Professional Documents
Culture Documents
2009-02 Frost On Air Cooling Evaporators
2009-02 Frost On Air Cooling Evaporators
net/publication/286726637
CITATIONS READS
5 160
2 authors, including:
Douglas T. Reindl
University of Wisconsin–Madison
90 PUBLICATIONS 1,711 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Douglas T. Reindl on 09 December 2016.
+ 35^ (2"C) to +50TdO^C) Heavy-Light Avoid using the high fin density coils in applications
4-6
with airborne particulates (e.g., packaging areas).
added benefit of increasing product yield. Yield savings almost ing systems, the extent of unfavorable frost conditions can be
certainly will far outweigh energy cost benefits from reduced minimized but not eliminated.
moisture loads on evaporators. For many low-temperature freez- For spaces such as holding freezers, one common approach
Call Digi-Cool today! Toll Free 1 866 511 Coot (2665) Visit our website and view our online demo: www.digi-cool.com
www. info.hotims.com/23932-8
30 ASHRAE Journal February 2009
for avoiding unfavorable frost conditions
is to lower the setpoint temperature of the
doek to increase the Ievei of moisture re-
moval at a higher evaporator temperature
(when compared to the freezer). Redue-
ing the docli setpoint temperature to
something in the range of 35°F (2°C),
will permit air defrosting while provid-
ing significantly more moisture removal
when compared to a 50°F (10°C) space
setpoint. In some cases., hot-gas reheat is Figure 5: Low density frosiforwing on an evaporator due to iiighcoiitemperataretlijfcrence
added at the dock evaporator to further
and presence of supersaturated air.
increase the space sensible heat ratio.
Figure 4 shows a dock maintained at a 35°F (2°C) dry-bulb capacity decrease due to airflow blockage. Unfavorable frost-
temperature with a relative humidity of 60%. A process iine ing conditions leads to the formation of ice crystals directly
from the entering eoil condition to the ADP shows it to be just in the airstream. There is a tendency for these ice crystals to
favorable as it approaches but does not cross the saturation precipitate onto cold surfaces within the space; however, they
curve. Adding reheat at the dock door can further increase the will ride along on air currents created by operating evaporator
dry-bulb temperature of infiltrating air, driving the process to fans. The frost crystals will readily adhere to the coil surface
an increasingly "favorable" frost condition process line. by physical impaction or interception; thereby, blocking airflow.
Cleland^ oiYers other strategies for avoiding unfavorable Figure 5 shows the structure of unfavorable frost adhering to
frosting conditions but rightly places a particular emphasis on the surfaces of a variably finned low-temperature evaporator
preventing the infiltration using door protection devices. freezing unpacked product and operating with a moderately
Frost Type. Somewhat related to discussions in the previous high TD (difierence in temperature between the entering air
section, the type of frost has an influence on the rate of coil and the evaporating refrigerant). In this case, the structure of
Measuring Coil Capacity Decrease Due to Frosting Face Area 88.6 ft2 (8.23 m^)
How significant is the rate oj capacity lo.ss due to frosting? Tube Diameter 3/4 in. (19.06 mm)
As mentioned previously, the loss of coil capacity under Tube Length 18 ft (5.5 m)
frosting operation is due to reduced airflow, as well as increased Number of Fans 5
resistance to heat transfer. The more significant of these two
Fan Power at -30°F (-34°C)
factors is the capacity loss due to blockage of airflow.--'''"'"-'- Air Temperature
3,125 HP (2.33 kW)
The effects offi-ostpresenting an increased resistance to heat
Rated cfm 60,000 cfm (1,699 m3/min)
transfer are significantly less important.^'^
Number of Tube Rows 10
Aljuwahel^ monitored the performance of a single 37 ton (130
kW) evaporator located in a penthouse in a low-temperature stor- Saturated Evaporator
-3O.F<^34.4-C,
Temperature
age freezer. Additional details on the coil are given in Table 2.
Coil Temperature Difference 10T(5.6''C)
The in situ performance of the unit was determined using an
extensive configuration of air-side instrumentation arranged to Rated Coil Capacity 37 tons (130 kW)
measure entering and leaving conditions (air temperature and Fin and Tube Material Aluminum
moisture content), as well as the average velocity of air flowing Evaporator Coil Type CPR-fed Liquid Overfeed
through the coil. In addition, data was collected to determine the
volume flow rate of air being conveyed by the unit's five fans. Table 2: Geometry and operating conditions of the experimentally
Figure 7 shows the average face velocity of air across the coil monitoreil air-cooling evaporator.
during frosting operation over a 41 hour period. The average tor capacity is gross because it does not include fan heat gains.
