Professional Documents
Culture Documents
Unit 4 1p Tmer - Secf - Ee - 17 18
Unit 4 1p Tmer - Secf - Ee - 17 18
Working:-
1] The transformer works on the principle of electromagnetic induction.
2] It essentially consists of two windings, the primary and secondary wound on a common
laminated magnetic core. These two windings are electrically separated but magnetically linked
through a path of low reluctance.
3] The winding connected to a.c. source is called as primary winding and the one connected to load
is called as secondary winding.
4] When an alternating voltage V1 is applied to the primary an alternating flux Ø is set up in the
core. This alternating flux links both the windings and induces e.m.f.’s E1 and E2 in them according
to Faraday’s law of electromagnetic induction.
5] If load is now connected across the secondary winding, the secondary e.m.f E 2 will cause a
current I2 to
flow through the load.
6] Transformer enables to transfer a.c. power from one circuit to another with change in voltage
level.
Ans: - The sinusoidal flux ‘Φ’ produced by primary can be represented as :- Φ = Φm sin ω t
Page 1 of 22
2
Divide E2 by E1 we get -
V 1 I1 = V 2 I2
Q.3) Explain the various features of Ideal Transformer. Draw its phasor diagram.
Ans: - An ideal transformer is one that has: -
i. No winding Resistance.
ii. No leakage Flux (i.e the maximum useful flux) links both the windings.
iii. Offers maximum permeability to low reluctance and maximum flux.
iv. No copper losses & iron losses in the core.
v. No voltage drops
Page 2 of 22
3
Page 3 of 22
4
Q.5] Explain working of Practical transformer “ON - LOAD” OR Transformer is a constant Flux
device. Justify.
Ans: - When load is connected between the secondary terminals of the transformer, the
transformer is said to be loaded or ON-Load.
2] When the transformer is loaded the current I2 flows through secondary winding and produces
m.m.f of (N2 x I2) and sets up its own flux Φ2 which opposes flux Φ.
Page 4 of 22
5
3] Flux Φ 2 momentarily reduces main flux Φ due to which primary induced e.m.f E1 also reduces.
Hence, voltage difference V1 – E1 circulates an additional current which is in anti-phase with
I2. The effect of this additional current drawn by primary is it sets up its own flux which
opposes Φ 2.
4] Fluxes Φ 2 and cancels each other and the only flux left in the core is Φ. Therefore,
Transformer is called as a constant flux device.
For Inductive load (Φ2 lags) For Resistive load (Φ2 = 0) For Capacitive load (Φ2 leads)
Phasor Diagrams
Angle between - I2 & V2 = Φ2; I ’2 & V1 = Φ2; Io & V1 = Φo & I1 & V1 = Φ1
Page 5 of 22
6
Where, Pout = Output power = V2 x I2 x cos Φ; Pin = Input power = Pout + Pi + Pcu & losses are
classified as iron loss (Pi) and copper losses (Pcu) & copper losses is given by . R2e
is equivalent resistance referred to secondary.
This above equation is applicable to full load but for fractional load we have to consider
following equation –
Page 6 of 22
7
Consider above equation for efficiency to derive condition for maximum efficiency of
Transformer.
Dividing Numerator and Denominator by I2
For a normal transformer V2 is approximately constant. Hence for a load of given p.f,
Efficiency depends upon load current I2. In the above equation numerator is constant.
And for efficiency to be maximum denominator should be minimum.
Since,
For Maximum Efficiency, Iron (Constant) loss (Pi) = Copper (Variable) loss (Pcu)
where, I2FL is Full load secondary current, PcuFL is full load copper loss =
Page 7 of 22
8
and Iron loss depends on flux (Φ) and hence voltage. Hence the total
loss in a transformer depends upon volt – ampere (VA) only and not on the phase angle between
voltage and current i.e. it is independent of load power factor. Hence rating of transformer is in
VA and generally it is expressed as KVA is given by –
.
1] Open Circuit Test or No Load Test: - In this test, rated voltage is applied to the primary low
voltage side while the secondary is left open circuited. The primary side is low voltage side but
having high current rating to get sufficient primary current for power measurement. The primary
voltage V1 is measured by voltmeter, no – load current IO by ammeter and no load input power P0
by wattmeter.
As the applied voltage is rated voltage, hence wattmeter will record the iron losses Pi. As
secondary side open circuited, the secondary current I 2 is zero & hence their reflection on
primary I ’2 is also zero, therefore, I1 = Io. The effect of this is secondary copper loss is zero and
small Io develops negligible copper loss on primary, hence total copper loss is negligibly small.
