UPS ON LINE
EA900 PRO 1/1 6-10KVA
1
Table of Contents
1 Safety Information........................................................................... 2
2 Product Overview............................................................................ 5
2.1 Features .................................................................................. 5
2.2 Specifications........................................................................... 6
2.3 Front panel features ................................................................. 7
2.4 Rear panel features ................................................................. 8
3 Installation ....................................................................................... 9
3.1 Unpacking inspection ............................................................... 9
3.2 Single System Installation ........................................................ 9
3.3 Connect the communication................................................... 11
3.4 Parallel System installation .................................................... 13
4 Operation Instructions .................................................................. 16
4.1 Display panel ......................................................................... 16
4.2 UPS On / Off operation .......................................................... 18
4.3 Parallel UPS operation........................................................... 19
4.4 Maintenance switch (optional)................................................ 19
4.5 Parameters inquiry................................................................. 19
4.6 UPS settings .......................................................................... 23
5 Operation Modes ........................................................................... 29
5.1 Power-up mode / Shutdown mode ......................................... 29
5.2 Standby mode ........................................................................ 29
5.3 Bypass mode ......................................................................... 29
5.4 Mains power mode (Frequency conversion mode)................. 30
5.5 Battery mode / battery self test mode..................................... 30
5.6 ECO mode ............................................................................. 30
5.7 Fault mode............................................................................. 30
5.8 Maintenance bypass (manual operation) ............................... 31
5.9 Test mode .............................................................................. 31
6 Troubleshooting ............................................................................ 32
1 Safety Information
CAUTION
Non-qualified electricians are forbidden to open the case due to hazard of electrical shock.
Consulting the dealer is required before using for below equipment. Its application,
configuration, management and maintenance must be specially considered and designed.
Medical equipment which is directly related to patients’ life
Elevator and other equipment which may endanger personal safety
WARNING
The UPS must be properly earthed / grounded and due to a high leakage current, the earthing
/ grounding conductor must be connected first.
2
Safety and General Information Seguridad e Información General
Lea atentamente toda la información de seguridad y las instrucciones de operación antes de intentar instalar, operar,
mantener o mantener el UPS.
Read all safety information and operating instructions carefully before attempting to install, operate, service or maintain the UPS.
El SAI contiene baterías internas y puede presentar un peligro de electrocución, incluso desconectado del circuito derivado
(red).λ
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit (mains).
The protective earth conductor for the UPS carries the leakage current from the load devices (computer equipment). An insulated
ground conductor is to be installed as part of the branch circuit that supplies the UPS. The conductor must have the same size and
insulation material as the grounded and ungrounded branch circuit supply conductors.
Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is recommended.
Disconnect all connection wiring before maintenance or cleaning to avoid the risk of electric shock.
Do not dispose of the batteries with fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte inside is harmful to the skin and eyes, and maybe toxic.
Do not connect the positive pole and negative pole directly, otherwise it will cause electric shocks or will be on fire.
It is not suitable to connect some electric equipment such as hair drier and heating appliance.
El conductor de tierra de protección del SAI transporta la corriente de fuga de los dispositivos de carga (equipo informático).λ Se instalará
un conductor de tierra aislado como parte del circuito de derivación que suministra el SAI. El conductor debe tener el mismo tamaño y el
mismo material de aislamiento que los conductores de alimentación del circuito de derivación conectados a tierra y sin conexión a tierra.
No use extintor de líquidos si hay un incendio, se recomienda un extintor de polvo seco.λ
Desconecte todos los cables de conexión antes de realizar el mantenimiento o la limpieza para evitar el riesgo de descarga eléctrica.λ
No deseche las baterías con fuego.λ Las baterías pueden explotar.
No abra ni mutile las baterías.λ El electrolito liberado en el interior es dañino para la piel y los ojos, y tal vez tóxico.
No conecte directamente el polo positivo y el polo negativo, ya que de lo contrario causará descargas eléctricas o estará en llamas.λ
No es adecuado conectar algún equipo eléctrico como secador de pelo y aparato de calefacción.λ
Note :
Symbol instructions
/I Turn on Bypass
AC Recyclable
DC Battery
¡Peligro! ¡Alto
Desconectar alarma
voltaje!
