Professional Documents
Culture Documents
Om FC Duo-Cel App 0
Om FC Duo-Cel App 0
DUO-CEL
Application Guide
PAGE 1 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
List of Contents
1. INTRODUCTION ...................................................... 4 11.3 AUXILIARY SUPPLY ................................... 27
2. GENERAL DESCRIPTION......................................... 4 11.4 FIRE SIGNAL OUTPUT ............................... 27
2.1 CABINET SPECIFICATIONS ........................... 4 11.5 FIRE RELAY OUTPUT ................................ 27
2.1.1 Panel Order Codes & Descriptions ........ 5 11.6 FAULT RELAY OUTPUT .............................. 27
2.1.2 Replacement PCB Order Codes and 11.7 REMOTE CONTROL INPUT ......................... 28
Descriptions ....................................... 6 11.7.1 Class Change .................................... 28
2.1.3 Optional Language Display Overlays .... 6 11.7.2 Alert ................................................... 28
2.2 FIRE DETECTION AND ALARM PANEL 11.7.3 Evacuate ............................................ 28
DESCRIPTION.............................................. 7 11.7.4 Silence Alarms ................................... 28
2.2.1 DUO-CEL control board ......................... 7 11.7.5 Reset ................................................. 28
2.2.2 Display overlay and insert ...................... 7 11.8 OPEN COLLECTOR OUTPUTS..................... 28
2.2.3 Power Supply ......................................... 8 11.8.1 Disabled Output ................................. 29
2.2.4 Repeater Panel ...................................... 8 11.8.2 Evacuate Output ................................ 29
3. FUNCTIONAL SPECIFICATION ................................. 8 11.8.3 Buzzer Active Output ......................... 29
3.1 PANEL INPUT/OUTPUT LIST ......................... 8 11.9 SOUNDER CIRCUITS.................................. 29
3.2 FEATURES LIST ........................................... 9 11.10 ELECTRICAL DESIGN OF DETECTION ZONES29
4. DUO-CEL PANEL – CONTROL BOARD FEATURES 11 11.10.1 Standard Panel Default Zone
5. DUO-CEL REPEATER – CONTROL BOARD Configuration ................................... 29
FEATURES ........................................................ 12 11.10.2 Standard Panel Resistor Zone
6. POWER SUPPLY .................................................. 13 Configuration ................................... 29
6.1 GENERAL.................................................. 13 11.10.3 Twin-Wire Panel .............................. 29
6.1.1 Supply Input ......................................... 13 11.10.4 Maximum Number of Detectors/MCPs
6.1.2 Supply Output ...................................... 13 on a Zone ......................................... 30
6.1.3 Battery Charger .................................... 13 11.11 PANEL TO REPEATER W IRING.................... 33
6.1.4 Battery Monitoring ................................ 13 12. MECHANICAL & ELECTRICAL SPECIFICATION ..... 34
6.1.5 Visual indications ................................. 14 13. ENVIRONMENTAL SPECIFICATION....................... 35
6.1.6 Fault Conditions ................................... 14 14. DUO-CEL INPUT AND OUTPUT SPECIFICATION .. 36
6.2 MECHANICAL PROTECTION ........................ 14 15. APPENDIX ......................................................... 39
6.2.1 DUO-CEL Power Supply Features and 15.1 EN54 MANDATORY FUNCTIONS ................ 39
Connections ..................................... 14 15.2 EN54 OPTIONAL FUNCTIONS W ITH
7. COMPATIBLE FIELD DEVICES ............................... 15 REQUIREMENTS ........................................ 39
7.1 FIELD DEVICE PART NUMBERS .................. 15 15.3 ANCILLARY FUNCTIONS NOT REQUIRED BY
8. OVERVIEW OF USER FUNCTIONS ......................... 18 EN54....................................................... 39
8.1 USER INDICATIONS .................................... 18 15.4 SAFE STATE ............................................. 39
8.2 USER CONTROLS ...................................... 19 15.5 POWER SUPPLY LOAD CALCULATION......... 40
8.3 SELECTION OF ZONES OR OUTPUTS FOR 15.6 MINIMUM STANDBY BATTERY CAPACITY
DISABLEMENT, ENABLEMENT OR TEST ....... 20 CALCULATION ........................................... 40
8.4 DISABLED ZONES AND OUTPUTS ................ 20 15.6.1 Standby Battery Capacity Calculation
8.5 DETECTOR ZONE TEST.............................. 20 Worksheet ........................................ 42
8.6 ALARM SOUNDER ONE MAN TEST .............. 20 15.7 A1466 INTERFACE RELAY ......................... 43
9. OVERVIEW OF ENGINEERS FUNCTIONS ................. 21 15.8 PANEL CONFIGURATION DESIGN CHART .... 44
9.1 ENGINEER‟S CONFIGURATION PROCESS ..... 21 16. GENERAL ASSEMBLY DRAWING ........................ 45
9.1.1 Zone Dependency selection ................ 21
9.1.2 Repeater configuration......................... 21
9.2 ZONE 1 NON-LATCH OPERATION ................ 22
9.3 RESISTOR EOL......................................... 22
9.4 TWIN W IRE ............................................... 22
9.5 ALERT MODE ............................................ 22
9.6 SELECTABLE ZONAL OR GENERAL ALARM
SOUNDER OPERATION ............................... 23
9.7 BUZZER DISABLE ...................................... 23
9.8 EARTH FAULT MONITORING........................ 23
10. PANEL REPEATERS ........................................... 23
10.1 REPEATER USER INDICATIONS ................... 24
10.2 REPEATER USER CONTROLS ..................... 25
11. CIRCUIT CONNECTION DETAILS.......................... 26
11.1 DUO-CEL PANEL MOTHERBOARD
TERMINATION DETAILS .............................. 26
11.2 DUO-CEL REPEATER MOTHERBOARD
TERMINATION DETAILS .............................. 27
PAGE 2 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
PAGE 3 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
mounted to the back box. An ABS cover is fixed
1. Introduction over the display/control board, leaving the field
This document contains technical information terminals, configuration switches, links and user
necessary for application design using the controls easily accessible.
FIRECLASS DUO-CEL Conventional Fire Detection The front cover of the enclosure clips onto the back
control panel. box and is fixed by one screw on the top and two
The following supporting documentation is also screws on the bottom.
available: The PCB cover is fitted with a polyester overlay
FIRECLASS DUO-CEL Sales Literature providing user controls and indications. All display
text is printed on the overlay, with an insert for the
FIRECLASS DUO-CEL User Manual zone location text that slides into a pocket in the
FIRECLASS DUO-CEL Installation and overlay.
Commissioning Manual. User controls are locked & unlocked via a plastic
FIRECLASS DUO-CEL Log Book. key which is inserted through a keyhole in the cover
and cannot be removed when in the ON position.
Note: References are made throughout this
document to “Fire Signal Output” and “Fire Relay All indications are implemented using LEDs, three
Output”. These refer to particular outputs from the of which are not visible when the enclosure front is
panel and are provided for specific purposes: fitted.
