Professional Documents
Culture Documents
Se 1504 Planning and Design of Fire Protection Systems Module-I
Se 1504 Planning and Design of Fire Protection Systems Module-I
MODULE- I
Fire detection- Need and importance of automatic fire detection system, principle of
detection, classification of detectors; Heat detectors – fixed temperature, rate of rise ,
thermistor rate of rise and rate compensated type detectors; Smoke detectors- optical
and ionization type, photo electric light scattering and light obstruction type
detectors; Flame detectors – infra red and ultra violet detectors; Flammable gas
detection- Pellistor and laser detectors; Testing of fire detection devices as per
relevant Indian standards specifications; Comparison of detectors; Performance
characteristics of detectors; Lag time associated with fire detection.
MODULE -II
Principles of Fire Extinguishments-extinction of premixed flames, diffusion flames
and burning metals, fire triangle, fire tetrahedron; Basic concept of fire fighting with
water, carbon dioxide, powders, foams, inert gases halons; Need for halon
replacement and halon substitutes; Extinguishant performance- flame extinguishing
concentration, inerting concentration, fire trials.
First aid fire protection – fire bucket, sand bucket, fire blanket, fire pails & water
barrels, hose reels; Description, working principle, method of operation of different
types of portable fire extinguishers-water type, foam type, dry powder type, CO2 type,
vapourizing liquid type; Care, inspection, and maintenance of portable extinguishers
as per relevant Indian standards specifications.
MODULE -III
Automatic water sprinkler system- requirement and source of water supply, automatic
pumps; Automatic sprinkler heads-Quartzoid type, fusible link type, modern types;
mounting and protection of sprinkler heads; Sprinkler pipe works-standard and
staggered lay out, hangers; Control valves for wet and dry installations; deluge valve.
Drenchers; High velocity and medium velocity spray system; Principles of water
sprinkler system design as per relevant standards (ISI).
MODULE -IV
Fixed fire fighting system using CO2, Dry chemical powder, and Foam - concept of
total flooding and local application, advantages and disadvantages of each system;
Basic system components; Design principles of fixed fire fighting systems for total
flooding and for local application as per relevant standards (ISI).
Fire alarm system- classification of alarm system as per NBC; Manually operated
system; Automatic alarm system; Component and features of Local system, Auxiliary
system, Remote station system, Central station system and Proprietary system
Text Books
1. Ron Hirst, “Underdowns Practical Fire Precautions”, Gower Publishing
Company Ltd., England, 1989.
2. Jain V.K., “Fire Safety in Buildings”, New Age International (P) Ltd., New
Delhi, 1996
3. Clark, W.E., “Fire fighting principles & practices ”,
4. HMSO : Manual of Firemanship, No. 4 to 7.
5. Kevin Cassidy, “Fire Safety and loss Prevention”
6. N F P A, “ Fire Protection Hand Book”
7. Hubert Walker, “Preventive maintenance/Apparatus”
8. Ervin L.W., “Fire fighting apparatus and procedures”
9. Fire services manual Vol 1 & Vol 2
10. Barendra Mohan Sen “Fire protection and prevention the essential hand book”
11. Relevant IS codes
- Heat
- Radiation
- Smoke, etc.
- The detector respond only to the conditions existing at the place they are
located.
[IS 2175 - Block Detector; NFPA - Spot detector]
- Line type detector – The detector may be several meter long and will
respond along its length.
A practical detector must be robust, reliable and sensitive. It should also have
long life, should not give false alarms and should be easily tested and readily
replaced.
Thermal lag describes a material's thermal mass with respect to time. A material with
high thermal mass (high heat capacity and low conductivity) will have a large thermal
lag.
Where,
L = thickness (m)
α = thermal diffusivity (m2/s)
When two metals having different coefficients of thermal expansion are bonded
together and then heated, differential expansion causes banding or flexing towards the
metal having the lower expansion rate. This action breaks or makes a circuit, causing
the detector to activate.
Low expansion metal- invar (alloy of nickel (36%) and iron (64%)
This is a spot type detector and its main drawback is that it can be operated only once
and is not reusable.
