3 3.0680 3.0000 *
212 40 160 0.0000 3 3.0680 3.0000 *
213 160 159 0.0000 3 3.0680 3.0000 *
214 8 145 0.0000 3 3.0680 3.0000 *
215 158 8 0.0000 3 3.0680 3.0000 *
216 157 150 0.0000 3 3.0680 3.0000 *
217 264 158 0.0000 3 4.0260 4.0000 *
218 141 142 0.0000 3 3.0680 3.0000 *
219 3 141 0.0000 3 3.0680 3.0000 *
220 145 139 0.0000 3 3.0680 3.0000 *
221 154 144 0.0000 3 3.0680 3.0000 *
222 128 157 0.0000 3 3.0680 3.0000 *
223 159 154 0.0000 3 3.0680 3.0000 *
224 185 187 2697.2761 10 10.4000 12.0000 *
225 143 151 0.0000 3 6.0650 6.0000 *
226 158 128 0.0000 3 3.0680 3.0000 *
227 142 137 0.0000 3 3.0680 3.0000 *
228 134 140 0.0000 3 3.0680 3.0000 *
229 139 147 0.0000 3 3.0680 3.0000 *
231 244 209 0.0000 3 3.0680 3.0000 *
232 94 133 0.0000 3 6.0650 6.0000 *
233 260 273 0.0000 3 3.0680 3.0000 *
234 200 241 0.0000 3 3.0680 3.0000 *
235 201 244 0.0000 3 3.0680 3.0000 *
236 207 224 0.0000 3 3.0680 3.0000 *
237 199 257 0.0000 3 4.0260 4.0000 *
238 257 261 0.0000 3 3.0680 3.0000 *
239 198 217 0.0000 3 3.0680 3.0000 *
240 264 199 0.0000 3 6.0650 6.0000 *
241 224 200 0.0000 3 3.0680 3.0000 *
242 236 266 0.0000 3 3.0680 3.0000 *

Page 114 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 24 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (US.g/min) Type (inches ) (inches ) Group
------------------------------------------------------------------------------------------
243 208 260 0.0000 3 3.0680 3.0000 *
244 267 223 0.0000 3 3.0680 3.0000 *
245 219 236 0.0000 3 3.0680 3.0000 *
246 261 208 0.0000 3 3.0680 3.0000 *
247 257 201 0.0000 3 3.0680 3.0000 *
248 241 267 0.0000 3 3.0680 3.0000 *
249 95 143 0.0000 3 6.0650 6.0000 *
265 192 88 2697.2759 9 12.2500 12.0000 *
266 88 279 1378.9541 9 12.2500 12.0000 *
267 123 138 1171.3867 9 12.2500 12.0000 *
268 187 192 2697.2759 9 12.2500 12.0000 *
269 138 179 1067.6219 9 12.2500 12.0000 *
270 179 180 963.8700 9 12.2500 12.0000 *
271 180 181 860.1282 9 12.2500 12.0000 *
272 181 253 756.3942 9 12.2500 12.0000 *
273 88 280 1318.3219 9 12.2500 12.0000 *
274 253 256 652.6610 9 12.2500 12.0000 *
275 256 258 548.9319 9 12.2500 12.0000 *
276 258 262 445.2050 9 12.2500 12.0000 *
277 262 269 341.4792 9 12.2500 12.0000 *
278 269 270 237.7539 9 12.2500 12.0000 *
279 270 271 134.0282 9 12.2500 12.0000 *
280 271 272 30.3019 9 12.2500 12.0000 *
281 272 274 -73.4247 9 12.2500 12.0000 *
282 274 275 -177.1507 9 12.2500 12.0000 *
283 275 276 -280.8762 9 12.2500 12.0000 *
284 276 277 -384.6015 9 12.2500 12.0000 *
285 277 278 -488.3275 9 12.2500 12.0000 *
286 278 255 -592.0552 9 12.2500 12.0000 *
287 279 123 1275.1672 9 12.2500 12.0000 *
288 280 281 1214.5322 9 12.2500 12.0000 *
289 281 282 1110.7596 9 12.2500 12.0000 *
290 282 283 1007.0009 9 12.2500 12.0000 *
291 283 285 903.2534 9 12.2500 12.0000 *
292 284 255 695.7827 9 12.2500 12.0000 *
293 285 284 799.5148 9 12.2500 12.0000 *

A * indicates that this is a SET diameter


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 25 OF 42
---------------------------------------------------------------------------------------------------
--------------------