Fire Relay Output: An output used to activate The power supply and standby batteries are
ancillary fire protection equipment or systems. housed within the panel enclosure. The power
For example, fire doors or plant shutdown. supply is fitted underneath the PCB with the mains
supply cable terminals accessible for easy
Fire Signal Output: An output used to send a installation. The batteries are fitted in the back box
common fire warning signal to a remote fire and retained by a plastic bar which is fixed to the
monitoring station. back box by a single screw.
Detailed descriptions of both outputs are provided Field cable Earth shields can be terminated to a
within the following text. functional earth bar located in the rear of the panel
The panel is currently available as a standard enclosure.
conventional panel, with a twin-wire version soon to
be released. This document describes features
available for both types of panel.
2.1 Cabinet Specifications
Enclosure construction:
2. General Description Three-part high quality moulded ABS plastic
enclosure.
The FIRECLASS DUO-CEL Panel range is fully
compliant with the mandatory requirements and Keyhole for access control key.
selected optional requirements of EN54 parts 2 and 14 knockouts for 20mm cable glands.
4. 5 mounting holes in the rear of the back box.
The FIRECLASS DUO-CEL equipment range
Integral bezel design for surface mounting or
consists of the following:
semi-flush mounting.
Standard Panels:
Logo recess on the top-right of the front cover.
1, 2, 4 and 8 zone versions.
Ingress Protection rating – IP30
Twin-Wire Panels:
1, 2, 4 and 8 zone versions. Finish:
Repeater: Fine-texture (spark finish)
8 zone 24Vdc & 230Vac versions. Colour – Light Grey RAL7035
Each panel in the range is housed in an
Acrylonitrile Butadiene Styrene (ABS) Plastic
enclosure with a combined display & control board
PAGE 4 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
262 mm
254 mm
273 mm
SUPPLY ON
GENERAL FIRE 1 EVACUATE
GENERAL FAULT
2
GENERAL TEST SILENCE
GENERAL DISABLE 3 BUZZER
ALERT / EVAC ON
4 SILENCE /
FIRE SIGNAL ON RESOUND
FIRE SIGNAL FAULT 5
ALARMS
SNDR FLT / DIS / TEST
6 RESET
SYSTEM FAULT
PSU FAULT 7
FUSED FAILED DISABLE
8
EARTH FAULT
REPEATER FAULT
TEST
REMOTE I/P FAULT
CONTROLS ON
SELECT
365 mm
356 mm
348 mm
4 mm
77 mm
29 mm
PAGE 5 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
PAGE 6 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
2.2 Fire Detection and Alarm Panel Description
Figure 2 shows the exploded view of the DUO-CEL panel.
Earth Bar
Control 3.4Ah
Board with Powersonic
Cover Batteries
Battery
Clamp
BAQ35T24
Power Supply
Enclosure
Front Cover
PAGE 7 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
2.2.3 Power Supply NOTE: The battery clamp is not designed to clamp
batteries other than the PS-1230.
The Power Supply is a self-contained switch-mode
unit and is mounted underneath the control board. 2.2.4 Repeater Panel
This unit provides 27.5VDC (nominal) at 1.5A to the
The repeater panel uses the same control board
control board.
and enclosure as the fire alarm panel. The
The output from the PSU is temperature components for the redundant circuits [zones,
compensated, i.e. the battery charging voltage is alarm circuits etc] are not present on the repeater
automatically adjusted to the safest optimum value control board. The repeater and fire panel
depending on the temperature of the batteries. mechanical arrangements are similar. The repeater
The PSU is connected to the control board by two can be supplied with its own battery-backed
leads: 230VAC PSU, or without a PSU (powered directly
The output lead has a 3-way socket, providing from the Fire Alarm panel‟s Auxiliary DC output).
0V, 28V and Mains Fault signals. (The Repeaters are only supported on the 4-zone & 8-
connector on the panel motherboard may zone panels.
th
have a 4 pin for Functional Earth connection Up to 3 repeaters can be connected to the panel.
from alternative power supplies).
The panel controls the Repeaters through the
The Thermistor lead connects to the RS485 serial communications link.
Thermistor socket on the control board, the
Thermistor being situated on the control 3. Functional Specification
board. (The Thermistor is used to monitor the
battery temperature).
The control board provides connections for the 3.1 Panel Input/Output List
standby batteries via spade terminals. See Table 1 below.
The enclosure accommodates 2-off 12V 3.4Ah
Sealed Lead-Acid Powersonic PS-1230 batteries.
PAGE 8 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
3.2 Features List
Battery disconnect Prevents permanent damage to the battery due to deep discharge by
automatically disconnecting it when the battery voltage falls below 21.6V.
Remote Control input providing
five controls:
1. Class Change Operates all sounders for up to 5 seconds without giving any panel
indications.
3. Evacuate Operates all sounders continuously and operates the fire buzzer.
4. Silence Alarms Latches the Silence Alarms condition until a new alarm condition is
detected or until panel reset.
5. Reset Returns the panel to the quiescent state after a fault or alarm
condition.
Configurable detection zones DIL switch configuration provides the following capabilities:
Latching or non-latching Fire indication on zone 1.
Resistor or capacitor EOL monitoring – applies to all zones. (Not
functional on Twin-Wire panels)
Zone Short Circuit gives fault or fire alarm (for backwards
compatibility) – applies to all zones.
Factory configuration:
Latching zone 1 Fire indication
Capacitor EOL (not for twin-wire)
Zone Short circuit gives fault.
Zonally configurable co-incidence Programmable facility which allows any zone to be configured for co-
(dependency) for Automatic Fire incidence (dependency) detection. Requires two occurrences of detector
Detectors activation within 30 minutes before an alarm is raised. Manual call points
are not affected.
PAGE 9 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Fire Signal Output Fully fault monitored output, providing 28VDC (nominal) at up to 250mA
when active.
Fire Relay Output Non- monitored Relay output, providing one set of volt-free change-over
contacts.
Fault Relay Output Non- monitored Relay output, providing one set of volt-free change-over
contacts, with fail-safe operation (fault signalled if total power failure)
Short Circuit Fire Option A DIL switch selectable option on the motherboard to allow a short circuit
on the zones to be indicated as an alarm. For compatibility with older
detectors which do not have current limiting circuits.
NOTE: Automatic fire Detector activation will be detected by the panel as
a Manual Call Point alarm.
Auxiliary 24VDC 250mA power Protected by a fast acting electronic fuse. Operation of the fuse is
supply output indicated on the display. Operation of the Reset button on the panel
display resets the electronic fuse.
DIL switch configurable to switch off for 10 seconds during panel reset.
Earth Fault monitoring Can be disabled by removing a link on the control board.
Buzzer disablement feature DIL switch selectable option to allow the buzzer and Buzzer Active output
to be prevented from operating.
Intended for use during commissioning and maintenance only.
One Man Zone Test Each zone can be independently set to the One Man test condition.
Sounders will operate momentarily as per configuration of zonal alarms &
alert mode.
NOTE: Zone Dependency (co-incidence) is not applied during one-man-
test on a test zone.
