Professional Documents
Culture Documents
D. Martin - Further Studies of A Vegetable-Oil-Filled Power Transformer
D. Martin - Further Studies of A Vegetable-Oil-Filled Power Transformer
D. Martin - Further Studies of A Vegetable-Oil-Filled Power Transformer
The transformers were fitted with a comprehensive monitor- by measuring the water activity of a thin strip of polymer [11].
ing system, which, as stated above, recorded data every minute Water activity is defined as the ratio of the partial pressure of
from the various sensors mounted around the transformer, i.e., water vapor to the partial pressure of water vapor above pure
load current, winding temperatures measured by eight fiber-op- water at the same temperature [12]. Accurate measurement re-
tic probes, oil temperature and wetness measured by four Vaisala quires that the polymer strip be in thermodynamic equilibrium
probes, oil temperature and cooling water temperature recorded with the surrounding fluid. Despite the fact that the temperature
by resistance temperature detectors, and ambient temperature within a transformer is usually changing continuously, due to the
and relative humidity recorded by a Vaisala probe within the fluctuating load, thermodynamic equilibrium between the probe
substation. The advantage of such a system is that the regular and the oil will be reached provided the time required for the
recording of data allows trends and relationships between the probe strip to equilibrate with the oil is short compared with the
different properties to be observed. time within which the transformer internal conditions change
The four Vaisala probes measuring the wetness of the oil significantly.
were inserted into the top and bottom of the transformer tank, To determine how quickly the Vaisala probes responded to
and top and bottom of one of the heat exchangers. They operate a change in fluid wetness, a probe was suspended in air and al-
lowed to equilibrate with the ambient humidity and temperature.
It was then inserted in a sample of FR3 fluid, with a water con-
centration of 40 ppm at ambient temperature, and its output was
Table 1. Transformer Ratings. observed. The fluid was stirred by a mechanical bar rotating at
352 rpm. To calculate the concentration of water dissolved in
Parameter Value
the fluid as a result of the probe measurement, the fluid solubil-
Year of manufacture 2008 ity at the relevant temperature must be known. Equation (1) was
used to calculate solubility using the coefficients published by
Date first energized 12 October 2008
Lewand, i.e., A = 5.3318 and B = 684 [13]. T is the temperature
Cooling class KDWF in °C.
Rated power 50 MVA B
A−
T +273
Rated voltage and frequency 132/11/11 kV, 50 Hz Solubility(T ) = 10 (1)
Rated current 218.7 A (HV winding)
When the probe was inserted in the fluid, its output reading
2 × 1,312.2 A (LV windings) fell rapidly for a short time and then reached an almost constant
value after approximately 100 minutes, as shown in Figure 2. It
Maximum temperature rise Top oil 60°C
follows that there will be a time lag between a change in water
Average winding 70°C content of the fluid within the transformer and the final response
of the probe to this change. Such time lags must be taken into
Insulation level HV lightning impulse 650 kV
account when analyzing temperature and moisture dynamics.
HV ac 275 kV However, under normal operating conditions the water content
of the fluid in the installed transformer would not be expected to
LV lightning impulse 95 kV
vary significantly over a 100-minute period.
LV ac 20 kV
The dissolved gas content of the fluid was measured and re-
corded every four hours by the online automated system, using
a gas chromatograph. Fluid was pumped from the transformer Figure 3. The highest temperatures within the transformer as
tank through the online system and returned to the tank. The measured by the fiber-optic probe array.
dissolved gases were extracted from the fluid with the aid of he-
lium carrier gas. The dissolved gas content of the fluid was also
measured periodically by independent laboratories, as a check adsorbed water will slowly migrate toward the center of the cel-
on the reliability of the automated system. A detailed analysis lulose. Du [15] calculated the time taken for water to diffuse
of our preliminary findings on gassing trends was given in [9]. through 1-mm-thick pressboard impregnated with mineral oil as
Elevated ethane and hydrogen concentrations were found, as 333 hours (≈14 days) at 20°C. Because much thicker blocks of
predicted by various researchers on the basis of laboratory tests cellulose had been used in the construction of the transformer,
[5], [8], [13], [14]. the corresponding diffusion times would be much longer. Con-
sequently, the water content of the oil may change slowly over
Transformer Condition Data a long period, as water is exchanged between the center of the
The temperatures of the oil and the paper insulation were thick cellulose block and the bulk oil.
continually monitored, because such data could be useful in in- Toward the end of its useful life mineral oil forms a sludge,
terpreting any observed changes in the condition of the insu- whereas vegetable oil becomes more viscous. The thermal per-
lation over long periods, or a phenomenon such as unusually formance of a fluid is related to its viscosity [16], [17]. It may
heavy gassing. The highest temperatures recorded by the array therefore be possible to assess the condition of the vegetable oil
of fiber-optic probes within the transformer are shown in Figure by monitoring the temperatures within the transformer and cor-
3; they do not suggest overheating of paper or oil. relating them with the load, i.e., when the viscosity changes the
The water content of the oil was calculated from the output of temperature distribution may change sufficiently to be detected.
one of the Vaisala probes. At room temperature the solubilities If the temperatures deviate from those expected, the usual oxida-
of water in mineral oil and in vegetable oil are approximately tion tests, which may include measurement of oxygen inhibitor
50 and 1,100 ppm, respectively, so that a higher water content content, dielectric dissipation factor, and acidity, should be car-
is to be expected in a transformer using vegetable oil. The water ried out.
concentrations calculated from the Vaisala probe data (Figure 4)
agree fairly well with the Karl Fischer titration measurements
shown in Table 2. On energization of the transformer the water
content of the oil was 30 ppm. It fell to 22 ppm after 5 months
of operation, and the same value was observed after 25 months.
