Kingspan Kooltherm k106 90mm Standard Details Brochure en GB v04
Kingspan Kooltherm k106 90mm Standard Details Brochure en GB v04
CI/SfB
(21.9) Rn7 M2
Fourth Issue January 2022
Low Energy –
Low Carbon Buildings
Contents
Page
Wall Details
E1 Open Back Lintel (Insulated) with Perforated Steel Base Plate 6
E1 Open Back Lintel (Insulated) with Perforated Steel Base Plate and Insulated Reveal 8
E1 Open Back Lintel (Uninsulated) with Perforated Steel Base Plate 10
E1 Open Back Lintel (Uninsulated) with Perforated Steel Base Plate and Insulated Reveal 12
E2 Open Back Lintel (Insulated) without Base Plate 14
E2 Open Back Lintel (Insulated) with Insulated Reveal but without Base Plate 16
E2 Open Back Lintel (Uninsulated) without Base Plate 18
E2 Open Back Lintel (Uninsulated) with Insulated Reveal but without Base Plate 20
E2 Independent Steel Lintel externally and Independent Concrete Lintel internally 22
E2 Independent Steel Lintel externally and Independent Concrete Lintel internally with Insulated Reveal 24
E3 Sill (Normal) 26
E3 Sill (Normal) with Insulated Reveal 28
E4 Jamb (Normal) 30
E4 Jamb (Normal) with Insulated Reveal 32
E5 Ground Floor – Solid Concrete Slab 34
E5 Ground Floor – Beam & Block (Parallel) 36
E5 Ground Floor – Beam & Block (Perpendicular) 38
E5 Ground Floor – Suspended Timber Floor (Parallel) 40
E6 Intermediate Floor within a Dwelling – Concrete 42
E6 Intermediate Floor within a Dwelling – Timber 44
E7 Party Floor between Dwellings (in Blocks of Flats) 46
E10 Eaves (Insulation at Ceiling Level) 48
E11 Eaves (Insulation at Rafter Level) 50
E12 Gable (Insulation at Ceiling Level) 52
E13 Gable (Insulation at Rafter Level) 54
E14 Flat Roof 56
E15 Flat Roof with Parapet 58
E16 Corner (Normal) 60
E17 Corner (Inverted) 62
E18 Party Wall between Dwellings (Filled Cavity) 64
E18 Party Wall between Dwellings (Unfilled Cavity) 66
Higher heat flows occur at junctions due to complex geometries, All thermal modelling work was undertaken by Competent
or from the use of materials with a higher thermal conductivity Thermal Modellers, who have successfully completed training
than the adjacent materials. This can cause localised reductions and portfolios with ACD Certification Ltd and are experienced
of internal surface temperatures, which can lead to surface in thermal modelling of junction heat losses, on behalf of
condensation and mould growth problems. Good design Kingspan Insulation Ltd.
detailing can help to avoid these issues. The details in this
The assessors who undertook the thermal modelling in this
guidance have been developed with the aim of being buildable,
document are:
achieving good thermal performance and minimising risk.
• Mr Jonathan Ducker
Linear thermal bridging describes the heat–loss occurring at
• Miss Samantha Lloyd
junctions between elements e.g. between a wall and floor, or
around openings e.g. at sills, lintels and jambs. A ψ–value All of the calculated ψ–values for the Kingspan Insulation
(psi–value) is the heat loss through a junction, which is junction details are better than the default ψ–values for the
additional to the heat flow through the adjoining plane accredited details as given in BRE IP 1/06 and Table K1 of
elements, and is measured in W/m.K. SAP 2012.
3
Kingspan Insulation Thermal Modelling
4
5
E1 – Open Back Lintel (Insulated) with Perforated
Steel Base Plate
General Construction Specification
l Wall lining l For normal reveals, ensure the window / door frame
l Inner leaf blockwork overlaps the insulated lintel by no less than 30 mm (take
values from the first two rows of the table below).
l 100 mm overall cavity width with 90 mm Kingspan
Kooltherm® K106 Cavity Board and 10 mm cavity l For fully overlapped / checked reveals, ensure the window
/ door frame overlaps the insulated lintel fully / by no less
l Outer leaf brickwork
than 80 mm (take values from the last two rows of the
table below).
U–value Range
l Kingspan Kooltherm® K106 Cavity Board should be firmly
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
held against the inner leaf of blockwork.
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
l The cavity and wall ties should be kept clean of mortar and
other debris during construction.
Thermal Performance Process Sequence
l Ensure Kingspan Kooltherm® K106 Cavity Board is in Air Barrier Process Sequence
contact with the lintel.
l Seal the joint between the window frame and the internal
l Kingspan Kooltherm® K106 Cavity Board and cavity tray linings.
