Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

s: en

:t> »
"'T1
m
-zJJ ~::!
m 0
G') -u
:t> z m
~ C
en :c
--I
en >< :c ~
c: z
m r () C)
m JJ :t> --I Ro
OJ 0 S
CD JJ Z
0 en »
1
m -<
0 en z
tIl --I
..C::> m
0 0 z
OJ
1 r »
0 m z
()
JJ m ~
OhllURI\ OhllURI\
- ---

Z BOILER Z BOILER -,

CONTENTS

& 1. Terms .................................................................................................. · .. · .. · .. ·· .. 5

& 2. Warning Label .. ...... . ............ ... .... .. .. ....... .................... . ..... ...... ....... .. ................... 6

& 3. Basic Precautions .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. ·· .... · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · '''7

4. Boiler External View'" .. ... ................................................................ .. . ........ . ..... ·· .. 8

5. Internal Structure .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. ·· .... · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. · .. ·9

6. Structure, Part Name, Inspection and Adjustment of each Device ........ . ............ ..... . ... '''10
MARINE A!JXlId-A - B 6-1 Fu el Oil Piping ·· ·· ·· ·· .. ···· · .. ·········· ·· ·· ····· ·· ····· ··· ·· ···· ········· ·· ····· ···· ·············· · ·· · ········ ···· 10
/~ KSERIES 6-2 Burner Assembly ..... ....... ...... .......... .... .. .. .......................... ..... .... . .... ... .. ..... ... ....... .. ·11
MANUAL
6-3 Damper (Fully Open - Fully Close) ··· .... ...... .. ···· ···· ........ .. · ........ ··· · .. ·· .. ........ ··· ·· .. · ·· · .. · .. ··12

6-4 Combustion Control Damper ....... .. .......... .... .... ... .... .............. ......... .. ..... .. ......... ........ · 12

6-5 Timing Switch for the Damper (High-Low Type) ..... ..... .......... . ... ... .. .... ... ... .. ....... ·· ···· ··· ··· 13

6-6 Blower ········· ···· ·· ················ ·· ···· ··············· ············ ······· ··· · ········ · ··· ······ ·· ····· ···· ··· · ··· ·· ·13

6-7BurnerNozzle .... . ... ......... .... .... .. ......... ... ......... ... ... ·· ············ ····· ········· ······ ···· ··········14
Introduction
6-8 Nozzle Tip .. .... ...... ..... ..... ..... ...... .. ...... ............. ..... ........ ........ .... ........ ...... ..... ....... .. '15

6-9 Solenoid Valve .. ........................ ..... .. ..... . .. ...... .... .... .... .. ..... ......... .... ................. .... . ·16
Thank you very much for selecting the Z-Boiler.
(1) Solenoid Valve for Pilot Burner ... .. ..... .. .... .................. .. ... ....... ... ... .. ···· ·· ··· ········ ···· 16
This manual gives you instructions on how to use the Z-Boil er. In using the boiler, make sure you
(2) Solenoid Valve for Main Burner .. ... ........ ... ... .. .... ...... .... ... ... ...... ... .... .. ..... .... .... .... " 17
choose a person in charge of handling the boiler (Engineer) and use the boiler after perusing the
manual and understanding the contents . In addition, we recomme nd that you always have this (3) Solenoid Valve Unit .... ..... ..... ..... ... ... ... .. ......... ... ........ .. .. ····· ·· ········ ·· ····· ······ ·· ····· ·18
manual at hand when you work.
6- 10 Fu el Oil Pump ...... .. .. .. ... ..... ... .. .. ........ .. ............ ..... ······ ·· ············· ······ ··········· ······· ···19
Th e main contents of this manual are : Outlin e of GK series Z-Boiler, main functions, descriptions of
the control system, operating procedure and maintenan ce. Precautions relating to operating 6-11 Flow Control Valve " .. .... .... ..... ....... ....... .. .. ...... ...... .. ..... .. .. ..... ....... ...... .. .... .... ..... ... . ·22
method and safety indicated in this manual from damages to measures only relate to usag e for 6- 12 Ignition Transform er . .......... .............. ... .. ... .. ....... .. .. ... .. ... ················ ········ ···· ·· ·········23
specified purposes.
Do not use the boiler by methods that are not mentioned in this manual. Pl ease be aware that we 6-13 Flam e Eye . .... ... .. . .......... .. ... ... .. .. .. .. ......... ....... . ·· ··· ···················· ···· ····· ·· ······ ··· ···· ··24
cannot be held respo nsible if the boiler is used by methods not mentioned in this manual. 6-14 Fu el Oil Heater .. .. .. ....... ..... ... .... .. .......... .. ...... ......... ·· ··· ··· ··········· ·· ········ ·· ··· ···· ··· ··· ·25
As a result of tireless res earch for Improvement Involving the desig n of the L-801Ie r, there are
6-15 Fu el Oil Temp erature Controller .. ... .. .. ... .... .. .... ....... ................. ..................... ... ....... ·26
detai ls that do not correspond to th e product you have purchased . Please note that the contents of
the manual may change without notice. 6-16 Thermostat (For fuel oil) ...................... .. ......... ... ................................................. "27
If you have any inquiries concerning the product you have purchased or about th e contents on this
manual, please do not hesitate to contact us. 6-17 Temprature for Heating Heavy Oil .. · .. .. · ............ · .... .. · .... .......... .......... · .... · .. · ........ ...... 29

2
omlUR~ omlUR~
[- Z BOILER [ Z BOILER

6-18 Feed Water Pump (Miura Water Pump) ....................................... : .......... .. .. ···············30 8. Safety Devices ................................................................................................ "'61

6-19 Water level gauge and Water level control cylinder····················································· ·31 9. Inspection Before Operation and Operation ......................................................... "'62

6-20 Exhaust gas thermostat· ············· ········· ······· ······ ········ ····· ·· ······························ ····· ··· ·33 9-1 Inspection of Every Check Points Before Operation .................... ... .............................. '62

6-21 Pressure Switch (For Steam and Fuel Oil) ......... ......... ... ....... ..... ....... .. ...... ....... ... .. ······34 9-2 Operation (In Case of Automatic Burner Operation) ..................................................... '63

6-22 Pressure Switch Adjustm en t ·· ···· .......... ........ .. ... ......... ... ... .......... .... .... ...... ............... ·35 9-3 Manual Combustion by CAM Switch··············· ···· ···· ··· ············ ···· ··· ·· ······ ········ ············· '65
(1) SNS Type .. ...... .. .. .. ...... .. .......... ......... .. ......... .... ..... ... .. ... .... ... ... .. .. ... .... ··· ······· ··35 10. Regular Maintenance .................................... ....... ............................................ "'66

(2) RT Type ................. .. ....... .... ..... ....... .. .... .. .... ······ ······ ················ ······· ····· ···········36 10-1 Regular Maintenance········ ··· ·········· ········ ······· ············· ·· ··· ··· ··································· '66
6-23 Safety Valve ..... .. . ... ... ... .. ........ ...... ......... .... .. ...... ....... ........ ..................... .... ..... .. ·37 10-2 Inspection and Precautions Before Starting Operation .... .. ... .. ... ................................. '68

6-24 Fuel Oil Strainer (Fuel System) ... .. ... .. ... ... .... .. ...... .... ..... ... ....... ....... ......... ......... ..... ·40 10-3 Inspection and Precautions During Operation .. .............. ................... . ....................... ·68

6-25 Y Shaped Strainer ..... ... .. ............... .... ....... ..... .. ....... ......... ........ .. .. ........ .. ... ........... ·42 10-4 Inspection After Operation ...... ... ...... ................................ .... ...... .... ........ . .... ... ...... ·68

6-26 Feed Water Check Valve ........................................ . ............................................ . '42 10-5 Handling Water in Storage Water Heating ....... .. ...... ...... ..... ........... ......... .... ............ '68

6-27 Sequencer (ProgramrT)able Controller) ................................................................ .. "'43 10-6 Long-term Shut-down .... .... ..... ........ ........... ..... ... ... ... ................... . ... .... .... ... ......... ·68

(1) Outline of The Sequencer ..... ....... ...... ....................... ································ ········43 11. Trouble Shooting ................................................................ ............... .. ......... " '69

(2) CQM1 H Unit Explanation ................... ......... ............ ........ ...... ····················· ··· ···43 11-1 Feed Water System ..... ....... .. .......................................... ................ ... ....... .... ..... . '69

(3) Display Function ..... ... ...... .. ............................... ... ................................. ········· ·47 11-2 Fuel System·· .. ····· .. · .. · .. ··· .. ········ .. ······ .. · .. ·· .... ··········· .. · .. · .. · .. · .. · .. ·· ···· · .... ·· .. · .. · .. · .. · .. ·70

(4) Errors and Their Measures ...................................................... ···························48 11-3 Combustion ...................... ... ................. ............. ......... .. ......... ........ · .. ······· .. · .. ···· .. ·71

6-28 Flame Detector (FS-1 00) .. .. .. ..... .......... ... ........... ........ ..... ... ....... ... .... .... ...... ........... '49 11-4 Safety Control and Alarm Circuit ................... .................. ......................................... 72

6-29 Water Level Detector (LM1-200) ................. . .......... .. ............ ...... ...... ........ .... ············50 11-5 Exhaust Control and Lines (Main Engine , Burner) .................. ... ................................ ·72

6-30 High Pressure Air Soot Blower .. ········ ······· ········ ·········· ············· ······ ············ ··· ······· ·····5 1 12. Remedy against Water Tube trouble .................................................................. '''73

6-31 Soot Cleaning in the Exhaust Gas Side while the ship is in Port ............ .. .... ....... ......... . ·53 12-1 Water Tube Leakage ........ ...... . .... .... . ....... .. .......... ..... ..... ... .......... ·· ···· .. ·· .. ··· .. · .. · .. · .. ·73

6-32 Washing while in Dock .. .. ........... ... ....... ... .......... .. ... ........ ...... ... ... ....... .. ......... ..... ... ·54 12-2 Repair for Water Tube Troubl e .... · .................................... · .. · .... · ...... · .. .. .................... 74

6-33 Excess Steam Dump Valve .......... ... ..... .. .. ...... ......... .......... ........................ ... ......... '55

7. Automatic Operation of the Boiler by the Sequencer ............................................. "'56

7-1 Summary .. .. ..... ..................... ...... ... ..... .. .................. ............. .. ...................... ....... 56

7-2 Basic Time Chart ........................... .... .. ...... ... ............ ········· ··· ····· ················ ·· ····· ··· ·· 56

7 -3 Flowcharts ... .............. .. .... .. ........ ... .. ...................................................................... 58

3 4
OhilURI\ ·OhlIURI\
Z BOILER] [ nnn Z BOILER

1. Terms 2. Warning Label

The following terms are used in this manual for your safe and effective operation.
& Warning
The body of the Z-Boiler GK series and its ancillary equipment have parts with th e following warning
label attached.
& Warning _. ]
1. Indicates a condition or practice which may cause death 2-1. Scald Warning Label
or serious injury to the operator. Attached near parts with hazard of scalding or hot parts (Parts with surface temperatu re of over 60°C) .

2-2. Entrainment Warning Label


Attached on rotating parts with gaps in the structure that could catch fingers (Fingers might get
trapped) .

& Caution ..... J


2-3. Electrocution Warning Label
2. Indicates a condition or practice which may result in Attached on electric parts or around the parts that cannot be disconnected (Or covered) completely.
damage or destruction of property and/o r minor personal
injury. 2-4. Trap Warning Label
Synonymous with the entrainment label, it is attached on moving parts .

2-5. Damage Warning Label


Attached on the water gage as there is a possibility of damage by aged deterioration when it is used
Note -J for long periods .

3. Indicates cautions for preventive the failure of the devices,


and points for effective operation.

u
4. Number in the pointing hand sign indicates the page for
related items .

5 6
OMIURJ\ OMIURJ\
Z BOILER Z BOILER

3. Basic Precautions 4. Boiler External View

& Warning 12) 1)

When operating the GK series Z-Boiler, please comply strictly with all precautions relating with safety
indicated in this manual. There is a danger of serious physical injury if the precautions are not observed .

3-1. Carry Out a Check Before Using The Device


Check the pipe system diagram of the completion drawing and the system of the vessel. Do not operate the
device with the wrong system as this could lead to serious accidents.
Moreover, refer to the completion drawing for specifications.
When handling the device, be sure to choose a person in charge of handling. The person in charge should
not operate or carry out maintenance of the device until they have perused the precautions relating to safety
indicated in the manual and have a sufficient understanding of the precautions.
10)
3-2. Wear Proper Outfit and Protection Gears
The device should not be operated or serviced wearing baggy clothes and accessories as they could catch 13)
on the valve or machinery parts. Do not wear oil stained clothes as they could catch fire .
Do not forget to wear a helmet, protection eyewear, safety shoes and gloves when working on the device.
Protection gears must be worn as there is a particular danger of scalding near hot parts. Moreover, protection
eyewear and gloves must be worn as chemicals could splatter on hands and eyes while injecting chemicals .
3-3. Do not Remodel The Device, Use The Genuine Products for The Parts.
Do not remodel the device without our approval. We may not be able to permit such remodeling by regulations.
Moreover, such remodeling could compromise safety. Use the manufacturer's genuine products for parts.
3-4. Use The Designated Fuel
4)
Do not use fuels other than those designated . There would be a danger of the device exploding if other fuels are used.
3-5. Do not Keep Flammable Goods Near The Boiler
Do not keep flammable goods near the boiler. There would be danger of fire .
It is highly dangerous as there would be a danger of fire if flame were brought near the boiler fuel.
Store flammable goods in a safe place away from flames, check where the fire extinguisher is kept, and leam
how to use it in case of emergency.
Dispose of cloths stained with fuel or oil. Such cloths could ignite spontaneously if kept in a wrong way.
5)
Wipe up spilt fuel and oil immediately.
3-6. Keeping a Fire Extinguisher and First-aid Kit
Keep a fire extinguisher in preparation for fire and learn how to use it.
Establish where to keep the first-aid kit.
Establish the contact numbers in case of fire or accident and how to handle such emergencies.

3-7. Advice on Moving The Boiler or Selling The Vessel


A correct installation and incidental work are required in operating the boiler. Please be sure to contact our 1 Hand Rail 8 Roll ing Stay
company when moving the boiler or selling the vessel.
2 Steam Pressure Switch 9 Water Level Controller Cylinder
Do not carry out incorrect installation or incidental work as there is a danger of such work leading to physical injury.
3 Steam Pressure Gauge 10 Water Level Gauge

& Warning
4
5
Soot Blower In let
Hand Hole
11
12
Bottom Blow Off Valve
Fuel Oil Heater
Al ways disconnect all electrical power at th e main circuit breaker, close the main and pilot manual shut off
6 Funn el Base of M/ E Inlet 13 Boiler Water Sampling Valve
valves before performing adjustments and/or maintenance. Failure to do so co uld cause electrical shock,
explosion , fires and/or burners which will result in serious personal injury and/or death . All adjustments and/or 7 Funn el Base of M/E Outl et 14 Burner Exhaust Gas Outlet
maintenance must be performed by qualified and experienced personnel only.