One Man Sounder Test Operates the general sounders (and twin-wire sounders if twin-wire
panel) intermittently.
Automatic fire detector and Each zone is capable of recognising whether a fire condition has been
manual call point fire event caused by an automatic fire detector or a manual call point (unless the
discrimination panel is configured to EOL resistor monitoring on the zones). This is used
in conjunction with the dependency (co-incidence) feature and Alert alarm
mode.
Alarm Counter The panel keeps a record of the number times it enters the alarm
condition. This count can be displayed on the display LEDs as a binary
value, up to a maximum value of 999 (1111101001). The counter can be
reset via a button on the motherboard which can only be accessed by
removing the front cover.
Repeater panels Support for up to 3 repeater panels via two-wire RS485 serial
communication. [Repeaters are not available for the 1 & 2 zone panels].
PAGE 10 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
PCB ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 7 ZONE 8 FIRE SIGNAL FIRE RELAY FAULT RELAY REMOTE REMOTE O/PS AUX 0.25A REPEATER ALARM CIRCUITS
ZONE 6
Z1 + Z1 – Z2+ Z2 – Z3+ Z3 – Z4+ Z4 – Z5+ Z5 – Z6+ Z6 – Z7+ Z7 – Z8+ Z8 – + – N/O P N/C N/O P N/C I/P 0V DIS. EVAC. BUZ. 24V 0V A B 24V 0V A B AL1+ AL1 – AL2+ AL2 – AL3+ AL3 – AL4+ AL4 –
ZONE USER
ALARM LOCATION CONTROLS
BATTERY COUNTER INSERT
FUSE RESET INTERNAL
MOUNTING ACCESS KEY BUZZER
BUTTON ENTRY MICROCONTROLLER
TAB PROGRAMMING
SOCKET
Note:
The Microcontroller programming socket is for use during manufacturing only and should not have any links
fitted across any of the pins. Improper use of the connector may result in permanent damage to the control
board.
PAGE 11 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
PCB ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 7 ZONE 8 FIRE SIGNAL FIRE RELAY FAULT RELAY REMOTE REMOTE O/PS AUX 0.25A REPEATER ALARM CIRCUITS
ZONE 6
Z1 + Z1 – Z2+ Z2 – Z3+ Z3 – Z4+ Z4 – Z5+ Z5 – Z6+ Z6 – Z7+ Z7 – Z8+ Z8 – + – N/O P N/C N/O P N/C I/P 0V DIS. EVAC. BUZ. 24V 0V A B 24V 0V A B AL1+ AL1 – AL2+ AL2 – AL3+ AL3 – AL4+ AL4 –
POWER
SUPPLY
LEAD
NOTE:
ZONE USER
Power Supply LOCATION
connections and CONTROLS
BATTERY INSERT
battery fuse are only FUSE ACCESS KEY INTERNAL
on the mains MOUNTING ENTRY MICROCONTROLLER BUZZER
powered repeater. TAB PROGRAMMING
SOCKET
Note:
The Microcontroller programming socket is for use during manufacturing only and should not have any links
fitted across any of the pins. Improper use of the connector may result in permanent damage to the control
board.
PAGE 12 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
6.1.3 Battery Charger
6. Power Supply
The power supply is capable of charging 2-off 12V
3.4Ah SLA Powersonic PS-1230 batteries.
The power supply unit monitors a Thermistor on the
panel control board and automatically adjusts the
output voltage to provide the optimum safe
charging voltage over an operating temperature
o o
range of -5 C to +40 C.
The charging voltage can be adjusted via the
trimmer potentiometer VR1 on the PSU. However,
the charging voltage is factory set and adjustment
should not be necessary (a 15K resistor can be
6.1 General o
used in place of the Thermistor to simulate 25 C).
The DUO-CEL uses a BENTEL BAQ35T24 switch NOTES:
mode Power Supply which has the following
features: 1. The battery charging voltage is temperature
dependant and should be set as detailed in
Input voltage: 230 VAC 50/60Hz Table 2. Charging at too high a voltage may
o
Output voltage: 27.15VDC (nominal @ 25 C) result in overheating, resulting in damage to
Stability over 1% with full load the batteries. Charging at too low a voltage
will result in insufficient charging of the
Overload protection batteries.
Short-circuit protection 2. The charging profile of the power supply unit
Insulation class 1 is optimised for Powersonic™ batteries and
Tested and approved to EN 60950:1996 + charging of other manufacturers’ batteries is
A4:1997 not recommended. Consult your battery
supplier or battery manufacturer before use.
Dimensions: 130mm x 100mm x 38mm
Weight: 389g Table 2 – Float Charge Voltages for
Powersonic VRLA batteries
The battery monitoring circuit is part of the control
board. This provides: Float Charge
Thermistor for temperature compensation Voltage (V)
Ambient Charger Set
(2x12V
Battery/charger fault monitoring Temperature voltage (V)
Batteries in
Automatic “battery disconnect” facility. series)
o o
Disconnects the battery when the battery -10 C (14 F) 28.32 – 28.42 27.84 – 28.44
terminal voltage falls below 21.6V, to prevent o o
0 C (32 F) 27.82 – 27.92 27.60 – 28.20
deep discharge of the batteries if supplying the o o
10 C (50 F) 27.45 – 27.55 27.36 – 27.96
panel for an abnormally long period of time. o o
20 C (68 F) 27.20 – 27.30 27.12 – 27.72
o o
6.1.1 Supply Input 25 C (77 F) 27.10 – 27.20 27.00 – 27.60
o o
30 C (86 F) 27.03 – 27.13 26.88 – 27.48
The PSU is designed to run from mains voltage at o o
40 C (104 F) 26.91 – 27.01 26.64 – 27.24
230Vac +10%, -15%, 50/60Hz. The input is o o
50 C (122 F) 26.84 – 26.94 26.40 – 27.00
protected by a 3A 20mm glass fuse. The fuse is
inside the metal cage and is not user-serviceable. 6.1.4 Battery Monitoring
6.1.2 Supply Output The health of the batteries, the battery connections
and fuse are checked by a battery monitor circuit on
The output from the PSU is 27.15Vdc ±1% at 25°C the panel control board.
with load up to 1.5A. The output is protected by a
6.3A 20mm glass fuse. The fuse is inside the metal The batteries are monitored for disconnection. If
cage and is not user-serviceable. the battery voltage falls to 18V or below then a
PSU fault is raised and the charging voltage is
The output current is shared between the panel removed from the terminals.
load and battery charging. The battery charging
current is therefore dependent on output current The batteries are monitored for low voltage. If
and will fall to zero as the panel load approaches the battery voltage drops below 21.6V when the
1.5A. mains power is disconnected, then the batteries
are electronically disconnected to prevent deep
The output is connected to the panel via a three- discharge. The batteries are reconnected only
wire flying lead, providing the DC power and a fail- after mains power is restored.
safe fault signal.
The batteries are monitored periodically for high
PAGE 13 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
internal resistance. A PSU fault will be raised if 6.2 Mechanical Protection
high resistance is detected. This test involves
Warning:
loading the batteries so a battery load test is
also performed. The power supply uses hazardous voltages.