/ proprietary insulated lintel should be taped with a
l Apply flexible sealant to all interfaces between the internal
50 mm (min.) overlap. This may require two or more strips
air barrier and the window / door frame.
of Wraptite tape.
l Seal all penetrations through the air barrier using a flexible
l Ensure there are no gaps between the insulation boards.
sealant.
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.231 0.247 0.259 0.283 0.337
Reveal)** Temperature Factor (f) 0.920 0.913 0.909 0.907 0.904
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
6
Wall tie with retaining clip
Wall lining
7
E1 – Open Back Lintel (Insulated) with Perforated
Steel Base Plate and Insulated Reveal
General Construction Specification
l Wall lining l For fully overlapped / checked reveals, ensure the window
l Inner leaf blockwork / door frame overlaps the insulated lintel fully / by no less
l 100 mm overall cavity width with 90 mm Kingspan than 80 mm (take values from the last two rows of the
Kooltherm® K106 Cavity Board and 10 mm cavity table below).
l Outer leaf brickwork l Kingspan Kooltherm® K106 Cavity Board should be firmly
held against the inner leaf of blockwork.
U–value Range l The cavity and wall ties should be kept clean of mortar and
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block) other debris during construction.
l 0.17 W/m .K (0.51 & 1.13 W/m.K block)
2
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.188 0.208 0.224 0.279 0.314
Reveal)** Temperature Factor (f) 0.911 0.904 0.899 0.891 0.894
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
8
Wall tie with retaining clip
Wall lining
9
E1 – Open Back Lintel (Uninsulated) with Perforated
Steel Base Plate
General Construction Specification
l Wall lining l For normal reveals, ensure the window / door frame
l Inner leaf blockwork overlaps the lintel by no less than 30 mm (take values from
the first two rows of the table below).
l 100 mm overall cavity width with 90 mm Kingspan
Kooltherm® K106 Cavity Board and 10 mm cavity l For fully overlapped / checked reveals, ensure the window /
door frame overlaps the lintel fully / by no less than 80 mm
l Outer leaf brickwork
(take values from the last two rows of the table below).
l Kingspan Kooltherm® K106 Cavity Board should be firmly
U–value Range
held against the inner leaf of blockwork.
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
l The cavity and wall ties should be kept clean of mortar and
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
other debris during construction.
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.265 0.284 0.300 0.359 0.397
Reveal)** Temperature Factor (f) 0.915 0.907 0.902 0.892 0.893
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
10
Wall tie with retaining clip
Wall lining
11
E1 – Open Back Lintel (Uninsulated) with Perforated
Steel Base Plate and Insulated Reveal
General Construction Specification
l Wall lining l For fully overlapped / checked reveals, ensure the window /
l Inner leaf blockwork door frame overlaps the lintel fully / by no less than 80 mm
(take values from the last two rows of the table below).
l 100 mm overall cavity width with 90 mm Kingspan
Kooltherm® K106 Cavity Board and 10 mm cavity l Kingspan Kooltherm® K106 Cavity Board should be firmly
held against the inner leaf of blockwork.
l Outer leaf brickwork
l The cavity and wall ties should be kept clean of mortar and
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.203 0.230 0.251 0.320 0.364
Reveal)** Temperature Factor (f) 0.927 0.916 0.893 0.881 0.880
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
12
Wall tie with retaining clip
Wall lining
13
E2 – Open Back Lintel (Insulated) without Base Plate
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.184 0.196 0.206 0.266 0.303
reveal)** Temperature Factor (f) 0.950 0.943 0.937 0.916 0.911
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
14
Wall tie with retaining clip
Wall lining
Cavity Board
15
E2 – Open Back Lintel (Insulated) with Insulated
Reveal but without Base Plate
General Construction Specification
l Wall lining l For fully overlapped / checked reveals, ensure the window
l Inner leaf blockwork / door frame overlaps the insulated lintel fully / by no less
l 100 mm overall cavity width with 90 mm Kingspan than 80 mm (take values from the last two rows of the
Kooltherm® K106 Cavity Board and 10 mm cavity table below).
l Outer leaf brickwork l Kingspan Kooltherm® K106 Cavity Board should be firmly
held against the inner leaf of blockwork.
U–value Range l The cavity and wall ties should be kept clean of mortar and
l 0.16 W/m .K (0.11, 0.15 & 0.19 W/m.K block)
2 other debris during construction.
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
Air Barrier Process Sequence
Thermal Performance Process Sequence l Kingspan Kooltherm® K118 Insulated Plasterboard
32.5 mm added to the window reveal with adhesive and
l Ensure Kingspan Kooltherm® K106 Cavity Board is in
supplementary fixings. Ensure Kingspan Kooltherm® K118
contact with the lintel.