Encender Bypass
3
AC Batería
DC
4
2 Descripción del producto
2.1 Características:
Mayor fiabilidad que el sistema autónomo con tecnología digital paralela avanzada¬Higher reliability than stand-alone system with
advanced digital parallel technology
High Availability
Wide input voltage range, self-adaptive 50Hz /60 Hz grid system, suitable for various grid environments
Linear derating in low voltage input, reducing battery discharging times, extending the service life of battery
Output power factor improved from 0.8 to 0.9, load-carrying capacity increased by 13%
Flexible battery configuration for using 14-20pcs batteries, saving costs for customers
Doubling the battery charging speed, 90% capacity restored in 4 hours for standard model UPS
Ability to turn on the UPS with batteries in the absence of mains power
UPS power supply mode has no transfer time to ensure uninterruptible power
Configurable delay start time when mains power is restored, reducing the impact on power grid or generator
Frequency conversion mode: 50Hz input / 60Hz output or 60Hz input / 50Hz output
Alta disponibilidad
Amplio rango de voltaje de entrada, sistema autoadaptable de cuadrícula 50Hz / 60 Hz, adecuado para diversos ambientes de
red¬
Reducción lineal en entrada de baja tensión, reduciendo los tiempos de descarga de la batería, extendiendo la vida útil de la
batería¬
Factor de potencia de salida mejorado de 0,8 a 0,9, capacidad de carga aumentada en un 13%¬
Configuración flexible de la batería para usar las baterías 14-20pcs, ahorrando costes para los clientes¬
Doblar la velocidad de carga de la batería, la capacidad del 90% restaurada en 4 horas para el modelo estándar UPS¬
Capacidad para encender el SAI con baterías en ausencia de alimentación de red¬
El modo de suministro de energía del UPS no tiene tiempo de transferencia para garantizar una alimentación ininterrumpida¬
Tiempo de inicio de retardo configurable cuando se restablece la alimentación de red, reduciendo el impacto en la red eléctrica o
generador¬
Modo de conversión de frecuencia: 50Hz de entrada / 60Hz de salida o 60Hz de entrada / 50Hz de salida¬
High Usability
LCD+LED display, multi-functional keys operation, friendly human-machine interface
Powerful background software for parameters configuration and online updating
Compact internal layout, miniaturized the complete unit for small footprint
High Intelligence
Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces are used for monitoring
5
UPS running status. Among them, SNMP is for remote network monitoring and management, by which can configure regular battery self
test.
Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, improving the reliability of charger
and extending battery service life by 50%;
6
RS232 & intelligent
slot (standard), USB & Supports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / 7 /
RS485 & dry contacts 8 / 10
(optional)
Power management from SNMP manager and web
SNMP (optional)
browser
OTHERS
Humidity 20 ~ 90% RH @ 0 ~ 40℃ (non-condensing)
Noise level ≤ 55 dB (1m)
Dimensions (W*D*H)
191×462×350 (H), 191×462×710 (S)
(mm)
267×573×436 (H)
Packaged dimensions
308×640×896 (S, with battery), 572×790×280 (S, without
(W*D*H) (mm)
battery)
15.6 (H), 58.7 (S, with 16.1(H), 67.2 (S, with
Net weight (kg) battery), battery),
26.7 (S, without battery) 27.2 (S, without battery)
17.9 (H), 64.8 (S, with 18.4 (H), 73.3 (S, with
Gross weight (kg) battery), battery),
32.8 (S, without battery) 33.3 (S, without battery)
Derate capacity to 70% in frequency conversion mode and to 90% when the output voltage is adjusted to 208 Vac.
Derate output PF to 0.7 in battery mode (14pcs batteries) and to 0.8 in battery mode (15pcs batteries).
S means standard model, H means long time model.
All specifications subject to change without notice.
Custom-made specifications are acceptable.
2.3 Front panel features
TEST/MUTE
ON OFF
BATTERY PACK
+ -
TEST/MUTE
ON OFF
7
2.4 Rear panel features
11 10 9
8
12 7
13
6 6
5 3
2
4
1
11 10 9
8
12 7
13
6 6
5
2
4
1
8
3 Installation
3.1 Unpacking inspection
Open the UPS package and inspect the contents upon receipt. The accessories attached to the UPS contain a user manual, RS232
communication cable, CD-ROM.
Check if the unit is damaged during transport. Do not power on and notify the carrier and dealer if find damaged or parts missing.
Verify this unit is the model you want to buy. Check the model name showed both on the front panel and rear panel.
Note:
Keep the packaging box and packaging materials for reuse. The equipment is heavy. Always handle it with care.