The unit is fitted with a protective cage to
6.1.5 Visual indications protect service engineers from electrical shock.
Do not attempt to open or access any of the
The Power Supply Unit has only one green LED.
internal components. The power supply
This indicates that there is power available on the
contains no user serviceable parts.
output of the power supply.
To prevent overheating, the ventilation holes in
6.1.6 Fault Conditions the cage must not be obscured.
The yellow fault wire from the PSU is normally at
27Vdc (nominal). The panel monitors this signal
and indicates a PSU fault if the voltage is removed.
6.2.1 DUO-CEL Power Supply Features
and Connections
Figure 5 shows the layout of the BAQ35T24 Power
Supply.
Leave the
Earth Wire to Earth wire 3cm
EARTH bar longer than the
Negative
Live & Neutral
Temperature
wires
Coefficient
Thermistor Input Power
Earth Wire to Connector. Connection to
Control Board Control Board
Mounting
Screw
TB2
NTC
GND
VR1
+V
B+
B-
L
- + N L
THERMISTOR
+V DC OUT
ADJ DC OUT TO PANEL 230VAC IN
27V
Thermistor
Connection to
Control Board
NOTE: The black wire may be connected to (B-) instead of (GND) on the PSU. This is quite normal and does
not affect the operation of the PSU in any way.
PAGE 14 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
ORB-OP-
Apollo Orbis Optical Smoke Detector 0.093 32 12 (13)
12001-APO
ORB-HT-
Apollo Orbis A1R Heat Detector 0.093 32 12 (13)
11001-APO
ORB-OH-
Apollo Orbis Multi-sensor Smoke/Heat Detector 0.093 32 12 (13)
13001-APO
ORB-HT-
Apollo Orbis CS Heat Detector 0.093 32 12 (13)
11006-APO
ORB-MB-
Apollo Orbis TimeSaver Base 0.000 N/A N/A
00001-APO
ORB-MB-
Apollo Orbis TimeSaver Base LX (simplified) 0.000 N/A N/A
00002-APO
ORB-DB-
Apollo Orbis TimeSaver Diode Base 0.000 N/A N/A
00003-APO
ORB-MB-
Apollo Orbis LX Base (low cost) 0.000 N/A N/A
00012-APO
ORB-BA-
Apollo Series 65 to ORBIS Base Adaptor 0.000 N/A N/A
10008-APO
Apollo 55000-217 Series 65 ionisation detector 0.035 32 16 (30)
Apollo 55000-317 Series 65 Optical detector 0.050 32 16 (24)
Apollo 55000-122 Series 65 heat detector A1R 0.035 32 16 (30)
Apollo 55000-125 Series 65 heat detector BR 0.035 32 16 (30)
Apollo 55000-132 Series 65 heat detector CR 0.035 32 16 (30)
Apollo 55000-137 Series 65 heat detector CS 0.035 32 16 (30)
Apollo 55000-200 Series 60 ionisation detector 0.035 32 NONE
PAGE 15 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Max. Max.
Devices Devices
Standby Per Per
Manufacturer Part no. Description Current standard Twin-wire
(mA) zone zone
(10uF
EOL)
Apollo 55000-210 Series 60 integrating ion detector 0.035 32 NONE
Apollo 55000-100 Series 60 Grade 1 heat detector 0.035 32 NONE
Apollo 55000-101 Series 60 Grade 2 heat detector 0.035 32 NONE
Apollo 55000-102 Series 60 Grade 3 heat detector 0.035 32 NONE
Apollo 55000-103 Series 60 Range 1 heat detector 0.035 32 NONE
Apollo 55000-104 Series 60 Range 2 heat detector 0.035 32 NONE
Apollo 55000-300 Series 60 optical detector 0.050 32 NONE
Apollo 55000-380 Series 60 optical/heat detector 0.050 32 NONE
Apollo 45681-200 Series 60 mounting base 0.000 32 NONE
KAC WR2072-470 Alert Manual call point (470R) 0.000 32 4
System
2351E Optical Smoke Detector 0.160 20 8
Sensor
System
2351TEM Optical & Heat Detector 0.270 10 4
Sensor
System
5351E ROR Heat Detector 0.140 20 8
Sensor
System
4351E High Temperature Heat Detector 0.140 20 8
Sensor
System
B401RSD Base c/w 470R resistor & Diode 0.000 20 8
Sensor
3. The maximum number of detectors and 7. When using twin-wire sounders, observe the
sounders per zone in section 7.1 assumes no following additional requirements:
mixing of devices. The total number of detectors a. DO NOT exceed the maximum number of
and/or manual call points per zone must not sounders per zone as listed in the above
exceed 32. This is a recommendation of BS table in section 7.1. These figures are based
EN54-2:1997 Annex D. The additional limitations on extensive testing and allow for operation
for twin-wire operation are listed in note (7)
below.
PAGE 16 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
at low battery voltage and no mains power, e. All detector bases must have a 1N4002
on long cable runs. diode fitted across the line IN and line OUT
terminals (usually on the positive line but
b. When mixing different types of sounders on sometimes on the negative line). Some
the same zone, use the lowest quantity detector bases come with Schottky diodes
shown in the table. For example, you can fitted. These are not compatible with the 2-
have 12 SQG3/SDR on a zone as long as no wire zone operation and must be replaced
other sounders are connected on that zone. with 1N4002 diodes. This applies even if no
If you want to mix SQG3/SDR with SQG3/AV sounders are connected. Use of a Schottky
then the TOTAL number of sounders on the diode will prevent the panel from detecting a
zone should be limited to 8 (e.g. 7 x detector head removal.
SQG3/SDR and 1 x SQG3/AV).
c. DO NOT leave any detector bases empty. All 8. If using detector bases without diodes fitted,
bases should have a detector fitted or be then removal of a detector head will result in an
linked through. Empty bases will introduce a open circuit of the cable. All devices fitted to the
diode into the positive line and this will zone cable beyond the detector head removed
adversely affect the operation of the will no longer be powered and will therefore not
sounders. operate. Only use detector bases without diodes
if the zone has no 2-wire sounders and no
d. Reducing the number of sounders WILL NOT Manual Call Points, or is configured to Resistor
allow more detectors to be used, unless no EOL.
sounders are connected (see number in
brackets in the table).
PAGE 17 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
SUPPLY ON
GENERAL FIRE 1 EVACUATE
GENERAL FAULT
2
GENERAL TEST SILENCE
GENERAL DISABLE 3 BUZZER
ALERT / EVAC ON
4 SILENCE /
FIRE SIGNAL ON RESOUND
FIRE SIGNAL FAULT 5
ALARMS
SNDR FLT / DIS / TEST
6 RESET
SYSTEM FAULT
PSU FAULT 7
FUSED FAILED DISABLE
8
EARTH FAULT
REPEATER FAULT
TEST
REMOTE I/P FAULT
CONTROLS ON
SELECT
PAGE 18 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
8.2 User Controls
SUPPLY ON
GENERAL FIRE 1 EVACUATE
GENERAL FAULT
2
GENERAL TEST SILENCE
GENERAL DISABLE 3 BUZZER
ALERT / EVAC ON
4 SILENCE /
FIRE SIGNAL ON RESOUND
FIRE SIGNAL FAULT 5
ALARMS
SNDR FLT / DIS / TEST
6 RESET
SYSTEM FAULT
PSU FAULT 7
FUSED FAILED DISABLE
8
EARTH FAULT
REPEATER FAULT
TEST
REMOTE I/P FAULT
CONTROLS ON
SELECT
PAGE 19 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
8.3 Selection of Zones or Outputs for 8.4 Disabled Zones and Outputs
Disablement, Enablement or Test Any or all of the zones can be disabled.