Insulated Plasterboard butts the window frame. Seal the
l Kingspan Kooltherm® K106 Cavity Board and cavity tray
perimeter with flexible sealant.
/ proprietary insulated lintel should be taped with a
50 mm (min.) overlap. This may require two or more strips l Seal the joint between the window frame and the internal
of Wraptite tape. linings.
l Ensure there are no gaps between the insulation boards. l Apply flexible sealant to all interfaces between the internal
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.143 0.160 0.182 0.243 0.285
reveal)** Temperature Factor (f) 0.936 0.929 0.921 0.904 0.901
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
16
Wall tie with retaining clip
Wall lining
17
E2 – Open Back Lintel (Uninsulated) without
Base Plate
General Construction Specification
l Wall lining l For normal reveals, ensure the window / door frame
l Inner leaf blockwork overlaps the lintel by no less than 30 mm (take values from
the first two rows of the table below).
l 100 mm overall cavity width with 90 mm Kingspan
Kooltherm® K106 Cavity Board and 10 mm cavity l For fully overlapped / checked reveals, ensure the window /
door frame overlaps the lintel fully / by no less than 80 mm
l Outer leaf brickwork
(take values from the last two rows of the table below).
l Kingspan Kooltherm® K106 Cavity Board should be firmly
U–value Range
held against the inner leaf of blockwork.
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
l The cavity and wall ties should be kept clean of mortar and
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
other debris during construction.
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.253 0.271 0.285 0.349 0.395
Reveal)** Temperature Factor (f) 0.937 0.928 0.921 0.897 0.891
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
18
Wall tie with retaining clip
Wall lining
19
E2 – Open Back Lintel (Uninsulated) with Insulated
Reveal but without Base Plate
General Construction Specification
l Wall lining l For fully overlapped / checked reveals, ensure the window /
l Inner leaf blockwork door frame overlaps the lintel fully / by no less than 80 mm
(take values from the last two rows of the table below).
l 100 mm overall cavity width with 90 mm Kingspan
Kooltherm® K106 Cavity Board and 10 mm cavity l Kingspan Kooltherm® K106 Cavity Board should be firmly
held against the inner leaf of blockwork.
l Outer leaf brickwork
l The cavity and wall ties should be kept clean of mortar and
U–value Range other debris during construction.
l 0.16 W/m .K (0.11, 0.15 & 0.19 W/m.K block)
2
Air Barrier Process Sequence
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
l Kingspan Kooltherm® K118 Insulated Plasterboard
32.5 mm added to the window reveal with adhesive and
Thermal Performance Process Sequence
supplementary fixings. Ensure Kingspan Kooltherm® K118
l Ensure Kingspan Kooltherm® K106 Cavity Board is in
Insulated Plasterboard butts the window frame. Seall the
contact with the lintel. perimeter with flexible sealant.
l Kingspan Kooltherm® K106 Cavity Board and cavity tray
l Seal the joint between the window frame and the internal
/ lintel should be taped with a 50 mm (min.) overlap. This linings.
may require two or more strips of Wraptite tape.
l Apply flexible sealant to all interfaces between the internal
l Ensure there are no gaps between the insulation boards.
air barrier and the window / door frame.
l For normal reveals, ensure the window / door frame
l Seal all penetrations through the air barrier using a flexible
overlaps the lintel by no less than 30 mm (take values from sealant.
the first two rows of the table below).
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.181 0.206 0.226 0.305 0.371
Reveal)** Temperature Factor (f) 0.921 0.911 0.903 0.881 0.873
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
20
Wall tie with retaining clip
Wall lining
21
E2 – Independent Steel Lintel externally and
Independent Concrete Lintel internally
General Construction Specification
l Wall lining l For normal reveals, ensure the window / door frame
l Inner leaf blockwork overlaps the Kingspan Kooltherm® Cavity Closer by no
less than 30 mm (take values from the first two rows of the
l 100 mm overall cavity width with 90 mm Kingspan
table below).
Kooltherm® K106 Cavity Board and 10 mm cavity
l For fully overlapped / checked reveals, ensure the window
l Outer leaf brickwork
/ door frame overlaps the Kingspan Kooltherm® Cavity
Closer fully / by no less than 80 mm (take values from the
U–value Range last two rows of the table below).
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
l Kingspan Kooltherm® K106 Cavity Board should be firmly
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block) held against the inner leaf of blockwork.
l The cavity and wall ties should be kept clean of mortar and
Thermal Performance Process Sequence other debris during construction.
l Ensure Kingspan Kooltherm® K106 Cavity Board is in
contact with the Kingspan Kooltherm® Cavity Closer. If Air Barrier Process Sequence
required, fill gap with insulating expanding foam.
l Seal the joint between the window frame and the internal
l Kingspan Kooltherm® K106 Cavity Board and cavity tray linings.
should be taped with a 50 mm (min.) overlap. This may
l Apply flexible sealant to all interfaces between the internal
require two or more strips of Wraptite tape.
air barrier and the window / door frame.
l Ensure there are no gaps between the insulation boards.
l Seal all penetrations through the air barrier using a flexible
sealant.