(No load current IO is very small 2 – 10 % of rated current).
1.
Page 8 of 22
9
2.
3.
2] Short Circuit Test: - This test is generally conducted on High voltage low current side The
secondary is short circuited with the help of thick conducting copper wire or an ammeter, which
makes secondary resistance very small and on rated voltage it may draw very large current. Such
large current can cause overheating and burning of transformer. To limit this S.C. current,
primary is supplied with low voltage which is just enough to cause rated current to flow through
primary. Hence this test is also called as Low Voltage test.
Now the currents flowing through the windings are rated currents hence the total copper losses is
full load copper loss. Iron loss in the core is negligibly small since rated voltage is very small.
Hence wattmeter will practically register the full load copper losses in the transformer winding.
This test is conducted always on High voltage side, step down transformer & calculations steps
must be referred to primary as R1e, Z1e & X1e. But if the given transformer is step up transformer
i.e. primary is low voltage side and secondary side is high voltage side then meters must be
conducted with high voltage side i.e. secondary side of the transformer and after measurement
results, the calculations must be done referred to secondary side i.e. follow above calculations to
find R2e, Z2e & X2e, and then do calculations referred to primary as R 1e, Z1e & X1e using
transformation ratio, .
Page 9 of 22
10
&
+ ve = For Inductive lagging load & - ve = For Capacitive leading load
Where, E2 = No load voltage; V2 = Full load voltage
Q.12] Draw the Phasor diagram of a single phase Transformer for resistive load, inductive load
(lagging load) & capacitive load (leading load).
Ans: - Equations are to make complete phasor diagram: -
STEPS: -
1. Consider flux Φ as reference. Make the resultant Io the summation of Iµ (which is in phase
with Φ) & Iw (which is in phase with V1).
2. E1 lags Φ by 90. Reverse E1 to get -ve E1. E1 & E2 are in phase.
3. Assume V2 lags E2 or in a particular direction.
4. Draw I2 phasor line with respect to type of load, for Inductive Load I2 lags V2 by Φ2 (hence
called as lagging load); for Capacitive Load I2 leads V2 by Φ2 (hence called as leading load) and
for Resistive Load I2 & V2 are in phase.
5. Reverse I2 & to get I ’2. Add IO & I ’2 to get I1.
6. Starting from tip of V2, draw (I2.R2) from V2 parallel to I2 & (I2.X2) perpendicular to (I2.R2).
Now draw resultant E2 to join V2, (I2.R2) & (I2.X2).
Page 10 of 22
11
7. Starting from tip of –ve E1, draw (I1.R1) from E1 parallel to I1 & (I1.X1) perpendicular to
(I1.R1). Now draw resultant V1 from origin to join –E1, (I1.R1) & (I1.X1).
Page 11 of 22
12
Q.13] Draw a complete equivalent circuit diagram & approximate equivalent circuit diagram
referred to primary of a single phase Transformer.
Ans: - Refer following equations to make equivalent circuit diagram: -
Hence,
And
Page 12 of 22
13
And
3) Effect of winding impedance: -
And
Based above expressions the equivalent circuit diagram can be made as,
The above complete equivalent circuit diagram can be reduced to approximate equivalent circuit
diagram by using above equivalent parameters.
Page 13 of 22
14
FORMULAE
PROBLEMS
1) A single phase transformer has 350 primary and 1050 secondary turns. The net cross-
sectional area is 55 cm². If the primary winding be connected to a 400 V, 50 Hz single phase
supply. Calculate: - i) The maximum value of flux density in the core. & ii) The voltage induced
in the secondary winding. Neglect voltage drop & power loss in the winding. S1/5M
2) A 10 KVA transformer having 50 number of turns on primary and 10 number of turns on
secondary is connected to 400 V, 50 Hz a.c. supply. Calculate i) Secondary voltage on no-load.
ii) Full load primary and secondary currents & iii) Maximum value of flux in the core. Neglect
voltage drop & power loss in the winding.
3) The required no load voltage ratio in a single phase 50 Hz core type transformer is 6600/500.
Find the number of turns in each winding if the flux is 0.06 Wb. Neglect voltage drop & power
loss in the winding. W96/4M
4) A single phase transformer has 500 primary and 1000 secondary turns. The area of the core is
75 cm². If the primary winding is connected to 400 V, 50 Hz supply. Calculate secondary voltage
and peak value of flux density. Neglect voltage drop & power loss in the winding.
