‫ﺑﺴﻢ ﷲ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬

‫ﺗﻘﺪﻳﺮ ﺍﻻﺣﻤﺎﻝ ﺍﻟﻜﻬﺮﺑﻴﺔ ﻷﻱ ﻣﺒﻨﻲ ﻁﺒﻘﺎ ﻟﻘﻮﺍﻋﺪ ﺍﻟﻜﻮﺩ ‪-: NEC‬‬


‫ﺃﻭﻻ ﺍﻟﻤﺒﺎﻧﻲ ﺍﻟﺘﺠﺎﺭﻳﺔ ‪-:Commercial unit‬‬

‫ﺍﻟﺨﻄﻮﺓ ﺍﻻﻭﻟﻲ‪-:‬‬
‫ﻣﻦ ﺍﻟﺠﺪﻭﻝ ‪ 220.12 NEC‬ﻧﺤﺪﺩ ﺍﺣﻤﺎﻝ ﺍﻻﺿﺎءﺓ ﺣﺴﺐ ﻭﺣﺪﺓ ﺍﻟﻤﺴﺎﺣﺎﺕ‬

‫‪Volt Ampere x Total square meter‬‬

‫ﻣﺜﺎﻝ‪ -:‬ﻣﺴﺘﺸﻔﻲ ﻋﻠﻲ ﻣﺴﺎﺣﺔ ‪ 1200‬ﻣﺘﺮ ﻣﺮﺑﻊ ﺍﺣﺴﺐ ﺣﻤﻞ ﺍﻻﺿﺎءﺓ ﻟﻬﺬﺓ ﺍﻟﻤﺴﺘﺸﻔﻲ؟‬
‫ﻣﻦ ﺍﻟﺠﺪﻭﻝ‬
‫‪22 x 1200 = 26400 VA‬‬
‫ﺍﻟﺨﻄﻮﺓ ﺍﻟﺜﺎﻧﻴﺔ‪-:‬‬

‫ﻣﻦ ﺍﻟﺠﺪﻭﻝ ‪ 220.42 NEC‬ﻧﺤﺪﺩ ﻋﺎﻣﻞ ﺍﻟﺘﺒﺎﻳﻦ ‪ Demand Factor‬ﻻﺣﻤﺎﻝ ﺍﻧﺎﺭﺓ ﺍﻟﻤﺒﻨﻲ ﺍﺫﺍ ﻛﺎﻥ ﺍﻟﻤﺒﻨﻲ ﻋﺒﺎﺭﺓ ﻋﻦ ﻣﺴﺘﺸﻔﻲ‪ ,‬ﻓﻨﺪﻕ‪ ,‬ﺍﻭ‬
‫ﻣﺨﺰﻥ ﻣﺎﻋﺪﺍ ﺫﻟﻚ ﻳﻜﻮﻥ ﻣﻌﺎﻣﻞ ﺍﻟﺘﺒﺎﻳﻦ ‪. %100‬‬

‫ﺍﻟﺨﻄﻮﺓ ﺍﻟﺜﺎﻟﺜﺔ‪-:‬‬
‫ﻧﻘﺎﺭﻥ ﺍﺣﻤﺎﻝ ﺍﻟﺘﻜﻴﻒ ﻭﺍﺣﻤﺎﻝ ﺍﻟﺘﺪﻓﺌﺔ ﺍﻳﻬﻤﺎ ﺍﻛﺒﺮ ﻧﺄﺧﺬﺓ ﻓﻲ ﺣﺴﺎﺑﺘﻨﺎ‪.‬‬
‫ﺍﻟﺨﻄﻮﺓ ﺍﻟﺮﺍﺑﻌﺔ‪-:‬‬
‫ﺍﻟﺒﺮﺍﻳﺰ ‪Sockets‬‬
‫ﺍﻣﺎ ﻓﻲ ﺍﻟﺤﺎﻻﺕ ﺍﻻﺧﺮﻱ ﻳﺘﻢ ﺣﺴﺎﺏ ﺍﻟﺤﻤﻞ ﺍﻻﺩﻧﻲ ﻟﻜﻞ ﺑﺮﻳﺰﺓ ﻋﻨﺪ ﺍﻟﺤﺎﻻﺕ ﺍﻻﺗﻴﺔ ‪-:‬‬
‫ﺃ‪ Heavy-Duty lampholder -‬ﺍﻭ ﺍﻟﺒﺮﺍﻳﺰ ﻣﻮﺟﻮﺩﺓ ﻓﻲ ﺣﺎﻣﻞ ﺍﻟﻤﺼﺒﺎﺡ ﻭﻳﻮﺟﺪ ﺑﻬﺎ ﺍﻛﺘﺮ ﻣﻦ ﺑﺮﻳﺰﺓ‪.‬‬