The commonly used alloy is Eutectic metal (-alloys of bismuth, lead, tin and
cadmium) which has an approximate melting point of 68 °C
They are line type detectors. In this case, two current carrying wires are kept
separated by a heat-sensitive insulation. The insulation gets softened at its rated
temperature and thus making the wires to have electrical contact.
- A quartzoid bulb (bulb in the shape of quartz) is filled with highly expansable
liquid with a small amount of gas inside. As the temperature increases, the liquid
expands and the pressure of liquid causes the bulb to burst, leading to the
activation of alarm.
- This type of detections are used in water sprinkler system and are available at
different temperature ranges (49 0C, 60, 74, 121, 160, 204, 2830C)
The rate of rise detector will respond to the rate at which the temperature rises. At a
slow temperature rise it will not respond quickly unless the temperature reaches a pre-
set value. Different principles are used to achieve this response.
The change in resistance of these thermistor is very large. For example, at 20 °C, its
resistance is 100 kΩ while at 100 °C it has only 100 Ω resistance.
- The circuit within the detector is designed to alarm when the change in
the resistance reaches a pre-set value.
- Here, the outer shell of the detector is made of rapidly expanding alloy stainless
steel, which is sensitive to the changes in the surrounding air temperature.
- The inner struts are made of alloy having lesser co-efficient of expansion.
- At slow rate of heat development, both outer shell and inner strut expands
almost evenly and contact is established at pre-set value.
- Under a rapid rate of rise in temperature, the shell expands at a faster rate and
alarm is activated earlier when the air temperature reaches its pre-set value.
- A transient temperature variation may heat up the outer shell, but may not cause
alarm.
Expansion struts
Adjusting/Setting Screw
Seal
Fig. : Rate compensated heat detectors - Cut section and general view
1 35 to 50 1
2 11 to 18 3
3 6 to 11 5
4 3 to 6 10
5 1.5 to 3.25 20
6 1 to 2.5 30
- Optical Type
Photo electric light obscuration type
Photo electric light scattering type
- Ionization type and
- Air Sampling Type
Combustion processes release solid and liquid particles, most of which appears as
smoke, with size ranging from 0.5 millimicron to 10 micron (0.5 x 10 -6 mm to 10 x
10 -3 mm).
- Size of particles which are released at temperatures below the fire point of a
fuel (pre-ignition heating) are generally in the range of 0.5-1.0 millimicron.
- When there is a disturbance in the air within the light beam due to
smoke , the intensity of light received by the receiver will be affected
and this variation, when reaches a preset value(say about 50% less)fire
alarm will be activated.
Fig.:- Working
When a turbulent
principlehot air or obscuration
of light gas passes through the light
Fig. beam,
Light the light beam
obscuration
will be irregularly
Type smoke detectors deflected and this may lead to a light flickering effect at
type smoke detector
the receiving end. This flickering effect can also be sensed by the receiver
fitted with appropriate electronic devises and an alarm can be activated based
on the frequency of flickering received (Typical flicker frequency associated
with a fire scenario ranges between 2 Hz and 20 Hz). Hence, this type of
system can detect both smoke and heat (combined heat and smoke detector)
Light obscuration type photoelectric smoke detectors are suitable for
- Dirt deposited on either the light source or the cell could cause a false alarm.
1.3.1.2 Photoelectric light scattering type smoke detector
This is a Spot type detector
Principle of working of a light scattering type photoelectric smoke detector is as
follows:
If a beam of light is directed into a cloud of particles some of the light will be
scattered sideways to the beam. There is an optimum angle from which maximum
amount of scattered light can be observed.
The photocell is placed in the detector in such a way that it receives no light from the
source (emitter) under normal condition.
When smoke particles enter the light path, light is scattered onto the photosensitive
receiver and causes the detector to respond (alarm signal)
- The life of photocell will be more in this case compared to obscuration type
detector due to the fact that in this case, the cell is exposed to light only when
light is scattered.
- The particle size less than 0.3 micron are too small to scatter light and are
invisible. So, a detector which operates by optical process will fail to detect
the pre-ignition particles and the invisible part of smouldering emission.