7 8
OJrlIURI\ OJrlIURI\
Z BOILER -- - - I Z BOILER -~

5. Internal Structure 6. Structure, Part Name, Inspection and Adjustment of each Device

& Warning
6-1 Fuel Oil Piping (Please Refer to The Final Drawing, If The Device is Specially Made.)

Before inspecting the interior of the unit, turn it off, purge with the bottom blow-off valve and ventilator, and cool both M-1 Auto-strainer for main line
the inside of the drum and the combustion chamber. Then make sure that the pressure inside the drum is 0 MPa.
M-2 Fuel oil pump for main line
Also, when conducting the inspection, make sure ventilation is provided by the air duct and/or the ventilator fan.
M-3 Fuel pump motor for main line
M-4 Y -shaped Strainer
9) The boiler consists of the doughnut shaped steam
M-5 Auto-strainer for pilot line
drum 1) and water drum 2) which are connected by
multiple water tubes 4). Water tubes with swagged M-6 Fuel oil pump for pilot line
ends are arranged as shown. C I RC U. OUTLE T M-7 Fuel pump motor for pilot line
7)
Fuel oil pressurized by the fuel pump is heated to FCV Fuel oil control valve
6) the specified temperature by the oil heater and is TC-1 Thermocouple for adjustment
~phl~III~.J , I I, atomized from the burner 9) . It is mixed with air
TS-1 Thermostat for low oil temperature
8) from the forced draft fan and ignited by the ignition
TS-2 Thermostat for high oil temperature
.------1111111111111 1 1111111111111 ! transformer to form a suitable flame in the furnace.
10) TS-3 Thermostat for protecting heater
""""-- ,, IIIII1 1 11111 I 11111 IIIII11 I / I I The flame transfers heat to water in inside water tubes
8) BLF," ER F. O. r£ATER SV-1 Solenoid valve for low combustion
by radiation . It becomes the combustion gas and is

4)
U~IIIII 1IIIIlfrr ~--/ ) j branched into two rows of water tubes and meets at
the exit and is discharged from the funnel 6). Contact
OILt ATE 1 w
z
-
-'
I-
SV-2
SV-3
Solenoid valve for high combustion
Solenoid shut-off valve
8) heat transfer is made when water passes in water Z
W
SV-4 Solenoid valve for pilot line
~ IIIIWJll!t~~~11J1WllI~, >

1
tubes and heat is transferred to water efficiently.
11 )

2)
Particulary.
The main engine exhaust gas side is provided with a
1 1 -«
0::

AIR VENT VALVE


I group of water tubes reasonably arranged circumfer-
12)
entially on upper and lower drums to transfer heat
efficiently. M- I
:q:::1::::r ~- 12)
The exhaust gas inflowed through the flue is separat- KD11E1<~F-.-O-.----,----
Mc--:A----:I--:-N-:-;-L~IN
;-;;:::
E"-
00
00
ed in two directions of left-hand and right-hand to
M- 3 \\~--
effect heat exchange and discharged through the AIR SEPAR ATOR
outlet funnel as low temperature exhaust gas.Inner
1-
and outer casings are arailable. Heat insulating mate- ~ F. O . PiLO T L IN E
FUEL OIL PUMP UNIT
rial 7) is placed between inner and outer casings to ®
M- 7
restrict radiation of heat.
The lower part of the furnace and the swaged part of
the water tube are insulated by refractory and short
C><J I Glove valve I r--.y I Y-shaped ttrainer
@ Ball valve I KD I Strainer
6) pass of gas is also prevented.
12) At the upper and lower drums, there are manholes C*J Needle valve qp Thermostat

which allow you to check the interior. Check the state -<>- Cock t$J Pressure twitch
1 Steam Drum 7 Insulation of deposits (scalinq), corrosion, pitchinq, and reflect the I Flanqe joint ® Pressure qauqe
2 Water Drum 8 Soot Blower results in processing boiler water. (For more details, ~ I Screw-down stop check valve ~ I Thermocouple
please refer to the separate manual for water treat-
3 Manhole 9 Burner ~~ Pump --i:~ Orifice
ment). When you check the inside of the furnace, look
4 Water Tube 10 Fixed Plate }<] Safety valve L..JLJ1- Copper pipe (0 10)
for deposits of soot, peeling of refractory, fuel leakage
5 Refractory 11 Manhole
on the furnace bottom, traces of water leakage, accu- ~ Solenoid valve I C:kJ Relief valve i

6 Funnel (Burner) 12 Handhole


mulations of unburnable materials, and so on. ----0L0- I Fle xible tube ----cFtP- Teflon lined flexible tube I

9 10
omlUR~ OmlURI\
Z BOILER - I Z BOILER

<How to Operate> 6-3 Damper (Fully Open - Fully Close)


1. All of the solenoid valves (SV-1 to SV-4) should be closed when operation is stopped. The shut-off valve (SV-3)
will open when operation starts and the main fuel pump motor is running. Pressurized fuel will enter the burner Series GK units come with a completely open-- fully
nozzle pipe from the heater, SV-3, flow control valve (FCV) and circulator opening and will be heated to the end close damper on the outlet side of the FD fan . When
of the pipe, then it will return to the air separator to begin the cycle again. the FD fan is running, it will be completely open; at all

2. When the main fuel oil is heated and pre-purge is undertaken, the pilot fuel pump and the ignition transformer other times, it will be completely closed.
will engage, the shut-off valve for the pilot (SV-4) will open and the pilot flame will ignite. The damper is opened and closed by the motor forward
or backward, Electricity usually flows through the
3. When the flame eye sense the pilot flame , the solenoid valve of the main burner will open and a flame will be
damper motor, which is held to the damper plate by a
ignited , then the pilot valve will close and the pilot flame will go out to keep combustion by the main burner. (In
strong torque . The damper motor is connected to the
three-step control , the valve for HIGH combustion will open and start high combustion .
damper shaft by a coupling and a lever.
4. Even during combustion, the pressurized fuel will continue circulation through the flow control valve (FCV) to Make periodic inspections to check for looseness in the
maintain steady temperature and pressure of the fuel oil. coupling set screw, etc., and to make sure there is no
rattling . The coupling rubber and the damper packing

6-2 Burner Assembly can become worn and deteriorate, so please replace
them whenever necessary,

6 Warning
Before opening the burner and making the inspection, you must first use the fan to make a purge , and
6-4 Combustion Control Damper
be sure the furnace chamber is sufficiently cooled and ventilated . Turn off the F.O. pump , F.O. booster
pumps, and close the main F.O. valve and pilot F.O. valve . If fuel oil is leaking from the flexible tube ,
Normal air flow adjustment bolt The unit comes equipped with a combustion control
burner, or elsewhere , wipe it up immediately and dispose it properly.
(High combustion) damper to adjust the air volume for proper combustion.
If there is ON-OFF control, there will be a fixed -in-place
damper at the forced draft fan inlet.
If there is 3-step control, it will be at the inlet/outlet of
,.".ns,,,,,,,,- . /
5) 2k 1)
, ~~ the burner, and the aperture will automatically be
changed at the damper motor.
6)
As with the fully open-- fully close damper, make periodic

"'
inspections of the set screw and coupling, and replace
when necessary.
Ignition/air flow adjustment bolt
(Pilot, low combustion)

.Adjusting the damper position


10)
You can adjust the air flow using the damper motor-type control chamber (see photo above) installed on the
/ T~ U t1 outlet side of the FD fan. The position during ignition and low combustion will be the same.
~
These apertures are set by the ignition/air flow adjustment bolt shown in the photo above. The high combustion
9) 8) 7) 4) 3)
position is set using the normal air flow adjustment bolt in the photo.
11 ) "'- / I I I 12) Flow Control Valve Turn the adjustment bolt toward the OPEN arrow to open the damper; turn it toward CLOSE to close the
1 Fan 9
damper. After you have made the adjustments, tighten the lock nut securely so that it will not become loose.
/ 14) 2 Fan Motor 10 Wind Box
13) .
"- I WLV 15) 3 Damper Unit High-Low 11 Nozzle rip e
* With ON-OFF control , the damper is set up so that it slides toward the F.D fan inlet. Please adjust the air flow
4 Damper Unit Fully Open-Close 12 Ignition Rod whi le the main burner is burning fuel.
16)
5 Iginition Transformer 13 Air Register * If you cannot change combustion conditions no matter how many times you adjust the damper, the problem
6 Flam e Eye 14 Burn er Insulation Plate probably lies with some other cause and not with the damper. If this is the case, you will need to check for other
7 Peep Hole 15 Shroud problems, like improper burner adjustment, change in oil pressure, too much soot in the combustion chamber,
and clogging of the F.D fan intake.
8 Solenoid Valve Unit 16 Baffle Plate

11 12
OmlURI\ OmlURI\
[m Z BOILER Z BOILER

6-5 Timing Switch for The Damper (High-Low Type) 6-7 Burner Nozzle
The Timing Switch for the Damper corrects the disparity
4) 9) ~
IF
M ,8 I E:I 1 of the operation timing of the Damper and the fuel High-Low Type 1 Upper Plate
-;~
2) Solenoid Valve during the switch over of the low fire and co i 8) 7) 2 Lead Rod

~:
high fire . <>
3 Ignition Rod
3) In other words, the momentaneous lack of air flow by the
4) 4 Nozzle Pipe
delay of the Damper function during the transition from low I' 6)
I'

fire to high fire, and the excessive air flow by the same High-Low Type ,/ 5 Baffle Plate

o o 6 Nozzle Tip (Pilot)


o 1) delay of the Damper function during the transition from high
fire to low fire are resolved by adjusting the operation timing
I,
2)
L
3) 5)
7 Nozzle Tip (Low)
1)
of the Fuel Solenoid Valve using the timing switch .

~
8 Nozzle Tip (High)

+ 0~
P Pilot IH 9 Shroud
CD
< Adjustment> L Low Fire
~; -.

Rotate the damper to mid-degree between low and high H High Fire
;' r

combustion, after its opening range is decided. CI Circu lation In Ip


ON-OFF Type
J2
-" ~ -

o
o o
Then, adjust it by sliding the cam, after loosening the
locking screw for the cam , so that the switch roller is turned
CO : Circulation Out

to the cam to switch ON . (the high fire solenoid valve is Type of Evaporation Measure of Burner Nozzle Type of Evaporation Measure of Burner Nozzle
open at this point). Make sure it clicks when the roller is on Boiler of Burner L F Boiler of Burner L F
Timing Switch the cam; sometimes the switch cannot be turned on, due to
1
the lack of stroke. 400kg/h 803 25 GK-20XX
2 Cam 1000kg/h 997 70
If it does not click, loosen the screw on the switch 500kg/h 823 45 GK- 22XX
3 Cam Adjusting Shaft GK-14XX GK-24XX
attachment and re-fix it after moving the whole the 600kg/h 819 70 GK-27XX 1200kg/h 997 70
4 Lock Bolt switch unit toward the cam.
700kg/h 824 75 GK- 22XX 1300kg/h 972 45
GK-24XX

I ...
6-6 Blower
. ------ -- Note GK-16XX
400kg/h
500kg/h
600kg/h
811
831
827
25
45
70
GK-27XX 1500kg/h 982 55

Check the blower regularly . 700kg/h 832 75


800kg/h 813 56
The Blower that forced air into the burner ensures velocity, pressure and airflow by rotating the impeller by a
motor. In addition, as the GK series allows for greater flue gas velocity to improve the heat exchange wiht the flue
The burner nozzle part is a device that burns fuel while igniting and keeping the flame effectively by
gas, a high speed blower with high static pressure is used.
atomizing the supplied fuel, and is an important part that determines the combustion .
Attention and care are required to prevent foreign particles clogging the wire mesh of the suction opening.
The fuel sent in by the fuel pump is sprayed from the nozzle tip via the Fuel Heater, Solenoid Valve and Burner
~ Regular Maintenance Nozzle Pipe, atomizes and expands the contact area with air, ignites and makes flame by the spark from the tip of
the Spark Rod.
If there is major vibration even after the impeller has been cleaned , you will need to either replace the bearings or
The spark disappears a few seconds after ignition and the flame is kept by pulling back the flame in front of
balance the impeller.
the nozzle tip by the reverse-flow region of air that is produced at the back of the Baffle Plate .
o Inspections
When the butterfly bolts for fixating the burner on the top part of the window box are removed and the plug caps on the
Check for vibrations, strange noises, and abnormal bearing temperature during operation. When not in
Spark Rod , fuel joint pipes are removed , the burner nozzle part can be pulled out as shown in the diagram above.
operation , turn off the power, then move the impeller by hand to check for abnormalities.
The pulled out burner nozzle can be disassembled further into Nozzle Pipe, Nozzle Tip , Spark Rod and Baffle
o Insulation test
Plate. The parts should be washed with light oil and cleaned with air for assembly. It is advisable to adjust the
You should conduct an insulation test either once every three months, after the unit is being restarted after a
relative distance of the Nozzle Tip , Baffle Plate and Spark Rod based on the value in the paragraph.
long period of being idle, or when otherwise necessary. If the value does not exceed 3M 0 , you should either
The fuel , air and respective conditions may differ depending on the boiler. As such , if the best fired condition
replace the motor, or fix it once the ship has docked in port.
cannot be obtained, make adjustments so that a good fired condition can be obtained by adjusting the
o Replacement of bearings
measurement of each part.
The bearings for the fan motor have shield type bearings. Replace the bearings once every two years .

13 14
omlUR~ omlUR~
l z a-OILER [n ZaOILER

Take care as although hexagon head bolts are fixed tightly in assembly, fixing the bolt too tightly on the 6-9 Solenoid Valve
Spark Rod could split or crack the insulator, causing the ignition to fail.
The Solenoid Valve opens and closes by the electric activation and non-activation to control the supply of
fuel oil to the burner nozzle .
Note
Take care in handing the Solenoid Valve as its style and valve opening action differ depending on the model.
Do not screw too tightly when assembling the Spark Rod and Lead Rod .
& Warning

& Warning To prevent the possibility of personal injury or property damage, check valve for proper operation
before returning to service . Also perform internal seat and external leakage test.
The combustion chamber should be cooled off and purged by the blower before remove and inspection the
burner. Wipe away the spilt fuel oil from burner nozzle and flexible tubes immediately and handle it properly.
Note
Clean and inspect the Solenoid Valve regularly. When replacing the valve check the flow direction .