3.2.2 Wiring
The UPS system uses terminal block for input and output connections. The requirements for the cable current are as follows:
Model Maximum current (A)
9
Input Battery Output
6kVA 41.8 37.5 27.3
10kVA 66.3 62.5 45.5
BATTERY
+ -
L N N L
Output L
PE
Input L + -
Output N Input N Battery
Terminal block
Note :
Ensure that the input / output cables must be connected firmly to the input / output terminals, bad contacts are not allowable. It is suggested
that the earth wire is close to the input / output wire size.
Model
Wiring spec mm ( 2
)
Input Battery Output Earth wire
6kVA 6 6 6 6
10kVA 10 10 10 10
Note :
It is need to select proper cable for long-lasting device to connect battery and UPS, and a DC breaker should be connected between battery
and UPS.
1-meter space should be spared before and after UPS host for avoiding foreign matters blocking the air duct of UPS.
Model
Wiring spec mm ( 2
)
Input Battery Output Earth wire
6kVA 8-5S / 8-5S 8-5S
10kVA 8-5S / 8-5S 8-5S
Note:
The recommended torque of screws on terminal block is 1.765N.M or 18kgf.cm.
Long backup mode UPS contains one external battery connector wire, standard mode UPS don’t contain the wire.
Note:
It is recommended that the input external breaker is two levels larger than the internal breaker of UPS. Model need be selected according to
the characteristics of switch trip in different brands and different modes as well as the system configuration for ensuring reasonable mode
selection of breaker cascade between upper and lower levels.
There is no output breaker in the interior of UPS, which needs to be configured by users.
Maintenance switch is optional, and it’s a rotary switch.
For the configuration of 16 batteries, the DC withstand voltage of battery breaker should be higher than 220VDC; for the configuration of 20
batteries, the DC withstand voltage of battery breaker should be higher than 270VDC. You can select the 3P breaker if the 2P breaker cannot
meet the demand of the configurations, Thereinto 2P should be used in series.
10
The requirements for air conditioning refrigeration are as follows:
Note:
The recommended air conditioning refrigeration capacity is only for the single heat source of UPS in room, and the actual air conditioning
configuration should be selected according to all heat sources in the room and room layout.
Battery breaker
+ -
16/20pcs batteries
...
+ - + - + - + -
Connect the UPS and monitoring equipment (computer) by standard RS232 port (standard configuration) and standard USB port (optional
configuration) to make single unit communication.
Connect RS232 (or USB) cable to the serial port of the computer (or USB port)
Connect RS232 (or USB) cable to the serial port of the UPS (or USB port)
RS232 port
Pins 1 2 3 4 5
Pins 6 7 8 9
11
USB port (optional)
Pins 1 2 3 4
Power source
Definition Data+ Data - GND
+5V
The Emergency Power Off (EPO) is a feature that will immediately disconnect all connected equipment from mains power. The EPO port is on the
rear panel of the UPS with green terminals. Its connection is as follows :
EPO function is not enabled by default. You need to set manually if you want to
enable this function. You can refer to the setup instructions in chapter 4.6.2.
The UPS has one intelligent slots for SNMP card, dry contacts card and RS485 card. Intelligent cards are installed in the intelligent slots on the
UPS rear panel, and there is no need to stop the UPS during installation. The installation procedure is as follows:
Remove the cover plate of the intelligent slots
Insert the required intelligent card into the slot
Tighten the screws
Pins Definition
PIN1 :
Close UPS fault
PIN2 Close:Alarm sounds (system fault)
PIN3 Grounding
PIN5 Common
PIN6 :
Close bypass working
PIN7 Close:low battery
Close:UPS working
Open:bypass working
PIN8
Refer to the parallel wiring diagram. The switch size in the diagram is referred to the maximum current of terminal block to match.
The output cable length requires: the cable length from each single UPS output to parallel UPS units output is almost same and more than 2 m
at least. When the distance between the load and each parallel UPS is less than 20 m, each cable length difference less than 20% is required.
When the distance between the load and each parallel UPS is more than 20 m, each cable length difference less than 10% is required.
13
Parallel cable connection for three or more UPS
Note:
For three or more parallel UPS units, removing the jumper cap of CN3 on the parallel card of the more unit than the third (including the third
unit) is required, only keep the jumper cap of CN3 on the parallel card of the two UPS.