PROBLEMS
1) The no load current of a transformer is 5 A at 0.3 p.f. when supplied at 230 V, 50 Hz. The
number of turns of the primary winding is 200. Calculate: (i) Maximum flux in the core, (ii) Core
loss, (iii) Magnetising current. W14/3M
Answers: - Φo = 72.543, sin Φo = 0.954; Φm = 5.1802 mWb; Wc (Pc) = 345 W; Im = 4.77 A
Page 14 of 22
15
PROBLEMS
1) A transformer takes 10 A on no load at a power factor of 0.1 lagging. The turns ratio is 4:1
(step down). If the secondary supplies a load of 200 A at a p.f. of 0.8 lagging, find the primary
current and its power factor. W12/7M
Answers: - I1 = 57.25 A; Ф1 = 44.26; cos Ф1 = 0.7162
2) A 400/200 V single phase transformer is supplying a load of 50 amp at 0.866 pf lagging. The
no load current is found to be 2 amp at 0.208 pf lagging. Calculate the current and power factor
on primary side of transformer. Draw the phasor diagram. W13/6M
Answers: - K = 0.5; Ф2 = 30; Ф0 = 78; I2’ = 25 A; I1 = 26.38 Amp; Ф1 = 33.28; pf = cos Ф1 =
0.835 lag
3) A transformer no load takes 1.5 A at a power factor of 0.2 lagging when its primary is
connected to a 230 V, 50 Hz supply. The transformation ratio is 1/3. Determine the primary
current when the secondary is supplied a current of 40 A at a pf of 0.8 lagging. Also find the
power factor its nature. S14/4M
Answers: - I2’ = 13.34 A; I1 = 14.5 A; Ф1 = 40.81; pf = cos Ф1 = 0.757 lag
4) A 400 V/ 100 V, 1-phase, transformer takes a no load current of 5 A at 0.2 lagging p.f.,
secondary winding supplies a load of 100 A at a p.f. of 0.8 lagging. Find the primary input
current. S16/6M
5) A 400/200 V, 1 phase transformer is supplying load of 50 A at the power factor of 0.866
lagging. The no load current is found to be 2A at 0.208 power factor lagging. Calculate the
current & power factor on primary side of transformer. W16/6M
Answers: - K = 0.5, Φ2 = 30O, ΦO = 78O, I2’ = 25 A, I1 = 26.38 A, Φ1 = 33.23O, cos (Φ1) = 0.8365
Page 15 of 22
16
1)
And
2)
And
3)
And
PROBLEMS: -
1) A 30kVA, 2400/120 V, 50 Hz transformer has a high voltage winding resistance of 0.1 Ω and
leakage reactance of 0.22 Ω. The low voltage winding resistance of 0.035 Ω and leakage
reactance is 0.012 Ω. Find equivalent winding resistance, reactance and impedance referred to –
(i) High voltage side & (ii) Low voltage side. S15/6M
Answers: - K = 0.05; R1e = 14.1 Ω; R2e = 0.03525 Ω; X1e = 5.02 Ω; X2e = 0.01255 Ω; Z1e =
14.97 Ω; Z2e = 0.03742 Ω
2) A 15 kVA, 2200/110 V transformer has R1 = 1.75 Ω, R2 = 0.0045 Ω. The leakage reactance
are X1 = 2.6 Ω and X2 = 0.0075 Ω. Calculate: (i) Equivalent resistance referred to primary and
secondary, (ii) Equivalent reactance referred to primary and secondary & (iii) Total copper loss.
