Generator Set With QSL9 Engine - Circuit Breaker Torque Check

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

08:49, 01/12/2021 Generator Set with QSL9 Engine: Circuit Breaker Torque Check

Technical Service Bulletin


Technical Service Bulletin: TSB200104 Released Date: 12-May-2020
Generator Set with QSL9 Engine: Circuit Breaker Torque Check

Generator Set with QSL9 Engine: Circuit Breaker


Torque Check
Warranty Statement
The information in this document has no effect on present warranty coverage or repair practices,
nor does it authorize TRP
or Campaign actions.

Contents
Product Affected
C230 D6e
C250 D5e
C250 D6
C250 D6e
C275 D5
C275 D5e
C275 D6
C275 D6e
C300 D5
C300 D5e
C300 D6
C300 D6e
C330 D5
C330 D5e
Issue
Inadequate torque applied to circuit breaker (CB) joints at factory. This may lead to higher
resistance in the current carrying
path, resulting in thermal damage on circuit breaker line poles,
which in turn can cause damage to neighboring components
in the control panel.
Symptom:
Loose power cable joints at line connections
Loose cable connector joints at line connections
Root Cause:
https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2020/tsb200104.html 1/6
08:49, 01/12/2021 Generator Set with QSL9 Engine: Circuit Breaker Torque Check

Inadequate torque applied to circuit breaker joints at factory


Verification/Confirmation
All units with models mentioned under Products Affected need to be checked for circuit breaker
connections during their periodic
maintenance.

Resolution
Re-torque circuit breaker connections as part of periodic maintenance. For more instructions, refer
to Service Instructions
section.
Service Instructions
This check needs to be performed during the next periodic maintenance schedule as part of
“Check Circuit Breaker for loose
connections – every 500 hours” (refer to Table 4 of Service
manuals, GLN- A052F957, A052F920).
Safely shut down and lock-out tag-out (LOTO) generator set according to LOTO procedures and
guidelines.
Make sure that the generator set is in OFF position and it is de-energized, electrically and
mechanically.
1. Open the control panel and access the circuit breaker. Part number (PN) of circuit breaker for
the various models of generator
set are listed in Table 1.

Table 1, List of Affected Circuit Breaker Part Numbers


Cummins PN of Manufacturer PN of
Amperage Poles
circuit breaker circuit breaker
A034J457 LV432676 400 3
A034J459 LV432876 630 3
A034J461 LV432677 400 4
A034J463 LV432877 630 4
A034H831 LV432693 400 3
A034H826 LV432893 630 3
A034H829 LV432694 400 4
A034H832 LV432894 630 4

2. Access Circuit Breaker line connections. Refer to Figure 1.

GRAPHIC NOT FOUND

Figure 1, Circuit breaker line connections highlighted


3. On the line connections, access one of the phases. Using H 5/16” Allen socket, remove top and
bottom Allen-screws and lift
the power cable/s up, refer to Figure 2.

https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2020/tsb200104.html 2/6
08:49, 01/12/2021 Generator Set with QSL9 Engine: Circuit Breaker Torque Check

Figure 2, 2-cable connector - remove the top and bottom Allen screws and lift the power cables
4. Inside the bottom terminal of 2-cable connector, locate the Allen screw that holds the cable
connector to the circuit breaker.
Using manual torque wrench and H 5/16” Allen socket, torque to
37 Nm. Refer to Figure 3. Cross-verify the torque. Mark it
with yellow torque-mark to show that it
has been torqued.
Note
: If the 2-cable connectors are damaged, they can be ordered. Cummins part
number for 3 pole connectors is 0320-2119-01 and
the part number for 4 pole
connectors is 0320-2119-02.

https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2020/tsb200104.html 3/6
08:49, 01/12/2021 Generator Set with QSL9 Engine: Circuit Breaker Torque Check

Figure 3, Torque the Allen screw inside the bottom terminal of 2-cable connector to 37 Nm
5. Reinsert the power cable/s correctly. After reinserting, using manual torque wrench and H 5/16”
Allen socket, torque the
top and bottom Allen screws to 31 Nm. Refer to Figure 4. Cross-verify the
torque. Mark it with yellow-mark to show that it
has been torqued. Refer to Figure 5.

GRAPHIC NOT FOUND

Figure 4, After reinserting the power cables correctly, torque the top and bottom Allen screws to
31 Nm

GRAPHIC NOT FOUND

Figure 5, Yellow torque-mark post torque application on Allen screws for power cables
6. Repeat steps 3, 4, 5 above for all the phases on the line connection side.
Note
: Report any issues found with the torqueing to your primary/regional service
engineering contact.
Service Parts Availability

Service parts are available. See Table 2 for part numbers.

Table 2, Service Parts


Part Existing Part New Part
Obsolete Superseded
Description Number Number

https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2020/tsb200104.html 4/6
08:49, 01/12/2021 Generator Set with QSL9 Engine: Circuit Breaker Torque Check

Table 2, Service Parts


Part Existing Part New Part
Obsolete Superseded
Description Number Number
Bare Cable
Connectors- 3 0320-2119-01 NA NA NA
pole
Bare Cable
Connectors- 4 0320-2119-02 NA NA NA
pole

Production Status

Implemented for production. See Table 3.

Table 3, Production Information


Product GSN First Build Date
1 Plant
C300 D5 H19I806281  08/26/2019 CPG-India Phaltan
1Generator Set/Engine build date can be found on the Generator Set/engine dataplate.

Publications Affected/Associated Publications

Table 4, Publications Affected


QSOL
Procedure /
Manual Type Document Part Procedure Section
Section Title
Number
Addition of:
Circuit Breaker
Steps to check
Service Manual A052F957 Maintenance 15.5
circuit breaker
Guidelines
connections
Added additional
checkpoint:
Periodic Check Circuit
Service Manual A052F957 4.1
Maintenance Breaker for
loose
connections
Addition of:
Circuit Breaker
Steps to check
Service Manual A052F920 Maintenance 6.13.5
circuit breaker
Guidelines
connections

https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2020/tsb200104.html 5/6
08:49, 01/12/2021 Generator Set with QSL9 Engine: Circuit Breaker Torque Check

Table 4, Publications Affected


QSOL
Procedure /
Manual Type Document Part Procedure Section
Section Title
Number
Added additional
checkpoint:
Periodic Check Circuit
Service Manual A052F920 4.1
Maintenance Breaker for
loose
connections

Document History
Date Details
2020-5-4 Module Created

Last Modified:  12-May-2020

https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2020/tsb200104.html 6/6