Project 1

04 / 21 / 2022

Operator
Telephone
Fax
e-Mail

Locker Room / Summary

Height of Room: 9.000 ft, Mounting Height: 9.000 ft, Light loss factor: 0.80 Values in Footcandles, Scale 1:114

Surface  [%] Eav [fc] Emin [fc] Emax [fc] u0


Workplane / 18 9.64 23 0.539
Floor 20 17 9.20 24 0.526
Ceiling 80 4.51 3.15 17 0.698
Walls (6) 50 11 4.02 88 /

Workplane:
Height: 0.000 ft
Grid: 128 x 32 Points
Boundary Zone: 0.500 ft
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.644, Ceiling / Working Plane: 0.252.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
ASD Lighting corp ASD-ELP02-22D2740-STD
1 1 3105 3105 27.0
(1.000)
ASD Lighting corp ASD-ELP02-24D4040-STD
2 4 4600 4600 40.0
(1.000)
Total: 21504 Total: 21505 187.0

Specific connected load: 0.27 W/sq ft = 0.15 W/sq ft/10 fc (Ground area: 703.16 sq ft)

DIALux 4.13 by DIAL GmbH Page 1