‫‪660w, 125v, pull‬‬


‫‪chain with 2 outlets‬‬

‫ﻓﻲ ﻫﺬﺓ ﺍﻟﺤﺎﻟﺔ ﻧﻀﻊ ﻟﻜﻞ ﻭﺣﺪﺓ ‪ 600‬ﻓﻮﻟﺖ ﺍﻣﺒﻴﺮ ﻋﻠﻲ ﺍﻻﻗﻞ‪.‬‬
‫ﺏ‪ -‬ﺍﻟﺒﺮﺍﻳﺰ ‪ Sockets‬ﺍﻻﺧﺮﻱ ﻧﻀﻊ ‪ 180‬ﻓﻮﻟﺖ ﺍﻣﺒﻴﺮ ﻟﻜﻞ ﺑﺮﻳﺰﺓ‪.‬‬
‫ﺝ‪ -‬ﺍﻟﺒﺮﺍﻳﺰ ﺍﻟﻤﺠﻤﻌﺔ ‪ Multioutlet assemblies‬ﺫﺍﺕ ﺍﻻﻏﺮﺍﺽ ﺍﻟﻌﺎﻣﺔ‪:‬‬

‫ﻳﺘﻢ ﺗﻘﺪﻳﺮﻫﺎ ﺑﻄﺮﻳﻘﺘﻴﻦ ﺣﺴﺐ ﺍﻟﻐﺮﺽ ﻣﻦ ﺍﻻﺳﺘﺨﺪﺍﻡ ﺍﻟﻄﺮﻳﻘﺔ ﺍﻻﻭﻟﻲ ﺍﺫﺍ ﺍﺳﺘﺨﺪﻣﺖ ﺍﻟﺒﺮﺍﻳﺰ ﻟﻠﻮﺣﺪﺓ ﺍﻟﻮﺍﺣﺪﺓ ﻓﻲ ﻭﻗﺖ ﻭﺍﺣﺪ ﻭﺑﺎﻟﺘﺎﻟﻲ ﻳﻘﺪﺭ ﻛﻞ‬
‫‪ 0.3‬ﻣﻢ ﻣﻦ ﻁﻮﻝ ﺍﻟﻮﺣﺪﺓ ﺏ ‪ 180‬ﻓﻮﻟﺖ ﺍﻣﺒﻴﺮ ﺍﻣﺎ ﺍﻟﻄﺮﻳﻘﺔ ﺍﻟﺜﺎﻧﻴﺔ ﺍﺫﺍ ﻟﻢ ﺗﺴﺘﺨﺪﻡ ﺍﻟﺒﺮﺍﻳﺰ ﻟﻠﻮﺣﺪﺓ ﺍﻟﻮﺍﺣﺪﺓ ﻓﻲ ﻭﻗﺖ ﻭﺍﺣﺪ ﻭﺑﺎﻟﺘﺎﻟﻲ ﻳﻘﺪﺭ ﻛﻞ‬
‫‪ 1.5‬ﻣﺘﺮ ﻣﻦ ﻁﻮﻝ ﺍﻟﻮﺣﺪﺓ ﺏ ‪ 180‬ﻓﻮﻟﺖ ﺍﻣﺒﻴﺮ‪.‬‬

‫ﺩ‪ -‬ﺑﺮﺍﻳﺰ ﻳﺘﻢ ﺗﺮﻛﻴﺒﻬﺎ ﺍﻋﻠﻲ ﻟﻮﺣﺎﺕ ﺍﻟﻌﺮﺽ ‪ Show Window‬ﻭﻳﺘﻢ ﺗﻘﺪﻳﺮﻫﺎ ﻋﻠﻲ ﺍﺳﺎﺱ ‪ 200‬ﻓﻮﻟﺖ ﺍﻣﺒﻴﺮ ﻟﻜﻞ ‪ 300‬ﻣﻢ ﻣﻦ ﻣﺴﺎﺣﺔ ﻟﻮﺣﺔ‬
‫ﺍﻟﻌﺮﺽ‪.‬‬
‫ﻓﻲ ﺍﻟﺼﻮﺭﺓ ﺍﻟﺘﺎﻟﻴﺔ ﻟﻮﺣﺔ ﺍﻟﻌﺮﺽ ‪ 10‬ﻗﺪﻡ = ‪ 3‬ﻣﺘﺮ ﻭﺑﺎﻟﺘﺎﻟﻲ‬
‫‪200 VA x 3/0.3 = 2000 VA‬‬
‫ﺍﻭ ﻣﻤﻜﻦ ﻳﺘﻢ ﺍﻟﺘﻘﺪﻳﺮ ﻋﻠﻲ ﻁﺮﻳﻘﺔ ﺍﻥ ﻛﻞ ‪ 3.65‬ﻣﺘﺮ ﺗﺤﺘﺎﺝ ﻋﺪﺩ ‪ 1‬ﺑﺮﻳﺰﺓ ﺗﻘﺪﺭ ﺏ ‪ 180‬ﻓﻮﻟﺖ ﺍﻣﺒﻴﺮ‪.‬‬

