Fireclass Prec en Ouput Exp Mod App - 0

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP

PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP


ISSUE No. & DATE: 0 09/03/12 APPROVED BY: JBJ

Precept EN Output Expansion Module

Application Guide

PAGE 1 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12

Contents
1 GENERAL DESCRIPTION.................................... 3 List of Tables
2 GENERAL FEATURES ........................................ 3
3 OUTPUT MODULES – SPECIFIC FEATURES ......... 4 TABLE 1 – MAX QTY OF O/P MODULES SUPPORTED BY
3.1 C1633 – 8 WAY OPEN COLLECTOR [TYPE 1 EACH PANEL ...........................................................3
– INDICATION] MODULE .......................................... 4 TABLE 2 – MAINS INPUT SPECIFICATION ...................... 11
3.2 C1634 – 8 WAY VOLT-FREE RELAY [TYPE 2 TABLE 3 – POWER SUPPLY UNIT OUTPUT
FIRE PROTECTION] OUTPUT MODULE...................... 5 SPECIFICATION ....................................................11
3.3 C1635 – 8-WAY MONITORED/POWERED TABLE 4 – BATTERY SPECIFICATION ............................ 12
RELAY [TYPE 2 FIRE PROTECTION OR TYPE 3 TABLE 5 – EXPANSION MODULE SIGNALLING O/P
ALARM] OUTPUT MODULE. ..................................... 6 SPECIFICATION ....................................................13
C1630 OUTPUT INTERFACE .................................. 7 TABLE 6 – EXPANSION MODULE 24V AUXILIARY
4 OUTPUT MODULE ENCLOSURES........................ 7 SUPPLY O/P SPECIFICATION............................... 13
4.1 PRECEPT EN 8/16 EXPANSION OPTIONS .. 7 TABLE 7 – EXPANSION MODULE INPUT SPECIFICATION
4.2 PRECEPT EN 32 EXPANSION OPTIONS ..... 7 .............................................................................13
4.3 DEDICATED OUTPUT EXPANSION TABLE 8 – EXPANSION MODULE POWER CONSUMPTION
ENCLOSURES ....................................................... 7 SPECIFICATION ....................................................13
5 ORDERING INFORMATION ................................ 10 TABLE 9 – OUTPUT EXPANSION PANELS – MODULE
6 FIELD WIRING CONNECTIONS.......................... 10 ACCOMMODATION, PSU OPTIONS AND
7 MECHANICAL, ELECTRICAL & ENVIRONMENTAL MECHANICAL DETAILS .........................................14
SPECIFICATION FOR EXPANDED PANELS .................. 11
8 EXPANSION MODULE – I/O SPECIFICATION ...... 13

List of Figures
FIGURE 1 – C1633 PCB LAYOUT .................................. 4
FIGURE 2 – C1634 PCB LAYOUT .................................. 5
FIGURE 3 – C1635 PCB LAYOUT .................................. 6
FIGURE 4 – C1630 PCB LAYOUT .................................. 7
FIGURE 5 – PRECEPT EN 16 INTERNAL VIEW SHOWING
OPTIONAL SINGLE O/P BOARD .............................. 8
FIGURE 6 – PRECEPT EN 16L INTERNAL VIEW [32 ZONE
ENCLOSURE] WITH TWO OUTPUT BOARDS............ 8
FIGURE 7 – PRECEPT EN 5-WAY EXPANSION BOARD
ENCLOSURE – EXTERNAL VIEW ............................. 9
FIGURE 8 – PRECEPT EN EXP 5 INTERNAL VIEW .......... 9
FIGURE 9 – C1633 FIELD W IRING CONNECTIONS ...... 10
FIGURE 10 – C1634 FIELD WIRING CONNECTIONS .... 10
FIGURE 11 – C1635 FIELD WIRING CONNECTIONS .... 10
FIGURE 12 – PRECEPT EN 8/16, 8/16 EXP AND EXP 4
OUTPUT MODULE PANELS .................................. 15
FIGURE 13 – 8/16 ZONE PANEL AND EXP 4 OUTPUT
MODULE PANEL WITH NO PSU ........................... 16
FIGURE 14 – 8, 16 OR 32 ZONE PANEL & EXP 5 OUTPUT
MODULE PANEL WITH 5 AMP PSU ..................... 17
FIGURE 15 – 32 ZONE PANEL & EXP 5 OUTPUT MODULE
PANEL WITH NO PSU .......................................... 18
FIGURE 16 – PRECEPT EN 16L WITH INTERNAL O/P
MODULES AND EXP 4 OUTPUT MODULE PANEL
WITH PSU ........................................................... 19