The panel provides a simple and straightforward A disabled zone will have power supplied to it but
means of selecting the sounder outputs and/or will not report fire or fault conditions. The zone
zones which need to be disabled, re-enabled or set power is switched off briefly when the zone is
to the test mode. The Fire Signal Output can also disabled, and also when the zone is re-enabled.
be disabled and enabled or placed into the test Detectors on a disabled zone are still able to enter
mode. the alarm condition but will not raise a fire alarm on
The zone or output is selected using the Circuit the panel.
Select feature. This allows the user to move a In the twin-wire mode, sounders on disabled zones
flashing cursor indication down through the yellow will still be activated during a fire alarm unless the
fault LEDs associated with the available circuits sounders have been disabled.
until the required zone or output is highlighted. The The fire panel will respond normally to fire device
yellow LED for the selected zone/output flashes in operations and wiring faults on all enabled zones.
“Cursor” mode, which is easily distinguishable from
all other indications. The following outputs can also be disabled and
enabled:
For each circuit that the Cursor is on, the General
Test and General Disablement LEDs will indicate All Sounder circuits including twin-wire (as a
the current status of the circuit; flashing Test group operation).
indicates the circuit is in Test mode, flashing The Fire Signal Output.
Disablement indicates the circuit is disabled. Both A disabled output will not report fault conditions and
LEDs OFF indicates the circuit is in normal will not be activated, although power for monitoring
operation. will still be applied.
If the circuit is in normal operation, pressing the
Disable button once will disable the circuit, 8.5 Detector Zone Test.
causing the General Disablement LED to flash
and the circuit fault LED to illuminate steady When selected to the Test mode, devices
(with flashing cursor). connected to the zone can be operated for test
purposes without operating the Fire Signal output or
If the circuit is in normal operation, pressing the the Fire Relay.
Test button once will set the circuit to test mode,
causing the General Test LED to flash and the The zone(s) to be set to the One Man Test
circuit fault LED to illuminate steady (with condition are selected using the Cursor Select
flashing cursor). feature described in 8.3.
The features of the One Man Zone Test condition
If the circuit is currently disabled, pressing the
are:
Disable button once will restore the circuit to
normal, causing the General Disablement LED A fire condition on a zone in Test Mode will not
to switch off and the circuit fault LED to switch operate any of the fire outputs.
off (with flashing cursor). Sounders operate for 5 seconds and then
If the circuit is currently in test, pressing the Test automatically silence. Sounders operate in
button once will restore the circuit to normal, general or zonal mode in accordance with the
causing the General Test LED to switch off and panel configuration.
the circuit fault LED to switch off (with flashing After each test the panel and the device being
cursor). tested are automatically reset allowing the next
If the circuit is currently disabled, pressing the device to be tested without needing to return to
Test button once will change the circuit status the panel to silence and reset.
from disabled to test mode, causing the General If a fire condition occurs on any zone other
Disablement LED to switch off and the General than a zone in test mode, the panel responds
Test LED to flash. fully to the fire condition as per its normal fire
If the circuit is currently in test, pressing the response and configuration.
Disable button once will change the circuit status
from test mode to disabled, causing the General 8.6 Alarm Sounder One man Test
Test LED to switch off and the General
Disablement LED to flash. The One Man Sounder Test operates all sounders
on an intermittent basis until the Test mode is
NOTE: Disablements are stored in EEPROM and manually cleared. This allows an engineer to walk
are not lost when the panel is powered down. Test the protected area and confirm the operation of all
conditions are cleared when the panel is powered the sounders. The sounder on/off cycle is 2
down. seconds on and 15 seconds off to allow operation
PAGE 20 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
to be confirmed without being too intrusive for other 9.1.1 Zone Dependency selection
occupants.
When the zone dependency configuration DIL
A genuine fire alarm condition overrides the test
switch (Depend Conf) is switched to the ON
mode and operates the sounders normally.
position, the panel sounds the internal buzzer and
illuminates the SYSTEM FAULT LED to indicate
9. Overview of Engineers that the programming mode has been initiated. The
Functions current status of the zones is displayed on the zone
fault LEDs; LED OFF – No Dependency, LED ON –
This section provides an overview of the functions zone configured for dependency.
available to the engineer.
Operation of the SELECT button will then switch
the Select cursor on, flashing at the zone 1 fault
9.1 Engineer’s configuration process LED.
On the DUO-CEL panel, most of the Engineer‟s Pressing the Select button again will move the
configuration facilities are controlled by DIL flashing cursor to the next zone. The cursor will be
switches located on the motherboard, accessed by switched off after the last zone (1, 2, 4 or 8,
removing the front cover of the panel. Each depending on the panel) or if no buttons are
configuration feature has its own dedicated DIL pressed for 30 seconds.
switch. The DIL switches are as follows:
Note that in the Engineer’s programming mode,
1: Z1 NON LATCH any faults, tests or disablements are masked
2: RESISTOR EOL and are not shown on the display. The panel will
3: ALERT MODE not respond to faults or fires.
4: DEPEND CONF With the cursor flashing on the required zone,
5: ZONAL ALARMS pressing the Disable button toggles the state of the
6: S/C FIRE Dependency mode for that zone.
7: AUX. RESET Once all required zones have been configured and
8: DISABLE BUZ the configuration DIL switch is returned to the OFF
9: REP CONFIG position, the panel will return to normal operation.
10: SNDR EXPAND (not used) Factory default:
11: SPARE All zones are configured for no dependency.
12: SPARE
Dependency Details:
Most functions simply require the appropriate DIL
switch to be either ON or OFF. This mode of operation conforms to BS EN54-
2:1997 Clause 7.12.1 Type A Dependency.
The DEPEND CONF DIL switch initiates a
programming mode in which the engineer is able to Operation of an automatic fire detector on a zone
select the required zone and set or clear it‟s configured to the dependency mode will not
dependency mode status. The dependency mode immediately indicate the fire alarm condition on the
status is stored in EEPROM and is not lost if the panel. A 30-minute counter will be started and the
panel is powered down. zone will be held in reset for 5 seconds (no power).