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.010 0.008 0.007 0.004 0.004
reveal)** Temperature Factor (f) 0.981 0.982 0.982 0.982 0.982
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
22
Wall tie with retaining clip
23
E2 – Independent Steel Lintel externally and
Independent Concrete Lintel internally with
Insulated Reveal
General Construction Specification
l Wall lining l For fully overlapped / checked reveals, ensure the window
l Inner leaf blockwork / door frame overlaps the Kingspan Kooltherm® Cavity
Closer / by no less than 80 mm (take values from the last
l 100 mm overall cavity width with 90 mm Kingspan
two rows of the table below).
Kooltherm® K106 Cavity Board and 10 mm cavity
l Kingspan Kooltherm® K106 Cavity Board should be firmly
l Outer leaf brickwork
held against the inner leaf of blockwork.
U–value Range l The cavity and wall ties should be kept clean of mortar
and other debris during construction.
l 0.16 W/m .K (0.11, 0.15 & 0.19 W/m.K block)
2
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.007 0.006 0.005 0.002 0.001
Reveal)** Temperature Factor (f) 0.977 0.977 0.977 0.978 0.978
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
24
Wall tie with retaining clip
Flexible sealant
Flexible sealant
25
E3 – Sill (Normal)
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.003 0.003 0.003 0.002 0.002
Reveal)** Temperature Factor (f) 0.959 0.961 0.961 0.964 0.966
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
NB The sill junction shown utilises a timber sill, however the modelled ψ–values also apply for the sill junction if a calcium silicate, cement–based or gypsum–based board of 12 mm thickness is
included below the sill, with no loss of thermal performance, or if a greater thickness of timber sill were used.
26
Flexible sealant
Flexible sealant
Wall lining
27
E3 – Sill (Normal) with Insulated Reveal
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) – 0.003 – 0.003 – 0.003 – 0.004 – 0.004
Reveal)** Temperature Factor (f) 0.983 0.984 0.985 0.988 0.989
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
NB The sill junction shown utilises a timber sill, however the modelled ψ–values also apply for the sill junction if a calcium silicate, cement–based or gypsum–based board of 12 mm thickness is
included below the sill, with no loss of thermal performance, or if a greater thickness of timber sill were used.
28
Flexible sealant
Flexible sealant
Wall lining
29
E4 – Jamb (Normal)
l 100 mm overall cavity width with 90 mm Kingspan l The cavity and wall ties should be kept clean of mortar
Kooltherm K106 Cavity Board and 10 mm cavity
® and other debris during construction.
l Outer leaf brickwork l Ensure Kingspan Kooltherm® K106 Cavity Board and
Kingspan Kooltherm® Cavity Closer are taped with a
U–value Range 50 mm (min.) overlap. This may require two or more strips
of Wraptite tape.
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
l At the vertical edges of openings and at vertical unreturned
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
or unbounded edges (e.g. movement joints), additional wall
ties should be used at a rate of one tie per 300 mm height
Thermal Performance Process Sequence or equivalent, placed not more than 225 mm from the edge.
l Kingspan Kooltherm® Cavity Closer should be installed to
l Alternatively, use an additional wall tie within 225 mm of
close the cavity.
the opening / vertical edge on each board course
l Ensure Kingspan Kooltherm® K106 Cavity Board is in
(450 mm) level to satisfy the structural requirements of the
contact with the full length of Kingspan Kooltherm® Cavity
wall. Avoid penetrating the board, as this may introduce
Closer. If required, fill gaps with insulating expanding foam.
an unacceptable risk of water penetration. Place additional
l Ensure there are no gaps between the insulation boards. ties on each board course to compensate.
l For normal reveals, ensure the window / door frame
overlaps Kingspan Kooltherm® Cavity Closer by no less Air Barrier Process Sequence
than 30 mm (take values from the first two rows of the l Apply flexible sealant to all interfaces between the internal
table below). air barrier and the window / door frame.
l For fully overlapped / checked reveals, ensure the window l Seal all penetrations through the air barrier using a flexible
/ door frame overlaps Kingspan Kooltherm® Cavity Closer sealant.
fully (take values from the last two rows of the table below).
l Seal the junction between the window sill board and the
window frame member.