PAGE 2 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
1 General Description 2 General features
 8 outputs per module.
The optional output expansion system provides a
range of output modules for use within the same  3 application types.
panel enclosure as the Precept EN 8, Precept EN o Type 1 – Indication output module.
16 or in an additional enclosure adjacent to the o Type 2 – Fire Protection output module.
Precept EN 8, Precept EN 16 and Precept EN 32
zone panels. The system comprises a o Type 3 – Sounder output module.
communication interface board and three output  Pre defined zone group allocation for types 1, 2
boards providing various output expansion options. and 3, which allows a group of 8 sequential
A total of 12 output boards can be supported via a zones to be allocated to each board. Zone
serial data link from the Precept EN panel. groups are - Zones 1-8, 9-16, 17-24, 25-32.
Various output options are available, which can be  All field wiring terminals for 2.5mm conductors.
configured to operate on zonal or general fire  Serial Data link to panel via ribbon cable.
conditions.  Power supply from fire panel via ribbon cable or
Low power applications can be powered from the from local PSU depending upon application.
24Vdc auxiliary power provided by the fire alarm
 Maximum quantity of modules per panel. See
panel [subject to load limitations]. For higher power
Table 1.
applications, PSUs and batteries can be
accommodated in the adjacent O/P expansion
module enclosure. Table 1 – Max Qty of O/P Modules supported by
A limited number of modules can be each panel
accommodated in fire panel enclosures. Two output
expansion enclosures, which match the 16 zone Max Qty of O/P Modules
and 32 zone fire panels, are available when higher Panel supported by each panel
quantities of modules are required. Type 1 Type 2 Type 3
Precept EN 8 1 1 1
Precept EN 16 2 2 2
Precept EN 32 4 4 4

PAGE 3 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
3 Output Modules – Specific Features  DIL switches to allocate module address.
 DIL switch to select module to general output
3.1 C1633 – 8 way open collector mode [all O/Ps operate for any zone in fire]
[Type 1 – indication] module operation or zonal operation.
 Typical application - zonal mimic type indicators.  DIL switches to allocate zone group.
 8 zonal open collector outputs rated at 60mA  LED indication for Module/Panel Comms Fault,
each. Module Processor Fault, Module Power Supply
Healthy.
 2 off 24V Auxiliary DC supply terminals
protected by a self-resetting monitored fuse.  Any failure of the Module or loss of the DC
[Max O/P 0.5Amps] supply that prevents the operation of the outputs
will raise a Common Fault alarm on the panel.
 Fuse failed signal indicated on Fire Panel.
 Header for optional local 24 and 0 volt power in.
 2 off fail-safe inputs to monitor local power
supply fault. [Mains failed and common PSU
fault].

Figure 1 – C1633 PCB Layout


Open Collector
+24V
+24V

24Vdc Output
OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8
Outputs 1 to 8

J2 Comms In/Out J2
OPEN COLLECTOR
OUTPUT BOARD

J6
J6 Comms In/Out
CEL C1633

05-05-2005
ISSUE 2

J4 – 24Vdc Power
In from panel or
Aux PSU, with J5 – Fit link to
optional PSU fault enable Auxiliary
monitoring inputs Power Supply Fault
J4
monitoring
0V +24

J3 – 24Vdc output J5
POWER
to other modules FAULT
ENABLE

SW1 – Configuration Switch.


0V +24

AD0 – Address bit 0 SW2 – Processor


AD1 – Address bit 1 J3
SW1
Fault Reset Button
ZN0 – Zone range bit 0
1

AD0
AD1
2

ZN1 – Zone range bit 1 ZN0


3

SW2

ZONAL – Zonal response


ZN1
4 5

ZONAL

PROC FAULT Power Supply ON LED


RESET
COMS

PROC

ON
PS

Communication Fault LED


FLT
FLT

Processor Fault LED

PAGE 4 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
3.2 C1634 – 8 way volt-free relay [Type  LED indication for Module/Panel Comms Fault,
2 Fire Protection] output module Module Processor Fault, Module Power Supply
Healthy.
 Typical application – non-EN54 type control of
ancillary equipment.  Any failure that prevents the operation of an
output is indicated on the panel as Fire
 8 off volt free changeover relay contacts rated at Protection Fault.
1 Amp at 30 V DC.
 All type 2-module outputs are disabled by the
 DIL switches to allocate address. common Fire Protection disablement facility
 DIL switch to select module to general output provided by the Precept EN.
mode [all O/Ps operate for any zone in fire]
operation or zonal operation.
 DIL switches to allocate zone group.

Figure 2 – C1634 PCB Layout


OP1 OP2 OP3 OP4 OP5 OP6 OP7 OP8

N/O
CEL C1634

05-05-2005

Relay Outputs:
ISSUE 2

N/O – normally open

POLE
POLE – common
N/C – normally closed

N/C
J2
J2 Comms In/Out
1 2 3 4 56 7 8
8 WAY RELAY BOARD

J3 Comms In/Out J3

SW1 – Configuration Switch.