14
Mains input
BATTERY BATTERY
+ - + -
L N N L L N N L
+ - + -
L N PE N L
OUTPUT PE INPUT BATTERY 1 BATTERY 2
15
4 Operation Instructions
4.1 Display panel
TEST/MUTE
ON OFF
4.1.1 Buttons
Power ON button ( + )
Press the Power ON button more than half a second to turn the UPS on.
Inquiry button ( , )
In Non-menu setting interface:
Press or more than half a second and less than 2 seconds to display option contents in sequence from left to right.
Press and hold more than 2 seconds to enter the history inquiry interface; press or more than half a second and less than 2
seconds to turn the page of history records inquiring; press and hold again to return to the main interface.
Press and hold more than 2 seconds to enter roll polling mode,display items are switched automatically in every 2 seconds. Press
and hold again to return to the main interface.
Press or more than half a second and less than 2 seconds to select setting options.
Menu settings button ( )
In Non-menu setting interface:
Press and hold more than 2 seconds to enter the menu settings interface.
In menu setting interface:
Press more than half a second and less than 2 seconds to confirm the setting option.
Press and hold more than 2 seconds to exit the menu setting interface.
16
Illuminated: The UPS is working in inverter mode (such as
Inverter indicator mains power mode, battery mode, battery self test mode,
(Green) ECO mode, frequency conversion mode).
Unilluminated: The UPS is working in non-inverter mode.
Operation mode
LCD display is divided into three areas: Icons display area, value display and settings area, and operation mode area.
Icons display area :
There are following contents in the area of display page
Load and battery icons indicate load and battery capacity, and each square represents 25% of capacity. Load icon will flash when UPS is
overloaded; battery icon will flash when battery capacity is too low or the battery is not connected.
Fan icon indicates the working status of fans. Normally, the fan shows rotation status. The icon will flash if fans are disconnected or faulty;
Buzzer icon indicates if the buzzer is mute. Normally, this icon doesn’t display. Press the mute button in battery or fault mode or set
backstage software set backstage software set backstage software set MUTE ON in any mode, the UPS will get into mute status and the
buzzer icon will be illuminated.
Fault icon is illuminated in fault mode, it doesn’t display in other cases.
The area of menu setting page showing the settable menu options
The area of event log query page showing page number of history records
Value display and settings area:
In non-setting interface, it indicates the relevant information of UPS. Press the inquiry button or to display input voltage and
frequency, output voltage and frequency, battery voltage and capacity, pieces of battery, load, temperature, software version ect.
The fault code will be displayed in fault mode.
In menu setting interface, press the menu settings button and inquiry button to set output voltage value (OPU), physical address(Id),
、
parallel Enable (PAL), end of discharge point (Eod), checking status OFF (CHE) Expert mode (EP), Clear warning function CLE ( )、Battery
、
numbers(PCS) Emergency power off (EPO),etc.
17
Long beep Fault mode
Low battery in battery mode
1 s per beep
Output overload
2 min per beep The inverter is not open
4 s per beep All other alarms
Startup with the battery: Method 1: press first key of each UPS, after each UPS having working power source, press the Power ON
button + of any one of UPS more than half a second to start up parallel UPS. All UPS units will be turned on at same time, then
meanwhile switch to inverter status, working in mains power mode. Method 2: Execute startup operation on each UPS one by one.
Interface Page 1 (output interface): Display UPS output information, as shown below:
19
Interface Page 2: Display UPS load information, as shown below:
Interface Page 3: Display UPS software version and temperature information, as shown below:
20
Interface Page 5: Display UPS battery voltage, battery capacity percentage, as shown below:
Warning code Page :Display UPS warning code, as shown below (ALA means alarm):
Press and hold the settings button more than 2 seconds to enter settings interface. Press inquiry button or more than half a
second and less than 2 seconds to select the function options. After selecting the output voltage setup interface, OPU will flash.
Press the settings button more than half a second and less than 2 seconds to enter the output voltage setting interface (OPU), at this
moment OPU is illuminated, and the value next to the OPU flashes. Press inquiry button or more than half a second and less than 2
seconds, select the corresponding values of OPU.There are 208V, 220V, 230V and 240V available for options. The default output voltage is
220V. The configured settings can be saved in real time.
After selecting the value, press the settings button more than half a second and less than 2 seconds, OPU setup is confirmed, at this
moment the value next to the OPU is illuminated and stop flashing.
Press and hold the menu settings button more than 2 seconds to exit the setting interface and return to the home screen.