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.004 0.003 0.003 0.003 0.003
Reveal)** Temperature Factor (f) 0.967 0.968 0.968 0.971 0.972
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
30
Kingspan Kooltherm® Inner leaf
Wall lining K106 Cavity Board blockwork
If required, fill gap with
insulating expanding foam
Kingspan Kooltherm®
Cavity Closer
Flexible sealant
225 mm max
Wraptite tape, 50 mm
Wall tie and Outer leaf Extra ties at jambs overlap required
retaining clip brickwork of all openings
31
E4 – Jamb (Normal) with Insulated Reveal
Detail
Full Overlap (Incl. Checked Linear Thermal Transmittance Ψ (W/m.K) 0.001 0.001 0.001 0.000 0.000
Reveal)** Temperature Factor (f) 0.982 0.983 0.984 0.986 0.988
* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.
** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.
See page 68 for further details.
32
Wall lining Kingspan Kooltherm® Inner leaf If required, fill gap with
K106 Cavity Board blockwork insulating expanding foam
Kingspan Kooltherm®
Cavity Closer
Flexible sealant
225 mm max
Wraptite tape, 50 mm
Wall tie and Outer leaf Extra ties at jambs overlap required
retaining clip brickwork of all openings
33
E5 – Ground Floor – Solid Concrete Slab
l 100 mm overall cavity width with Kingspan Kooltherm® l Ensure Kingspan Kooltherm® K106 Cavity Board is
K106 Cavity Board and 10 mm cavity installed at least 150 mm (UK) / 225 mm (Republic of
Ireland) below the top surface of Kingspan Kooltherm®
l Outer leaf brickwork
K103 Floorboard perimeter insulation.
l The cavity and wall ties should be kept clean of mortar
U–value Range
and other debris during construction.
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
l 0.17 W/m2.K (0.51 W/m.K & 1.13 W/m.K block)
are lightly butted and taped with a 50 mm (min.) overlap.
Detail
34
Wall lining
Kingspan Kooltherm
K106 Cavity Board
Inner leaf blockwork
Wall tie and retaining clip Insulating expanding foam and / or flexible sealant
Wraptite tape, 50 mm
overlap required Kingspan Kooltherm® K103 Floorboard perimeter strip
Damp proof course Floor finish
Floor screed
25 mm sand binding
Kingspan Kooltherm® K106 Cavity Board to start of cavity fill
35
E5 – Ground Floor – Beam & Block (Parallel)
l 100 mm overall cavity width with 90 mm Kingspan l Ensure Kingspan Kooltherm® K106 Cavity Board is
Kooltherm® K106 Cavity Board and 10 mm cavity installed at least 150 mm below the top surface of the floor
beam / bottom of the insulation.
l Outer leaf brickwork
l The cavity and wall ties should be kept clean of mortar
Detail
36
Kingspan Kooltherm® Wall lining
K106 Cavity Board
Inner leaf blockwork
Brick outer leaf
Wraptite tape, 50 mm overlap required Cavity tray over cranked vent only
37
E5 – Ground Floor – Beam & Block (Perpendicular)
l 100 mm overall cavity width with 90 mm Kingspan l Ensure Kingspan Kooltherm® K106 Cavity Board is
Kooltherm® K106 Cavity Board and 10 mm cavity installed at least 150 mm below the top surface of the floor
beam / bottom of the insulation.
l Outer leaf brickwork
l The cavity and wall ties should be kept clean of mortar
Detail
38
Kingspan Kooltherm®
K106 Cavity Board Wall lining
Wraptite tape, 50 mm overlap required Cavity tray over cranked vent only
Weep holes above DPC / cavity tray Insulating expanding foam and / or flexible sealant
at specified centres
Kingspan Kooltherm® K103 Floorboard Floor finish
perimeter strip
Damp proof course 75 mm screed
39
E5 – Ground Floor – Suspended Timber Floor
(Parallel)
General Construction Specification
l Wall lining l Kingspan Kooltherm® K106 Cavity Board should be firmly
l Inner leaf blockwork held against the inner leaf of blockwork.
l 100 mm overall cavity width with 90 mm Kingspan l Ensure Kingspan Kooltherm® K106 Cavity Board is
Kooltherm® K106 Cavity Board and 10 mm cavity installed at least 200 mm below the top of the floor joist.
l Outer leaf brickwork l The cavity and wall ties should be kept clean of mortar
and other debris during construction.
U–value Range l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
Detail
40
Kingspan Kooltherm® Wall lining
K106 Cavity Board
Inner leaf blockwork
Brick outer leaf Flexible sealant
Insulating expanding foam and / or flexible sealant
Wall tie and retaining clip Cavity tray over air brick / vents
Floor finish
41
E6 – Intermediate Floor within a Dwelling – Concrete
l 100 mm overall cavity width with 90 mm Kingspan l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
Kooltherm® K106 Cavity Board and 10 mm cavity are lightly butted and taped with a 50 mm (min.) overlap.