AD0 – Address bit 0
AD1 – Address bit 1
ZN0 – Zone range bit 0 SW2 – Processor
ZN1 – Zone range bit 1 SW1
Fault Reset Button
ZONAL – Zonal response
1

AD0
AD1
2

VDR – Voyage Data ZN0


3

SW2

ZN1
4 5

Recorder output mode ZONAL

(for Marine Panel Use Power Supply ON LED


6

VDR PROC FAULT


RESET

only)
COMS

PROC

ON
PS

Communication Fault LED


FLT
FLT

Processor Fault LED

PAGE 5 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
3.3 C1635 – 8-way monitored/powered  DIL switches to allocate zone group.
relay [Type 2 Fire Protection or  LED indication for Module/Panel Comms Fault,
Type 3 Alarm] output module. Module Processor Fault, Module Power Supply
Healthy.
 8 off fault monitored, powered outputs, all
open/short circuit fault monitored. Outputs  Synchronised pulsed alarms across all sounder
provide a 24 /0VDC output in the alarm [active] modules via a special command code
condition. implemented in the comms protocol.
 Terminals for optional local 24 and 0 volt power  Any failure that prevents the operation of an
in. output is indicated on the panel as Fire
Protection Fault or Sounder Fault depending on
 2 off fail-safe inputs to monitor local power
the module type configuration.
supply fault. [Mains failed and common PSU
fault].  When configured as type 2 modules, all outputs
are disabled by the Precept EN’s common Fire
 8 off zonal fault LEDs to indicate a fault detected
Protection disablement facility. When configured
condition on each output.
as type 3, all outputs are disabled by the
 DIL switch for site configuration as type 2 [all common Sounder disablement facility.
Fire Protection Outputs] or type 3 [all sounder
circuits].
 DIL switches to allocate address.

Figure 3 – C1635 PCB Layout


8 WAY MON O/P BD
+ OP1 - + OP2 - + OP3 - + OP4 -

Outputs 1 to 8
(Top row = 1 to 4,
Bottom row = 5 to 8)

+ OP5 - + OP6 - + OP7 - + OP8 -


J2
J2 Comms In/Out

J6
J6 Comms In/Out

J3 – 24Vdc Power In
from panel or Aux PSU,
J4 – Fit link to
with optional PSU fault
enable Auxiliary
monitoring inputs
Power Supply Fault
monitoring
0V +24

J5 – 24Vdc output to J3 J4

POWER
other modules FAULT
ENABLE
Communication
SW1 – Configuration Switch. Fault LED
0V +24

AD0 – Address bit 0


SW2 – Processor
AD1 – Address bit 1 J5
SW1
Fault Reset Button
ZN0 – Zone range bit 0
1

AD0
AD1
ZN1 – Zone range bit 1
2

ZN0
3

SW2

ZONAL – Zonal response ZN1


4 5

ZONAL
FP – Fire Protection FP Power Supply ON LED
6

PROC FAULT
RESET
Outputs
1
2
3
4
5
6
7
8
COMS

PROC

ON
PS
FLT
FLT

OUTPUT FAULTS
Fault LEDs for each output CEL C1635 ISSUE 2 05-05-2005 Processor Fault LED

PAGE 6 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
C1630 Output Interface C1652 5Amp PSU fitted in place of the standard 3
Amp version to cater for an additional output load.
This board provides the RS485 communications
between the panel and output modules. It includes Expansion beyond two boards is provided by the
a 7-way DIL switch used to set up the total quantity addition of a separate enclosure as described in 4.2
of each type of O/P module connected to the panel. below.
The C1630 is plugged into sockets J4 and J5
located in the upper right hand quarter of the C1627 4.2 Precept EN 32 Expansion Options
motherboard, under the fault routing relay. The 2 The 32-zone panel has no space for expansion
sockets are dissimilar which assists the correct within the standard product. All expansion is
fitting and orientation of the board [see Figure 5 and provided in a separate enclosure described in 4.3
Figure 6]. below
Figure 4 – C1630 PCB Layout
4.3 Dedicated Output Expansion
Enclosures
Expansion beyond the capabilities of enclosures
1

F/P 0
F/P 1 Configuration Switch already described is provided by two external
2

expansion boxes, one to match the Precept EN 16


S/C 0 to set quantity & type
3

S/C 1
fire panel enclosure and the other to match the
4 5

of modules connected. Precept EN 32. These enclosures are fitted with a


LED 0 completely blank door hinged at the right and
6

LED 1
include space for an optional C1652 5A power
7

VDR
supply.
The enclosures are designed to be installed to the
right of the fire panel enclosure. O/P expansion
wiring passes between the panel and expansion
enclosures through a 25mm knockout on the right
of the panel and the left of the expansion box. The
boxes can be joined by a 25mm cable bush to
provide enclosure integrity and mechanical
4 Output Module Enclosures alignment.
In the unlikely event of more than five modules
4.1 Precept EN 8/16 Expansion being required on a 32-zone panel, these can be
provided in further expansion boxes of five
Options
modules, joined in the same way. The second and
Precept EN 8 zone and 16 zone panels have space subsequent boxes will require spacing apart to
within their standard enclosures for a single I/O avoid door interference between the doors when
board as shown in Figure 5. opening the third and subsequent enclosures.
The Precept EN 16 is available in an extended
enclosure with space for two I/O boards as shown
in Figure 6. The 16 zone extended panel has a