DESIGNED DIAMETERS & FLOWRATES


------------------------------

Pipe Materials are :


Pipe Type Lining Type Thickness(inches )

3 -- ANSI B36.10 Sch.40 Not Lined


9 -- ANSI B36.10 Sch.20 Not Lined
10 -- HDPE Not Lined

Page 115 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 26 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
2 43 5 12.00 145.1 145.0 6.9290E-02 6.9290E-02
2697. 3.105
3 19 9 12.00 143.5 143.4 2.6184E-02 2.6184E-02
2697. 3.105
4 5 32 12.00 145.0 143.5 1.524 0.1040
2697. 3.105
5 23 7 12.00 145.0 143.5 1.443 2.3553E-02
2697. 2.238
6 27 228 6.00 137.5 126.2 11.36 1.8120E-05
0.000 0.000
7 131 41 3.00 126.2 126.2 0.000 0.000
0.000 0.000
8 4 20 12.00 145.5 145.3 0.1940 0.1940
2697. 3.105
9 21 13 6.00 145.3 145.3 0.000 0.000
7.4407E-02 2.5186E-04
10 13 14 6.00 145.3 145.3 0.000 0.000
4.9371E-02 1.6712E-04
11 15 14 6.00 145.3 145.3 0.000 0.000 -
1.3030E-02 -4.4104E-05
12 35 28 6.00 145.3 145.3 0.000 0.000
0.2597 8.7908E-04
13 15 31 6.00 145.3 145.3 0.000 0.000
7.4407E-02 2.5186E-04
14 14 12 6.00 145.3 145.3 0.000 0.000 -
2.5036E-02 -8.4745E-05
15 13 17 6.00 145.3 145.3 0.000 0.000
2.5036E-02 8.4745E-05
16 48 12 6.00 145.3 145.3 0.000 0.000
2.5036E-02 8.4745E-05
17 22 42 12.00 143.9 143.8 0.1386 0.1386
2697. 3.105
18 9 4 12.00 143.4 145.5 -2.035 1.514
2697. 3.105
19 42 43 12.00 143.8 145.1 -1.316 0.1039
2697. 3.105
20 29 6 6.00 145.3 145.3 0.000 0.000
6.1378E-02 2.0776E-04
21 7 19 12.00 143.5 143.5 7.0786E-02 7.0786E-02
2697. 2.238
22 24 25 6.00 145.3 145.3 0.000 0.000
0.2597 8.7908E-04
23 25 26 6.00 145.3 145.3 0.000 0.000
0.2597 8.7908E-04
24 26 34 6.00 145.3 145.3 0.000 0.000
0.2597 8.7908E-04
25 34 35 6.00 145.3 145.3 0.000 0.000
0.1553 5.2572E-04
26 21 28 6.00 145.3 145.3 0.000 0.000 -
7.4407E-02 -2.5186E-04
27 28 24 6.00 145.3 145.3 0.000 0.000
0.1853 6.2722E-04
28 29 14 6.00 145.3 145.3 0.000 0.000 -
6.1378E-02 -2.0776E-04
29 6 136 12.00 145.3 145.3 0.000 0.000
6.1378E-02 5.3623E-05
30 31 24 6.00 145.3 145.3 0.000 0.000
7.4407E-02 2.5186E-04