Detail
42
Kingspan Kooltherm® K106 Cavity Board
Wall lining
Floor finish
Flexible sealant
43
E6 – Intermediate Floor within a Dwelling – Timber
l 100 mm overall cavity width with 90 mm Kingspan l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
Kooltherm® K106 Cavity Board and 10 mm cavity are lightly butted and taped with a 50 mm (min.) overlap.
This may require two or more strips of Wraptite tape.
l Outer leaf brickwork
Detail
44
Kingspan Kooltherm® K106 Cavity Board
Wall lining
Floor finish
Flexible sealant
Joist hanger
Ceiling lining
45
E7 – Party Floor between Dwellings
(e.g. in Blocks of Flats)
General Construction Specification
l Wall lining l Ensure Kingspan Kooltherm® K106 Cavity Board is firmly
l Inner leaf blockwork held against / butted lightly to the fire stop & taped.
l 100 mm overall cavity width with 90 mm Kingspan l Ensure Kingspan Kooltherm® K106 Cavity Board and fire
Kooltherm® K106 Cavity Board and 10 mm cavity stop (if used instead of slate or Euroclass A1 rated building
board) are taped with a 50 mm (min.) overlap. This may
l Outer leaf brickwork
require two or more strips of Wraptite tape.
U–value Range
Air Barrier Process Sequence
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
l Seal between the wall lining and floor screed lining with
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
flexible sealant or plaster / screed mortar.
l Seal between the wall lining and ceiling lining with flexible
Thermal Performance Process Sequence
sealant or plaster mortar.
l Kingspan Kooltherm® K106 Cavity Board should be firmly
l Apply flexible sealant between the skirting board and the
held against the inner leaf of blockwork.
floor screed / finish.
l Continue Kingspan Kooltherm® K106 Cavity Board
l Seal all penetrations through the air barrier using a flexible
across the intermediate floor abutment zone.
sealant or plaster mortar.
l The cavity and wall ties should be kept clean of mortar
l Ensure a continuous bed of mortar between the floor slab
and other debris during construction.
and blockwork.
l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
are lightly butted and taped with a 50 mm (min.) overlap.
This may require two or more strips of Wraptite tape.
Detail
46
Kingspan Kooltherm® K106 Cavity Board
Wraptite tape, 50 mm
overlap required Outer leaf brickwork
Wall lining
Floor finish
DPC cavity tray
Insulating expanding foam
and / or flexible sealant
Reinforced concrete floor slab
Flexible sealant
Weep holes
Wraptite tape, 50 mm
overlap required
47
E10 – Eaves (Insulation at Ceiling Level)
l 100 mm overall cavity width with 90 mm Kingspan l Kingspan Kooltherm® K106 Cavity Board and eaves
Kooltherm® K106 Cavity Board and 10 mm cavity insulation should be firmly held against / butted tight
against the fire stop.
l Outer leaf brickwork
l The cavity and wall ties should be kept clean of mortar and
Detail
NB Calculations based on a ceiling with 100 mm mineral wool (0.039 W/m.K) between joists and 250 mm mineral wool (0.039 W/m.K) above joists.
48
Membrane
Proprietary
eaves ventilation
Ceiling lining
Wraptite tape, 50 mm
overlap required Kingspan Kooltherm® K106 Cavity Board
49
E11 – Eaves (Insulation at Rafter Level)
l 100 mm overall cavity width with 90 mm Kingspan l Kingspan Kooltherm® K106 Cavity Board and eaves
Kooltherm® K106 Cavity Board and 10 mm cavity insulation should be firmly held against / butted tight
against the fire stop.
l Outer leaf brickwork
l The cavity and wall ties should be kept clean of mortar and
Detail
NB Calculations based on 150 mm Kingspan Kooltherm® K107 between rafters and 62.5 mm Kingspan Kooltherm® K118 Insulated Plasterboard beneath rafters.
50
Proprietary eaves ventilator
Membrane
Roof tiles
51
E12 – Gable (Insulation at Ceiling Level)
l 100 mm overall cavity width with 90 mm Kingspan l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
Kooltherm® K106 Cavity Board and 10 mm cavity are lightly butted and taped with a 50 mm (min.) overlap.
l Outer leaf brickwork l Ensure Kingspan Kooltherm® K106 Cavity Board and
proprietary fire stop (if used instead of slate / Euroclass
U–value Range A1 rated building board) are taped with a 50 mm (min.)
overlap. This may require two or more strips of Wraptite
l 0.16 W/m2.K (0.11 0.15 & 0.19 W/m.K block)
tape.