PAGE 7 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 5 – Precept EN 16 internal view showing optional single O/P board

Secondary Earth bar 3 x Enclosure Cable Clip for incoming Mains Warning /
for cable screens fixing holes mains cable Primary Earth Label
Mains
Terminal
Block and
primary Earth
Removable
Connection
Chassis

CHANGE

ACTIVE
ZONE CIRCUITS ALARM CIRCUITS AUX INPUTS OUTPUTS REPEATER

RESET
ZONE OUTPUTS

CLASS

EVAC.
EVAC

BUZ.
RST.

SCN
A
B
DIS.
D.C.

N/O
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-

SIL.
1 2 3 4
1 2 3 4 + - + - + - + -

Removable
24V 0V

TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21

RL1
RL2
RL3
RL4
RL5
RL6
RL7
RL8
+
9
- +
10
- +
11
- + - + - + -
12 13 14
+
15
- +
16
-
FS6

O/+ P C/-
FAULT ROUTING
C/+ P O/-
FIRE ROUTING
C/+ P O/-
FIRE PROTECTION
N/C P
RESET
Chassis
N/O
ZONE CIRCUITS

I/O EXPANSION
J17
J16 J15 J14
J12 J11 J10
J17

J6
J8 J7
N/C

Motherboard

J20
COM

Relay output

C1630 ISSUE 0
SW1 SW1

ZONE EXPANSION
R0

CEL C1631 ISSUE 0


F/P 0

1
F/P 1 R1 J20

2
S/C 0 R2

3
Module
S/C 1

4
LED 0

5
LED 1

6
Mains
LOG

7
+

C88
HS2
+
BUZ1 C78

+
Transformer
C78

BUZ1

HS1
BR1
U27

C1630

~ ~
Output
C84

TB23
J1

BR1
U13
U1
U28
DISPLAY

R296A
J1 VR1

Expansion
OUTPUT R296B
R297B
VR1
R297B
SW1 SW2
INHIBIT F/P ON NLZ SILENCE BEFORE RESET D52
1

DELAY ALARM SIL & RESET 1 +

C90
2

DELAY ON AUTO 2 J18B


3

DELAY/ I1
MINUTES
CONFIG CONFIG NON-LATCH ZONES 4

Interface
4

L1 L2 OUTPUT
ENABLED
CONFIG I/S ZONES 8 OK
5

C90
D51
CONFIG M/S ZONES ZONAL ALARMS BAT/CHG
6

L3
FAULT
CONFIG DELAY ZONES PULSE NON-ALARM ZONES
7

CONFIG DELAY O/PS SILENT ZONE TEST L4 INTERNAL


8

FAULT
2 STAGE DELAY BUZZER DISABLE
9 10

9 10

TB11 TB13 MAINS

Board
L5
ORIGN1 ALARMS ON EVAC ONLY LATCHED FAULTS FAULT
FS1 - +
C1627 ISSUE 1 BATTERY FUSE BATT THERM

Motherboard

Batteries
Batteries

Figure 6 – Precept EN 16L internal view [32 zone enclosure] with two Output boards

Secondary Earth bars 3 x Enclosure Cable Clip for incoming Mains Warning /
for cable screens fixing holes mains cable Primary Earth Label

Mains
Terminal
Block and
primary Earth
Connection
CHANGE

ACTIVE

ZONE CIRCUITS ALARM CIRCUITS AUX INPUTS OUTPUTS REPEATER


RESET
CLASS

ZONE OUTPUTS
EVAC.
EVAC

OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8

OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8
RST.

BUZ.

SCN
DIS.

A
B

D.C.
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
N/O
SIL.