Page 116 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

31 136 15 6.00 145.3 145.3 0.000 0.000


6.1378E-02 2.0776E-04
33 36 37 6.00 145.3 145.3 0.000 0.000
7.0865E-02 3.3923E-04
34 33 38 6.00 145.3 145.3 0.000 0.000
7.0865E-02 3.3923E-04
35 34 30 6.00 145.3 145.3 0.000 0.000
0.1044 4.9973E-04
36 135 37 6.00 145.3 145.3 0.000 0.000 -
7.0865E-02 -3.3923E-04
37 30 135 6.00 145.3 145.3 0.000 0.000
3.3527E-02 1.6049E-04
38 30 33 6.00 145.3 145.3 0.000 0.000
7.0865E-02 3.3923E-04
39 35 135 6.00 145.3 145.3 0.000 0.000 -
0.1044 -4.9973E-04
40 38 36 6.00 145.3 145.3 0.000 0.000
7.0865E-02 3.3923E-04
41 20 22 12.00 145.3 143.9 1.351 1.351
2697. 3.105
42 20 6 6.00 145.3 145.3 0.000 0.000 -
2.2453E-09 -1.0749E-11
43 44 23 12.00 145.0 145.0 2.3605E-02 2.3605E-02
2697. 2.238
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 27 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
50 17 50 6.00 145.3 145.3 0.000 0.000
2.5036E-02 8.4745E-05
51 50 48 6.00 145.3 145.3 0.000 0.000
2.5036E-02 8.4745E-05
55 87 27 6.00 140.4 137.5 2.840 0.000
0.000 0.000
56 53 80 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
57 54 55 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
58 55 75 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
59 56 57 12.00 135.3 136.7 -1.420 2.4080E-05
3.3960E-02 3.9094E-05
60 58 57 12.00 136.7 136.7 0.000 0.000 -
3.3960E-02 -3.9094E-05
61 59 58 12.00 135.3 136.7 -1.420 2.4080E-05 -
3.3960E-02 -3.9094E-05
62 60 59 12.00 135.3 135.3 0.000 0.000 -
3.3960E-02 -3.9094E-05
63 52 83 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
64 61 62 12.00 135.3 136.7 -1.420 2.4080E-05 -
3.3960E-02 -3.9094E-05
65 62 63 12.00 136.7 136.7 0.000 0.000 -
3.3960E-02 -3.9094E-05
66 63 64 12.00 136.7 135.3 1.420 2.4080E-05 -
3.3960E-02 -3.9094E-05
67 64 65 12.00 135.3 135.3 0.000 0.000 -
3.3960E-02 -3.9094E-05
73 65 70 12.00 135.3 135.3 0.000 0.000 -
3.3960E-02 -3.9094E-05
74 70 60 12.00 135.3 135.3 0.000 0.000 -
3.3960E-02 -3.9094E-05

Page 117 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

75 32 87 12.00 143.5 140.4 3.145 3.145


2697. 3.105
76 71 72 12.00 135.3 136.7 -1.420 2.4080E-05
0.000 0.000
77 72 73 12.00 136.7 136.7 0.000 0.000
0.000 0.000
78 73 74 12.00 136.7 135.3 1.420 2.4080E-05
0.000 0.000
79 56 75 12.00 135.3 135.3 0.000 0.000 -
3.3960E-02 -3.9094E-05
80 74 75 12.00 135.3 135.3 0.000 0.000
0.000 0.000
81 83 77 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
82 77 53 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
83 78 52 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
84 97 78 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
85 97 61 12.00 135.3 135.3 0.000 0.000 -
3.3960E-02 -3.9094E-05
92 184 93 12.00 140.1 139.2 0.8356 0.8356
2697. 3.105
93 93 94 12.00 139.2 138.4 0.8356 0.8356
2697. 3.105
98 94 95 12.00 138.4 137.6 0.8010 0.8010
2697. 3.105
99 95 96 12.00 137.6 135.3 2.313 2.313
2697. 3.105
100 96 71 12.00 135.3 135.3 0.000 0.000
0.000 0.000
102 80 54 12.00 135.3 135.3 0.000 0.000
3.3960E-02 3.9094E-05
121 130 10 3.00 126.2 126.2 0.000 0.000
0.000 0.000
123 10 132 3.00 126.2 126.2 0.000 0.000
0.000 0.000
124 184 124 6.00 140.1 137.2 2.840 0.000
0.000 0.000
125 132 129 3.00 126.2 126.2 0.000 0.000
0.000 0.000
126 116 117 3.00 126.2 126.2 0.000 0.000
0.000 0.000
127 115 11 3.00 126.2 126.2 0.000 0.000
0.000 0.000
128 39 125 3.00 126.2 126.2 0.000 0.000
0.000 0.000