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
l Kingspan Kooltherm® K106 Cavity Board is to be
installed a minimum of 200 mm above the top surface of
Thermal Performance Process Sequence the ceiling insulation.
l Kingspan Kooltherm® K106 Cavity Board should be firmly
held against the inner leaf of block work. Air Barrier Process Sequence
l Pack flexible insulation between the last truss / joist and l Seal the gap between the wall and ceiling linings with
gable wall. flexible sealant / plaster mortar.
l Ensure the ceiling insulation over the truss / joist tightly l Seal all penetrations through the air barrier using a flexible
abuts the flexible insulation packed between the last truss sealant / plaster mortar.
/ joists.
l Ensure the ceiling insulation between and over the truss /
joists extends to the inner edge of the wall.
Detail
NB Calculations based on a ceiling with 100 mm mineral wool (0.039 W/m.K) between joists and 250 mm mineral wool (0.039 W/m.K) above joists.
52
Weep holes
Insulation
Wall lining
Outer leaf brickwork
53
E13 – Gable (Insulation at Rafter Level)
l 100 mm overall cavity width with 90 mm Kingspan l Ensure Kingspan Kooltherm® K106 Cavity Board and
Kooltherm® K106 Cavity Board and 10 mm cavity proprietary fire stop (if used instead of slate / Euroclass
A1 rated building board) are taped with a 50 mm (min.)
l Outer leaf brickwork
overlap. This may require two or more strips of Wraptite
tape.
U–value Range
l The cavity and wall ties should be kept clean of mortar and
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
other debris during construction.
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
are taped with a 50 mm (min.) overlap. This may require
Thermal Performance Process Sequence two or more strips of Wraptite tape.
l Kingspan Kooltherm® K106 Cavity Board should be firmly
held against the inner leaf of blockwork. Air Barrier Process Sequence
l Ensure the gap between the wall plate and eaves ventilator l Bed the wall plate on a continuous layer of mortar.
is completely filled with flexible insulation. The flexible l Seal the gap between the wall and ceiling linings with
insulation is to have an R–value of 1.2 m².K/W or higher. flexible sealant or plaster mortar.
l The flexible insulation should be tucked down the head l Seal all penetrations through the air barrier using a flexible
of the cavity to enable continuity of this and Kingspan sealant / plaster mortar.
Kooltherm® K106 Cavity Board throughout the junction.
l Ensure the full depth of ceiling insulation, between and
over joist ceiling insulation, abuts the eaves insulation.
Detail
54
Wraptite tape, 50 mm overlap required Roof tiles
Timber battens
Either use proprietary insulated fire stop,
slate or Euroclass A1 rated building board Kingspan Kooltherm® K107
to close the cavity Pitched Roof Board
Ceiling lining
Wall lining
55
E14 – Flat Roof
U–value Range are lightly butted and taped with a 50 mm (min.) overlap.
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block) l Ensure Kingspan Kooltherm® K106 Cavity Board and
proprietary fire stop (if used instead of slate / Euroclass
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
A1 rated building board) are taped with a 50 mm (min.)
overlap. This may require two or more strips of Wraptite
Thermal Performance Process Sequence tape.
l Kingspan Kooltherm® K106 Cavity Board should be firmly
held against the inner leaf of blockwork. Air Barrier Process Sequence
l Ensure Kingspan Kooltherm® K106 Cavity Board is taken l Seal the gap between the wall and ceiling linings with
up level with the top of the wall firmly held against / butted flexible sealant or plaster mortar.
tight against the fire stop and taped.
l Seal all penetrations through the air barrier using a flexible
l Pack flexible insulation between the last joist / gable sealant / plaster mortar.
ladder. Fully fill the void and ensure the insulation is in
contact with the roof deck and cavity closer.
Detail
56
Waterproofing
18 mm WBP plyboard
Ceiling lining
Flat roof joist
Insulating expanding foam
and / or flexible sealant
Wall lining
Wraptite tape, 50 mm
overlap required Kingspan Kooltherm® K106
Cavity Board
57
E15 – Flat Roof with Parapet
Detail
Wall lining
59
E16 – Corner (Normal)
U–value Range l The cavity and wall ties should be kept clean of mortar and
other debris during construction.
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
Air Barrier Process Sequence
l Seal the gap between the wall and ceiling linings with
Thermal Performance Process Sequence
flexible sealant or plaster mortar.
l Kingspan Kooltherm® K106 Cavity Board joints should be
l Seal all penetrations through the air barrier using a flexible
staggered at the building corners.
sealant / plaster mortar.
l Ensure all Kingspan Kooltherm® K106 Cavity Board joints
are lightly butted and taped with a 50 mm (min.) overlap.
This may require two or more strips of Wraptite tape.
Detail
60
Wall lining
Board joint
61
E17 – Corner (Inverted)
Detail
62
Board joint
50 mm (min.) overlap
Wraptite tape, 50 mm overlap required
Wall lining
63
E18 – Party Wall between Dwellings (Filled Cavity)
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block) l The cavity and wall ties should be kept clean of mortar and
other debris during construction.