1 2 3 4
1 2 3 4 + - + - + - + - 24V 0V

Removable
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21 O/C O/C

FS6

+ - + - + - + - + - + - + - + - O/+ P C/- C/+ P O/- C/+ P O/- N/C P +24V +24V


9 10 11 12 13 14 15 16

Chassis
FAULT ROUTING FIRE ROUTING FIRE PROTECTION RESET
I/O EXPANSION

ZONE CIRCUITS
J17
J16 J15 J14
J12 J11 J10

J17
J6

+ - + -
J8 J7

LOOP IN LOOP OUT


J20
ZONE EXPANSION

LOOP
C1630 ISSUE 0

SW1 SW1

INTERFACE R0
CEL C1631 ISSUE 0

F/P 0
1

Output
F/P 1 R1 J20
2

BOARD S/C 0 R2
3

S/C 1
4

LED 0
5

LED 1
6

LOG
7

+
C88

BUZ1 C78
+ HS2

Modules
+

C78

BUZ1

U27

HS1
BR1
~ ~

C84
TB23
J1

C1630
+
BR1

U13
U28
DISPLAY

R296A
J1 VR1
OUTPUT R296B
R297B
VR1

Output
R297B
SW1 SW2
INHIBIT F/P ON NLZ SILENCE BEFORE RESET D52
1

DELAY ALARM SIL & RESET 1 +


C90
2

DELAY ON AUTO 2 J18B


3

DELAY/ I1
MINUTES
CONFIG CONFIG NON-LATCH ZONES 4
4

L1 L2 OUTPUT
ENABLED
CONFIG I/S ZONES 8 OK
5

C90
D51
CONFIG M/S ZONES ZONAL ALARMS BAT/CHG
6

L3

Expansion
FAULT
CONFIG DELAY ZONES PULSE NON-ALARM ZONES
7

CONFIG DELAY O/PS SILENT ZONE TEST L4 INTERNAL


8

FAULT
2 STAGE DELAY BUZZER DISABLE
9 10

9 10

ORIGN1 ALARMS ON EVAC ONLY LATCHED FAULTS


TB11 TB13 L5 MAINS
FAULT
FS1 - +
C1627 ISSUE 1 BATTERY FUSE BATT THERM

Interface
Board

Motherboard
with 5A PSU
&
Transformer
underneath

Batteries

PAGE 8 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Figure 7 – Precept EN 5-way expansion board enclosure – external view

441mm
400mm 131mm

Figure 8 – Precept EN Exp 5 internal view


Secondary Earth bars 3 x Enclosure Cable Clip for incoming Mains Warning /
for cable screens fixing holes mains cable Primary Earth Label
Mains
Terminal
Block and
primary Earth
Connection

Removable
Chassis

Space for up
to 5 Output
Boards

PSU &
transformer
mounted
under the
output boards

Batteries

PAGE 9 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
5 Ordering Information
Part Number Description
FIRECLASS Precept EN 8 [3A PSU] in enclosure with space for 1 O/P module.
508.032.703 Note: Order 2605330 and output board separately.
FIRECLASS Precept EN16 [3A PSU] in enclosure with space for 1 O/P module.
508.032.704 Note: Order 2605330 and output board separately.
FIRECLASS Precept EN 16L [5A PSU] in expanded enclosure with space for 2 O/P modules.
508.032.705 Note: Includes C1630 interface and cable. Order output boards separately.
FIRECLASS Precept EN Exp 4. 4-way expansion board enclosure (c/w board fixings, earth bars).
2605326 Note: Order output boards [c/w wiring] separately.
FIRECLASS Precept EN Exp 4. 4-way expansion board enclosure with 5A power supply (c/w board
2605327 fixings, earth bars and internal power lead).
Note: Order output boards [c/w wiring separately.
FIRECLASS Precept EN Exp5. 5-way expansion board enclosure (includes board fixings, earth bars).
2605328 Note: Order output boards [c/w wiring] separately.
FIRECLASS Precept EN Exp 5. 5-way expansion board enclosure with 5A power supply (includes
2605329 board fixings, earth bars and internal power lead).
Note: Order output boards [c/w wiring] separately.
FIRECLASS Precept EN IO expansion installation kit (c/w C1630 expansion interface and fixing
screws).
2605330 Note: Required to use expansion boards with parts 2605102, 2605103 and 2605104 [32 zone panel]
only
2605063 C1633 8 way open collector output board, ribbon cable and power lead
2605064 C1634 8 way relay board and ribbon cable [power lead not required]
2605065 C1635 8 way alarm board, ribbon cable and power lead

6 Field Wiring Connections Figure 11 – C1635 Field Wiring Connections


Figure 9 – C1633 Field Wiring Connections Typical Alarm Typical Remote
Typical LED indication wiring Circuit Wiring Relay Circuit
3k9 resistor
Wiring
2k2 0.5W

end-of-line
resistor

Max current sink into O/P: 60mA


Max load on 24V [total for both Suppression diode
+24V O/Ps]: 0.5A
+ -
+24V
+24V
OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8

+ -
3k9 resistor
I/P polarised end-of-line
[All sounder
devices] + - Polarising diode

C1633 Open collector output module terminals + -

Figure 10 – C1634 Field Wiring Connections


+ OP1 - + OP2 - + OP3 - + OP4 -
Relay contact rating: 1A at 30Vdc
Do not exceed Lower
OP1 OP2 OP3 OP4 OP5 OP6 OP7 OP8 terminal
tier
Lower
N/O

terminal Upper
tier terminal
tier
Middle
POLE

+ OP5 - + OP6 - + OP7 - + OP8 -


terminal
tier C1635 powered/fault monitored
output module terminals [2- tier]
Upper
N/C

terminal
tier
C1634 Volt free relay output module
terminals [3- tier]

PAGE 10 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
7 Mechanical, Electrical & Environmental Specification for Expanded Panels

Table 2 – Mains Input Specification


Expansion Panel
Mains Input
Specification Precept EN 8 with
Precept EN16L Precept EN Exp 4 Precept EN Exp 5
1 x O/P module
Maximum Input Power: 165W 240W 240W 240W
Protection:
[Warning: Replace T3.15A T3.15A T3.15A T3.15A
only with identical H250V H250V H250V H250V
type & rating of BEAB [3.15A anti-surge] [3.15A anti-surge] [3.15A anti-surge] [3.15A anti-surge]
or VDE approved fuse]
Voltage: 230V AC +10%/-15%
2
Cable requirements: Minimum of 1mm copper protected by a 5A fuse.