In either of the Solenoid Valves , ignition may fail when there is foreign particles on the seat as the oil
pressure will not rise due to oil leakage . Moreover, as obstruction may cause oil leakage inside the
6-8 Nozzle Tip combustion chamber, which could develop into ignition failure and other problems related to combustion,
please carry out a regular inspection . Take care in disassembling the device, as internal parts , valve seat
and springs can easily be lost.
- -- "" H,,\\fl i

~~jj,Wtr' ~
.....:J ,~ ,':.J

1. Solenoid Valve for Pilot Burner

Body Screw Pin Cut Off Valve This solenoid valve is used in the pilot system and its capacity is relatively small.lt opens when activated
and two valves are used for the pilot burner. During pre-purge, the solenoid valve is closed, and fuel
The oil coming into the nozzle passes through the cut off valve for prevention of oil leakage and enters the circulates in the fuel pump . And oil pressure keep rises . When pre-purge is completed , the solenoid valves
Spinning Chamber via a thin channel of the Distributor. This Spinning Chamber is conical and th e tip has is activated and opens , and combustion is started .
an orifice . The oil increases its velocity while it swirls inside the Spinning Chamber, passes through the ori-
2) 3) 4)
fice and sprayed to the Combustion Chamber. As the machine work of the nozzle is very precisely, care 1 External Cabinet Stop Bolt
/
must be exercised in handling the nozzle . In addition, a hard material is used for the nozzle as oil always 2 Attractor
frictions th e o rifice 8.nd other p8.rtS Rt R VAry hiOh rrASSIJre 8nd speed , it should be exchanged every year. 6) 3 Top Plate
The size by the model differs slightly. Please check the notes on the final drawing.

• There is a cut-off valve attached to the nozzle tip. When replacing the nozzle tip, please remove the filter
5)\ 4
5
Coil
Label
6 Plunger Spring
and attach the cut-off valve .
7 External Cabinet
• When removing and fitting the nozzle tip use the special box wrench wh ich is provided as special tool. 9)
8 Plunger Tube
9 Plunger

& Warning
17) ~1~
10
11
Bottom Plate
Coil Packing
Improper sp ray volume, spray angle, and/or sp ray pattern can lead to poor combustion , which may some- 16) 12 Cover Plate
times cause backfiring that can damage the unit. Please use only genuine parts.
13 o Ring
14 Stopper
15 Body
16 Spacer
17 Valv8
~

15 16
OJrlIURI\ OhilURI\
[ Z BOILER Z BOILER

2. Solenoid Valve for Main Burner 3. Solenoid Valve Unit


The main burner of Series GK uses a valve that opens when an electrical current passes through it.
(p )
ON-OFF Control

10)
1 Valve Case To Burner Nozzle Port Pilot F.O . Outlet

::= IIIYI~
2 Spring (H)

3 Valve Fitting To Burner Nozzle Port


4 Piston Rod I
7) (CO \
5 Body I
6 Case Set Nut I f
{
7 Spring 3)
8 Plunger Pressure Gauge 3/8X75X3 .5MPa

~
5) 9 Suction Body
1) 1 '1="':1 10 Coil h.. II .,.J
-2)

6)
Pilot F.O. Inlet

Main F.O . Inlet 2)

Three Position Step Control I


3) 1)
/
.I j \ -1:
Pilot F.O . Inlet . I~~
@08amJ nn[~~
J
I
[,I
Ii
• Pilot F.O. Outlet (p)

Ii

~ 5)
Main F.O . Inlet - --
6)l;i
~lt~~
~ =
II
- '
/' IL/~ To Burner Nozzle Port (cO
~i
[I
L

--- To Burner Nozzle Port (H)

.
I

rnt~~~
1//2~tr
3)/ '
II

1-
To Burner Nozzle Port (L)

\
" ',.1'
...... h)
1
2
Pilot Solenoid Valve
Fu el Oil Flow Control Valve
3 Pressure Gauge
From Burner 4 Low Combustion Solenoid Valve
Nozzle Port (co )
5 High Combustion Solenoid Valve
6 Solenoid Valve Shut Off

17 18
OmlURI\ OmlURI\
[ Z BOILER [-- Z BOILER

6-10 Fuel Oil Pump 2. GFH Type (Used for The Main Burner)

~t
Note
Please try not to disassemble major components such as the rotor when making repairs. The manufacturer
will not be liable for problems arising from a disassembled pump.

Three types of the fuel pump are used in models of GK type boiler. The pump is connected to the motor by Vent valve
PT 1/8
coupling and is operated at about 3500 r.p.m to send fuel to the nozzle though the solenoid valve.

f .
/ ., . . <... \.
~.
1 , £ ,-
?;
t~;. @). ,,- ,

V
~

~ ~' ''I

o
. I '¥l;"·
........
j -,
I , '"I Suction port
PT 1/4
\ ..
\ '. J } Use the pressure adjusting screw to adjust pressure. Put 5 mm All wrench in the pressure adjusting screw and turn it to
\ ,:> ",.1;
~.
adjust pressure in the range from 10 to 25 kg/cm2. Turn it clockwise to increase pressure and counterclockwise to
decrease pressure. Do not tum it excessively to prevent a trouble. Do not turn it beyond the limit.
.' -.
< Inspections and Maintenance>
The fuel pump is of the trochoid system as shown above and generates high pressure by revolution of Check every day to make sure that there are no leaks from the cover, oil seals, and other parts. There is no
inner and outer rotors . The rotor has the profile shown above and inner and outer rotors rotate in light strainer inside. In case of breakdown, do not disassemble the unit, but have it repaired when you reach port.
contact with each other and tooth surface slippage is quite limited . Noises and wear are hardly caused
because no oil containment.

3. GD Type (Used for The Main Burner)


/ Return Opening
1. GFS Type (Used for the Pilot)

,
/ Pressure Regulating Valve
< Adjustment> Discharge Opening PT1 /8
Pressure is adjusted by the "Pressure
Regulating Screw" . Loosen the lock nut and
turned clockwise with a hexagon wrench, the
pressure rises and the pressure drops when it Suction Opening ......_ - ... Vent
~ Return
is turned counterclockwise, allowing for easy Opening
adjustment of pressure within a 0.6- 1.2MPa PT1 /4
range.
Standard, set pressure 0.8MPa.
.. < How to Adjust>
Use the pressure adjustment valve to adjust the pressure . Turning it to the right will increase pressu re ,

\
< Inspections and Maintenance >
Please check every day to make sure that turn ing it to the left will decrease pressure. Make periodic adjustments of the pressure follow ing the
instructions given in 6-7-(4) .
there are no leaks from the cover, oil seals,
t
and other parts . There is a strainer inside ,
which should be cleaned once a month . Pressure
Regulating
Screw
~ Suction PT 1I4
Opening
< Inspections and Maintenance >
Check every day to make sure that there are no leaks from the cover, oil seals , and other parts. There is no
strainer inside . In case of breakdown, do not disassemble the unit, but have it repaired when you reach port.

19 20
omlUR~ omlUR~

Z BOILER J Z BOILER

4. Setting The Pressure Range of The Fuel Pump 6-11 Flow Control Valve

& Warning The fuel oil is pressurized by the fuel pump and heated by the heater. The flow control valve in the solenoid valve
unit keeps the fuel oil at a constant pressure. Some of the fuel oil is cycled through during combustion. The burner
Periodically (once a month), set the pressure of the fuel pump. If you don't set this pressure, then you will not be able to nozzle and the return pipe are heated and kept at a constant temperature . The flow control valve is plays an
accurately adjust the rate of combustion of the CS bumer. Adjustments can be made with heavy oil A, but if you switch over to important role in combustion and maintaining the temperature of the combustion equipment, so it should be
heavy oil C, then you will have to redo your adjustments. Set the safety valve pressure of the FO heater to less than 2.3 MPa.
periodically inspected and the pressure adjusted when necessary.

FUEL OIL PUMP UNIT


< How to Inspect The Flow Control Valve >
During its test run at the factory, the flow control valve was set at 1.8MPa (specification for heavy oil A is 1.5MPa).
~ FOP Please make sure that the fuel oil pressure gauge in the fuel pump unit shows a reading of at least 1.8MPa, and that the

2) fuel pressure gauge next to the flow control valve shows 1.8MPa (1.5MPa is the specification for heavy oil A).

< How to Adjust The Flow Control Valve >


Before starting this procedure, please adjust the pressure, following the instructions in 6-10-Ai4). Please switch over to
Return -----' heavy oil A, and lower the temperature of the fuel oil.
Remove the adjustment screw cover and loosen the lock nut. While manually operating the fuel pump, make your
3)
Oil Air Separator adjustments as you check the fuel pressure gauge on the side of the flow control valve.

1. Remove the adjust screw cover at the top of the


Burner Specification Pressure
flow control valve when the specified pressure is
Diesel Oil Only 1.5MPa (15kgf/cm 2)
different from the standard et pressure.
2. Unscrew lock nut Heavy Oil 1.8MPa (18kgf/cm 2)
3 . Adjust the pressure to the standard set pressure
FO IN - -----"
\'
by turning adjust screw. t To pump suction Side~cap
Turn clockwise the screw to increase pressure r-----,L~ /
and combustion flow .
Turn counterclockwise the screw to decrease
rpl ' , ~S0
pressure and combustion flow.
Pressure
4. Make sure again that pressure is the standard
. . ~~~~
set pressure , and tighten the lock nut. Pressunzed fuel 011 from
5. Put the cover screw. the fuel oil pump Lock nut
1. Operate the fuel oil pump running (manual combustion) . Stop the combustion .
2. Close fuel pipe return valve 1). The pressure rises in Pressure gauge 2).
3 . Turn the pressure adjust screw of F.O. pump and adjust the pressure in Pressure gauge 2) to 2.1 ~2 . 2MPa .
(Refer to the boiler instruction manual "Fuel Pump" section in adjusting the pressure of F.O. Pump.)
4. Open fu el pipe return valve 1). Th e pressure falls down in Pressure gauge 2) and this is normal. & Warning
5. Check if the fuel oil is circulating . (Close fuel pipe return valve 1) and Open drain valve 2) and check the Wear safety equipment during operation to avoid durn when fuel oil temperature is high . The defective of
fuel oil go out.) combustion and explosion may occur by malfunction of combustion adjustment. If you decide that combustion
6. Carry out combu stion rate adjustment of C S burn er followin g the instructio n for CS burner. adjustm ent is necessary. contact maintenance staff of ou r company first, and follow the directions.

& Caution
& Caution
You should make this adjustment when you replace the oil pu mp. Make adjustments with the flow control
valve after you have completed adjusting the pressure of the fuel pump. Over time , the oil pump will When replacing the flow control valve , adjust the pressure for heavy oil A, then switch over to heavy oil C.
deteriorate and its performance will gradually decline. Make sure that oil pressure is steady.

21 22
omlUR~ . omlUR~
Z BOILER --J Z BOILER

6-12 Ignition Transformer 6-13 Flame Eye

Primary side

2)

1)

AC 100V

The Ignition Transformer is an important device


3) -i-
for creating sparks from the Ceramic Insulator for
the Ignitor by changing the 100V voltage on the
primary side to high voltage .(1 Okv)
The primary voltage of the transformer has dual 5)
#'fij
{1J
voltages ; 100V and 200V. When the control circuit .~
1 Flame Eye
voltage is 100V, install the wire on the primary
2 Fitting Box
side as shown in the right diagram. E
3 Fitting Stand
4 Flame Eye Glass
Primary side
5 Packing

& Warning
The Flame Eye is a device that gives an indication to the combustion circuit by detecting the flame during
Beware of electrocution as the Ign ition AC20 0V
combustion and monitors the flame using its photosensitive characteristic (Normally, when a resistance of
Transformer conducts high voltage.
1OOk 0 catches flame , it drops under 5000) of CdS (Cadmium sulfide cell) .
Th e Flam e Eye will not be able to catch th e brightne ss of th e flam e inside th e furnace when it is damaged
Avoid using it with rubber disconnected from the
or the protection glass is blackened with soot. Such soiling could stop the burner as it produces the same
boiler as it cannot be earthed , which would cause
condition to failed ignition or mis-fire . The failure of the Flame Eye may be caused by soiled protection
the transformer to burn out.
glass if the flame dies out in about 3-4 seconds after combustion as the burner is ignited by turning the
burner switch to combustion while looking inside the furnace from the sight glass . Do not neglect cleaning
th e protection glass at all times.

Note
Cl ean the protection glass regularly.

23 24
OmlURI\ OmlURI\
C Z BOILER -] [U_ Z BOILER

6-14 Fuel Oil Heater 6-15 Fuel Oil Temperature Controller

The appropriate heating temperature of fuel oil differs by the viscosity of the oil. Determine the temperature
following the Heavy Oil Heating Temperature Chart.
U Heavy Oil Heating Temperature Chart

F.O. Outlet
Control Output Indicator Lamp
C. Green
Safety Valve
Lights up when the control '""'"
II'\.IICT1IIC
·c
output is ON.
- CO HO LO

o
PV [ ,n n n 1
Reading Indicator Lamp S; IUUU (
PV. Red The value is decreases
Lights up whe n a reading is by 1 when pressed once.
indicated. The value decreases
F.O . Inlet -
c::::z.. -
c:::::)
when continu ously
pressed.
Set Value Indicator Lamp
SV. Green
Drain Lights up when a set value is
indicated. The value increases by 1
when pressed once.
Select Key The value increases
Used in chang ing the set when continuously
value . pressed.

& Caution
Note
Op en th e fuel oil heater then insp ect and clean once a year. • Set up the data by pressing the key steadily with the fingertip .
• The data is automatically registered 3 seconds after it is set up.
• The indicator automatically reverts to indicate reading in approximately 30 seconds after set up .
The electric heater as shown in the figure is used as standard to heat fuel oil to a proper temperature. The • Don't press SEL key for one second or more .
heater is installed in the outlet side of the oil pump and oil temperature is regulated by the temperature • Don't change the parameter and inside data.
controller.
The element in the heater has a nichrome wire coil in the center of the pipe. The pipe is filled with special
power which has high conductivity and good high-temperature electric insulation . Both of them are < How to Set Up The Set Value (SV) >
solidified under high pressure . Example: Changing the set value (SV) from 120'C to 130'C .
After use for a long period , oil sludge is accumulated in the heater and this may cause lower heating
Key Operation Explanation Indication
temperature . Therefore, the heater must be overhauled and cleaned during drydocking or as necessa ry.
SEL Reading indicated (PV)
L::)
The SV indicator lamp lights up when SEL is pressed once to indicate the
PV'O' 1/12101
current set value. SV'O' 1/12101
/'-.
L::) Keep pressing until the changed value reaches 130. SV'o' 1/13101
(The value is automatically reQistered 3 seconds after set up)

SEL Reading is indicated (PV) when pressed once .


L::)
(The reading is also indicated automatically in approximately 30 seconds
PV'O' I 1/12101
after set up without this operation)

25 26
OJrlIURJ\ OJrlIURJ\
Z BOILER Z BOILER

6-16 Thermostat (For fuel oil) 2. RT Type

Use the RT model shown at the left based on your specifications.