‫ﺍﻟﺨﻄﻮﺓ ﺍﻟﺨﺎﻣﺴﺔ‪-:‬‬
‫ﻣﻦ ﺍﻟﺠﺪﻭﻝ ‪ 220.44 NEC‬ﻳﺘﻢ ﺗﺤﺪﻳﺪ ﺍﻝ ‪ Demand Factor‬ﺍﻟﺨﺎﺹ ﺑﺎﺣﻤﺎﻝ ﺍﻟﺒﺮﺍﻳﺰ‪.‬‬

‫ﺍﻟﺨﻄﻮﺓ ﺍﻟﺴﺎﺩﺳﺔ‪-:‬‬
‫ﻣﻦ ﺍﻟﺠﺪﻭﻝ ‪ 220.56 NEC‬ﻳﺘﻢ ﺗﺤﺪﻳﺪ ﺍﻝ ‪ Demand Factor‬ﺍﻟﺨﺎﺹ ﺑﺎﺣﻤﺎﻝ ﺍﺟﻬﺰﺓ ﺍﻟﻤﻄﺒﺦ‪.‬‬
‫ﺍﻟﺨﻄﻮﺓ ﺍﻟﺴﺎﺑﻌﺔ‪-:‬‬
‫ﺑﺎﻟﻨﺴﺒﺔ ﻻﺣﻤﺎﻝ ﺍﻟﻤﻮﺗﻮﺭﺯ ﻳﺘﻢ ﺯﻳﺎﺩﺓ ﺍﻋﻠﻲ ‪ Full Load Current‬ﻟﻤﻮﺗﻮﺭ ﺑﻨﺴﺒﺔ ‪ %25‬ﺛﻢ ﻳﺘﻢ ﺟﻤﻊ ﺗﻴﺎﺭﺍﺕ ﺍﻟﻤﻮﺗﻮﺭﺯ ﺍﻻﺧﺮﻱ ﻋﻠﻴﺔ‪.‬‬
‫ﺍﻟﺨﻄﻮﺓ ﺍﻟﺜﺎﻣﻨﺔ‪-:‬‬

‫ﻟﺘﺤﺪﻳﺪ ﺣﺠﻢ ﺍﻟﻜﺎﺑﻞ ﺍﻟﺮﺋﻴﺴﻲ ‪ Service‬ﺑﻮﺍﺳﻄﺔ ﻗﺴﻤﺔ ﺍﻝ ‪ Volt Ampere‬ﺍﻟﻜﻠﻴﺔ ﻋﻠﻲ ﺟﻬﺪ ﺍﻟﺨﻂ ‪.‬‬