After the zone power is reinstated, if any automatic
The REP CONFIG DIL switch (not available on the 1
fire detector on the same zone operates within 30
& 2 zone panels) initiates a programming mode in
minutes, the panel will raise the fire alarm condition.
which the engineer is able to set the number of
repeaters connected to the panel. This data is If no detectors or MCPs are operated on the zone
stored in EEPROM and is not lost when the panel is before the 30-minute timer ends, the zone will
powered down. return to coincidence detection (i.e. a detector
alarm on the zone will start the 30-minute timer
On the DUO-CEL repeater, only two DIL switches
again).
are available:
Operation of Evacuate MCPs at any time will
1: NUM REP A
always raise a fire alarm immediately.
2: NUM REP B
Operation of an automatic fire detector or MCP on
Their setting is shown below:
any zone not configured for dependency will always
Repeater No. NUM REP A NUM REP B raise a fire alarm immediately.
0 (Disabled) OFF OFF
9.1.2 Repeater configuration
1 ON OFF
When the Repeater configuration DIL switch (REP
2 OFF ON
CONFIG) is switched to the ON position, the panel
3 ON ON sounds the internal buzzer and illuminates the
SYSTEM FAULT LED to indicate that the
programming mode has been initiated. The current
PAGE 21 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
status of the repeater configuration is also 9.4 Twin Wire
displayed on the Repeater Fault LEDs, which are
The Twin Wire panels support Fulleon twin-wire
visible when the front cover is removed.
sounders on the zone circuits along with compatible
Operation of the Select button will increment the detectors (see section 7.1).
number of repeaters, up to a maximum of 3, after
Each zone can monitor detectors and operate
which the number is reset to zero.
sounders on the same two wires. The sounders are
Number activated by pulsing the zone voltage between
REP1 FLT REP2 FLT REP3 FLT
of 11Vdc & 24Vdc (nominal).
LED LED LED
Repeaters The EOL device consists of a Zener diode and
0 OFF OFF OFF resistor which draws about 4mA in quiescent. A
1 ON OFF OFF detector head removal (assuming diode bases are
2 ON ON OFF used) will result in a small voltage drop, which the
3 ON ON ON panel can monitor & indicate a zone fault.
The zones are also capable of discriminating
Once the required quantity of repeaters has been
between detector and manual call point alarms and
configured and the configuration DIL switch is
so zone dependency mode is compatible with twin-
returned to the OFF position, the panel will return to
wire panels.
normal operation.
NOTE:
Factory default: No Repeaters
Only TYCO CP211 Manual Call Points can be
used. This is because standard call points will
9.2 Zone 1 Non-latch operation apply a resistive load and if multiple call points
The Zone 1 non-latch DIL switch allows zone 1 to are operated on a single zone then the load will
be set to non-latching fire indication. be too great to allow the twin-wire sounders to
In this mode a fire condition on zone 1 operates the operate. The CP211 contains current limiting
sounders but not the Auxiliary Fire Relay. The circuitry such that multiple call points will draw
alarm indication automatically clears when the fire as much current as a single call point (current
condition is removed from zone 1, without the need is shared between call points) and will not affect
to manually reset the panel. sounder operation. The CP211 also prevents
excessive loading on the zone when the zone
sounders are operated
9.3 Resistor EOL
The Resistor EOL DIL switch configures all zones 9.5 Alert Mode
to monitor an end-of-line resistor (6K8 to 3K9)
instead of the default 10uF capacitor. This feature The Alert Mode DIL switch configures all zones to
is not available on the twin-wire panel (i.e. the discriminate between detector alarms and MCP
switch has no effect). alarms. Detector Alarms are treated as Alert, MCP
alarms are treated as Evacuate.
In the default mode, the panel actively checks for
the presence of a 10uF capacitor at the end of the The Sounder circuits are pulsed (1.5 second on, 1.5
zone wiring. Diodes are fitted to detector bases and second off) during the Alert alarm and operate
removal of a detector will result in a fault condition continuously during the Evacuate alarm.
being raised at the panel whilst still providing power When used in conjunction with Zonal Sounder
to all devices on the zone. operation, a detector alarm will only pulse the
In Resistor EOL mode, the panel monitors the relevant zonal sounder circuit with all other sounder
current drawn by the EOL resistor and indicates a circuits silent. A MCP alarm will operate the
fault if the current drops below the threshold. relevant zonal sounder circuit continuously and
Diodes cannot be fitted to detector bases otherwise pulse all other sounder circuits.
a detector removal could not be detected. On the display, the left zonal fire LED operates for
Therefore, a removal of a detector will create an MCP alarms, the right zonal fire LED operates for
open circuit and remove power from all devices detector alarms.
beyond the removed detector. NOTE:
NOTE: Call points should be TYCO CP211 for Twin-
Resistor EOL monitoring is provided for older Wire panels. For the standard panels the TYCO
installations where it is difficult to change the CP211 or a conventional type may be used, but
EOL resistor to a capacitor. the MCP resistor needs to be 220R to 360R.
In addition, detector/MCP discrimination will not Standard call points with 470R to 680R will be
work when the zone monitoring is configured monitored as a detector alarm instead of a MCP
for Resistor EOL and therefore zone alarm alarm.
dependency (coincidence detection) and Alert This feature will not work correctly with
Mode will not work correctly. Resistor EOL monitoring.
PAGE 22 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
9.6 Selectable Zonal or General 9.8 Earth Fault monitoring.
Alarm Sounder operation The DUO-CEL panel is designed to monitor for low
The Zonal Alarms DIL switch allows the sounder impedance faults to earth on the field cables. Earth
circuits to operate zonally in line with the zone in faults can lead to false alarms or failure to operate
alarm. The actual operation of the alarm circuits will the sounders or other outputs.
vary depending on the type of zone detection and For installations where earth fault monitoring is
number of zones available on the panel. unsuitable, it can be disabled by removal of the
Twin-wire panels (1 to 8 zone): insulated jumper link (see Figure 3). The link can be
rotated and placed just on one pin rather than
All twin-wire sounders operate zonally, sounder
across both pins. This should be done only after
circuits on the motherboard operate as general
all field cabling has been tested and confirmed
alarms (i.e. all four alarm circuits on the
to be free from faults.
motherboard operate for any zone fire)
Standard panels, 1 to 4 zone panels: 10. Panel Repeaters
Sounder circuits 1 to 4 operate individually for a
The DUO-CEL repeaters duplicate the panel
fire condition on the respective zone.
indications and main user controls at a location
Standard panels, 8-zone panel: remote from the main panel. The repeater uses the
Sounder circuits 1 to 4 operate as general same enclosure & control board as the fire alarm
alarms (i.e. all four alarm circuits on the panel although most of the components are
motherboard operate for any zone fire). Zonal depopulated from the control board. Up to 3
sounder operation is not available. repeaters can be connected to a single panel using
an RS485 serial connection.
9.7 Buzzer Disable Each repeater can be powered either from the
The DISABLE BUZ DIL switch allows the panel Auxiliary 24Vdc output of the panel or an internal
buzzer and Buzzer Active output to be disabled so power supply (optional).
tat they do not operate for alarms or faults. The Note:
panel buzzer will still operate for button presses. The disable/enable/test facilities and the
The panel does not give any indication that the configuration functions are not available at the
buzzer has been disabled. This feature is repeaters.
provided for use during panel commissioning Repeaters cannot be used with the 1 & 2 zone
and maintenance only. Ensure that the DIL panels.
switch is returned to the OFF position after
commissioning/maintenance tests are
complete.