These types of detectors are sensitive to the invisible particles which are released,
particularly in the initial stages of a fire.
The radioactive material is to produce alpha radiation and is usually Americium 241
or Radium 226. Americium has minimum radiation of particles other than α-
radiation and hence it is preferred.
Principle of operation of an ionization type smoke detector is as follows:
- The emission of alpha radiation keeps the air ionized in the air chamber.
- When a potential is applied to the chamber electrode, the ions flow to their
respective electrodes (+ve ions to –ve electrode and –ve ion to +ve electrode)
and hence a small measurable electric current flows across the chamber air
gap.
- When smoke particle enter the chamber, ions are captured on the surface of the
smoke particles and hence the current flow is reduced.
- This change in the current flow is amplified and when the difference in the
current flow is more than a preset value, a signal is transmitted to the fire
alarm control unit.
Since the current detected is very small, a small variation in the current due to other
reasons many make a false alarm. The variation in the current may occur due to
- Radio transmission
- Use of cellular phones
- Reduced radiation due to the dirt or moisture, which may get deposited on the
surface of the emitter/ receiver.
- If there is air movement –(ionized air may get displaced from the chamber due
to wind and leading to a reduced current formation).
In fact, ionization type smoke detectors have the greatest false alarm rate among
smoke detectors from the cooking and other non-fire sources.
Photoelectric smoke detectors respond faster to fire in its early, smouldering stage
(before it breaks into flame).
Ionization smoke alarms may not operate in time to alert occupants early enough to
escape from smouldering fires. So, it has been made mandatory to use photoelectric
smoke alarms rather than ionization type in most of the recommendations meant for
residential buildings (sleeping rooms).
An aspiration fan in the detector housing draws air from the protected area back to the
detector through air sampling ports, piping, or tubing.
Air Sampling Smoke Detectors are capable of detecting a fire at its earliest stage.
Air Sampling Smoke Detectors actively pulls room air through a piping network to its
detection chamber where it can detect the presence of particles that are created in the
very early stages of combustion, even before smoke is visible.
They are best suited to detect fires wherein submicron particles are produced during
pyrolysis or precombustion phase of incipient fires.
They are most often used where the protected space has high value and demands very
early warning of incipient fires such as in computer rooms, air conditioning ducts,
archives, etc.
After the air sample has been raised to high humidity level (relative humidity
approximately 100%), the pressure is slightly lowered with the help of vacuum pump.
If smoke particles are there in the chamber, they act as condensation nuclei for water
droplets and form cloud.
The density of this cloud is measured with a photoelectric light scattering detector.
When the “cloud” reaches a predetermined density, the detector will respond with an
alarm.
The oldest and original air sampling technology is the Cloud Chamber Systems.
However, the maintenance of these type of systems is difficult due to the fact
that, there is a requirement of frequent replacement of evaporated water and
monitoring of ongoing water levels. Also, there are more more moving parts in
this system than other systems, leading to more mechanical failures and is more
labor intensive to service and repair.
A fan continually drawing air into a pipe network attached to a detector unit, and
passes the air through a dual stage filter to remove dirt and particles larger than 25
microns, sending the clean air to a laser detection chamber for smoke detection.
The detector measures the light scatter caused by any smoke and processes the
detector signal.
Here, a fan continuously draws air from the protected area through the detection
chamber. Once inside, particles pass through the laser beam while the photo collector
measures reflected light from the particles. The collector counts the number of
discrete particles to determine the level of smoke concentration. A particle size
discriminator prevents large particles, such as dust, from contributing to the smoke
concentration.
1.4 FLAME DETECTOR (ELECTROMAGNETIC RADIATION DETECTOR)
An ideal flame detector would reliably sense a flame of interest, while totally
ignoring
all other flames or signal sources and would, in the process, be totally unaffected
by
ambient operating conditions. However, no completely ideal flame detector
exists.
Flame detector detects the radiation from a fire. The radiation from a flame will travel
at the speed of light. So, flame detections have fastest possible response time. They
are of surveillance type (single unit protects large volume). The ultraviolet and
infrared region of the radiation spectra is considered for the fire detection.