Note:
Configure the output voltage setting of parallel UPS units in standby or bypass mode. The settings of single UPS unit can be configured in any
mode.
Press and hold the settings button more than 2 seconds to enter the setting interface. Press inquiry button or more than half a
second and less than 2 seconds to select the function options. After selecting the ID setting interface, ID will flash.
Press the menu settings button more than half a second and less than 2 seconds to enter the ID setting interface, at this moment ID is
illuminated, and the value next to the ID flashes. Press inquiry button or more than half a second and less than 2 seconds to select the
corresponding value of ID function. There are 1/2/3/4/5/6 available for options. The default address is 1. The configured settings can be saved
in real time.
After selecting the address, press the menu settings button more than half a second and less than 2 seconds, ID setup is confirmed, at
this moment the selected value is illuminated and stop flashing.
Press and hold the settings button more than 2 seconds to exit the setting interface and return to the home screen.
Note:
The physical address setting can be only configured in case of single UPS operating, it cannot be done in parallel UPS units.
23
※Configure parallel Enable(PAL)
Press and hold the settings button more than 2 seconds to enter the setting interface. Press inquiry button or more than half a
second and less than 2 seconds to select the function options. After selecting the PAL Enable setting interface, PAL will flash.
Press the settings button more than half a second and less than 2 seconds to enter the PAL Enable setting interface, at this moment PAL
is illuminated, and ON or OFF next to the PAL flashes. Press inquiry button or more than half a second and less than 2 seconds to
select ON to use the PAL Enable function, select OFF not to use the PAL Enable function. PAL is OFF by default. The configured settings can
be saved in real time.
After selecting ON or OFF, press the menu settings button more than half a second and less than 2 seconds, PAL Enable setup is
confirmed, at this moment ON or OFF is illuminated and stop flashing.
Press and hold the menu settings button more than 2 seconds to exit the setting interface and return to the home screen.
Note:
The single UPS is forbidden to start on after PAL Enable.
Power up again after power off in fault mode, the UPS enters checking status (CHE). Judge if keep bypass output and forbid turning on the
UPS according to the fault information. It is not allowed to turn on the UPS until failure is solved and manually close CHE.
Press and hold the settings button more than 2 seconds to enter the setting interface. Press inquiry button or more than half a
24
second and less than 2 seconds to select the function options. After selecting CHE setting interface, CHE will flash.
Press the settings button more than half a second and less than 2 seconds to enter the CHE setting interface, at this moment CHE is
illuminated, and ON next to the CHE flashes. Press inquiry button or more than half a second and less than 2 seconds and select OFF,
at this moment OFF flashes.
After selecting OFF, press the settings button more than half a second and less than 2 seconds, CHE Enable is confirmed, at this
moment OFF next to the CHE is illuminated and stop flashing.
Press and hold the menu settings button more than 2 seconds to exit the setting interface and return to the home screen displaying UPS
output information.
Power up again after power off, the UPS enter normal mode.
Note:
The function setting interface will not have CHE option until failure, there is no CHE option when the UPS is normal.
25
4.6.2 Other settings
※ECO mode setting (ECO)
The economic operation mode is OFF by default, which can be opened to improve the operating efficiency of the system.
Note:
Output voltage has switching time of 15ms at most when economic operating mode is
switched to utility mode / battery mode. As for the load having strict requirements for switching time, please select carefully whether to open
economic operating mode or not.
Instruction: Frequency conversion mode is OFF by default. UPS can be set to operate in
frequency conversion mode, and you can select output of 50Hz or 60Hz.
Note:
UPS operates in frequency conversion mode without bypass function, and the output capacity
drops to 70%.
Expert mode is ON, then enter the settings page again, and there are some options available for setup: numbers of battery (PCS), end of discharge
point (EOd), emergency power off (EPO),clear warning (CLE). If Expert mode is OFF, these options will not be shown in the settings interface.
Note:
Expert mode is OFF by default. After setting it to be ON, EP will be restored to be OFF if power up again.
When set EP as ON, PCS option shows up in the setting interface, allows to configurate the number of batteries.There are 14/15/16/17/18/19/20
pcs of batteries for options,and the default value is 16.
Note:
When set EP as ON, PCS option shows up in the setting interface, allows to configurate the number of batteries. There are dEF, 9.8V, 9.9V, 10V,
10.2V and 10.5V available for options. EOd is dEF by default (Eod varies with load).