Page 118 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 28 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
129 121 39 3.00 126.2 126.2 0.000 0.000
0.000 0.000
130 125 113 3.00 126.2 126.2 0.000 0.000
0.000 0.000
131 11 116 3.00 126.2 126.2 0.000 0.000
0.000 0.000
132 126 120 3.00 126.2 126.2 0.000 0.000
0.000 0.000
133 228 121 4.00 126.2 126.2 0.000 0.000
0.000 0.000
134 121 16 3.00 126.2 126.2 0.000 0.000
0.000 0.000
135 127 131 3.00 126.2 126.2 0.000 0.000
0.000 0.000
136 117 118 3.00 126.2 126.2 0.000 0.000
0.000 0.000
137 16 127 3.00 126.2 126.2 0.000 0.000
0.000 0.000
138 183 162 3.00 125.0 125.0 0.000 0.000
0.000 0.000
139 155 171 3.00 125.0 125.0 0.000 0.000
0.000 0.000
140 268 174 4.00 125.0 125.0 0.000 0.000
0.000 0.000
141 153 183 3.00 125.0 125.0 0.000 0.000
0.000 0.000
142 174 161 3.00 125.0 125.0 0.000 0.000
0.000 0.000
143 41 115 3.00 126.2 126.2 0.000 0.000
0.000 0.000
144 96 185 12.00 135.3 134.3 0.9916 0.9916
2697. 3.105
145 129 126 3.00 126.2 126.2 0.000 0.000
0.000 0.000
146 93 18 6.00 139.2 136.4 2.840 1.6451E-05
0.000 0.000
147 113 130 3.00 126.2 126.2 0.000 0.000
0.000 0.000
148 124 122 6.00 137.2 116.6 20.59 0.000
0.000 0.000
149 182 166 3.00 125.0 125.0 0.000 0.000
0.000 0.000
150 171 156 3.00 125.0 125.0 0.000 0.000
0.000 0.000
151 175 153 3.00 125.0 125.0 0.000 0.000
0.000 0.000
152 164 165 3.00 125.0 125.0 0.000 0.000
0.000 0.000
153 163 155 3.00 125.0 125.0 0.000 0.000
0.000 0.000
154 156 148 3.00 125.0 125.0 0.000 0.000
0.000 0.000
155 149 163 3.00 125.0 125.0 0.000 0.000
0.000 0.000
156 162 167 3.00 125.0 125.0 0.000 0.000
0.000 0.000
157 148 164 3.00 125.0 125.0 0.000 0.000
0.000 0.000

Page 119 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

158 216 195 3.00 120.9 120.9 0.000 0.000


0.000 0.000
159 229 215 3.00 120.9 120.9 0.000 0.000
0.000 0.000
160 196 188 3.00 120.9 120.9 0.000 0.000
0.000 0.000
161 174 149 3.00 125.0 125.0 0.000 0.000
0.000 0.000
162 165 172 3.00 125.0 125.0 0.000 0.000
0.000 0.000
163 166 175 3.00 125.0 125.0 0.000 0.000
0.000 0.000
164 167 186 3.00 125.0 125.0 0.000 0.000
0.000 0.000
165 161 182 3.00 125.0 125.0 0.000 0.000
0.000 0.000
166 191 214 4.00 120.9 120.9 0.000 0.000
0.000 0.000
167 214 213 3.00 120.9 120.9 0.000 0.000
0.000 0.000
168 188 229 3.00 120.9 120.9 0.000 0.000
0.000 0.000
169 228 191 6.00 126.2 120.9 5.253 3.0041E-05
0.000 0.000
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 29 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
170 233 216 3.00 120.9 120.9 0.000 0.000
0.000 0.000
171 189 226 3.00 120.9 120.9 0.000 0.000
0.000 0.000
172 230 196 3.00 120.9 120.9 0.000 0.000
0.000 0.000
173 222 189 3.00 120.9 120.9 0.000 0.000
0.000 0.000
174 190 233 3.00 120.9 120.9 0.000 0.000
0.000 0.000
175 226 211 3.00 120.9 120.9 0.000 0.000
0.000 0.000
176 195 222 3.00 120.9 120.9 0.000 0.000
0.000 0.000
177 212 230 3.00 120.9 120.9 0.000 0.000
0.000 0.000
178 213 212 3.00 120.9 120.9 0.000 0.000
0.000 0.000
179 221 232 3.00 120.9 120.9 0.000 0.000
0.000 0.000
180 211 231 3.00 120.9 120.9 0.000 0.000
0.000 0.000
181 214 190 3.00 120.9 120.9 0.000 0.000
0.000 0.000
182 235 203 3.00 119.8 119.8 0.000 0.000
0.000 0.000
183 234 251 3.00 119.8 119.8 0.000 0.000
0.000 0.000
184 215 221 3.00 120.9 120.9 0.000 0.000
0.000 0.000
185 202 259 3.00 119.8 119.8 0.000 0.000
0.000 0.000
186 243 248 3.00 119.8 119.8 0.000 0.000
0.000 0.000