Table 3 – Power Supply Unit Output Specification

Expansion Panel
Power Supply Output
Precept EN 8 with Precept EN Exp 4 Precept EN Exp 5
Specification Precept EN16L
1 x O/P module [2605327] [2605329]
Maximum Short Term
Current Output 3A 5A 5A 5A
(I max b)
Maximum Continuous
Current Output 2A 2A 2A 2A
(I max a)
N/A (PSU is part
Minimum Output Current
of the 0A 0A 0A
(I min)
motherboard)
Voltage Output, Mains
26.5 - 28.6V (27.3V Nominal)
On
Maximum Current
3A 5A 5A 5A
Output, Mains Failed
Voltage Output, Mains
Failed 20.0* - 28.6V 20.0* - 28.6V 20.0* - 28.6V 20.0* - 28.6V
[* at full load]
Max Ripple including
switching spikes [full
load/battery 200 750 750 750
disconnected]
(mV p-p)
Output Voltage
Factory Set
adjustment:
Output protection: Electronic current limiting
Common fault output: N/A 25mA 25mA 25mA
Mains failed fault output: N/A 25mA 25mA 25mA

PAGE 11 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Table 4 – Battery Specification

Expansion Panel
Battery Specification Precept EN 8 and
Precept EN 16L Precept EN Exp 4 Precept EN Exp 5
16 with 1 x O/P
[2 O/P modules] [4 O/P modules] [5 O/P modules]
module
Battery charger output:
[Temperature
compensated float
charger 3A 5A 5A 5A
28.6V 0.1V@-5C
26.5 V0.1V@ +40 C.
Maximum internal
resistance of battery &
charger cicuit 0.6Ω 0.35Ω 0.35Ω 0.35Ω
(Ri max)
Battery type:
2 off 2 off 2 off 2 off
POWERSONIC
PS1270 PS12180 PS12120 PS12180
[Warning: Replace only
[12V 7Ah] [12V 18Ah] [12V 12Ah] [12V 18Ah]
with identical battery]
Battery size (mm):
W

L = 151 L = 181 L = 151 L = 181


W = 65 W = 76 W = 98 W = 76
H = 94 H = 167 H = 94 H = 167
HT H
HT = 98 HT = 167 HT = 100 HT = 167

Battery circuit protection:


F5AL250V 20mm F6.15A F6.15A F6.15A
[Warning: Replace only fast blow glass L250V 20mm fast L250V 20mm fast L250V 20mm fast
with identical type & fuse blow glass fuse blow glass fuse blow glass fuse
rating of fuse]
Mains failed fault battery 45mA + module 50mA + module 17mA + module 17mA + module
current: current current current current
Mains failed alarm battery 80mA + module 85mA + module 17mA + module 17mA + module
current: current current current current

Environmental
All Panels
Specification
Operating temperature: -5ºC to 40ºC
Operating humidity: 5% to 95%

PAGE 12 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
8 Expansion Module – I/O Specification
Table 5 – Expansion Module Signalling O/P Specification

Expansion Module
C1633 C1634 C1635
Signalling O/Ps
Qty of Outputs/module 8 8 8
2 wire, reverse polarity
Single pole change over open and short circuit
Output description Open collector
volt-free relays fault monitored, powered
when activated.
Output Quiescent Off. De-energised Fault monitoring mode
Operating
conditions Alarm On Energised Powered
Volt-free contacts rated 0.5 A at 24 V [nom]
Activated O/P 60mA 30 V max 1Amp at 30VDC. [Subject to PSU
Do not exceed. limitations]
Protection [Self resetting Protection [Self resetting
O/P Protection electronic] N/A electronic]
Fuse rating 0.5A Fuse rating 0.5A
No special requirements.
1A minimum current
rating. Minimum voltage
Cable requirements No special requirements. N/A at end-of-line must be
above sounding device
minimum operating
voltage.