The difference between oil water content measured by Karl
Fischer titration, and that calculated using the Vaisala probe,
may be due to absorption of water by the oil sample in transit
from the transformer to the laboratory.
The insulation at the top of an energized transformer is usu-
ally hotter than the insulation at the bottom, and therefore water
released from the warmer cellulose at the top will tend to be
adsorbed on the cooler cellulose at the bottom. Over time this Figure 4. The concentration of water dissolved in the oil at the
top of the transformer tank, calculated from Vaisala probe data.
75; IEC 60156; VDE 0370 68.2; IEC 60156; VDE 0370 67.2; IEC 60156; VDE 0370
Breakdown voltage (kV) —
electrodes electrodes electrodes
Moisture (ppm) Karl Fisher titration 30; ASTM D1533 22; IEC 60814 22; IEC 60814 7; IEC 60814
Acidity (mg of KOH/g of oil) 0.03; ASTM D974 0.03; AS 1767.2.1 0.03; AS 1767.1 0.03; ASTM D974
Interfacial tension (mN/m) 21.6; ASTM D971 21.6; ASTM D971 21.6; ASTM D971 24.5; ASTM D971
Fiber-optic probes were inserted into different sections of the appear that the ethane-generating reactions slowed down and
windings to locate the hottest points within the transformer. Ex- possibly ceased. The concentration of hydrogen fell, perhaps be-
cessive heat and oxygen can together degrade oil and cellulose. cause hydrogen was consumed in further reactions. The online
Consequently, it is necessary to ensure that the cooling of the dissolved gas analysis measurements agreed satisfactorily with
transformer is adequate and the number of hot spots is mini- the independent laboratory measurements (Table 4).
mized. The dissolved gas content of the oil in the stored transformer
was measured (Table 5) to compare its dissolved gas analysis
Analysis of Dissolved Gas Concentrations to signature with that of the operating transformer. No ethane was
Determine Transformer Condition detected during factory acceptance tests conducted in July/Au-
Oil FR3 is known to produce higher levels of ethane (C2H6) gust 2008. However, two years later ethane was found in concen-
and hydrogen than mineral oil under nonfault conditions [5], trations comparable with those in the operating transformer. The
[7], [8], [13]. Some of the components of soybean vegetable oil, second transformer was energized only during carefully con-
such as linolenic acid, generate ethane by reacting with oxy- trolled factory testing two years prior to the sampling; therefore,
gen [18]. A catalyst, e.g., copper, is required for the ethane-pro- it would appear that ethane can be produced in the absence of
ducing reaction to proceed. The reaction noted by Schaich [18] a fault, in agreement with Duval’s observations of stray gassing
may be the source of ethane production within the transformer. [7], [8]. High ambient temperatures may have been responsible.
Atanasova-Hoehlein et al. [19] suggest that ethane is generated
by the lipid peroxidation mechanism, which can occur in all Using Water Content to Verify Absence of Vegetable-
omega-3 unsaturated fatty acids. They also suggest that ethane Oil Biodegradation in Transformer Tank
can be considered as the main gas involved in thermal-oxidative
degradation of vegetable oils.
Mineral oil generates less ethane than does vegetable oil be-
cause of differences in hydrocarbon molecular structure, i.e.,
Table 3. Ostwald Solubility Coefficients for FR3 and Mineral Oil.
ring structures in mineral oil but straight chains in vegetable oil
triglycerides. Consequently, ethane generation within a trans- FR3 Mineral oil
former may be related to the proportion of linolenic acid form-
Gas 25°C [19] 70°C [20] 25°C [19] 70°C [20]
ing the triglyceride, the temperature, the availability of oxygen,
and the copper surface area exposed to the oil. H2 0.05 0.097 0.05 0.092
A common measure of gas solubility is the Ostwald coef-
O2 0.15 0.255 0.17 0.208
ficient, which is the concentration of gas dissolved in the oil
divided by the concentration of free gas in the headspace of a N2 0.07 0.141 0.09 0.127
vessel, such as a sampling syringe [20]. Thus the concentration
CH4 0.30 0.387 0.43 0.432
of a gas dissolved in the oil can be calculated from a measure-
ment of the concentration of the same gas in the headspace of the CO 0.09 0.148 0.12 0.143
syringe. The Ostwald solubility coefficients for various gases in
FR3 and in mineral oil are given in Table 3 [21], [22]. CO2 1.33 1.187 1.08 0.921
The levels of dissolved gas in the transformer oil were moni- C 2H 2 1.63 1.763 1.20 0.992
tored for nearly two years. The ethane level increased around the
time of energization, plateaued at approximately 120 ppm, and C 2H 4 1.19 1.389 1.70 1.419
remained at that level for nearly two years (Figure 5). It would C 2H 6 1.45 1.677 2.40 2.022
Table 4. Laboratory Measurements of Dissolved Gas in the Oil of the Operating Transformer.1
Gas (ppm) Lab 1 Lab 3 Online May 2009 Lab 3 Online July 2010
H2 47 52 33 11 7
CO 77 60 55 53 55
C2H2 0 0 0 0 0
The laboratory measurement in March 2009 is compared with the closest online measurement in May 2009, and the laboratory
1
measurement in November 2010 is compared with the closest online measurement in July 2010.
Factory testing
17 November 2010
August 2008
H2 12 37
O2 156 5,833
N2 4,211 58,742
CH4 0 <1
CO 10 32
CO2 65 146
C2H2 0 <1
C2H4 0 <1
C2H6 0 62
Water activity is a ratio, based on water vapor pressure, covering the range 0 to 1,
1 1
The authors’ measurements were performed at several temperatures, and the data
where 0 = dry and 1 = saturation. interpolated to the commercial laboratory measurement temperatures.