1. Dial Type

Thermostat specifications For Heater Protection

1) Setting Knob
2) Setting scale plate
For High Temp Alarm
For Low Temp Alarm 3) Differential Setting Disk

The Fuel Oil Thermostat switches the electrical switch on and off by sensing the temperature, and uses a
fluid with high expansion co-efficiency in its thermos sensor. When it senses temperature, the expanded
fluid and pressure inflates the diaphragm inside the body, releases the lever to open the electrical contact
and when the diaphragm deflates, the electrical contact closes. < Adjusting Range>
The following thermostats are used for the GK type boiler. Rotate the Setting Knob to adjust to the specific figure on the Graduated Dial.

< How to adjust> < Differential Control>

As shown in the above diagram, the thermostat is a dial type. After loosening the dial set hardware, Adjust differential pressures by using the Differential Setting Disk. The specified value should be decided using
arrange the dial scale to align with the set points so that the designated temperatures will be reached . the chart. Connect the main preset value (A) with preset differential value (B) by straight line, and locate where
Then tighten the set hardware . it crosses with the differential value (C) . This value should be identified as preset value of the disk.

CD Low temperature alarm thermostat : Set the temperature to be about 20-30°C lower than the
heating temperature.
Note
<IJ High temperature alarm thermostat : Set the temperature to be about 30-40°C higher than Since the thermostat has been adjusted . Do not try to adjust frequently.
the heating temperature .

Chart to set differentials.


G) Heater protecting thermostat : Set it to 180°C.
"C "C
"C "C 1.8
110

~:
70 1. 6
130
Once every three months , turn the dials to change the settings and perform a check of the electrical system . 50

I
140

I
90 150 10
11
100 · A 10 160 A .14
110
B 170 16
~ B 16
~
15 IRIl
I~U {U

130
190 77 A. = Main preset value
10 14

140
200
25 B. = Pres et differential valu e
210 29
150 RT 107 25 215 RT 120 30 c. = Differential value

27 28
omlUR~ omlUR~
Z BOILER -- I Z BOILER

6-17 Temperature for heating heavy oil 6-18 Feed Water Pump (Miura water pump)

For optimum combustion conditions, keep the viscosity of the fuel oil in the nozzle section at 12 cSt or less.
For the proper temperature for heating different viscosities of fuel oil, please refer to the following chart.

MSY User's Manual


Redwood No.1 Sec'/1 00' F 1500sec. 25aOsec. 3500sec. Please refer to the user's manual for
the MSY feed water pump (separate
Kinematic Viscosity (cSt) at 5a'C IF-180 IF-38a
from this manual)
(IF) Residual Fuels, cSt/5a'C 180cSt (290cSt) 380cSt

Kinematic Viscosity (cSt) at 1aa'c 25cSt 35cSt


-
CIMAC and ISO Fuels, cSt/1 aa'c CIMAC/RM-25 CIMAC/RM-35

Fuel heating temperatures


~ 125 'C 130'C 135~140 'C
(Setting the temperature of the temperature adjuster)
--- -_ . _ -

Air Vent Valve, Plug

IN
<=

Drain Valve

OUT
-I <L ---1-1:- c=:;:;.

Air Vent Valve, Plug

29 30
OmlURI\ omlURI\
Z BOILER Z BOILER - I

6-19 Water Level Gauge and Water Level Control Cylinder In addition to the water level gauge to check water level by eyesight, the level control cylinder has four (or
five) water level detecting rods 3) with different lengths inside the cylinder to electrically detect water level
and put out a signal to automatically start/stop the feed pump and stop the burner when the level is low.
& Warning The stainless detecting rod is screwed in the electrode holder and further tightened with set screws.
As the water level detecting rod may get dirty with conc entrated boiler water and cause malfunction , pull
As the water level gauge glass may be damaged due to aged deterioration, replace it on regular basis
the water level detecting rods out and clean them at least once a three months.
(once a year)

The water level gauge is built in with the water level control cylinder as an integral-type as shown below .
1) -"~ ~~
~~ ~Ip)
..... 1) 3) 1

2)~1 D0' lJ'"~


9)

-~3==~\===
1)g ®
t t t
@
® 3)
2)~B)
'; '
I+--l

3) -· 5)
6) 4)
1 Electrode Holder s
7)
2 Water Leve l Gauge Box
M
3 Water Level Detecting Rod
L
,". I "'--10) 4 Drain Valve Flange _ .. . -

LL ----
1 Water Level Gauge Box 6 Hexagon Bolt
2 Gauge Glass Seat 7 Hexagon Nut 4) ~I I '-------J
3 Gauge Glass Cover 8 Connecting Pipe
4 Gauge Glass 9 Water Level Control Cylinder Cover
5 Gauge Glass Packing 10 Drain Valve
Continuity and Insulation Check of The Electrode Holder
Check continuity and insulation of the electrode holder every three months.
Continuity check ® ~ @ 00
Insulation check ® ~ ® 0.1 MOor more
Water level control cylinder is installed in the top and the bottom (on the steam side and water side) of the
Replace the electrode holder periodically (once/2 years) as it causes insulation and continuity failure due to
steam drum via th e valve and combines the water level gau ge and water level control cylinder with the
aged deterioration .
gauge glass attached on the body.
The water level gauge is an important device for safety to check if the prescribed water level is kept in the
boil er. As th e glass of th e water level gauge always needs to be kept cl ean, cl ean it by blowing th e water < How to Blow The Water Level Gauge >
level gauge at least once a day. 1. Close the steam valve of the water level gauge and open the drain valve to discharge water in the gauge.
Th e water level gauge glass uses the reflective type and the size varies among boiler models . 2. Close the drain valve and open the steam valve.
3. Close the water valve , open the drain valve, discharge steam and cle an the water level gauge .
4. Open the water valve and close the drain valve .

31 32
OJrlIURI\ OMIURI\
[ --- Z BOILER - - _.-
Z BOILER

6-20 Exhaust Gas Thermostat 6-21 Pressure Switch (For Steam and Fuel Oil)

Steam pressure switch


ON-OFF control Oil Pressure switch
The exhaust duct comes with a thermostat to
measure the temperature of the exhaust gas.
=t!~
If there is an abnormal temperature, an alarm will . ,

~
J'#
sound and operation will be stopped electrically.
At the time the thermostat leaves the factory, it is set
.
"/ .,' "
,

at 450·C . ~f; 't-

~ = .;::,,-

m=,

';:::;';).<','

< Inspection>
Make sure that steam is not leaking at the connections or into the cover.
• Once every three months , lower the setting of the pressure switch of the high pressure alarm system and
conduct a test run of the equipment.
• Once every three months, heighten the setting of the pressure switch of the low pressure alarm system
and conduct a test run of the equipment.
After a test run , reverse the pressure switch setting .

On GK series models, there are two types of pressure switches : one for oil, and one for vapor.
If it appears that the thermostat is working but the boiler is stopped when the boiler is supposed to be
(a) Vapor pressure switch
running, take a reading of the gas temperature with a thermometer, then decide whether the problem is
ON-OFF control: One standard switch
due to a defect in the thermostat, or whether the temperature is actually increasing .
3-level control: Two standard switches
If the temperature of the exhaust gas exceeds 450·C, there is a high possibility that there is some sort of
malfunction in the combustion chamber, Open th e furnace, and check whether some sort of un burnable In ON-OFF control , there is one switch that controls the vapor pressure.
material has fallen into the furnace , or there is some other sort of cause. If there is a malfunction , In 3-level control, there are two switches: low vapor pressure, and high vapor pressure.
immediately take corrective action. * In some cases, there are more switches, as some are used for alarms.
If incomplete combustion continues for a long time, there is a chance that soot has accumulated on the
water pipes in the furnace and the temperature of the exhaust gas is higher than it should be. (b) Oil pressure switch
Pay constant attention to the furnace to keep complete combustion . Th is mainly uses a low oil pressure alarm system .
If the oil pressure falls below the level set at the pressure switch, an alarm will sound.
< Inspection >
About once every three months, lowe r the set temperature and make a test run of the equipment. < Inspections >
· Make sure that fuel oil is not leaking at the co nn ections or into the cover.
• Conduct a test run of the equipment once every 3 months.
• During combustion, make sure that the oil pressure is 1.8 MPa (1.5 MPa for heavy oil A). During
automatic combustion, gradually close the fuel pump outlet valve to decrease the oil pressure, and make
sure it can run at 1.4 MPa (1.1 MPa for heavy oil A) .

33 34
omlUR~ omlUR~
Z BOILER .. J ,------------
Z BOILER
.

6-22 Pressure Switch Adjustment 2. RT Type

1. SNS Type

Spring regulator - - - - - - , , . - - - - - - - - - - Spring regulator


for pressure difference for pressure
1)

Pressure pointer _ 2)

Differential pressure pointer -..... 3)


Scale prate ~

1) Setting knob
2) Setting scale plate
3) Differential setting disk

1) Control Range
Rotate the setting knob to adjust to specific figures on the setting scale plate.

2) Differential Pressure Control


Adjust differential pressures by using settin g disk. Refer to the left table to see the appropriate value.
1) Control Range
Contact pressure goes up by rotating the spring regulator for pressure counter-clockwise , as it is shown
on the gauge. When contact pressure goes up , disconnection pressure goes up, too . As you see, the
spring regulator for pressure cannot adjust differential pressure of gating. Relation between differential disk scale and differential pressure

2) Differential Pressure Control 1 2 3 4 5 6 7 8 9 10


The differential pressure can be widened between contact pressure and disconnection pressure , by
rotating the spring regulator for pressure difference clockwise (by tugging) . Comprehensively, the RT 5
1.:2 1t 6 12. 0 2.14
• 1
1
, '
2I. 8 13. 2'. 3. 1I6 4.0
f bar
spring regulator for pressure adjusts contact pressure and the spring regulator for pressure difference I\
0.[3
,I I
\

0. 5
I
\
i
I

O. 71
1 I
.
1 I
1. 1 I 1. 3
I
I

p. 9,
adjusts disconnection pressure . The contact pressure is shown in the pressure pointer, and differential
pressure of gating is shown on the differential pressure pointer on the calibrated dial.
RT 116
I,
1
I
.,
I 1
I i I I
I
I I I
1 bar
1 .' 1 , , , 1 .' ,
Therefore, disconnection pressure == contact pressure - differential pressure of gating. 1.,0 1. 5 2.,0 2. 5 3.10 3. 5 4. 0
RT 117 I I " 'I 1 bar
For your reference , the above-mentioned description about how to read thes scale plate is based on I I I J I J I 1 1 1
(contact A) point of view ; (contact 8) should , then , be just the opposite. MIN . MAX.
1 2 3 4 S 8 7 8 9 10
1 . 1 • • • • • 1 . 1 . 1 • • • 1 ••

35 36
omlUR~ omlUR~

Z BOILER [ __ U. Z BOILER

6-23 Safety Valve

& Warning
It is not allowed to change the outlet pressure of the safety valve. <Type SP-B1 M 40A >

The safety valve is a safety device implemented to prevent the boiler steam pressure from rising to the 7)
maximum allowable working pressure and the full-bore safety valve is used for GK type. Normally, the 2)
safety valve won't operate as the steam pressure switch work. In case the pressure switch does not work 1 Cap
for some reason, combustion continues and the steam pressure abnormally or abruptly rises due to rapid 2 Lock Nut
5)
load change , it protects the boil er by blowing steam off and lowering the steam pressure . Two or more 3 Lever
8)
safety valve are installed and an adequate margin of safety is provided to the total relieving capacity with 4 Adjusting Needle
more than the maximum amount of evaporation of the boiler. 5 Lock Bolt
9)
The boiler's safety valve is set at the presence of 6 Body
<Type 1627> 4) ~ ~ 10)
an sureyor, so as to blow off at the strictly limited 7 Pin
pressure ; nobody should be allowed to make an 11)
8 Adjusting Screw
attempt of further adjustment on board. However, 5)
12) 9 Spring
only in case of emergency, such as when the
13) 10 Spindle
safety valve leaks, or some kind of appropriate
11 Guide
countermeasure can be taken on the judgment of
chief engineer discretion. In that case, the 12 Valve Disk
following procedure should be followed to adjust 13 Valve Seat
blowout pressure of the safety valve.

1 Valve Casing

~
2 Valve Seat
3 Valve Body
4 Adjusting Ring
5 Valve Body Cylinder
6 Lift Stopper
7 Spring
8 Valve Stem Adjustment of set pressure
9 Adjusting Bolt & Nut Turn the adjusting screw to adjust the set pressure. Be careful to ensure that the valve stem is not turned.
10 Cap
11 Lift Valve Leve r
To increase the opening pressure Turn the adjusting screw clockwise as viewed from top.
< How to Adjust>
1. Unlock the key on the 11) lift valve lever arm then , pull off the shaft and take off the lever. To decrease the opening pressure Turn the adjusting screw counterclockwise as viewed from top .
2. Take off the cap by loosening its setting screw.
3. Activate safety valve, while 9) adjusting nut is loose . (Check blowout pressure when the boiler gets
shifted to manual operation and steam goes up)
4. Rotate the 9) adjusting bolt to the left, if blowout pressure is higher than limited pressure, to the right , if
it is lower, so that it blows off at the limited pressure .
5. After the adjustment, fasten the 9) adjusting nut tightly to fix it securely.
6. Put back the cap , restoring 11) lift valve lever, lock it and fix it.

37 38
OmlURI\ OmlURI\
,-------------- --------------

Z BOILER Z BOILER

Adjustment of closing pressure 6-24 Fuel Oil Strainer (Fuel System)


The closing pressure is adjusted with the adjusting guide and bac kpressure needle . Remove the valve
cage fixing bolt, insert a screwdriver or fine stick through the tapped hole , and turn the gear type teeth on The oil strainer removes dust and impurities from the fuel entering the boiler and prevents them from
the peripheral of the adjusting guide to adjust the closing pressure. Change the backpressure adjusting entering into and damaging the fuel pump , solenoid valve, or burner nozzle .
ne edle throttling condition to adjust the closing pressure easily. It is installed on the suction side of the fu el pump . Since it is an oil strainer, its element can be cleaned
during operation . Turn the handle once a day to prevent it from clogging .
Open the plug then drain all water and sludge out once a month.
To increase the closing pressure. l8i Adjusting the needle clockwise with a screwdriver
23)
(112 to 1/4 turns each at a time) .
l8i To increase the closing pressure more, turn the adjusting guid e 21 )
!
(5 teeth each at a time) Clockwise , peeping through the tapped !

,
3)
hole.
4)
6)
5)
7)
To decrease the closing pressure . :::Hurn the backpressure adjusting needle counterclockwise (loosen)
with a screwdriver (1 /2 to 114 turns each at a time) .
l8i To decrease the closing pressure more, turn the adjusting guide
(5 teeth each at a time) counterclockwise , peeping through the
tapped hole .