PAGE 23 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
10.1 Repeater User Indications
SUPPLY ON
GENERAL FIRE 1 EVACUATE
GENERAL FAULT
2
GENERAL TEST SILENCE
GENERAL DISABLE 3 BUZZER
ALERT / EVAC ON
4 SILENCE /
FIRE SIGNAL ON RESOUND
FIRE SIGNAL FAULT 5
ALARMS
SNDR FLT / DIS / TEST
6 RESET
REPEATER FAULT
REPEATER PSU FAULT 7
PANEL PSU FAULT TEST
8
EARTH FAULT
COMM FAULT
REMOTE I/P FAULT
CONTROLS ON
PAGE 24 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
10.2 Repeater User Controls
SUPPLY ON
GENERAL FIRE 1 EVACUATE
GENERAL FAULT
2
GENERAL TEST SILENCE
GENERAL DISABLE 3 BUZZER
ALERT / EVAC ON
4 SILENCE /
FIRE SIGNAL ON RESOUND
FIRE SIGNAL FAULT 5
ALARMS
SNDR FLT / DIS / TEST
6 RESET
REPEATER FAULT
REPEATER PSU FAULT 7
PANEL PSU FAULT TEST
8
EARTH FAULT
COMM FAULT
REMOTE I/P FAULT
CONTROLS ON
PAGE 25 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
SOUNDER OUTPUT
ZONE DETECTION CIRCUITS
CIRCUITS
PAGE 26 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
11.2 DUO-CEL Repeater Motherboard Figure 8 – Fire Signal Output Connections
Termination Details
Panel Terminals Field Wiring
Figure 7 below shows the available field wiring
terminals for the DC powered DUO-CEL Repeater.
The mains AC powered repeater does not have the
+ DIODE
1N4002
-
11.5 Fire Relay Output
The Fire Relay output is a single pole relay with
UNFUSED UNFUSED volt-free change over contacts. The relay is
24VDC 24VDC normally de-energised and energises for any fire
INPUT OUTPUT TO NEXT alarm condition. The relay remains energised until
(DC powered REPEATER panel reset. This relay will not energise if zone 1 is
repeaters only) (DC powered configured as non-latching and only zone 1 is in
repeaters only) alarm. See Figure 9 for details.
RS485
RS485 COMMS.
COMMS. TO NEXT 11.6 Fault Relay Output
FROM PANEL OR REPEATER
REPEATER The Fault Relay output is a single pole relay with
volt-free change over contacts. The relay is fail-safe
and is therefore normally energised, de-energising
11.3 Auxiliary Supply for any faults. The marking on the control board
An auxiliary supply is available to power the terminals is for the energised condition. See Figure
repeaters and other external field equipment from 9 for details.
the panel. This voltage is nominally 27.15VDC but
varies with temperature and during mains-failed NOTE:
conditions, depending on battery voltage. See The volt-free relay contacts are rated at 30Vdc
section 14 for details of maximum load. with a maximum current of 1A. Do not exceed
The output is fused using an electronic device, and the rated voltage and current.
fuse activation will be indicated as Fuse Failed on
Figure 9 – Relay contact connection details
the panel display. The fuse can be reset after
clearing the fault by operating the Reset button on Panel Circuit Field Wiring
the display.
The auxiliary supply terminals are labelled Aux N/O
0.25A 24V and 0V.
Fire Relay
An additional UNFUSED 24V output is provided on
repeaters for connection to additional DC powered P
repeaters. Fire Relay shown in
Note: If equipment draws current from the de-energised condition.
auxiliary supply during the mains-failed N/C
condition this must be included in the battery
capacity calculations.
N/O
11.4 Fire Signal Output
The Fire Signal output is fault-monitored in the non- Fault Relay
energised condition. It is designed to operate a
P
signalling relay at the routing equipment. The Relay
Fault Relay shown in
coil must be polarised and suppressed, because
energised condition.
the 10k end-of-line device is reverse-polarity
monitored for open & short circuit faults. See Figure N/C
8 for details.
PAGE 27 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
11.7 Remote Control Input faults to be cleared, returning the panel to the
quiescent state. The Auxiliary 24VDC supply may
A single 2-terminal input allows remote operation of
also be switched off for 10 seconds if configured to
the following functions:
do so.
Control Control When the Reset resistor is applied with the panel in
Function the fire alarm condition, any active sounder circuits
Level Resistor
1 Class Change 4K7 will be deactivated, all zone circuits will reset the
2 Alert 2K2 detectors, the fire relay will de-energise, the fault
3 Evacuate 1K relay will deactivate and all fire and fault indications
4 Remote Silence will clear. The Reset function is momentary and the
470R resistor needs to be removed and applied again in
Alarms
order to re-operate the Reset function.
5 Remote Reset 220R
Figure 10 – Remote Control I/P connections
Control Level 1 is lowest priority, 5 is highest
priority.
10K ¼ W EOL
The input is monitored for open and short circuit
faults. Each control level requires a different
resistor load as shown in the above table. A 10K
resistor acts as the end-of-line device for fault CLASS
monitoring. See Figure 10 for wiring details. CHANGE
4K7 ¼ W
11.7.1 Class Change
The Class Change function allows all sounder ALERT
2K2 ¼ W
circuits to be operated for a maximum of 5 seconds.
When the Class Change control resistor is applied,
the sounders will operate continuously and then EVACUATE
1K ¼ W
automatically silence after 5 seconds. No
indications will be given on the panel. The resistor
SILENCE
needs to be removed and applied again if the signal ALARMS
needs to be repeated. 470 ¼ W
PAGE 30 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Figure 14 – Resistor EOL Zone Wiring Figure 15 – Twin-Wire Zone Wiring Diagram
Diagram
6K8 to 3K9 (¼ W)
end-of-line resistor
EOL Device.
Zener & Resistor
Manual Call Point. + 1A 2A -
CP200, CP211,
CP230, CP260,
or equivalent with
internal resistor Sounder. + -
between 220R & 1K + 1 2 -
Twin-Wire sounder
+ -
ZONE 1
Z1 + Z1 – Detector. +
Smoke or Heat
Detector with -
1N4002 diode
base
+
ZONE 1
Z1 + Z1 –
PAGE 31 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Figure 16 – Alarm Circuit Wiring Diagram Figure 17 – Remote Indicators Wiring
Diagram
10K ¼ W
EOL Resistor
Current
Limiting
Resistors
+ -
Polarised 590R
Electronic 1.5W
Sounder
+ - minimum
24Vdc
+ Buzzer,
LED 50mA
+ - Indicators _
maximum
Polarised Or Lamps
Electronic current
Sounder
+ -
Solenoid
Driven Bell, + -
fitted with
polarising &
suppression
diodes
(1N4002)
Solenoid + -
Driven Bell,
fitted with
polarising &
suppression
diodes
(1N4002)
AL1+ AL1–
PAGE 32 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
11.11 Panel to Repeater Wiring If the cable includes a screen then this should be
earthed at the panel & all repeaters.