Page 120 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

187 250 243 4.00 119.8 119.8 0.000 0.000


0.000 0.000
188 238 239 3.00 119.8 119.8 0.000 0.000
0.000 0.000
189 205 238 3.00 119.8 119.8 0.000 0.000
0.000 0.000
190 259 234 3.00 119.8 119.8 0.000 0.000
0.000 0.000
191 263 202 3.00 119.8 119.8 0.000 0.000
0.000 0.000
192 246 235 3.00 119.8 119.8 0.000 0.000
0.000 0.000
193 265 205 3.00 119.8 119.8 0.000 0.000
0.000 0.000
194 251 254 3.00 119.8 119.8 0.000 0.000
0.000 0.000
195 248 237 3.00 119.8 119.8 0.000 0.000
0.000 0.000
196 240 263 3.00 119.8 119.8 0.000 0.000
0.000 0.000
197 243 204 3.00 119.8 119.8 0.000 0.000
0.000 0.000
198 237 240 3.00 119.8 119.8 0.000 0.000
0.000 0.000
199 204 246 3.00 119.8 119.8 0.000 0.000
0.000 0.000
200 239 252 3.00 119.8 119.8 0.000 0.000
0.000 0.000
201 203 265 3.00 119.8 119.8 0.000 0.000
0.000 0.000
202 268 250 4.00 125.0 119.8 5.253 3.0041E-05
0.000 0.000
203 87 184 12.00 140.4 140.1 0.3118 0.3118
2697. 3.105
204 18 268 6.00 136.4 125.0 11.36 2.5749E-05
0.000 0.000
205 273 198 3.00 118.9 118.9 0.000 0.000
0.000 0.000
206 209 207 3.00 118.9 118.9 0.000 0.000
0.000 0.000
207 217 219 3.00 118.9 118.9 0.000 0.000
0.000 0.000
208 150 134 3.00 124.2 124.2 0.000 0.000
0.000 0.000
209 133 264 6.00 135.5 124.2 11.36 2.5749E-05
0.000 0.000
210 147 40 3.00 124.2 124.2 0.000 0.000
0.000 0.000

Page 121 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 30 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
211 140 3 3.00 124.2 124.2 0.000 0.000
0.000 0.000
212 40 160 3.00 124.2 124.2 0.000 0.000
0.000 0.000
213 160 159 3.00 124.2 124.2 0.000 0.000
0.000 0.000
214 8 145 3.00 124.2 124.2 0.000 0.000
0.000 0.000
215 158 8 3.00 124.2 124.2 0.000 0.000
0.000 0.000
216 157 150 3.00 124.2 124.2 0.000 0.000
0.000 0.000
217 264 158 4.00 124.2 124.2 0.000 0.000
0.000 0.000
218 141 142 3.00 124.2 124.2 0.000 0.000
0.000 0.000
219 3 141 3.00 124.2 124.2 0.000 0.000
0.000 0.000
220 145 139 3.00 124.2 124.2 0.000 0.000
0.000 0.000
221 154 144 3.00 124.2 124.2 0.000 0.000
0.000 0.000
222 128 157 3.00 124.2 124.2 0.000 0.000
0.000 0.000
223 159 154 3.00 124.2 124.2 0.000 0.000
0.000 0.000
224 185 187 12.00 134.3 131.4 2.926 8.6595E-02
2697. 3.105
225 143 151 6.00 134.7 114.2 20.59 0.000
0.000 0.000
226 158 128 3.00 124.2 124.2 0.000 0.000
0.000 0.000
227 142 137 3.00 124.2 124.2 0.000 0.000
0.000 0.000
228 134 140 3.00 124.2 124.2 0.000 0.000
0.000 0.000
229 139 147 3.00 124.2 124.2 0.000 0.000
0.000 0.000
231 244 209 3.00 118.9 118.9 0.000 0.000
0.000 0.000
232 94 133 6.00 138.4 135.5 2.840 1.6451E-05
0.000 0.000
233 260 273 3.00 118.9 118.9 0.000 0.000
0.000 0.000
234 200 241 3.00 118.9 118.9 0.000 0.000
0.000 0.000
235 201 244 3.00 118.9 118.9 0.000 0.000
0.000 0.000
236 207 224 3.00 118.9 118.9 0.000 0.000
0.000 0.000
237 199 257 4.00 118.9 118.9 0.000 0.000
0.000 0.000
238 257 261 3.00 118.9 118.9 0.000 0.000
0.000 0.000
239 198 217 3.00 118.9 118.9 0.000 0.000
0.000 0.000
240 264 199 6.00 124.2 118.9 5.253 0.000
0.000 0.000

