100W Triple Output Switching DC Power Supplies: Applications

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

1403/1405

100W Triple Output


Switching DC power Supplies

Applications Overview
The 1403 and 1405 can provide a
These power supplies are continual 100 W of power through their
ideal for trouble shooting three output terminals. They feature
circuit boards or devices constant current or constant voltage
which require two or modes with automatic crossover.
three different input
voltages such as 3, 5, 12 Their small size, light weight, and
and 1-36 V. Ideal for: economical price make them ideal for
classroom and lab settings where space
z Educational labs and dollars are a premium.
z Technical schools

z Internal training
facilities

z Hobbyists Features
z Main Output: 1-20 VDC, 5 A (1403) and
1-36 VDC, 3 A (1405)
z Aux Output 1: 3.3 or 5 VDC (selectable),
2.0 A
z Aux Output 2: 12 VDC, 1.0 A
z Coarse & fine voltage/current controls
z CV/CC mode with automatic crossover
z Illuminated LCD indicators for A, V,
Output On/Off, CC & CV.
z 4-digit display for main output
z 2-digit display for auxiliary current output
z Compact slim tower housing
z Output power on/off switch at front panel
z Over voltage, short circuit, overload, and
over temperature protections.

22820 Savi Ranch Parkway


Yorba Linda, CA 92887
800-572-1028
20200227 A Cal Test Electronics Company globalspecialties.com
Downloaded from Arrow.com.
All specifications apply to the unit after a temperature stabilization time of 15
minutes over an ambient temperature range of 25 °C ± 5 °C.
1403/1405

1403 1405
Input Voltage (Universal 100–240 VAC, 50/60 Hz 100–240 VAC, 50/60 Hz
input)
Full Load Input Current 0.83 A 0.83 A
at 230 VAC
Output Voltage 1.0 – 20 VDC 1.0 – 36 VDC
Adjustable Range
Output Current 0.25 – 5 A 0.25 – 3 A
Adjustable Range
Voltage Regulation
Load from 10% to 90% 70 mV 70 mV
Variation
Line from 90 to 264 VAC 25 mV 25 mV
Variation
Ripple & Noise (peak to ≤120 mV ≤150 mV
peak)
Current Regulation
Load from 10% to 90% 50 mA 50 mA
Variation
Line from 90 to 264 VAC 20 mA 20 mA
Variation
Ripple & Noise (peak to ≤50 mA ≤50 mA
peak)
Switching Operation 50 kHz to 150 kHz 50 kHz to 150 kHz
Frequency
Aux Output 1 Fixed 3.3 /5 VDC. 1.8 mA Fixed 3.3 /5 VDC. 1.8 mA
cont. 2 A Max. cont. 2 A Max.
Aux Output 2 Fixed 12 VDC, 800 mA Fixed 12 VDC, 800 mA
cont. 1 A Max. cont. 1 A Max.
Power Factor >0.9 >0.9
Efficiency at Maximum ≥80.5% ≥80.5%
Power

22820 Savi Ranch Parkway


Yorba Linda, CA 92887
800-572-1028
A Cal Test Electronics Company globalspecialties.com
Downloaded from Arrow.com.
Volt and Amp Control Rotary Encoder Rotary Encoder
Type
1403/1405 Voltmeter and Ammeter 4 Digit LCD 4 Digit LCD
Display
Voltmeter Accuracy 5 counts, V<5 V 5 counts, V<5 V
±0.2%+5 counts, V≥5 V ±0.2%+5 counts, V≥5 V
Ammeter Accuracy 15 counts, I≤1 A 20 counts, I≤1 A
±0.5% +6 counts, I>1 A ±1% +6 counts, I>1 A
LCD Indication CC, CV, Amp, Volt, Output ON-OFF, Aux output current
Protection Short Circuit, Overload, Over Temperature, Tracking
OVP
CE Approvals LVD: EN 61010, EMC: EN 55011
Cooling System Natural Convection
Dimensions (WxHxD) 70 x 150 x 250 mm (2.8 x 6.0 x 9.8 in)
Weight 2 kg (4.4 lbs)
Remarks All data based on 230 V/50 Hz

Specifications are subject to change without notice. To ensure the most current
version of this manual, please download the current version from our website:
globalspecialties.com.

22820 Savi Ranch Parkway


Yorba Linda, CA 92887
800-572-1028
A Cal Test Electronics Company globalspecialties.com
Downloaded from Arrow.com.