When the lift is not perfect. l8i Turn the backpressure 10 to 20 teeth counterclockwise with the
adjusting stick. 14)
l8i If stabilized operation is still not achived, turn it a further 5 teeth 13)
each at a time, counterclockwise .
16)
15)

~:: II~ 13)

21 ) 17)

22) 2)

~ I l{ 20)
L ! - ) - - - -- - 19)

1 Cleaner Cover 9 Air Plug 17 Square Rod


2 Oil Tank 10 Packing 18 Round Rod
3 Handle 11 Upper End 19 Plug
4 Mdirr Slrdr[ 12 Lower En d 20 Packing
5 Gl and 13 Fi xi ng Plate 21 Wash e r
6 O-ring 14 Packing 22 Nut
7 Ring 15 Filter Plate 23 Cap Nut
8 Packing 16 Scraper Plate

39 40
OJrlIURI\ OJrlIURI\
Z BOILER [------ Z BOILER

Oil strainer for pilot burner 6-25 Y Shaped Strainer (Miura Feed Water Pump) (Fuel Oil)

1) Draining 1. V-Shaped strainer for feed water line.

~II
..
.
Close the supply valve of the oil tank, then Handle The strainer removes impurities such as dust and sand in feed water supplied to the boiler and prevents
loosen the drain release bolt at the bottom of them from entering the feed water pump and the feed water check valve and damaging them. When the
the strainer and flush out any water or ~. Air vent screw strainer is choked, the inlet side will be in negative pressure and cause cavitation in the pump. Periodically
contaminants that have collected on the clean the element to avoid the situation . The el ement has an internal net of 60-mesh with an external net.
,
.,
- Strainer
bottom . Replace it with a new one if the net is broken or damaged .
.. . . 'J '

2) Disassembly and cleaning


After making sure that the valve of the oil tank
is closed, remove the bolt at the top of the oil Drain cock plug
strainer, then remove the cup section and flush
out any gunk on the filter plate with cleaning oil.

3) Air release
Open the valve of the oil tank and slightly
tighten the air release screw at the top of the oil Note
burner. Clean the protection glass regularly.
If, after releasing the air, oil starts to come out
from the place where the screw was loosened,
then tighten the screw. 2. V-Shaped strainer for fuel oil line
There is a Y-shaped strainer at the fuel heater outlet and burner inlet. This is for removing contaminants in the
fuel oil that could prevent damages of solenoid valves and other parts. Depending on the condition of the fuel oil,
approximately once every three months, you should open the strainer, clean it, and check to make sure there is
no deformation or other damage to the element. If the element is damaged or deformed, replace it.

6-26 Feed Water Check Valve

Feed water check


A check valv e is provid ed in front of the feed
water inlet valve to prevent boiler water from
flowing back.
If the check valve leaks, the steam pressure lowers.
Furthermore, when th e feed water pump is activated ,
.... high temperature in the pump generates air bubbles
I( t I II Q)
II I l it
ro~ due to cavitation . disables pump operation and feed
wate r to the boil er and finally causes abnormal low
"0
<lJ
Q) water level.
LL
It is important to periodically che ck the valve seat
and valve disc of the check valve and exercis e
care to reduce wear and tear.

41 42
OJrlIURI\ OmlURI\
Z BOILER---j Z BOILER

6-27 Sequencer (Programmable Controller) 1) Names and explanation of parts of CPU unit

CQM1H-CPU11
1. Outline of the sequencer
The conventional sequencer is the one called hard wired logic (for short, hard logic) to compose a logic Battery storage cover Ir--- - - - - - - - - - , - - - Slider
(logical circuit) by wiring among devices composed of relays and timers . If you open the cover, you will find Fi x adjacent units.
a battery and a front dip switch.
A computer does nothing with the hardware alone and takes advantage of its function with software called
Install the memory cassette inside
programs. It can also have various functions depending on how software is created. Namely, logic can the cover. LED display
change by software even on th e same hardware and the computer logic is subject to software logic.
Applying the same idea to the sequence control, we can replace "wiring" assembly of relay circuit logic with Peripheral port Connector
software called programs. As software plays a role of wiring, it is called soft wired logic (for short, soft logic) . This is for connection with mainly Mate connectors of adjacent units
peripheral tools (eX-Programmer, to connect them. (
To realize the sequence control with soft logic, we install a storage device (memory) on the hardware to be programming console). Upward
able to load various programs on it exactly like a computer. Such devices designed for sequence control is link and NPP communication are
CPU unit built-in
called a programmable controller or simply a sequencer. also available.
16-point input
If you open the cover, you will
find a 16-point input terminal
block.

How to open the battery storage cover


2. CQM1 H unit explanation Insert your finger tip or a small slotted screwdriver into the gap Status of the dip switch
on the bottom of the battery storage CD and open the cover
upward C1). 1 OFF
CQM1H
2 ON

3 OFF

4 OFF
® ¢
5 OFF

CPU
I 1- 1
- ··--.1.1 .
6 OFF

Input unit ~ Battery


7 ON
Output unit Dip switch
8 OFF

Memory cassette (option)


You will find a slot to install a
memory cassette on the back.

43 44
omlUR~ omlUR~

Z BOILER [ Z BOILER

Installing the memory cassette 2) Replacement procedure of the built-in battery


Replace the built-in battery according to the following steps.

CPU unit
1.Turn off the boiler power.
If the power is on, turn on the power once and leave it at least for 5 minutes.
2.Pull off the connector of the battery in the cover of CQM1 H and replace the battery with a new one .
Memory cassette

Once you have removed th e old battery, install a


new battery within five minutes . If the power is not
supplied to th e CPU for five minutes or more , the

l~~_,~
stored data may be lost.

Til
Insert a memory cassette along the slot and tuck it in until the connector is engaged .
Turn off the boiler power to replace the memory cassette. 3) Battery
A battery is built in the CPU unit.
The following data will be backed up by the battery.
• EIIO memory (including PC system configuration)
• User programs
• Clock data (when the memory cassette with clock function is installed)
The battery lasts for 5 years in 25'C ambient temperature . When the battery runs out , the front
ERR/ALM LED flashes . You need to replace it with a new one within a week. Contact to our maritime
application maintenance section . Prepare a spare battery in advance .

4) Input unit
An operation switch , a pressure switch on the detector and the thermostat will be connected to
work as a joint.

5) Output unit
An electromag neti c relay, an electromag netic valv e and indication lig hts are co nnected. Relay contact
output is adopted. You can ch eck the operation status of output points with LED on the unit surface .
(The light is on wh en the output relay is on )

40 46
OhilURI\ OhilURI\
Z BOILER Z BOILER

3. Display Function 4. Errors and Their Measures

r'-1 Run (RUN) I (Green) Abnormal phenomenon Probable cause Measures


! The light is on when the
operation is normal.

rpOWER J LED does not Loose connection of the power Terminal block:
1
light up. terminal block connector Correctly insert the connector.
INH ..
:"
<'<"
r .. ..
I '··'·';«<'I /'·:-« //' ;J~ CPU unit built-in input relay (O~15) I (Yellow)
;;: ." .,/,: ,:,,:<c·:.: ": :;:j:;>< :;£Njil,?O:~H~~~ .. . .
PRPHl . .. . , .•• 1'.".,,,,.: .. .. x . . " , >. ' ' ' ' ' . '
J .' . . . . •. • This Indicates the ON/OFF status of the Input relay OCH
built in the CPU unit (lights up when the relay is on).
Power line failure Replace CPU unit.
2 r RUN J LED does not light up.
Error (ERR/ALM) I (Red) L___ \ Load rejection (INH) I (Yellow) Program mistake Correct the program.
(
The light is on. . The light is on when the load rejection relay (25215) is on.
Operation stops. All outputs of the output unit will be shut ofI. Loose connection of the unit Correctly insert the unit.
RUN LED lights out. All output (i nput) units won't
cP~ripher~~rt(PRPtR) I(Yellow) 3 Loose connection of the terminal Correctly insert the terminal
Y Alarm (ERRIALM) (Red) I I turn on .
block connector block connector.
l
Unava ilable
The light flashes.
Operation continues, """ \ Built-in RS-232C port (COMM) I(Yellow)
Unavailable All output (input) units won't
4 Input circuit failure Replace the output (input) unit.
turn off.

External voltage is low. Use rated external voltage.


Output (input) units turn on Loose terminal screw Fasten the screw.
S I
LED Color Status Condition and off. Loose connection of the terminal Correctly insert the terminal
block connector block and lock it.
CPU unit is running a program in " Monitor"
RUN Green D and " Run " mode. Output (input) operation indicator LED
6 LED failure Replace output (input) units.

• Under operation stop and irregular stop

CPU stops operating when an operation stop


does not light up. (normal operation)
- I

D error is detected by self-diagnosis,


All outputs will be shut off.

ERR/ALM Red CPU continues operating when an operation


~ continuation error is detected by self-diagnosis.

• CPU is operating normally,


However, this LED lights out when WDr error occurs.

When the auxiliary relay for load rejection is on ,


INH Yellow D all outputs of the output unit will be shut off.

D :Light on
I
l1: :
• Flashing •
When the auxiliary relay for load rejection is off

Light out

47 40
OhiIURJ\ OhiIURJ\
Z BOILER [ Z BOILER

6-28 Flame Detector (FS-1 00) 6-29 Water Level Detector (LM1-200)

The flame detector is the relay to detect burner flame and take it out as an electric signal and includes 1. Outline
built-in operational amplifier, electrolytic capacitor, transistors, diodes, auxiliary relay and many other 1) Summary
electronic parts . LM1-200 is a water level detector which is an integral type of the conventional level detector consisting
of two switches and sequencer output without changing the sequencer program and major connections.

2) Characteristics
LM 1-200 is characterized as follows .
• 100V/200V voltage available
• No relay is used and open collector is used for output.
• IC (TC4584) for detection can be replaced.
Terminal

Terminal block 2. Rating


1) Rated Voltage : 1 <I> AC1 00V/200V 50/60Hz
Voltage variation : +10%~-15%
Rating
1. Rated voltage :AC1 00/11 OV 50/60Hz Output 2) Permissible ambient temperature : -1 O'C ~+60'C
.---r----11 ON
2. Permissible ambient temperature :-5'C ~+55 'C 3) Basic connection
, II'
3. Action
15 10.5
OFF - ---
4. Output : 1 a relay contact Flame eye resistance (k Q ) OFF

* Flame eye (Flame detecting sensor) .. · .. ·


5. Basic connection Cadmium sulfide cell (CdS) P621-03 type Water level detector LM1-200

"1J
0
~
C1l
Logic ci rcuit r-- ~

Q.
Level detecting ci rcuit 0
c
;:::;:

I I I ~
I Semlconductor
' I I
contact
u .A .A A I
NPN·type

, ,
r=~]~311
100 100
000 00\ 00' ooe A. A. 8 C C, o. 0, TC ~ ov
Flame detecting circuit
Power re,OH

I h
FR ,. t~
:~oov
,b-..~
IDC:(V,
4. 000 001 00 J 00'
,
,

4 Sequencer input te rm inal


Note) Irreleva nt te rm inals
I - A,
A.-I-
I I are omitted. B. J L -B,
I I c· c,
~ n. 0,

e-
Output
Flame eye
BOILER WATER LEVEL
-
; :::;'"

49 50
omlUR~ omlUR~

Z BOILER [ Z BOILER .. -~

6-30 High Pressure Air Soot Blower 4. Finish


CD When all of the above mentioned process is completed , the soot blower has been finished.
Series GK units come with high pressure air soot blower. Adjust the time for operation while referring to the range of the air pressure gauge installed on the
equipment because it is standard time .
If there are no capacity of the air tank to spare, the operation time is possible to be cut down , please
1) Make sure that the pressure in the air tank reaches the preset pressure (2.5MPa).
refer to the minimum time required in the attached sheet.
2) Make sure that all of the soot blower main valve on the boiler side are closed. (?) During voyage, carry out soot blow at least once a day and decide the appropriate number and time
3) Open the main valve on the air tank side. of the operation according to your experience while checking the effect caused by soot remove.
4) Carry out soot blower according to the following procedure.

1. Soot Blower (1) (2) of Upper Tube Plate HIGH PRESS AIR SOOT BLOWER
CD Open the soot blower main valve No.(1) of the upper tube plate and carry out soot blower for about 20
seconds. (The valve is open , soot blows and then the valve is close in about 20 seconds.)
(?) Carry out soot blow at No.(2) of the upper tube plate same as mentioned item CD.
(Operation : about 20 seconds X 2 sets {Soot blower of the upper tube plate} ::: about 40 seconds.)

& Caution
When the pressure in the air tank is sufficient (over about 2.2 MPa). the next operation will be able to be
followed . If the pressure is below about 2.2 MPa, make sure that it will charge up into the preset pressure.
Start the next operation after making sure that the pressure will return to the preset pressure.

& Caution
When the pressure in the air tank decreases (into about 1.8 MPa) , stop the operation even in the middle of the

.(~.:..~.
-:}~?
operation and make sure that the pressure in the air tank will charge up into the preset pressure.
Continue the operation after making sure that the pressure in the air tank will return to the preset pressure.
"" ~<
~~.
,!J.#,~
'

2. In case GK 14XX, 16XX, 18XX operate the soot blower as same way as soot blower (1) (2).
Soot Blower (3) (4) on the Middle
CD Open the rotary soot blower main valve No.(3) on the middle and then carry out soot blow for about
30 seconds. (The valve is open , soot blows and then the valve is close in about 30 seconds .)
(?) Carry out rotary soot blow at No. (4) on the middle same as mentioned CD.
(Operation : about 30 seconds X 2 sets {Rotary soot blower on the middle}::: about 60 seconds.)

3. Soot Blower (5) (6) of Lower Tube Plate j.'\


y0 n· ) (5) (6) Soot Blower of
CD Open the soot blower main valve No .(5) of the lower tube plate and carry out soot blow for about 20 ,1-/ LJ Under Tube Plate
seconds. (The valve is open, soot blows , and then the valve is close in about 20 seconds.) 1j'J)
--.;.:...:Jo'

(?) Carry out soot blow at No. (6) of the lower tube plate same as mentioned item CD.
(Operation: about 20 seconds X 2 sets {Soot blower of the lower tube plate} ::: about 40 seconds .)