The Repeater RS485 communication and 24Vdc
power connections should all be made via a single Terminal A at the panel must be connected to
multi-core data cable. The number of cores Terminal A at all repeaters, Terminal B at the panel
required is two if the repeater is mains powered, or must be connected to Terminal B at all repeaters.
four if powered from the panel. A cable screen is
not required but is usually present in most data
cable types. The A & B lines should be connected
via one set of twisted pair cores, the 24V & 0V lines
should be connected via another set of twisted pair
cores.
To Next Repeater
PAGE 33 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
PAGE 34 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Environmental Specification
Ingress Protection
IP 30
Rating
Panel operating ambient
-5oC to +40oC
temperature range
Storage temperature
-10oC to + 70oC
range
Operating and storage
95% Non condensing
humidity
Max operational
Frequency range: 10 Hz to 150 Hz – acceleration amplitude: 0.1g.
vibration
Mains Supply Voltage Variations:
BSEN 50130-4: 1996
Mains Supply Voltage Dips and Interruptions:
BSEN 50130-4: 1996
EMC Radiated Immunity:
BSEN 50130-4: 1996 [Amd 1 & 2] clause 10
ESD:
BSEN 50130-4: 1996 [Amd 1 & 2] clause 9
Fast Transient Burst:
Electromagnetic
BSEN 50130-4: 1996 [Amd 1 & 2] clause 12
Compatibility
Surge:
BSEN 50130-4: 1996 [Amd 1 & 2] clause 13
Conducted Immunity:
BSEN 50130-4: 1996 [Amd 1 & 2] clause 11
Conducted Emissions:
BSEN61000-6-3: 2007
Radiated Emissions:
BSEN61000-6-3: 2007
PAGE 35 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Quiescent:
≥ 2.2mA, <11.7mA. (≥ 1k2, ≤ 8k4)
Ancillary Inputs
PAGE 36 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Outputs
Alarm Circuits
1-Zone 2-Zone 4-Zone 8-Zone
Quantity 2 2 4 4
Maximum Current
per circuit 0.5 0.5 0.5 0.5
[Amps]
Output Voltage
(battery operation) 27 – 20 (dependent on battery condition)
[Volts DC]
Output Voltage
(mains operation) 28.4 – 26.4 (dependent on temperature)
[Volts DC]
End-Of-Line resistor 10k
Fault Monitoring
Reverse polarity monitored for open and short circuit faults
Protection [Self
resetting electronic] 0.7 0.7 0.7 0.7
[Amps]
Cable resistance and current load must allow a voltage at the
Cable requirements end-of-line which is above the minimum operating voltage of the
sounders.
PAGE 37 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Auxiliary Supply
Maximum Current
0.25
[Amps]
Auxiliary supply
(battery operation) 27 – 20 (dependent on battery condition)
[Volts DC]
Auxiliary supply
(mains operation) 28.4 – 26.4 (dependent on temperature)
[Volts DC]
Protection
[Electronic] 0.4
[Amps]
Cable requirements Cable resistance and current load must allow a voltage at the
end-of-line which is above the minimum operating voltage of the
equipment connected.
Repeater Output
Number of repeaters 1 to 3
Maximum panel to
1200m
repeater cable length
Communication
RS485 serial data
protocol
Protection Electronic, current limited
Cable Type See Below
PAGE 38 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
PAGE 39 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
15.5 Power Supply Load Calculation
The power supply load must not exceed 1.5 Amps.
To determine the maximum power supply load perform the following steps:
1. Look-up the mains failed panel load in alarm. Enter this value as Ipanel.
2. Calculate the maximum load on the alarm circuits in mA in an alarm condition. Enter this value
as Ialarms.
3. Calculate the load on the auxiliary supply in mA in an alarm condition. Enter this value as Iaux.
4. Calculate the maximum power supply load using the formula below:
Ipanel = ______mA
Ialarms = ______mA
Iaux = ______mA
PAGE 40 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Ipanelfault = ______mA
Iauxfault = ______mA
Ifault = [Ipanelfault + Iauxfault] ______mA
Tfault = ______hrs
Ipanelalarm = ______mA
Ialarms = ______mA
Iauxalarm = ______mA
Ialarm = [Ipanelalarm + Ialarms + Iauxalarm] = ______mA
Talarm = ______hrs
Notes:
1. The DUO-CEL panel is designed to house and charge POWERSONIC 3.4Ah batteries to
80% capacity in 24 hours.
2. Any batteries that cannot be accommodated within the DUO-CEL enclosure must be
located in an enclosure adjacent to the DUO-CEL.
PAGE 41 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
Detectors on zones
Tyco M600 Series
Apollo Series 65
Apollo Orbis
PAGE 42 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
15.7 A1466 Interface Relay Polarity and suppression diodes are also mounted
on the board.
The A1466 Interface Relay board is available as an
optional item. The A1466 board should be mounted inside the
equipment to be controlled by the Fire Signal
This relay is compatible with the Fire Signal Output
output. The 10K EOL resistor should be connected
on the DUO-CEL panel. It provides two sets of volt-
across the 24V & 0V terminals of the A1466 board..
free normally open & normally closed contacts.
24VDC N/C
N/O TB2
TB1 P1
N/C
TB3
N/O
0VDC P2
Circuit Diagram
Specification
Terminals
Max conductor: 2.5mm.
24V, 0V: Relay coil connections – observe polarity . Dimensions
P1: Relay contact 1 pole. Board size: 30mm x 45mm.
N/C: Relay contact 1 normally closed. Height: 15mm.
N/O: Relay contact 1 normally open. Fixing centres: 24mm x 30mm
Fixing hole sizes: M4 clearance.
P2: Relay contact 2 pole.
N/C: Relay contact 2 normally closed. Installation
N/O: Relay contact 2 normally open. Must be installed within enclosure of
the equipment being controlled.
Ratings Environmental: Clean, dry location
Coil: Operating voltage range: 17.5 to 30VDC. not subject to excessive vibration or
Operating current: 8mA at 24VDC. shock.
Resistance: 2900 Ohms. Temperature: -10 to +70 deg C
Relay contacts: 2A at 30VDC
Warning – Do not exceed the rated voltage or
current.
PAGE 43 of 45
EQUIPMENT: FIRECLASS DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_APP CHECKED BY: AP
ISSUE No. & DATE: 0 01/03/12
PAGE 44 of 45
MAINS TERMINAL LABEL
BACKBOX
BATTERY CLAMP
PUBLICATION:
ISSUE No. & DATE:
0
LOGO
OM_DUO-CEL_APP
BOARD COVER
DISPLAY OVERLAY
FIRECLASS DUO-CEL
PAGE 45 of 45
SADDLE CLAMP
EARTH LEAD
SADDLE CLAMP
EARTH LEAD
CONTROL BOARD
THERMISTOR
PSU LEAD
MONITOR LEAD
KEY
FRONT
CHECKED BY: AP
COVER
WRITTEN BY: RKP