W15/6M
Answers: - K = 0.05; R 1e = 3.55 Ω; R2e = 0.008875 Ω; X1e = 5.6 Ω; X2e = 0.014 Ω; I1 = 6.82 A;
Pcu = 165.031 W
Page 16 of 22
17
For Maximum Efficiency, Iron (Constant) loss (Pi) = Copper (Variable) loss (Pcu)
Voltage Regulation -
&
+ ve = For Inductive lagging load & - ve = For Capacitive leading load
Where, E2 = No load voltage; V2 = Full load voltage
OC & SC TEST: -
SIDE / OBSERVATIONS OR
CALCULATIONS
TYPE GIVEN
LV OR V1 Io Po Cos Φo Sin Φo Iw Im Ro Xo
OC HC /
-1 Io x Cos Io x Sin
TEST STEP Rated Pi Sin (Cos Φo)
Φo Φo
UP
Page 17 of 22
18
LC / LV (10 Rated
STEP % to (Full Pcu(FL)
DOWN 15 %) Load)
PROBLEMS
1) A 600 KVA single phase transformer has an efficiency of 92 % both at full load and half load
and at unity power factor. Determine the transformer efficiency at 60 % of full load and 0.8
power factor lag. W12/7M
Answers: - % η 0.6, 0.8 lag = 90.50 %
2) A single phase 40 KVA, 6600 V / 250 V transformer has primary and secondary resistances of
10 Ω and 0.02 Ω respectively. The equivalent leakage reactance referred to primary is 35 Ω. Find
full load voltage regulation for the load power factor of (i) Unity (ii) 0.8 lead. S13/5M
Answers: - R1e = 23.94 Ω; K = 0.0379; I1(FL) = 6.06 Amp; % V.R. = 2.198 %; % V.R. = - 0.17 %
3) The iron and full load copper losses in a 40 KVA single phase transformer are 250 W and 750
W respectively. Calculate the efficiency at: (i) 50 % of full load, 0.8 power factor leading; (ii)
Find the load at which the efficiency is maximum and maximum efficiency at unity power factor.
S13/5M
Answer: - % η = 97.34 %; KVA at ηmax = 23.094 KVA; % ηmax = 97.364 %
4) A 5 KVA, 2300/230 V, 50 Hz single phase transformer was tested for iron losses with normal
excitation and Cu losses at full load and these were found to be 40 W and 112 W respectively.
Calculate the efficiencies of the transformer at 0.8 pf for (i) Half load (ii) Full load. W13/5M
Answers: - % η HL, 0.8 lag = 96.77 % & % η FL, 0.8 lag = 96.33 %
5) The primary and secondary windings of 500 kVA, 11 kV/415 V, single phase transformer
have resistances of 0.42 Ω and 0.019 Ω respectively. Its core losses are 2.9 kW. Calculate: (i)
copper loss at full load (ii) efficiency of transformer at full load, 0.8 pf lag (iii) efficiency of
transformer at 70 % of full load, upf (iv) the load at which the maximum efficiency occurs.
S14/8M
Page 18 of 22
19
Answers: - (i) 28,448.2 W (ii) 92.74 % (iii) 95.41 % (iv) 159.64 kVA
6) A 10 kVA single phase transformer has a maximum efficiency of 98 % at full load, 0.8 p.f.
Determine copper loss and efficiency at half load. What is iron loss? W14/6M
Answers: - Pi = 81.633 W = Pcu; % ηHFL = 97.513 %
7) A 100 kVA, 1 KV/10 KV, 50 Hz, single phase transformer has iron losses of 1100 watts and
the copper loss with 5 A in high voltage winding is 400 W. Calculate the efficiency at 25 % of
full load at (i) UPF and (ii) 0.8 pf lag, the output being maintained at 10,000 V. W15/6M
Answers: - I2 = 10 A; New Pcu = 1600 W; n = 0.25; % η = 95.42 %; % η = 94.34 %
8) A 5kVA, 230 V / 400 V single phase transformer takes 0.7 A and 60 W on an open circuit
when the low voltage winding is short circuited and 20 V is applied to high voltage terminals, the
current and power are 10 A and 90 W respectively. Calculate: (i) The full load efficiency at unity
p.f. & (ii) Full load regulation at 0.8 p.f. lagging. S16/6M
Answers: - P2 = 5 kW (since UPF); I2FL = 12.5 A; cos Φ = 0.8; sin Φ = 0.6; Z 2e = 2 Ω; R2e = 0.9
Ω; X2e = 1.786 Ω; % η = 97.1 %; % V.R. = 5.6 %
9) The iron and full load copper loss in a 40 kVA single phase transformer are 250 W and 750
W respectively. Calculate: i) Efficiency at 50% of full load 0.8 p.f. leading ii) Load at which the
efficiency is maximum. W16/6M
Answers: - n = 0.5, η = 97.33 %, kVAmax = 23.094 kVA
10) The iron and full load copper loss in a 40 kVA single phase transformer are 250 W and 750
W respectively. Calculate: i) Efficiency at 50% of full load 0.8 p.f. leading ii) Load at which the
efficiency is maximum. S17/6M
Answers: - n = 0.5, η = 97.33 %, kVAmax = 23.094 kVA
PRACTICE NUMERICALS
1. A 1-phase transformer has a primary winding of 1000 turns and secondary winding of
200 turns. The no load current is 3 A at a 0.2 pf lagging. Calculate the primary current and power
factor when the secondary current is 280 A at 0.8 pf lagging. S5/6M; S10/7M
2. The test result obtained from open and short circuit tests on 10 KVA, 450/120 V, 50
Hz, 1-phase transformer are –
O.C. test: 120 V 4.2 A 80 W (on L.V. side) & S.C. test: 9.65 V 22.2 A 120 W (on H.V.