Page 122 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

241 224 200 3.00 118.9 118.9 0.000 0.000


0.000 0.000
242 236 266 3.00 118.9 118.9 0.000 0.000
0.000 0.000
243 208 260 3.00 118.9 118.9 0.000 0.000
0.000 0.000
244 267 223 3.00 118.9 118.9 0.000 0.000
0.000 0.000
245 219 236 3.00 118.9 118.9 0.000 0.000
0.000 0.000
246 261 208 3.00 118.9 118.9 0.000 0.000
0.000 0.000
247 257 201 3.00 118.9 118.9 0.000 0.000
0.000 0.000
248 241 267 3.00 118.9 118.9 0.000 0.000
0.000 0.000
249 95 143 6.00 137.6 134.7 2.840 1.6451E-05
0.000 0.000
265 192 88 12.00 109.4 107.9 1.499 1.499
2697. 2.238
266 88 279 12.00 107.9 107.8 5.4535E-02 5.4535E-02
1379. 1.144
267 123 138 12.00 107.8 107.7 4.5395E-02 4.5395E-02
1171. 0.9719
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 31 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW IN PIPES
-------------

Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss
Flowrate Velocity
Label Node Node (inches ) (psi G ) (psi G ) (psi ) (psi )
(US.g/min) (m/sec )
---------------------------------------------------------------------------------------------------
--------------------
268 187 192 12.00 131.4 109.4 21.99 21.99
2697. 2.238 P
269 138 179 12.00 107.7 107.7 3.8216E-02 3.8216E-02
1068. 0.8858
270 179 180 12.00 107.7 107.7 3.1654E-02 3.1654E-02
963.9 0.7997
271 180 181 12.00 107.7 107.6 2.5604E-02 2.5604E-02
860.1 0.7137
272 181 253 12.00 107.6 107.6 1.0117E-02 1.0117E-02
756.4 0.6276
273 88 280 12.00 107.9 107.8 5.6458E-02 5.6458E-02
1318. 1.094
274 253 256 12.00 107.6 107.6 1.5373E-02 1.5373E-02
652.7 0.5415
275 256 258 12.00 107.6 107.6 1.1162E-02 1.1162E-02
548.9 0.4555
276 258 262 12.00 107.6 107.6 7.5836E-03 7.5836E-03
445.2 0.3694
277 262 269 12.00 107.6 107.6 4.6387E-03 4.6387E-03
341.5 0.2833
278 269 270 12.00 107.6 107.6 2.3956E-03 2.3956E-03
237.8 0.1973
279 270 271 12.00 107.6 107.6 7.9346E-04 7.9346E-04
134.0 0.1112
280 271 272 12.00 107.6 107.6 7.6294E-05 7.6294E-05
30.30 2.5142E-02
281 272 274 12.00 107.6 107.6 -1.4496E-04 1.4496E-04 -
73.42 -6.0922E-02
282 274 275 12.00 107.6 107.6 -1.3809E-03 1.3809E-03 -
177.2 -0.1470
283 275 276 12.00 107.6 107.6 -3.2272E-03 3.2272E-03 -
280.9 -0.2330
284 276 277 12.00 107.6 107.6 -5.7983E-03 5.7983E-03 -
384.6 -0.3191

Page 123 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

285 277 278 12.00 107.6 107.6 -8.9951E-03 8.9951E-03 -


488.3 -0.4052
286 278 255 12.00 107.6 107.6 -6.4163E-03 6.4163E-03 -
592.1 -0.4912
287 279 123 12.00 107.8 107.8 2.6543E-02 2.6543E-02
1275. 1.058
288 280 281 12.00 107.8 107.8 4.8515E-02 4.8515E-02
1215. 1.008
289 281 282 12.00 107.8 107.7 4.1115E-02 4.1115E-02
1111. 0.9216
290 282 283 12.00 107.7 107.7 3.4302E-02 3.4302E-02
1007. 0.8355
291 283 285 12.00 107.7 107.7 2.8069E-02 2.8069E-02
903.3 0.7494
292 284 255 12.00 107.6 107.6 1.7296E-02 1.7296E-02
695.8 0.5773
293 285 284 12.00 107.7 107.6 2.2369E-02 2.2369E-02
799.5 0.6634