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
Detail
64
Outer leaf
brickwork
50 mm overlap
Kingspan Kooltherm®
K106 Cavity Board
Wraptite tape, 50 mm
overlap required
Wall lining
65
E18 – Party Wall between Dwellings (Unfilled Cavity)
l 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block) l The cavity and wall ties should be kept clean of mortar and
other debris during construction.
l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)
Detail
66
Outer leaf
brickwork
50 mm overlap
Kingspan Kooltherm®
K106 Cavity Board
Wraptite tape, 50 mm
overlap required
Wall lining
67
E2 – Lintel (Checked Reveal)
Detail
Wraptite tape, 50 mm
Proprietary insulated lintel
overlap required
Weep holes
Flexible sealant
Flexible sealant
68
E3 – Sill (Checked Reveal)
Detail
Flexible sealant
Flexible sealant
69
E4 – Jamb (Checked Reveal)
Kingspan Kooltherm®
Cavity Closer
Flexible sealant
225 mm max
Wraptite tape, 50 mm
overlap required
70
E5 – Solid Ground Floor (Cavity Tray)
Detail
Wall lining
25 mm sand binding
25 mm (min.) from underside of Kingspan Kooltherm® K106
selected hardcore
** Typically the DPM / Radon / Gas membrane will form the cavity tray detail.
71
E5 – Timber Floor – Perpendicular
Detail
Wall lining
Kingspan Kooltherm® K106 Cavity Board
Inner leaf blockwork
Flexible sealant
Brick outer leaf Insulating expanding foam and / or flexible sealant
Wall tie with retaining clip Cavity tray over air brick / vents
Floor finish
Kingspan Kooltherm®
K103 Floorboard
Weep holes above
200 mm
72
E16 – Corner – Normal (alternative Mitre Joint)
Detail
Wall lining
73
E17 – Corner – Inverted (alternative Mitre Joint)
Detail
Board joint
50 mm (min.) overlap
Wall lining
74
Flue (Core Drilled, no Separation)
Detail
Wall lining
Outer leaf brickwork
Cement mortar
Flue
NB This detail may be used where a separation between the flue / air duct and Euroclass B - E rated material is not required, for example plastic flues serving appliances that operate under 100°C .
Always refer to the manufacturer of the heating system and obtain guidance from a competent person (Gas safe, OFTEC, HETAS or equivalent) to determine the requirements.
Manufacturer’s instructions may detail a specific clearance from the flue / air supply duct (s) and Euroclass B - E rated materials, irrespective of flue–gas or duct temperature, therefore see flue
(built in, separation) detail on page 68.
75
Flue (Built In, no Separation)
Detail
Wall lining
Outer leaf brickwork
Cement mortar
Cavity tray DPC
Flue
NB This detail may be used where a separation between the flue / air duct and Euroclass B - E rated material is not required, for example plastic flues serving appliances that operate under 100°C .
Always refer to the manufacturer of the heating system and obtain guidance from a competent person (Gas safe, OFTEC, HETAS or equivalent) to determine the requirements.
Manufacturer’s instructions may detail a specific clearance from the flue / air supply duct (s) and Euroclass B - E rated materials, irrespective of flue–gas or duct temperature, therefore see flue
(built in, separation) detail on page 66.
76
Flue (Built In, Separation )
Detail
Wall lining
50 mm (min.)
Dimension varies, check with appliance
manufacturer or competent person
Weep holes
Proprietary sleeve
(if required – possibly integral flue)
NB This detail illustrates when separation from the flue / air duct and Euroclass B - E rated material is required.
The appliance manufacturer’s instructions must be sought, which may detail a specific clearance from the flue / air supply duct (s) and Euroclass B - E rated materials, irrespective of flue–gas or
duct temperature.
The dimension of Euroclass A1 rated insulation around flue pipes / terminal can vary, for example, all flues serving oil fired boilers require a 300 mm minimum area around the flue pipe / terminal
free from Euroclass B - E rated material.
77
Wall Tie
Detail
Wraptite tape, 50 mm
overlap required
78
79
Contact Details
To check that you have the latest version of this brochure please
visit www.kingspaninsulation.co.uk/downloads.
To access pre-existing product information or information relating
to previously sold/discontinued products please email
literature@kingspaninsulation.co.uk KI\GB\SD\K10690\004\Jan22a
®
Kingspan, Kooltherm, Thermaroof, Thermataper and the Lion Device are Registered Trademarks of the Kingspan Group plc in the UK, Ireland and other countries. All rights reserved.
Registered in England & Wales, No. 01882722. Registered Office: Pembridge, Leominster, Herefordshire HR6 9LA UK. VAT GB428602456.