side)
Calculate (1) the equivalent circuit constants, (2) efficiency and voltage regulation for full load
0.8 pf lagging. S5/9M
3. A 4 KVA, 400/200 V, 50 Hz, 1-phase transformer has the following test data –
O.C. test (L.V. side): 200 V 1 A 64 W & S.C. test (L.V. side): 15 V 10 A 80 W
Page 19 of 22
20
Determine equivalent circuit parameters as referred to L.V. side. Also calculate the secondary
terminal voltage on full load at 0.8 pf lag. W5/8M
4. A 3300/300 V, 1-phase transformer gives 0.6 A and 60 W as ammeter and wattmeter
reading when rated input voltage is given to low voltage winding and high voltage winding is
kept open. Find (1) pf of no load current, (2) magnetizing component of input current, (3) iron
loss component of input current. W5/7M
5. The instrument readings obtained from open and short circuit tests on 10 KVA,
415/120 V, 50 Hz transformer are –
O.C. test: 415 V 1.12 A 80 W (reads on H.V. side)
S.C. test: 2.6 V 83.25 A 120 W (with H.V. winding short circuited)
Compute (i) full load efficiency and voltage regulation for 0.8 pf lag, (ii) half load efficiency and
voltage regulation for 0.8 pf lag, (iii) draw the equivalent circuit. S6/8M
6. A transformer has a primary winding of 800 turns and secondary winding of 200
turns. When the load current on the secondary is 80 A at 0.8 pf lagging, the primary current is 25
A at 0.707 pf lagging. Determine the no load current and its power factor. S6/6M
7. A 5 KVA, 500/250 V, 50 Hz, 1-phase transformer gave the following reading –
O.C. test: 500 V 1 A 50 W (L.V. side open) and S.C. test: 25 V 10 A 60 W (L.V. side shorted)
Determine (i) the efficiency at full load 0.8 pf lagging, (ii) the voltage regulation on full load 0.8
pf leading, (iii) the efficiency on 60 % of full load 0.8 pf leading, (iv) draw the equivalent circuit
referred to primary and insert all the values in it. W6/14M
8. A 5 KVA, 250/500 V, 1-phase, 50 Hz transformer gave the following test results –
S.C. test (with LV winding short circuited): 20 V, 10 A, 100 W
O.C. test (on LV side): 250 V, 1 A, 80 W
Determine (i) the circuit constants, (ii) efficiency at full load at 0.8 lagging power factor, (iii)
efficiency at half load at unity power factor. S7/S12/8M
9. A 5 KVA, 2300/230 V, 50 Hz transformer was tested for the iron losses with normal
excitation and Cu losses at full load and these were found to be 40 W and 112 W respectively.
Calculate the efficiencies of the transformer at 0.8 power factor for the KVA outputs .125, 3.57
and 7.5. S7/7M
10. A 5 KVA, 250/500 V, 50 Hz, 1-phase transformer gave following test data –
No load: 250 V 0.6 A 50 W (L.V. side)
Short Circuit: 9V 6A 24 W (H.V. side)
Page 20 of 22
21
Calculate (i) the magnetizing current and the components corresponding to iron losses at normal
voltage and frequency, (ii) the efficiency at full load unity pf, (iii) the corresponding terminal
voltage on full load at 0.8 pf lagging. W7/9M
11. A 400/200 V, 1-phase transformer is supplying a load of 40 A at the power factor of
0.866 lagging. The no load current is found to be 1.8 A at 0.208 pf lagging. Calculate the current
and power factor on primary side of the transformer. W7/8M
12. The primary and secondary winding of a 30 KVA, 6000/230 V, 1-phase transformer
has resistance of 10 Ω and 0.016 Ω respectively. The reactance of transformer referred to
primary is 34 Ω. Calculate primary voltage required to circulate full load current when secondary
is short circuited. What is the power factor on short circuit? S8/6M
13. A 100 KVA, 6600/250 V, 50 Hz transformer gives the following test results –
O.C. test: 900 W, normal voltage and S.C. test: 290 V, 12 A, 860 W (H.V. side)
Calculate (i) the efficiency and percentage voltage regulation at full load at 0.8 power factor
lagging and (ii) the load at which maximum efficiency occurs and also find maximum efficiency.