NOTE: A P indicates a Pipe containing an Orifice Plate


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 32 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (psi G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
29 10 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
30 126 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
31 127 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
32 132 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
33 39 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
34 125 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
35 130 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
36 16 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
37 113 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
38 129 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
39 120 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
40 162 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
41 116 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
42 41 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
43 11 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
44 117 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
45 131 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
46 118 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
47 115 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00

Page 124 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

48 153 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01


0.0000E+00
49 167 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
50 166 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
51 161 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
52 156 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
53 165 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
54 163 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
55 148 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
56 149 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
57 155 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
58 182 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
59 175 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
60 186 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
61 183 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
62 172 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
63 171 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
64 164 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
65 222 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
66 196 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
67 188 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
68 215 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 33 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (psi G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
69 212 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
70 221 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
71 213 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
72 226 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
73 190 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
74 229 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
75 230 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
76 216 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00

Page 125 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

77 189 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01


0.0000E+00
78 211 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
79 195 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
80 233 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
81 232 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
82 240 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
83 251 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
84 231 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
85 246 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
86 234 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
87 204 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
88 237 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
89 202 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
90 248 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
91 263 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
92 235 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
93 254 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
94 259 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
95 265 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
96 252 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
97 238 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
98 239 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
99 203 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
100 205 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
101 236 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
102 273 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
103 224 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
104 198 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
105 208 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
106 219 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
107 260 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
108 244 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00

Page 126 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 34 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (psi G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
109 207 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
110 200 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
111 201 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
112 266 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
113 267 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
114 261 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
115 241 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
116 217 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
117 209 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
118 223 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
119 8 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
120 147 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
121 159 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
122 160 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
123 40 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
124 128 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
125 139 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
126 145 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
127 157 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
128 140 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
129 3 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
130 142 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
131 137 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
132 134 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
133 150 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
134 154 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
135 144 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
136 141 0.00000E+00 13.2300 0.0000 * -100.00 0.2700E+01
0.0000E+00
149 151 0.00000E+00 509.2200 0.0000 * -100.00 0.2700E+01
0.0000E+00

Page 127 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

150 122 0.00000E+00 509.2200 0.0000 * -100.00 0.2700E+01


0.0000E+00
151 123 0.10770E+03 103.0700 103.7803 0.69 0.1100E+01
0.1108E+01
152 138 0.10767E+03 103.0700 103.7646 0.67 0.1100E+01
0.1107E+01
153 179 0.10764E+03 103.0700 103.7517 0.66 0.1100E+01
0.1107E+01
154 180 0.10762E+03 103.0700 103.7415 0.65 0.1100E+01
0.1107E+01
155 181 0.10761E+03 103.0700 103.7337 0.64 0.1100E+01
0.1107E+01
156 253 0.10761E+03 103.0700 103.7329 0.64 0.1100E+01
0.1107E+01
157 256 0.10760E+03 103.0700 103.7290 0.64 0.1100E+01
0.1107E+01
158 258 0.10759E+03 103.0700 103.7266 0.64 0.1100E+01
0.1107E+01
159 262 0.10759E+03 103.0700 103.7254 0.64 0.1100E+01
0.1107E+01
160 269 0.10759E+03 103.0700 103.7252 0.64 0.1100E+01
0.1107E+01
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 35 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW THROUGH NOZZLES


--------------------

Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens
FlowDens
Label Label (psi G ) (US.g/min) (US.g/min) (
US.g/min/metres **2 )
---------------------------------------------------------------------------------------------------
-----------
161 270 0.10759E+03 103.0700 103.7255 0.64 0.1100E+01
0.1107E+01
162 271 0.10759E+03 103.0700 103.7260 0.64 0.1100E+01
0.1107E+01
163 272 0.10759E+03 103.0700 103.7264 0.64 0.1100E+01
0.1107E+01
164 274 0.10759E+03 103.0700 103.7257 0.64 0.1100E+01
0.1107E+01
165 275 0.10759E+03 103.0700 103.7252 0.64 0.1100E+01
0.1107E+01
166 276 0.10759E+03 103.0700 103.7251 0.64 0.1100E+01
0.1107E+01
167 277 0.10759E+03 103.0700 103.7257 0.64 0.1100E+01
0.1107E+01
168 278 0.10759E+03 103.0700 103.7274 0.64 0.1100E+01
0.1107E+01
169 255 0.10759E+03 103.0700 103.7273 0.64 0.1100E+01
0.1107E+01
170 284 0.10760E+03 103.0700 103.7319 0.64 0.1100E+01
0.1107E+01
171 285 0.10762E+03 103.0700 103.7384 0.65 0.1100E+01
0.1107E+01
172 283 0.10763E+03 103.0700 103.7472 0.66 0.1100E+01
0.1107E+01
173 282 0.10766E+03 103.0700 103.7584 0.67 0.1100E+01
0.1107E+01
174 281 0.10769E+03 103.0700 103.7724 0.68 0.1100E+01
0.1107E+01
175 280 0.10772E+03 103.0700 103.7895 0.70 0.1100E+01
0.1108E+01
176 279 0.10772E+03 103.0700 103.7865 0.70 0.1100E+01
0.1108E+01