‫ﻣﻊ ﻣﻼﺣﻈﺔ ﺍﻥ ﺍﻟﺠﺪﻭﻝ ‪ 250.66 NEC‬ﻻﺧﺘﻴﺎﺭ ﻣﻘﻄﻊ ﻣﻮﺻﻞ ﻗﻀﺐ ﺍﻟﺘﺄﺭﻳﺾ ﻣﻊ ﺍﻟﻌﻠﻢ ﺍﻧﺔ ﻳﺨﺘﺎﺭ ﺑﺤﻴﺚ ﻻﻳﻘﻞ ﻋﻦ ﺍﻟﺤﻴﺎﺩﻱ ‪Neutral‬‬
‫ﻣﻌﻠﻮﻣﺎﺕ ﺍﺿﺎﻓﻴﺔ‪-:‬‬
‫ﺧﺪﻣﺎﺕ ﺩﺧﻮﻝ ﺍﻟﺘﻐﺬﻳﺔ‬
‫ﺑﺎﻟﻨﺴﺒﺔ ﻟﻠﺴﻌﻮﺩﻳﺔ‪-:‬‬
‫ﺗﻜﻮﻥ ﺧﺪﻣﺎﺕ ﺩﺧﻮﻝ ﺍﻟﺘﻐﺬﻳﺔ ﻣﻦ ﺷﺮﻛﺔ ﺍﻟﻜﻬﺮﺑﺎء ﺇﻣﺎ ﻣﻦ ﺷﺒﻜﺔ ﺍﻟﺠﻬﺪ ﺍﻟﻤﻨﺨﻔﺾ ﺃﻭ ﺷﺒﻜﺔ ﺍﻟﺠﻬﺪ ﺍﻟﻌﺎﻟﻲ‪.‬‬
‫ﺍﻟﻤﺒﺎﻧﻲ ﺫﺍﺕ ﺍﻷﺣﻤﺎﻝ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻷﻗﻞ ﻣﻦ ‪ 400‬ﺃﻣﺒﻴﺮ)‪ 1000‬ﻛﻴﻠﻮ ﻓﻮﻟﺖ ﺍﻣﺒﻴﺮ( ﺗﻜﻮﻥ ﺧﺪﻣﺎﺕ ﺩﺧﻮﻝ ﺍﻟﺘﻐﺬﻳﺔ ﺑﺎﻟﺠﻬﺪ ﺍﻟﻤﻨﺨﻔﺾ‪ ,‬ﺃﻣﺎ ﺍﻟﻤﺒﺎﻧﻲ‬
‫ﺫﺍﺕ ﺍﻷﺣﻤﺎﻝ ﻣﻦ ‪ 400‬ﺃﻣﺒﻴﺮ ﻓﻤﺎ ﻓﻮﻕ ﻓﻴﺘﻢ ﺗﻐﺬﻳﺘﻬﺎ ﻣﻦ ﺍﻟﺸﺮﻛﺔ ﺑﺎﻟﺠﻬﺪ ﺍﻟﻌﺎﻟﻲ‪ ،‬ﻭﻳﺘﻢ ﺗﺄﻣﻴﻦ ﻣﺤﻄﺔ ﺗﺤﻮﻳﻞ ﻓﺮﻋﻴﺔ‪.‬‬
‫ﺑﺎﻟﻨﺴﺒﺔ ﺍﻟﻲ ﻣﺼﺮ‪-:‬‬
‫ﺗﻜﻮﻥ ﺧﺪﻣﺎﺕ ﺩﺧﻮﻝ ﺍﻟﺘﻐﺬﻳﺔ ﻣﻦ ﺷﺮﻛﺔ ﺍﻟﻜﻬﺮﺑﺎء ﺇﻣﺎ ﻣﻦ ﺷﺒﻜﺔ ﺍﻟﺠﻬﺪ ﺍﻟﻤﻨﺨﻔﺾ ﺃﻭ ﺷﺒﻜﺔ ﺍﻟﺠﻬﺪ ﺍﻟﻤﺘﻮﺳﻂ‪.‬‬
‫ﺍﻟﻤﺒﺎﻧﻲ ﺫﺍﺕ ﺍﻷﺣﻤﺎﻝ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻷﻗﻞ ﻣﻦ ‪ 500‬ﻛﻴﻠﻮ ﻭﺍﺕ ﺗﻜﻮﻥ ﺧﺪﻣﺎﺕ ﺩﺧﻮﻝ ﺍﻟﺘﻐﺬﻳﺔ ﺑﺎﻟﺠﻬﺪ ﺍﻟﻤﻨﺨﻔﺾ‪ ,‬ﺃﻣﺎ ﺍﻟﻤﺒﺎﻧﻲ ﺫﺍﺕ ﺍﻷﺣﻤﺎﻝ ﻣﻦ‬
‫‪ 500‬ﻛﻴﻠﻮ ﻭﺍﺕ ﻓﻤﺎ ﻓﻮﻕ ﻓﻴﺘﻢ ﺗﻐﺬﻳﺘﻬﺎ ﻣﻦ ﺍﻟﺸﺮﻛﺔ ﺑﺎﻟﺠﻬﺪ ﺍﻟﻤﺘﻮﺳﻂ‪ ،‬ﻭﻳﺘﻢ ﺗﺄﻣﻴﻦ ﻣﺤﻄﺔ ﺗﺤﻮﻳﻞ ﻓﺮﻋﻴﺔ‪.‬‬