Table 6 – Expansion Module 24V Auxiliary Supply O/P Specification

Expansion Module 24V


C1633 C1634 C1635
Auxiliary Supply O/Ps
Qty 2 N/A N/A
Maximum Current: 0.5A total for the 2 O/Ps N/A N/A
Auxiliary supply (battery
20–27 VDC N/A N/A
operation):
Auxiliary supply (mains
28.6 – 26.5 V DC N/A N/A
operation):
Protection: [Electronic] 0.5 A N/A N/A
Cable requirements No special requirements. N/A N/A

Table 7 – Expansion Module Input Specification

Expansion Module
C1633 C1634 C1635
Inputs
Non-fault monitored. 0V Non-fault monitored. 0V
PSU and Mains Failed
I/P to activate. I/P N/A I/P to activate. I/P
I/Ps [local I/P]
sensitivity: 0-1k Ohm sensitivity: 0-1k Ohm

Table 8 – Expansion Module Power Consumption Specification

Expansion Module
C1633 C1634 C1635
Power Consumption
Quiescent (including
15mA 15mA 20mA
mains failed)
All outputs active 25mA 95mA
70mA
(including mains failed) [Not including field load] [Not including field load]

PAGE 13 of 19
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD APP CHECKED BY: AP
ISSUE No. & DATE: 0 09/03/12
Table 9 – Output Expansion Panels – Module Accommodation, PSU Options and Mechanical Details

Enclosure Top
Number
Dimensions Entry
of Weight,
Part PSU W cable
Panel Panel Description Modules excluding
Number options H Entry
in batteries
D Knock -
enclosure
[mm] outs
230V 3A
[Part of 370
Precept EN Standard Precept EN 8
508.032.703 1 Panel]. 325 7.1kg 26
8 panel
7 or 12Ah 126
battery
230V 3A
[Part of 370
Precept EN Standard Precept EN 16
508.032.704 1 Panel]. 325 7.1kg 26
16 panel
7 or 12Ah 126
battery
C1652
230V 5A
441
Precept EN Expanded Precept EN 16 PSU
508.032.705 2 400 9.3kg 32
16L in 32 zone enclosure 7,12 or
131
18Ah
battery
4-module O/P expansion
Precept EN 370
enclosure with blank door.
Exp 4 2605326 4 No PSU 325 5.1kg 26
Matches Precept EN 8/16
[no PSU] 126
zone enclosure.
4-module O/P expansion
Precept EN 230V 5A 370
enclosure with blank door.
Exp 4 2605327 4 7 or 12Ah 325 8.4kg 26
Matches Precept EN 8/16
[with PSU] battery 126
zone enclosure.
5-module O/P enclosure
441
Precept EN with blank door. Matches
2605328 5 No PSU 400 5.9kg 32
Exp 5 Precept EN 32 zone
131
enclosure.
5-module O/P enclosure 230V 5A
441
Precept EN with blank door. Matches with 3,7,12
2605329 5 400 9.2kg 32
Exp 5 Precept EN 32 zone or 18Ah
131
enclosure. battery

PAGE 14 of 19
Precept EN 8 or 16 fire panel with 1 x C1634 V/F Relay O/P module Precept EN 16L with 2 x C1635 Sounder O/P module
C1634 C1635 C1635
J2 J2 J2
Data ribbon Data ribbon
EQUIPMENT:

J17 J17
PUBLICATION:

C1627 C1627
Motherboard J3 Motherboard J6 Data J6
ISSUE No. & DATE:

with 3Amp with 3Amp ribbon


PSU PSU
J3 J3
0

Aux DC Aux DC
J24 J24
J5 J5

Max current for O/P modules = 2.5A


PSU load calculation must be
09/03/12

[156mA/output for 2 x modules]


carried out for each application

Precept EN 16 Panel with internal Output Modules Precept EN Exp 4 [4 way O/P expansion enclosure with 4
modules powered from the Precept en panel
C1633 C1635 C1633 C1635 C1634 C1634
Data
J2 J2 Data J2 Data J2 J2
ribbon J2
ribbon ribbon
J17
Data

PAGE 15 of 19
FIRECLASS PRECEPT EN

C1627 J6 ribbon J6 J6 Data J6 J3 Data J3


Motherboard ribbon ribbon

Aux DC J4 J3 J4 J3
J24 Aux DC Aux DC
J3 J5 J3 Aux DC J5

Note: All C1634


FIRECLASS PREC EN OUTPUT EXP MOD APP

modules must be
connected at the end
Standard Panel Expansion Systems. of the sequence
PSU load calculation must be
Figure 12 – Precept EN 8/16, 8/16 Exp and Exp 4 Output Module Panels

1] Precept EN 8 with 1 off O/P module. carried out for each application
2] Precept EN 16 with 1 off O/P module.
3] Precept EN 16L with 2 off O/P modules.
4] Precept EN 16 with Exp 4 [4 way O/P enclosure with max 4 O/P modules,
with or without optional 5 Amp PSU and batteries]. Note: To reduce the quantity of standard cable looms, any modules that are to be powered from the
fire alarm panel need to be located in the left hand side of the output expansion enclosure.
CHECKED BY: AP

5] Precept EN 32 with Exp 5 [5 way O/P enclosure with max 5 O/P


WRITTEN BY: RKP

modules, with or without optional 5 Amp PSU and batteries].


EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:

Precept EN 8 or 16 Panel [no internal Output


0

Precept EN Exp 4 [4 way O/P expansion enclosure with 4


Modules] modules powered from Precept EN panel]
C1633 C1635 C1634 C1634
Data
ribbon J2 J2 Data J2 J2
ribbon
09/03/12

J17
C1627 J6 Data J6 J3 Data J3
Motherboard ribbon ribbon

Aux DC J4 J3
J24
J3 J5
Aux DC

PAGE 16 of 19
FIRECLASS PRECEPT EN

Note: All C1634 modules must be


connected at the end of the sequence

Standard Panel Expansion Systems. PSU load calculation must be


carried out for each application
1] Precept EN 8 with 1 off O/P module.
2] Precept EN 16 with 1 off O/P module.
3] Precept EN 16L with 2 off O/P modules.
FIRECLASS PREC EN OUTPUT EXP MOD APP

4] Precept EN 16 with Exp 4 [4 way O/P enclosure with max 4 O/P Note: To reduce the quantity of standard cable looms, any modules that are to be
modules, with or without optional 5 Amp PSU and batteries]. powered from the fire alarm panel need to be located in the left hand side of the output
5] Precept EN 32 with Exp 5 [5 way O/P enclosure with max 5 O/P expansion enclosure.
modules, with or without optional 5 Amp PSU and batteries].
Figure 13 – 8/16 zone panel and Exp 4 Output Module Panel with no PSU
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:

Precept EN Exp 5 [5 way O/P expansion enclosure with 5 modules c/w 5 Amp PSU ] Note: All C1634
Precept EN 8, 16 or 32 modules must be
0

connected at the end


C1633 C1635 C1635 C1635 C1635
of the sequence
Data Data Data Data
J2 J2 J2 J2 J2
ribbon ribbon ribbon ribbon
J17
09/03/12

C1627 Data
J6 J6 J6 Data J6 J6
Motherboard ribbon ribbon
Further expansion
J4 J3 J3 J3 J3 modules
J24 Aux DC or use
J3 Aux DC J5 Aux DC J5 Aux DC J5 Aux DC J5 additional PSU
Aux DC

CFlt

PAGE 17 of 19
FIRECLASS PRECEPT EN

MFlt
C1652 Power lead TB5
0V
28V PSU load calculation must be
Aux DC, Mains Flt & TB1 carried out for each application
C1652
Comm PSU Flt PWR
& Flt 5 Amp
O/Ps PSU
J1
FIRECLASS PREC EN OUTPUT EXP MOD APP

Note: To reduce the quantity of standard cable looms, any modules that are to be powered from the
fire alarm panel need to be located in the left hand side of the output expansion enclosure.
Figure 14 – 8, 16 or 32 zone panel & Exp 5 Output Module Panel with 5 Amp PSU
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
0

Note: All C1634


Precept EN 32 Precept EN Exp 5 [5 way O/P expansion enclosure ] modules must be
with 5 Amp PSU connected at the end
C1633 C1635 C1635 C1635 C1635
of the sequence
Data Data
09/03/12

J2 J2 J2 J2 J2
ribbon Data ribbon Data ribbon ribbon
C1627 J17
Precept EN J6 J6 J6 J6 J6 Further expansion
Aux DC Data ribbon Data ribbon
Motherboard J24 modules
J4 J3 J3 J3 J3 Aux DC or use
J19 additional PSU
J3 Aux DC J5 Aux DC J5 Aux DC J5 Aux DC J5
Aux DC

J1

PAGE 18 of 19
FIRECLASS PRECEPT EN

C1652 PWR
5 Amp & Flt
O/Ps
PSU
TB1 PSU load calculation must be
28V carried out for each application
0V
TB5
MFlt
CFlt
FIRECLASS PREC EN OUTPUT EXP MOD APP

Figure 15 – 32 zone panel & Exp 5 Output Module Panel with no PSU
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT:
PUBLICATION:

Precept EN Exp 4 [4 way O/P expansion enclosure with 4


ISSUE No. & DATE:

Precept EN 16L Panel with internal Output Modules


modules powered from the Precept EN panel
0

C1633 C1635 C1633 C1635 C1634 C1634


Data
J2 J2 Data J2 Data J2 J2
ribbon J2
ribbon ribbon
J17
Data
C1627 ribbon Data
J6 J6 J6
09/03/12

J6 J3 Data J3
Precept EN ribbon ribbon
Motherboard
Aux DC J4 J3 J4 J3
J24 Aux DC
J3 J5 J3 Aux DC J5

Note: All C1634


modules must be

PAGE 19 of 19
FIRECLASS PRECEPT EN

connected at the end


of the sequence
C1652
Power lead
CFlt
MFlt
PSU load calculation must be TB5
carried out for each application 0V
FIRECLASS PREC EN OUTPUT EXP MOD APP

28V

Aux DC, Mains Flt & TB1


C1652
Comm PSU Flt PWR
& Flt 5 Amp
O/Ps PSU
J1
Figure 16 – Precept EN 16L with internal O/P Modules and Exp 4 Output Module Panel with PSU
CHECKED BY: AP
WRITTEN BY: RKP