61 S2
OJrlIURJ\ OJrlIURJ\
Z BOILER J Z BOILER

6-31 Soot Cleaning in the Exhaust Gas Side while the ship is in Port 6-32 Washing while in Dock

Series GK units come equipped with high pressure air soot blower. Soot that cannot be removed by the 1. Using a high pressure cleaning pump, blow the soot away from the exhaust gas inlet and toward the
soot blower while the ship is at sea must be periodically removed . At that time, the soot should be removed middle area and the exhaust gas outlet, as described previously in (1).
with a vacuum cleaner and a compressed air blower. 2. Blow the soot adh ering to the water pipes from the top toward the bottom .
3. Remove the soot remaining on the top cover and the cleaning water, then use a fan on the manhole on
The following is the procedure for removing the soot from the water pipes on the exhaust gas. side: the inlet side to dry the water pipes.
1) Leaving the manhole on the inlet side of the exhaust open, collect the soot that has built up on the 4. When the water pipes have dried , sometimes some of the remaining soot will have fallen onto the bottom
bottom cover. If you have a vacuum cleaner, suck up all the soot that is within reach of the nozzle . cover. In such a case, remover the soot using either compressed air or high pressure cleaning water,
2) Use a compressed air blower to blow away remaining soot in the same direction as th e exhaust gas flow. 5. Immediately after cl eaning with water, dry the water pipes and start the boiler.
3) Open the cleaning opening in the middle portion and collect the soot that has accumulated .
4) Use a compressed air blower to blow the soot away from the middle cleaning opening toward the exhaust outlet.
5) Open th e m8nhole on th e outl et sid e of the exhau st and collect the soot that has accumulated . As soon
as possible after cleaning, close the manhole and the cleaning opening and start the boiler. 6 Warning
Frequent washing with water can cause sulphur-induced corrosion of the water pipes , drum, and casing .
Therefore , you should use water as little as possible .

Cleaning opening

Inlet side manhole Outlet side manhole


,, /-';'
-'

\:.. 0
00
o~~o
000 /" __ ',
o~oo
)(
(, ;;/r IU
m

0°0
0°0°0° ~ ;/
°°
0
000
..
2 '\
sri- 9
0 ,"'. ° / /
....').°g0 . 31\ °g0 :,"":
oU '
'"_/''' i, J
j 4 ;
',.j .

~ g !\ ,g /
~,
" '- - Cleaning opening

~3 ~4
OJrlIURI\ OJrlIURI\
Z BOILER --j [- Z BOILER

6-33 Excess Steam Dump Valve 7. Automatic Operation of the Boiler by the Sequencer
The pressure of the steam that is generated in this boiler is affected by the loaded condition of the ship. When the
7-1 Summary
steam pressure is low, the auxiliary boiler can supply additional steam from additional fire (concurrent operation) ,
Sequence control is an automatic control to sequentially perform a series of different operations different
but when the steam pressure rises rapidly, it is sometimes impossible to adjust the exhaust gas volume.
from the set-point control that allows the feedback control to maintain controlled variable during operation
Therefore, some of the generated steam is released through the drain cooler to adjust the steam pressure. In
and the proportional control that maintains the ratio of two controlled variables at a constant level.
other words, there is an excess steam release valve between the main steam line and the drain cooler; when the
Speaking of this boiler, it activates the timer and relay to sequentially and automatically performs a series
set pressure is exceeded, the excess steam is released through the drain cooler.
of actions such as starting the feed water pimp and the fan motor, activating the ignition device afte r full
pre-purge, opening the fuel valve to ignite the burner, shutting off the ignition device and gradually
steaming up to terminate startup with a press of button .

From Load
7-2 Basic Time Chart
The following shows basic patterns for the normal operation , flame failure during operation, ignition failure

I l!!J M" I Ii II
I i i' ',j, IIII i '
By-Pass Valve CooHng se:wate
q Drain Cooler
"
V
in operating the boiler.

1. Normal operation
Combustion SW ---"- - - - - - - - - - - - - - - - -

II I I II
U I I II Observation Tank
Burner motor ! as
Cascade .:os~ 1 I ..

1f:::r~ I~
Tank
Ignition transformer _ _ _-LI_.LI- - - - - - - - - - -- --
5S ~ , : 1 .. 128 ~ 1

Pilot solenoid valve : I

~: I/S
,--------------- - -
1) Body There are basically two types of excess steam release Combustion solenoid valve ___ _-!-_--1._ _ _ _ _ _ _ _ _ _ _ __
2) Bottom Cove r
@ 3) Top Cove r
valves: a direct driven type, and a pneumatic type .
@ 4) Sp ri ng Chambe r The type installed depends on the ship's specifications.
@ 5) Cylinder
6) Piston The release valve for the direct-driven type has the Flame eye ----~-------------
®
@ 7) Main Valve same structure as the pressure redu cing valve .
8) Mai n Valve Seat
@ ~ I~\~\
@~ ~®, 9) Pi lot Valve Seat (Referring to the figure below.) You can adjust the set
Q)
.......-@ 10)
11)
12)
Pi lot Valve
Cap
Cap Pilot Valve Screw
pressure by removing the cap (11) from the upper part
of the release valve , then loosening th e lock nut (17)
.
2. Flame fa.lure
during operation
Combustion switch
:358
:--1I
13) Washer Of Sp ring
and adjusting the regulating screw. Please monitor the
14) Washer Of Spring
15) Washer Of Spring pressure gauge as you make your adjustments.
16) Adjusting Screw
The pneumatic release valve monitors senses the Burn e rm o tor -------------~~--L----
17) Lock Nut
@ 18) Plug actual steam pressure and convents th e difference
19) Diaphragm
@ with set pressure of the release valve into an air
20) Str:Jinor
@ Combustion sol enoid valve :
21 ) Main Valve Spring signal that moves the diaphragm adjustment valve
® 22) AdjustinQ Screw SprinQ I
3.S3
®?~~ ,
I
23) Pilot Valve Spring which in turn regulates the steam pressure. Flame failure fire It · i '"
@/// ==t== d Ii. 24) Strai ner Spring ------------------------
1
:
(Jj
@
CD
'3 25)
26)
27)
Bolt & Nut
Bolt & Nut
Bolt & Nut
*For more information about the direct-driven and Flame eye I

(g) 28) Valve Guide


pneumatic release valves , pl ease consult the
29) Thrust Bearing operating manual. Alarm bell - -- - - - - - -- -- . . . - L - - - - -

55 56
OmlURI\ OmlURI\
------~

Z BOILER [ Z BOILER

3. Ignition failure 7-3 Flowcharts

-i_
Combustion SW
1

~ NFBON Power Lamp ON


Fan Motor r
I.. 358 • I :I" 3.58
1

Pilot Solenoid Valve n


Flame Failure
Flame Eye Low level lamp On YES Low Water
Feed Wate r Level
Pump Run
Alarm Bell
NO

Turn off the combustion switch once or press the alarm reset button to reset operation when you
experienced the situation stated (2) and (3). NO Normal Water
Level

Note YES
Time charts varies depending on specifications. See the final drawing for details . Combustion Oil pump, Fan on
start button Boiler running
3-4B ON (COM MODE )
Lamp ON
(B)

Oil Heater SW
""0
"A " "- Position is at..,
-,
CD
,
""0
c-,
co
CD "AlC" I "C"
c.u
U1
(Jl
CD
()
Oil Heater operation ~ Normal Temp
NO

YES

(A)

57 58
Z BOILER Z BOILER

__ hh __ h______ h________ j Three Level Control I-hh-______ hhh_h_h __ :________ hh_hh _____ hj ON-OFF control Ih--hhh __ h___ hU ___ :
(8)
(A)
o ! 0'
! !

Low steam pressure OPEN


Is there any YES Switch contact is
other interlock
cause

NO
"1J
....
CD
-6
/ c
toCD (
High steam Low steam pressure CLOSE
Pressure SW Stand by Switch contact is
is

CLOSE

Steam pressure CLOSE


Switch contact is
@
CLOSE High steam pressure
Switch contact is

Mis fire lamp ON


Ignition Trans OFF f---------'
Pilot Solenoid Post-purge
Valve OFF
YES
CLOSE
Steam pressure
Switch contact is

Low Oil Pressure Post-purge


lamp ON Combustion stop switch
Pressure rise? Pilot Solenoid 3-4B ON
Valve OFF

Combustion Solenoid
Valve OFF
Low Comb Solenoid Valve ON
(3 Position Control) NFB OFF

I~nition tran~former ?~ I Caution


I t-'ilot SOlenoid valve UN I
If the warning lamp for the burner interlock lights up, the burner will not automatically return to its
(C) previous setting-it will have to be reset

59 60
OhllURI\ OhllURI\
Z BOILER Z BOILER

9.
8. Safety Devices
ffi Caution
Inspection Before Operation and Operation
The m a in boiler system is always alert for th e The specifications of your warning apparatuses 9-1 Inspection of Every Check Points Before Operation
following malfunctions may vary.
ffi Warning
6 . Are there any clogging or loosened parts at
Status Response by system How to reset The following points should be examin ed to
the connections throughout th e fuel piping?
prevent accidents .
Ignition failure to burner Shut off burning appliances Reset button On 7 . Are there any air in the fuel line?
Burner flame out (ignition transformer, solenoid valve) in 3.5 8. Isn 't the fuel strainer clogged?
1 seconds Mis-fire, flame failure lamp lights 1. Around The boiler
False flame detected during burner 9. Is oil properly running from every tank
stand -by (pre-purge) on ,Activate alarm bell. Post purge start 1. Area around the boiler cleaned thoroughly? through the fuel pump?
2. Any obstacles on the way? 10. Check thoroughly for any leaks from the fuel
Lower water level Shut off burning appliances, Reset button On
3. Any flammable around the boiler? plumbing above the boiler.
(burner cut the water level) lower water level lamp lights on, (Reset after the wate r
2 4. Is there ai r inlet, or proper ventilator? 11. Is every needle of the pressure gauge and
Activate alarm bell , Post purge start level recovered)
5 . Is air pressure in engine room appropriate? thermometer o .k.?
If it is negative, make it positive by add ing 5. Burner
Fuel oil temperature drop Shut off burning appliances, Reset button On another ventilator. 1. Is installment of every equipment around the
(lower than specified oil temperature F.O temp drop lamp lights on 6. Is fire distinguishing system equipped ? burner O.k.?
3 set by thermostat) Activate alarm bell, Post purge start
I
2. The boiler and its Accessories 2 . Is the glass or flame eye not contaminated?
1. Is equipment installation such as inspection 3 . Is the ignition rod dirty, or is the size of each
holes, covers, valves o.k.? part O.k.?
F.O pressure drop (lower than specified Shut off burning appliances in 2seconds, Reset button On
2 . Is valve opening / closing, or switching of 4. Is the lead wire from the ignition transformer
pressure set by F.O pressure switch, Indicator light up for lower
4 every drain valves all right? through the rod, and each attachment O.k.?
during burner ignition.) F.O press drop lamp lights on , Activate
alarm bell , Post purge start 3 . Is draining direction out of safety valve o .k.? 5. Is the nozzle tip not clogged?
4 . Is glass stained or broken on the water level 6. Is a solenoid valve running properly? Are
Abnormal rise of exhaust gas temperature Shut off burning appliances, Reset button On gauge? there any oil leaks, or is the installment of the
(higher than specified temperature set Exhaust high temp lamp lights on , 5. Are needles of each pressure gauge O.k.? exiting open/close type o.k.?
5 by exhaust gas thermostat) Activate alarm bell , 3. Feed water system 7. Are there any deviance i n the damper
Post purge start 1. Is the Cascade Tank filled w ith water? caused by loose screws or levers, etc.?
2 . Is it dirty, or is there any oil in it? 8 . Does the damper motor run properly?
Fan stop Shut off burning appliances, Operate thermal relay
3 . Is automatic feed water valve (ball tap) 6. Electricity
(when thermal trips due to overload Fan abnormal stop lamp lights on , reset button ,
6 function normally? 1. Does every motor of the draft fun , the water
upon draft fun ) Activate alarm bell Reset button On
4 . Is switching of every valve for feed water line feeding pump, fueling pump, etc. run properly?
O.k.? And/Or, does it turn to the right direction?
Flame detected during post purge Shut off burning appliances, Reset button On 5 . Does the switch No . on the control panel 2 . Is every value for the thermostat (exhaust gas,
operation Abnormal fire lamp lights on , match with feed water pump for actual use? fuel heater, etc.), fuel oil temperature adjuster
7 Activate ala rm bell, 6 . Is there any clogging, air, leaking , or loos e and pressure switch specified correctly?
Extend post purge ope ration part in pipes? 3 . Is ignition transformer running normally?
7 . Isn 't strainer for sucking clogged ? Does it generate any sparks?
Abnormal rise of fuel oil temperature Shut off fuel heater, Automatic restoration
8. Isn't there any leaking from mechanical seal 4. Is the control panel not broken, or is every
(higher than specified temperature set F.O temp high lamp lihjts on F.O temp high lamp
8 of the feed water pump? attachment tool O.k.?
by high temperature thermal alarm) Activate alarm bell lights on
F.O high tempe rature thermostat 9 . Ar e needles of pressure gauge and 5. Are th ere any disconnected lead wires, loose
compound gauge o .k.? screws, broken lumps or switches?
Low water level (Alarm level) Low water level lamp lights on Automatic restoration 4. Fuel oil system 6. Is voltage 440V (220V) provided for regular
Activate alarm bell 1. Is there oil in the service tank for the boi ler operation , and 1OOV for operating the circuits?
9
(0 .0 tank and FO tank)? 7. Are there not any disco nnections throughout
2 . Is the FO tank heated properly ? the external wiring of all equipment?
3 . Is the FO purified by the purifi er. 8. Is every relay on the control p anel ru nn in g
Abnormal CP U, Other abnorma lity of Shut off every sequencer output such Power restoration
4 . Is th e tank drained properly? properly? Or flame detector, eve ry time r
the sequencer as the feeding water pump,burning
10 5. Is every valve switching through the fuel running o.k.?
appliances
piping from the tank to the boiler o.k.? 9. Is the sequencer runni ng?