velocity of air across the frost-free coil is approximately 560 ft/ The net effect is that an evaporator's capacity, while operating
min (2.85 m/s) but that average velocity decreases by nearly 50% under frosting conditions will decrease and the system s operat-
to 315 fl/min ( 1.6 m/s) at the end of its operating cycle. Figure S ing efficiency suffers as a result. To counter these effects, the
shows the average dry-bulb temperature of air entering and leav- accumulated frost must be removed from the evaporator surface
ing the evaporator during frosting operation. The average entering on either a continuous or intermittent basis.
air temperature (i.e., space temperature) is relatively constant at
-17.5°F (-28°C) while the leaving temperature decreased from Alternative Approaches
-24°F (-31°C) to -26°F (-33°C) as the coil accumulated fi-ost. Are there other approaches that can further reduce or elimi-
The drop in leaving air temperature is a byproduct of the decreased nate the need for defrosting evaporators?
airflow rate through the coil, which allows longer dwell time to The short answer to this question is "not really." Some alterna-
give up its heat to the refrigerant. Unfortunately, that decreased
tive approaches use a liquid desiccant media such as glycol. which
coil leaving air temperature is not sufficient enough to overcome
is sprayed directly onto the evaporator surface to preferentially
the drop in airflow rate. Consequently, the coil's reñigeration
absorb the moisture into the freezing point depressed working
capacity decreases over time asfrostaccumulates on the coil. The
fluid. As moisture from the air goes into the liquid solution, the
actual measured gross capacity of the coil is shown in Figure 9.
concentration of glycol will be reduced and reconcentration
The average clean coil capacity over four separate runs is 33
becomes necessary to avoid freeze-ups. In this case, the equiva-
tons ( 116 kW) and the capacity of the unit decreases to 27 tons
(95 kW) after 41 hoursofoperation, representing a capacity loss lent to a hot gas defrost for a typical evaporator occurs remotely
of nearly 20%. Two other observations were made regarding the from the unit as heat is added to drive off the accumulated water;
measured coil capacity. First, thefield-measuredcapacity is 8% thereby, re-concentrating the gtycol for reuse.
less than the unit s rated capacity. Second, the measured evapora- Another alternative that has been promoted to reduce latent
loads is the use of solid desiccants. The solid desiccant system
32 ASHRAE Journal ashrae.org February 2009
approach can reduce latent loads in temperature 4,00
controlled spaces but the added cost of the desic-
3,50
cant system operation must be carefully evaluated
to understand whether or not the total cost of 3,00
Conciusions ^ 2 00
With the exception of sprayed desiccant units, T —T"
Region of Experiment Uncertainty
evaporators operating at lower temperature conditions
will result in frost formation on the coil surface. Many 1,00
factors influence the rate and nature of frost formation
0.50
including: evaporator unit fin spacing, coil location,
latent (moisture) load, and frost type or structure. The 0,00
250 500 750 1000 1250 1500 1750 2000 2250 2500
accumulation of frost on a coil causes its capacity to Time (min)
decrease due to blockage of airflow; as well as the
Figure 7: Average face velocity of air across the coil during frosting operation.
insulating effects of the frost layer itself As a result,
periodic removal of the accmnulated frost layer is
-24 -I I
required to maintain system capacity and efficiency.
H Run #2 «Run #4 -13
A Run #3 • R u n # 5
Average Inlet Air Temperature
References — Model Predtaion -IS
1. 2006 ASHRAE Handbook—Refrigemtion. Chapter -17
42. "Forced-Circulation Air Coolers." «it
2. Stoecker.W.F 1957."How frost formation on coils -19
affects refrigeration systems." Refrigerating Engineer- -21
ing. 65{2):44-45. Average Outlet A!r Temperature
3. Cleland, D,J. 2005. "Implications of coil frosting -23
on system designs for low-temperature applications."
25
ASHRAE Transactions, 111 (l):336-345. -32 - - :Run#2 a R u n # "»asU
4. Mago. PJ. and S.A, Sherif 2005. "Coil frosting and -33 Run #3 O R " n # 27
defrosting issues at low freezer temperatures near satura- — Modei Prediction
tion conditions." ASHRAE Transactions. 111( 1 ):3- 17, -34 -29
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
5. Aljuwayhei. N.F.. D,T, Reindl. S,A, Klein. G,F Time (min)
Nellis, 2008. "Experimental investigation of the per-
formance of industrial evaporator coils operating under Figure 8: Average coil inlet and outlet temperatures during frosting operation.
frosting conditions," International Journal of Refrigem-
tion, 31(1 ):98-106. 40
6. Smith. G,R. 1989. "Theoretical cooling coil calcu-
lations at freezer temperatures to avoid unfavorable coil
frost." ASHRAE Transactions. 95(2): 1138- 1148.
126
H
1 ^ R u n # l •Run#3
A Run #2 «Run #4 35
M
— Model Prediction
7. Smith, G.R, 1992, "Latent heat, equipment-related •108 - »MM <
>"•• 30
load, and applied psych rometrics at freezer tempera- ' * " •