The low voltage alarm point of each battery is (Eod + 1V) (Battery low voltage shutdown point + 1V)×Numbers of battery.
After setting EPO Onb, the output power fails when emergency power off.
27
Clear warning setting interface
Note:
when set EP as ON, CLE option shows up in the setting interface, allows to clear away ECO instability, overload frequently, over temperature
frequently, Mains high voltage unstable locking battery mode and other alarms.
28
5 Operation Modes
This UPS is a kind of on-line dual conversion UPS, which has following operation modes :
Power-up mode (LCD display power capacity )
Standby mode (Stdby)
Bypass mode (byPASS)
Mains power mode (LInE)
Battery mode (bAT)
Battery self test (bATT)
Fault mode (FAULT)
Frequency conversion mode (FC)
Economy control operation (ECO)
Shutdown mode (SHUTdn)
Test mode (TEST)
Maintenance bypass mode (manual operation)
5.1 Power-up mode / Shutdown mode
In the condition of power off and the display screen being black out, connect batteries and press first key or connect mains power to illuminate
the screen, the UPS gets into power-up mode, all illuminated LED indicators are turned into off (as shown in the figure below), meanwhile LCD
display power capacity (6kVA/10kVA).
In standby mode, the UPS detects that mains power less than 85 V, it will delay 1 min to automatically enter shutdown mode, all LED indicators are
turned off, meanwhile LCD display SHUTdn characters.
All LED indicators are turned off in standby mode operation (as shown in the figure below), meanwhile LCD display Stdby characters.
Note:
The inverter output frequency in frequency conversion mode is configured output frequency and cutting off bypass is necessary; the inverter
output frequency in mains power mode is related to bypass frequency (the default is 50 Hz when bypass is abnormal and frequency conversion
disenable). Please contact with supplier or after sales staff if need to set frequency conversion mode.
5.5 Battery mode / battery self test mode
In battery mode, the batteries go through DC / DC boost and supply DC voltage to the inverter, and then supply AC power to the load via the inverter
circuit.
LED indicator in battery mode is as shown in the figure below: the inverter LED indicator (green) is illuminated and battery LED indicator (yellow) is
illuminated, and alarm LED indicator (red) flashes while giving alarm, meanwhile LCD display bAT characters.
When the batteries process in manual self-test and regular self-test, the inverter indicator, bypass indicator, battery indicator and fault indicator will be
illuminated circularly, meanwhile LCD display bAT characters.
When the mains circuit input is abnormal, the UPS transfers to battery mode immediately.
When bypass input meets ECO input range and ECO function come to use, the UPS works in ECO mode. At this time bypass supply power to the
load, meanwhile rectification, boosting and inverter work normally, and the charger charges the batteries. When bypass input is out of ECO range,
the UPS transfers to mains power / battery mode operating.
If bypass input is beyond ECO range for five times within 1 hour, the UPS operates time after time from ECO mode to mains power mode, the UPS
will automatically operate in mains power mode and close ECO function.
Note:
When use ECO mode and ECO transfers to inverter, the output probably break off 15ms. For those loads which require strict transfer time, be
cautious to choose whether start ECO mode or not. Please contact with supplier or after sales staff if need to set economy control operation.
When UPS is faulty, the alarm indicator is illuminated, the sound of the UPS buzzer lingers on. According to fault type, fault mode is divided into the
fault of cutting off output and the fault of bypass output.
30
Keep bypass supplying power to the load for other faults beyond above status.
After the UPS enter fault mode, press mute button to mute the sound (auto cancel mute in one day), meanwhile contact your supplier or service man
for troubleshooting.
Note: Make sure the system bypass is normal and not to start frequency conversion, otherwise it may cause power failure or even damage to loads.
If the UPS has no output and needs manual operation on maintenance switch, please ensure to disconnect all input breaker and the UPS display
screen is extinguished completely, then put the maintenance switch to “BYPASS” by hand, otherwise it may cause damage to the UPS.
Refer to 4.4 for details.
5.9 Test mode
Test mode is specially used for test purpose, It is available to control UPS step-startup and drive test ect. by back-end software.
31
CODIGOS DE FALLOS Y ALARMAS EA900 PRO 6-10 KVA 1/1
6 Troubleshooting
LCD display in fault mode is as shown below:
Fault icon
Fault code
Fault mode
32
LCD display warning code is as shown below (ALA means alarm):
33