61 62
omlURI\ omlURI\
Z BOILER - I Z BOILER

7. Steam 4. Has the valve for excess steam dump valve 4. Temporarily turn off the boiler and booster 6. Cold Start
1. Is every valve line opening/closing of the boiler o.k.? been installed? Or, is it set at the specified pump . Close the D.O. return valve of the When the water in the water heater body cools
2. Is overboard discharge valve closed? pressure properly? booster pump , and open the F.O . return down, or especially during test drive and using new
3. Is coding sea water flowing through the drain 5. Thoroughly examine other valve switching valve. body, the following attention should be paid.
cooler? for steam pipes, loosened parts around 5. Open slightly the air vent valve of the oil air 1. Do not raise steam drastically, when the entire
flange, before operation . separator. the boiler cools down; it should take enough
6. Close the supply valve of the D.O . tank, time before steam pressure is raised to 0.1 MPa.
9-2 Operation (in case of automatic burner operation) open the supply valve of the F.O. tank, and Raise steam pressure gradually up to 0.1 MPa
run the booster pump. by repeating 1 minute combustion and 4 minute
1. Confirm operating switches for the boiler o Any vibration?
7. Set the boiler to automatic operation, then when purge. Hold 10 minutes at steam pressure
Make sure all the switches (incl. N.F.B) are set 6. Stop combustion, if there is any. Check oil
the oil in the pipe between the booster pump 0.1 MPa. Between 0 . 1 MPa and 0 .2MPa
at the OFF position ; if not, set it OFF. pressure, oil temperature, the damper
outlet and the boiler FO. pump unit switches (lkgf/cm2-2kgf/cm2) repeat 2 minute combustion
2. Feeding water to the boiler opening burner nozzle etc.
over to fuel oil (F.O.), turn the heater switchover and 3 minute purge to raise pressure.
Always before starting burner operation, feed water 7. If steam pressure rises, check for any
switch to AlC. 2. When it reaches around 0.2MPa (2kgf/cm2),
to the boiler, following the procedures below: leaking from any parts.
B. Confirm that F.O temperature is raised up to stop the boiler, and retighten the screws and
1. Open all valves throughout systems from the B. When steam pressure rises up to specified level
the proper level and that pressure is stable . nuts around connecting pints of each valves
cascade tank through the boiler. set by pressure switch , examine combustion
9. Open slightly drain valve of oil air separator, onto the water heater body, man haul packing,
2. let out air from the feeding water pump and control if it works by following the order, from low
to check outgoing of FO . the water level gauge, etc.
systems. combustion middle combustion high combustion
10. When FO temperature reaches close to the 3. Blow off the water level gauge to give the
3. The boiler power on. (NFB) middle combustion low combustion - stop.
specified temperature, shift heater switch to "C". clear sight of gauge .
4. Set the feeding water pump at automatic (auto 9. Stop combustion .. .. .. confirm.
11. Confirm that there is no smoke in normal 4. Blow off the water in the water heater body,
vs. manual shifting) and set No. 1 and No.2 Is pressure gauge running O.k.?
operation . and purify the water.
shifting switch at arbitrary; to activate the 10. Suspend fan motor after 60 seconds post-
• Shifting from F.O (Heavy oil C) to 0.0 5. When the above process is all done , turn on
feeding water pump, light up operation indicator purge .... Confirm.
(Heavy oil A) the combustion switch to combustion again.
lump, low and lower water level lamp, and bell 11. Open main steam valve little by little, not to
1. Operate normally with F.O. 6. When steam pressure reaches the maximum
for low water level .... .. press on stop bell button . cause water hammer, to supply through systems.
2. Open 0 .0 supply valve, and then close F.O pressure for general use , check if any steam
5. Alert for noise of feed water pump/ motor, and 12. Examine if there is any leakage in pipes of
supply valve quickly. leaking .
overheat. steam system.
3. Close steam trace valve in the boiler fuel oil 7. Open main steam valve, to start automatic
6. Are compound gauge and pressure gauge 4. Termination with 0.0 (Heavy oil A)
piping. operation .
running properly? 1. Raise steam pressure close to the maximum
4. Shift the heater switch to "A", exactly when 0.0 7. How to assure alarm bell
7. Is it easy to view the water level gauge? Did pressure for general.
fills pipes from 0.0 valve through FO pump unit. 1. Bell and lump for ignition failure
the water feeding stop at the proper level? 2. Close main steam valve .
5. Open the D.O . return valve of the booster Before push the combustion switch, take off lead
B. Double check against any leaking water 3. Press down combustion stop button.
pump, then close the FO. return valve . wire extending from transformer at upper burner, by
around boiler body. 4. Blow off the water surface, bottom of the
6. Confirm that temperature at heater outlet pulling off the cap. Burner flame out occurs due to
9. Lower water level lump turns off by pressing water, and water level control cylinder.
drops and pressure is stable. no spark from ignition rod . When it happens, check
reset the switch . 5. Close valve in the feed water system and
7. Close fully the air vent valve of the oil air to see if flame off lamp lights up, switching off on
3. Combustion; Start from 0.0 (A heavy oil) 0.0 valve .
separator. burner circuit, and alarm bell rings after post purge.
1. Close the air vent valve of the air separator, open 6. Close the valve, checking the amount of the
B. Confirm outgoing 0 .0 by opening slightly 2. Burner Cut for lower water level
the booster pump return line valve to the D.O.tank cascade tank/oil service tank.
drain valve of oil air separator. Drain the water inside, by opening drain valve
and close the return line valve to the F.O.tank. 7. Turn off the boiler (NFB) .
9. Confirm that there is no smoke in normal and closing upper and lower detective piping
2. Open the supply valve of the D.O. tank, close 5. Switching fuel
combustion . valve on one of the water level control cylinder
the supply valve of the FO. tank , open the • Switching from 0.0 (Heavy oil A) to F.O
(Heavy oil C) the combustion. Make sure alarm bell goes off
inlet/outlet valve of the booster pump and run
the booster pump .
3. Turn the heater switchover switch to the A side.
1. Operate with 0.0 properly.
2. Raise F.O service tank to BO - 90'C
& Warning
in 10 seconds and burner is cut. After
restoration of each valve, examine other side for
3. Open steam trace valve in the boiler fuel oil pipe. proper operation. Then restore each valve.
4. Press combustion button . Stop combustion right away, when alarm bell
Be careful for F.O pump motor, noise of draft rings or faulty combustion occurs at shifting fuels .
fun , and temperature.
Pre -p urge ... confirm & Warning If any appropriate fuel oil temperature and pres-
sure is not given , manual operation should be
& Caution
Start combustion ... combustion indicator lump lights on activated to operate heater, oil pump to reach the
Alarm bell for low temperature of fuel oil is can- Switch fuel to 0 .0 (Heavy oil A) when the boiler is
5. Pay attention to the following points during proper temperature and pressure. No manual
celed , the moment heater switch shifted into suspended for a long time. Low temperature FO
combustion : combustion should be attempted at switching
"AlC". Stop the combustion, when inappropriate (Heavy oil C) should lead to damaging oil pump,
o Color of flam e, exp(msion, stability fuels ; it causes accidents such as backfire.
fuel oil temperature causes faulty combustion. its mechanical seal , solenoid valve, heater, etc.
o Color of smoke , any gas leak from its path

03 /34
omlURI\ omlUR~

Z BOILER
Z BOILER - ---- - -------1
10. Regular Maintenance
9-3 Manual Combustion by CAM Switch
& Caution

& Warning 10-1 Regular Maintenance


Carry out conduct the following maintenance regularly.

In the manual combustion, ignition error may cause dangers such as backfire , or over heat; do not use
unless otherwise emergency. In case of using, the following rules should be followed . 1. Cleaning of inside of the cascade tank When docked

2. Cleaning of filter within the cascade tank Every 6 months

Feeding Water 3. Cleaning of strainer/suction side of feedi ng water Every 2 months


Start Combustion Stop operation
System 4. Over hauling and inspection of the feed water check valve Every 6 months
1) Tum Cam Switch to off position, to stop automatic a) Return combustion change over switch to (Low
5. checking of feed water pressure compound gauge On demand
combustion. Comb.) to reverse the above-mentioned operation,
2) Shift fuel heater switch to A . Confirm that and turn Cam Switch counter-clockwise. 6. Cleaning of water level detecting rod, electrode holder Every 3 month
combustion shifting switch is set at (Low Comb) . Keep running more than 60 seconds at FAN 1. Examination/cleaning of the inside of the fuel service tank When docked
3) Turn Cam Switch to (F.O.Pump/heater) position. position.
2. Drain age of the fuel service tank Every day
At this point, check that fuel is properly circulating.
In manual operation as well, combustion is restricted 3. Cleaning of the fuel strainer Every 1 week
(by pressure gauge)
4) Shift fuel heater switch to C, in case of C heavy by interlocking of safety system as follows: 4. Cleaning of the strainer inside fuel oil pump (Pilot pump) Every 1 month
oil, and make sure the temperature goes up to the a) in case of flame-out, or ignition failure 5. Inspection/cleaning of fuel oil heater element On demand
specified level properly. If not, stand-by until it b) when steam pressure rises Fuel System
6. Fuel oil pump (contact manufacturer) On demand
reaches the proper level. c) when the water level of the boiler goes down to
lower water level 7. Major cleaning/exam of the fuel heater Every 1 year
(A heavy oil should not require this step) .
5) Turn Cam Sw itch to ( Fan Running) position. d) when the temperature of exhaust gas rises 8. Inspection/adjustment of the fuel oil thermostat and Temperature indicator/adjuster Every 3 months
Make sure that draft fun is running properly. e) when the fan motor stops 9. Inspection/adjustment of the coupling for fuel pressurized pump Every 2 months
6) Sufficient pre-purge lamp should be confirmed on.
10. Cleaning of V-type oil strainer for fuel line Every 3 months
7) Turn C am Switch to (Ign ition ) position. In manual operation where there is not enough inter-
locking system for safety, pay extra attention to the 1. Inspection of the fuel oil solenoid valve Every 3 months
Pilot burner comb usti on should be confirmed
through sight glass, and co mbustion lamp . boiler status. 2. Ch eck for any leakage of the burner nozzle Every 3 months
If there is no comb ustion, immediately set the a) Take sufficient time for pre-purge before manual
3. Maintenance of the burner body (baffle, rectifier grid, etc) Every 1 week
switch to FAN RUNNING. operation and post-purge after operation . (mo re
4. Inspection/adjustment for ignition rod Every 1 week
8) Turn Cam Switch to (Pre. Comb) position. than 70 seconds)
After confirming combustion through sight glass, b) Run/or stop the feed water pump, while checking 5. Inspection of th e nozzle tip Every 1 week
Burner system
turn Cam Switch to (Comb) position. the water level of the boiler. 6. Inspection of the air register Every 3 months
If it is not burning, return Cam Switch to (Fan 7. Inspection/adjustment of th e motor related parts of the damper Every 1 month
Running) right away.
8. Inspection of the dirt on flame eye/glass. Every 1 month
9) Turn combustion change over switch to (High
CAM Switch Combu stio n
Comb), after confirming the right status of 9. In spection of the draft fan , ball bearing, etc. On demand
Changeover Switch
combustion. IGNITION 10. Window box insulation On demand
FAN PRE.COMB.
RUNNING Every 1 year
1. Inspection within the boiler (manhole)
F.O.PUMP

COWCSJ""
HEATER COMB.
2. Inspection within combustion chamber When burner Every 6month
orr
& Warning AUTO
COMB.
Storage Water
Heater Body
3. Inspection within exhaust line Extracted

Every 1 year
4. Every type of valve attachment
Sufficient purg e should be conducted before
ign itio n ; lack of pre-purge can cause accidents 5. Blow of the water level gauge and control cylinder Every 1 year
such as backfire. 6. Blow of the surface/bottom of the boiler Every day

65 60
omlUR~ omlUR~
[ -- Z BOILER Z BOILER

1. Check insulating resistance of the relative motors Every 3 months 10-2 Inspection and Precautions Before Starting Operation
1. Be aware of the oil level, heating temperature and drainage in the fuel tank.
Electricity 2. Inspection of the ball bearing of the relative motors Every 1 month
2. Check the cascade tank level and cleanliness.
3. Check resistance of the water level detector and holder Every 3 months 3. Gating of the valves for water feeding and fueling.
4. Operative test for burner interlocking Every 3 months 4. Check the water level of the storage water tank.
5. Check steam pressure.
6. Make sure every switch on the control panel is OFF.
Burner Control Panel
Cut Alarm Bell Display 10-3 Inspection and Precautions During Operation
Ignition failure and/or mis-fire 0 0 0 1. Be aware of overheat, motor sound, vibration of accessories.
Draft fan suspended 0 0 0 2. Be aware of pipes/tubes leaks.
(
Heavy oil pressure goes down 0 0 0 3. Be aware of flame color, sound of burning , vibration .
Heavy oil temperature goes down 0 4. Ensure if pressure gauge, pressure switch , and thermostat are working properly.
0 0
5. Examine if the water level gauge is visible , and be aware of the water level change .
Water level drops specified low water level X 0 0
6. Check against earth in the motor system.
Exhaust gas temperature abnormally goes up 0 0 0
7. Check against any vibration of the control panel.
The feeding water pump delivelY pressureabnormall y rises 0 0 0 8. Ensure that the water feed pump stops/starts normally.
Water level drops specified very lower water level 0 0 0 9. Check if there is any overheat around the boiler body or other parts .
Heavy oil temperature abnormally rises X 0 0 10. Check condensed water temperature and see if there is any condenser overheat.
Sequencer malfunction 0 X 0 11. Ensure that the ampere meter gauges correctly.
Power shut off 0 X X

Refer to completed archive of each boiler for details 10-4 Inspection After Operation
1. Check for any water or oil reservoir.

5. Various automatic control test Every 3 months 2 . Check water level gauge instruction and steam pressure.
3. Check fuel tank level.
* Automatic start/stop of the feed water pump Every 3 months
4. Check gating of every system valve .
* Check On-Off/3-position control of the boiler Every 3 months 5 . Check the power switch .
* Oil temperature control of the F.O. heater Every 3 months
10-5 Handling Water in Storage Water Heating
The details are shown in the accompanied boiler water log book.
Be aware that most of the water tube accidents come from faulty water treatment. Through understanding of
the instruction book it should contribute to good management . The instruction book refers to how to
preserve the water tank, in case of a long-term shut-down, as well .

[ ) Refer to the "Manual for Water Treatment" .

10-6 Long-term Shut-down

it Warning
Be aware that non-compliance of the proper procedures may damage the boilAr rClrirlly or r.ClIISP. r.nrrnsinn
Details should be consulted with our Marine maintenance service.