Note: A * after a value indicates that this is a specification

Page 128 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 36 OF 42
---------------------------------------------------------------------------------------------------
--------------------

ORIFICE PLATES
--------------

Plate Pipe Pressure Drop Diameter


Label Label (psi ) (inches )
-------------------------------------------------------------------
X05/0 268 0.21750E+02 5.3132
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 37 OF 42
---------------------------------------------------------------------------------------------------
--------------------

FLOW AT INLETS
--------------

Inlet Node Pressure Flowrate Equivalent K-factor


(psi G ) (US.g/min) (US.g/min , psi G )
------------------------------------------------------------
44 145.0 * 2697. 224.00

Note: A * after a value indicates that this is a specification


1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 38 OF 42
---------------------------------------------------------------------------------------------------
--------------------

Materials Take-off
------------------
Pipe lengths
------------

ANSI B36.10 Sch.40 HDPE ANSI B36.10 Sch.20

Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length
Nom. Size Tot. Length
(inches ) (metres ) (inches ) (metres ) (inches ) (metres ) (inches ) (metres )
(inches ) (metres )
---------------------------------------------------------------------------------------------------
-------------------
3.000 183.6 6.000 618.3 12.000 259.0
4.000 6.700 12.000 791.9
6.000 1747.
12.000 109.0

Page 129 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 39 OF 42
---------------------------------------------------------------------------------------------------

Materials Take-off
------------------
Nozzles
-------

Type K-Factor Number


---- -------- ------
Condensate Tank Nozzle 1.8000 108
Mushroom Nozzle 48.5000 2
Foam Maker 10.0000 26
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 40 OF 42
---------------------------------------------------------------------------------------------------

Materials Take Off


------------------
Fittings
--------

Fitting
Nominal
Size Fitting Type
(inches ) 1 2 3 4 5 6 7 8 9
-------------------------------------------------------------------------

3.000 0 0 0 108 0 0 0 0 0
4.000 0 0 0 1 0 0 0 0 0
6.000 4 34 0 50 27 0 0 0 0
12.000 12 4 0 29 11 0 0 0 1

Fitting Types are :


1 -- 45 Deg Elbow 4 -- Tee or Cross 7 -- Non-Return Valve
2 -- 90 Deg Standard Elbow 5 -- Gate Valve 8 -- Ball Valve
3 -- 90 Deg Long Radius Elbow 6 -- Swing Check Valve 9 -- Butterfly Valve

All fittings are as specified by user - no additional fittings have been generated automatically.

Other Equipment
---------------
Type Number
---- ------
Orifice Plates 1

The supply demand graph is not available for the network without pump
1

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 41 OF 42
---------------------------------------------------------------------------------------------------

IMPORTANT NOTICE
----------------

Your attention is drawn to the need to maintain adequate standards. SUNRISE SYSTEMS Ltd
has itself taken steps to ensure that this program produces valid results when properly
used. Users are reminded of their responsibilities in the application of program results
and, in particular, you should ensure that pertinent output documents are examined and
approved by qualified staff prior to use.

Page 130 of 131


Onspec Tawakol Engineering & Contracting
Engineering of Fire Fighting Network
Fire Fighting System Hydraulic Calculation Report

TITLE : Firefighting Hydraulic Calculation for WASCO EW PLANT DATE : 15-Feb-2020


PAGE 42 OF 42
---------------------------------------------------------------------------------------------------

COMMENTS
--------

Analysis Converged in 4 Iterations


1

====================================================================================================
====================

Firefighting Hydraulic Calculation for WASCO EW PLANT


Condensate tanks dike foam Case - Scenario 2
FEB. 16, 2020
Designed by : Mohamed Hamed

====================================================================================================
====================

Page 131 of 131