S8/S11/8M
14. A 200 KVA transformer has an efficiency 0f 98 % at full load. The maximum
efficiency occurs at three quarters of full load. Calculate the efficiency at half load. Assume
negligible magnetizing current and power factor of 0.8 lagging at all loads. S8/7M
15. Obtain the equivalent circuit of a 200/400 V, 50 Hz, 1-phase transformer from the
following test data –
O.C. test: 200 V, 0.7 A, 70 W --- L.V. side
S.C. test: 15 V, 10 A, 85 W --- H.V. side
Calculate the secondary voltage and regulation when delivering 5 KW at 0.8 p.f. lagging, the
primary voltage being 200 V. W8/7M; W10/9M
16. A 100 KVA transformer has 400 turns on the primary and 80 turns on the secondary.
The primary and secondary resistances are 0.3 Ω and 0.01 Ω respectively and the corresponding
leakage reactance are 1.1 and 0.035 respectively. The supply voltage is 2200 V. Calculate (i)
equivalent impedance referred to primary, (ii) the voltage regulation and the secondary terminal
voltage for full load having a power factor of 0.8 leading. W8/8M
17. A 660/220 V, 1-phase transformer takes a no load current of 2 A at a power factor of
0.225 lagging. The transformer supplies a load of 30 A at a power factor of 0.9 lagging.
Calculate the current drawn by the primary from the mains and the primary power factor.
Neglect winding resistances and reactance. S9/S12/W12/7M; W11/6M
Page 21 of 22
22
18. A 5 KVA, 230/400 V 1-phase transformer takes 0.7 A and 60 W on an open circuit.
When the low voltage winding is short circuited and 20 V is applied to the high voltage
terminals, the current and power are 10 A and 90 W respectively. Calculate (i) the full load
efficiency at unity pf, (ii) full load regulation at 0.8 pf lagging, (iii) output terminal voltage.
S9/8M
19. The no load current of a transformer is 15 A at a power factor of 0.2 when connected
to a 460 V, 50 Hz supply. If the primary winding has 550 turns, calculate (a) the magnetizing
component of no load current, (b) the iron loss component of no load current and (c) the
maximum value of the flux in the core. W9/7M
20. A 30 KVA, 2400 / 120 V, 50 Hz transformer has a high voltage winding resistance of
0.1 Ω and a leakage reactance of 0.22 Ω. The low voltage winding resistance is 0.035 Ω and the
leakage reactance is 0.012 Ω. Find equivalent winding resistance, reactance and impedance
referred to the (i) high voltage side and (ii) the low voltage side. W9/7M
21. A 50 KVA transformer has on full load a copper loss of 600 watts and iron loss of
500 watts. Calculate maximum efficiency and the load at which it occurs. W9/6M
22. A 10 KVA, 500 / 250 V, 1-phase transformer has its maximum efficiency of 94 % of
its rated output at unity power factor. Estimate its efficiency when delivering full load output at
power factor of 0.8 lagging. S10/8M
23. A 20 KVA, 440/200 V, single phase, 50 Hz transformer has iron loss of 324 W. the
copper loss is found to be 100 W when delivering half of full load current. Determine (i)
efficiency when delivering full load current at 0.8 lagging power factor and (ii) the percentage of
full load when the efficiency will be maximum.
24. A 250/500 V, 1-phase, 50 Hz transformer gave the following test results –
S.C. test (with LV side shorted): 20 V, 12 A, 100 W
O.C. test (on LV side): 250 V, 1 A, 80 W
Determine (i) the equivalent circuit parameters, (ii) Applied voltage when output is 10 A, 500
volt at 0.8 pf lagging (iii) efficiency of transformer when output is 10 A, 500 volt at 0.8 lagging
power factor. W11/9M
25. A 1000 V / 200 V, 50 Hz, single phase transformer gave the following test results:
(No load HV side) 1000 V, 0.24 A, 90 W
(Short circuit LV side) 50 V, 5 A, 110 W, Full load
Calculate (i) Rating of the transformer, (ii) Equivalent circuit constants referred to primary &
(iii) KVA load for maximum efficiency. W12/8M
Page 22 of 22