87 68
OmIURJ\ OmIURJ\
.r Z BOILER _ _ _ _ _ _-' Z BOILER

11. Trouble Shooting 11-2 Fuel System

1. Fuel oil pump does not run.

& Caution
o Fuel oil pump magnet contactor 880 is defective.
o Fuel oil pump switch thermal relay 490 is actuated.
o Push the start button 3-4B is defective or not turned ON.
Details should be consulted with marine maintenance service.
o Rotor is seized or foreign matter is present.
o Bearing is seized or shaft is locked.
11-1 Feed Water System o Defective coupling .
o Motor main body burned, single-phase operation or disconnection of external wiring .
1. Suction failure of feed water pump 2. Fuel oil pump sounds loud or is overheated.
o Mixing of air from suction side . Or insufficient venting . o Pump cavitation or excessively-high discharge pressure .
o No water in feed water tank. o Clogging of discharge piping , valve, or so on .
o Clogging of feed water line , strainer, etc ., or excessive suction resistance. (
o Air mixing from suction side.
o Feed water tank is installed at a position much lower than feed water pump . (i.e. lack of NPSH) o Shaft locking or rotary section seizure .
o Cavitation due to back flow of boiler water or abnormally-high feed water temperature . o Vapor locking due to excessively-high fuel oil temperature.
o Insufficient capacity due to abnormal wear of impeller or guide plate of feed water pump. o Excessive draining of fuel oil.
o When priming occurs due to high concentration of boiler water, feed water supply is not enough and o Misalignment of pump and motor center lines.
low water level alarm may sound . o Damage of shock absorbing rubber coupling .
3. Fuel booster pump does not run.
2. Excessive rise of feed water pump discharge pressure
o Clogging of discharge side valve system or piping. o Defective pressure gauge.
o Defective pressure gauge . o Improper pressure adjustment.
o Clogging of discharge side piping or valve.
o Flooding of boiler due to improper feed water control. o Defective solenoid valve.
3. Water leakage from feed water pump o Clogging of nozzle pipe .
o Defective mechanical seal. o High fuel viscosity. Excessively-low heating temperature.
o Defective cover a-rings . 4. Fuel oil temperature does not rise.
o Defective air vent cock or improper fitting of pressure gauge piping joint. o Mixing of air.
4. Feed water pump does not start or stop properly or at the specified water level o Temperature setting of thermostat 23T is too low.
o Wrong connection of water level detecting rod with lead wire or disconnection . o Defective thermostat 23T.
o Poor conductivity due to green rust in joint of water level detecting rod and lead wire . (In some cases no o Disconnection of heater heating coii.
change is seen on the surface and conductivity is normal when measured with a tester because of its small
o Defective steam heater solenoid valve.
current used .)
o Fuel heater switch 43H is defective .
o Defective combustion start button 3-4B or not being pushed ON .
o Loose fitting parts on terminal board . o Decrease in capacity of heater due to its stained inside.
o Detecting rod is stained or in contact with main body cylinder. 5. Fuel does not spray.
o Water level detecting rod drops from the holder due to vibration . o Defective fuel solenoid valve (for circulation or combustion).
o Defective feed water pump switch (88W1 or W2) . o Clogging of nozzle tip (Filter, screw pin , etc)
o Clogging of valve for water level control cylinder. o Leakage from fuel piping or joint or clogging of pipe .
o Clogging of water level control stand pipe . o Improper discharge pressure of fuel booster pump.
o Improper water level indication due to stained water level gauge glass. o Excessively-high fuel viscosity... lock of heating .
o When priming or foaming occurs due to high concentration of boiler water, normal feed water control o Defective fan switch 88F or defective contact.
may not be made . 6. Will not go on high fire.
o Defective water level detector LM1-200. o Defective steam pressure switch 63SL (Defective contact).
o Defective fan switch 88F or defective contact.
5. Water level in water level gauge is not known. o Defective high combustion solenoid valve 20VH.
o Water level gauge glass is stained . o Defective damper limit switch and improper adjustment.
o Water level gauge is filled completely with boiler water.
o Water level gauge valve is blocked or not opened .
Note
6. Water leakage from water level gauge
o Defective glass packing .
Regarding trouble shooting of fuel pump and fuel booster pump refer to separated instructions.
o Improper fitting or uneven tightening of water level gauge.

69 70
OJrlIURJ\ OJrlIURJ\
l Z BOILER l-- Z BOILER

11-3 Combustion 11-4 Safety Control and Alarm Circuit

1. Fan does not run. 1. NFB is ON, but the boiler does not start.
o Defective fan switch 88F. o Power is not turned ON .
o Thermal relay 49F of fan switch 88F is actuated. o Damaged NFB.
o Steam pressure rises above steam pressure switch set pressure .
o Defective combustion start button 3-4B or not being pushed ON . 2. Combustion start button is pushed, but the combustion does not start.
o Motor burned out, disconnection , or defective bearing. o Low-low watef level (Low-low water level alarm lamp illuminates.)
o Manual combustion switch is set at Manual. Or manual operation switch is not turned OFF.
2. Ignition failure o Steam pressure rises to set pressure of high set pressure switch 63S.
1) Fire goes out after burning far 2 or 3 seconds.
o Refer to Item 11-3 Combustion.

o Defective flame eye or stained lens . (


3. Water is Low-low level, but no indicator lamp illuminates. Alarm bell does not sound either.
o Improper air flow adjustment (Improper damper adjustment). o Defective lamp or socket.
o Clogging of chimney. o Defective bell stop pushbutton switch 3-28B.
o Defective fuel solenoid valve . o Defective bell.
o Improper position between nozzle tip and baffle plate.
2) Fire goes out after burning for about 10 seconds. 4. When ship rolls, water level becomes lower one and burner stops immediately.
o Improper position relative to the nozzle tip, baffle plate, and flam e funnel. o Defective water level detector LM 1-200.
o Oil pressure drop in about 10 seconds due to defective solenoid valve, etc. o Wrong connection of lead wire with water level detecting rod terminal or disconnection.
o Wrong flame detecting position of flame eye.
o Flame blowout due to excessive airflow. 5. Ignition tails, but ignition failure lamp does not illuminate. Alarm does not sound either.
o Defective flame detector FS-1 00.
3. Vibration combustion. o Defective lamp or socket. Defective bell.
o Air is included in fuel. o Defective bell stop switch 3-28B.
o Burner ignition position is not proper. (Ignition delay is caused.)
o Oil heatinQ temperature is too high or too low.
o Nozzle tip size does not fit air flow.
o Oil collects in the combustion chamber and burns.
o Air register is burned . 11-5 Exhaust Gas Lines (Main Engine, Burner)
o High combustion solenoid valve leaks during low combustion.
1. Exhaust gas temperature of burner side is high.
o Low and high combustion pipes leak in the nozzle pipe.
o Too much fuel consumption.
o Oil pressure rises slowly. (ignition delay is caused.) o Adhesion of soot to water tubes and smoke tubes.
o Leak from cut-off valve.
o Insufficient air flow. 2. Exhaust sparks from a funnel and condition of main engine become out or order.
o When fuel property changes extremely, combustion condition may be affected delicately. o Adhesion of soot to water tubes.
o Funnel is clogged.
3. Leakage of gases from burner at main engine running (burner stop)
o Refractory are broken off.
o Bend of innermost tubes due to over-heat.

Simple causes of problems are described above During boiler operation, unexpected troubles may occur
including troubles with the sequencer itself which is in charge of contro l. Th erefore, pay special attention to
a meter valuo, prossure gauge indication , hoating and abnormality of components, etc. , so that abnormal
symptoms can be discovered in the early stages.
With regard to electric items, check terminal screws for looseness, damage of lead wire, etc. re gu larly to
prevent any possible troubles.

71 2
OmlURI\ OmlURI\
,. Z BOILER [iUaOILER ._,

12. Remedy against Water Tube trouble 12-2 Repair for Water Tube Trouble

The GK typ e boiler is a vertical natural -circulation boiler. Since , Deposits of impurities in feed water
12-1 Water Tube Leakage
(calcium , magnesium , and silica) may form on the heating surface which could hinder the heat exchange
No leakage from the water tube of the GK type boiler occurs if water quality control is carried out properly. process, damage the water tubes , and cause leakage, if boiler water is not controlled as shown in the
External water treatment with the water softner and boiler internal water treatment with boiler compound attached "Manual for water treatment. To operate this boiler most economically and efficiently, it is essential
are absolutely essential. If leakage is found from the boiler water tube due to improper boiler water to control boiler water by blowing down boiler water and using proper boiler compounds and a water
treatment, check it as follows: softener, etc ." This chapter describes ways to fix damaged water tubes and leakage which are caus ed by
unsatisfactory boiler water control.

1) Remove the burner and wind box from the upper section of the boiler. (Open the chimney manhole on & Warning
(
\
the exhaust gas side .)
Before inspecting the interior of the unit, tum it off, purge with the bottom blow-off valve and ventilator, and cool both
the inside of the drum and the combustion chamber. Then make sure that the pressure inside the drum is 0 MPa.
2) Enter the boiler combustion chamber and check the water tube wall. (Enter the chimney on the exhaust Also, when conducting the inspection, make sure ventilation is provided by the air duct and/or the ventilator fan .
gas side. ) (It can be checked in this stage, if a leak location is discovered.)

3) Set the feed water pump switch to Manual and perform a hydraulic test.
1. Stopper treatment applied from inside the water drum

4) If water is leaking from the connection of a water tube and tube plate, remove castabe filled around the Stopper This method uses the 12 steel stoppers that are
connection and check it. ~ included as boiler spare parts to plug up from the
When water is leaking from the back side of the first row of tubes toward the second row of tubes, we
~ inside of the water drum, and upper and lower steam
may easily consider that water is leaking from the second row of tubes. Therefore, check it carefully in drums. Before inserting the stoppers, you will have to
full consideration of the above . determine which water tube(s) is/are leaking.
First of all , remove the ventilator, burner assembly
5) When the leaking water tube is found , drive a stopper, replace it or so on in accordance with "Damaged and window box at the top of the boiler, then enter
water tube". the combustion chamber.
Sometimes, you can determine by sight where the
6) Investigate the cause of water tube leakage and use it as reference for future operation . If the use it as Combustion
Chamber leak is coming from . However, in all other cases
reference for future operation. If the water treatment is the problem , it may continue to occur until it is you will have to conduct a water pressure test to
properly looked after. determine the origin . Operate the water supply
When water is leaking on th e exhaust economizer side , open manhol e on the exhaust gas inlet and pump manually. Loosen the pressure gauge and
outlet and hand hole on middle portion and check it. the ground part of the pressure switch valve to
release the air. (For boilers with an air release
cock, use the cock to let the air out).
Once you have identified the leaking water
tube(s ), enter the drum through the manhol e and
insert the stoppers from inside as shown in the
diagram.
In this case , you should cl ean the area so that
junk or foreign substan ces wil l not accumul ate
where the stopper touches the water tube ; this is
t esp ecially im po rt ant if there is som e sort of
Stopper damage . It is also effective the polish the parts
with carborundum or similar substance .

73 74
OMIURJ\ OJrlIURI\
[-- Z BOILER Z BoiLER ---- --- - - I

2. Repair by stopper welding from inside the combustion chamber. (Tubes in the first line)
MIURA PROTEC CO.,LTD. 7,HORIE-CHO,MATSUYAMA-SHI, TEL : (+81)899797066
4)
SHIP MACHINERY DEPT EHIME, JAPAN 799-2696 FAX : (+81) 89 979 7067
",r.:

I AUTHORIZED DISTRIBUTORS: 1-4-26,TAKANAWA MINATO-KU, TEL: (+81) 3 3449 3821


Combustion N. Y.CO.,LTD. TOKYO, JAPAN 108-0074 FAX : (+81) 3 3440 0944
Chamber
1 Steam Drum
I
Cut by Gas 2 Water Drum
4-28-2,ABRAYA-CHO,MINATO-KU, TEL : (+81) 52 383 3166 ,

3 Water Tube CHUO MACHINERY CO. ,LTD.


NAGOYA, AICHI , JAPAN 455-0824 FAX: (+8 1) 52 383 3607
4 Castable
------- -

• KOREA • THE NETHERLANDS


DONG YANG ENGINEERING NICOVERKEN HOLLAND B.V.
#10-11 ,2Ka MYEONG-RYUN -DONG REGOUTSTRAAT1 3125 BH SCHIEDAM,
2) THE NETHERLANDS
DONGRAE-KU PUSAN,KOREA
TEL: (+82)51 552 6503 TEL: (+31)104370877
FAX: (+82)51 5574830 FAX: (+31)104157150
This method is exactly like the previous method up to the point where the water pressure test is conducted inside the FUJI TRADING (MARINE) B.V.
• TAIWAN POST BOX 2498
combustion chamber to determine which tube(s) is/are leaking. However, the stopper treatment method is completely
NAIKAI ENGINEERING CONSULTANT CO.,LTD. 3000 CL ROTTERDAM
different; in this case , the stoppers are welded from inside the combustion chamber, as shown in the diagram .
3F.NO .34 LANE55 TUNG HSIN RD . SLUISJESDIJK 109
Therefore, the number one prerequisite for using this method is to have a certified welder on board the ship. KEELUNG,TAIWAN ,R. O. C. THE NETHERLANDS
TEL: (+886) 22 4657554 TEL: (+31) 10 429 8833
FAX : (+886) 22 4652182 FAX: (+31)104295227
MING YUNG MACHINERY.,LTD.
27.SHIN SHING STREET. • GERMANY
YAN CHERNG DISTRICT TAKANAS MARINE ENGINEERING GMBH
I Anchor KAOHSIUNG, TAIWAN, R. O . C. "FRUCHTHOF" OBERHAFENSTR .1
Welding
I I I I "'.;.. '1111 , ~ 11.1111,
TEL: (+886)7521 6266 20097 HAMBURG
FAX: (+886)7521 9368 GERMANY

ICastable
• SINGAPORE
TEL: (+49)4032 1305
FAX: (+tl9)tlO 33 0608
Combustion Combustion TAKNAS ENGINEERING PTE. LTD.
Chamber Chamber 102, PANDAN LOOP SINGAPORE 128310 • USA
I I V ' IIII . 1111 1 1111 1 TEL: (+65)67775856 CISCO BOILER SERVICE CO., INC.
FAX: (+65)67796711 5709 OLD SPANISH TRAIL HOUSTON ,
FUJI HORIGUCHI ENGINEERING PTE.LTD. TX 77023
BLOCK 11 PIONIEER RD NORTH USA
#01-66 SINGAPORE 628462 TEL: (+1)7139285700
TEL: (+65)68636368 FAX: (+ 1)713 928 5795
FAX: (+65)68638310 INDUSTRIAL BOILER SERVICE, INC.
23132 EAST ECHO LAKE ROAD SNOHOMISH ,
If you undertake the stopper treatment from just the top and bottom without welding the stoppers, keep in mind
W!\ 98296
that the water tube (which doesn't contain water) will become damaged and water will leak from the exhaust gas • UAE
IN CONJUCTION WITH FUJI TRADING CO., LTD. USA
outlet. Therefore , the previous type of work should be done only in case of emergency; it is highly recommended P. O . BOX 64 88 DUBAI TEL: (+1)2066241171
that the stoppers be welded once the ship reaches port. However, if there is some technical issue, such as with UAE FAX: (+1)2064839 112
welders, and application of castable refractories is neglected after the stopper treatment as shown in the fi gu re, TEL: (+971)4342211
this may other problems to develop. Therefore , you must follow the manufacturer 's instructions precisely. FAX : (+971)4342662

75 77
Safety, Operating & Maintenance in Instructions

AUXILIARY BOILER - GK SERIES


• First edition published in Augast 2004
• Revised edition
E 890-0408-01
• No.
• Published by Miura Protec Co., Ltd. Ship Machinery Dept.

• Home Page www.miuraz.co.jp/ marine/


• Service News www.miuraz.co.jp/marine/mente/news.html

All right reserved, Copyright © 2004 MIURA PROTEC CO.,LTO .


No part of this publication may not be reproduced , transmitted, distributed or modified,
in any from or by any means, without the written permission of the publisher MIURA
PROTEC CO.,LTD.

Printed in Japan

You might also like