Filter
cum
Visual Indictor
amplifier
Lens and
Photoelectric Relay Alarm
optical
cell
filter
Fig. : Schematic diagram of IR type flame detector
The photoelectric cell converts light energy into electric energy. They are usually
made of materials such as thallons sulphide, lead sulphide, lead telluride, lead
selenide, selenium and silicon.
The lens and optical filter system filters the radiation and allows the transmission
of the IR radiation of the desired wavelength.
Materials like quartz, cesium bromide and calcium flouride are used for making
this lens cum filter
The filter cum amplifieer has two functions
IR sensor
The IR type detectors are best suited where there is a chance of more smoke in a fire,
fires in chemical factories, generating stations, computer facilities, etc.
1.4.2 Ultra Violet Type Flame Detectors
The UV detector detects the UV radiation with the help of a UV sensitive photocell,
or with a gas filled tube.
The working principle of UV detector having photocell as the sensing element is the
same as that of IR detector, except for the change in the frequency response, which is
normally of the range from 1850 Å to 2450 Å. (sunlight could have a UV radiation as
low as 2900 Å and this radiation should be avoided by flame detectors)
The UV detector with gas filled tube essentially consists of a UV sensing tube,
amplifier, relay and alarm Unit.
The UV detectors consider a wavelength less than 0.30 micron for flame detection to
avoid the UV radiation from sunlight and artificial light. Detectors are sensitive only
to radiation at wavelengths less than 0.3 micron. However, only a small fraction of the
energy emitted by flames is in this region and it is necessary to have a very sensitive
sensing tube. A Geiger- Muller tube is generally used for this purpose.
The UV radiation passes through a quartz glass window and strikes on the sensing
tube. The sensing tube (Geiger-Muller tube) comprises of a glass envelop, which is
transparent to the desired radiation, containing two electrodes and filled with a
suitable gas.
Gas filled tube
Electrodes
The electrodes are close together and a voltage is applied between them. The metal of
the electrode is selected in such a way that, when a photon of radiation at the right
wavelength is absorbed, it releases electron and this in turn ionizes the gas in the tube.
This ionization sets up a small current between the electrodes and is fed to the
amplifier.
The amplifier sets up the current and transmits it to the relay, which activates the
alarm when the signal to it persists for a preset time period.
UV sensor
It is important to ensure that the glass window is kept clean, particularly of oil
deposits(thin film of oil will absorb the UV radiation). Also, performance of UV
detector is affected by the presence of smoke and fog, as UV radiation is absorbed by
them. UV detector will respond to the radiation caused by welding, X-rays, etc. Hence
UV detectors are best suited for the monitoring of aircraft engines, fuel storage tanks,
oil drilling rigs, etc.
1.4.3 UV/IR Type Flame Detector
The dual UV/IR type detectors are used to reduce the effect of false alarm and for
specific applications. Since UV and IR detection occurs at different wavelengths (less
than 0.30 micron for UV and 4.2 to 4.5 micron (CO2) for IR, the combination of UV
and IR detection helps to reduce the false alarm caused by individual detection. The
system will activate only if both the detectors are activated as well as based on a pre
set threshold ratio between them.
UV sensor
IR sensor
Dual IR (IR/IR) flame detectors compare the threshold signal in two infrared ranges.
In this case one sensor looks at the 4.4 micron range and the other sensor at a
reference frequency.
IR sensor
IR sensor
IR sensor
In some detectors a sensor for visible radiation is added to the design in order to be
able to discriminate against false alarms better or improve the detection range.
Visual flame detectors employ standard charged couple device (CCD) image sensors,
(commonly used in closed circuit television cameras) and flame detection algorithms
to establish the presence of fires. The imaging algorithms process the live video image
from the CCD array and analyze the shape and progression of would be fires to
discriminate between flame and non-flame sources. Unlike IR or UV flame detectors,
CCTV visual flame detectors do not depend on emissions from carbon dioxide, water,
and other products of combustion to detect fires, nor are they influenced by fire’s
radiant intensity. As a result, they are commonly found in installations where flame
detectors are required to discriminate between process fires and fires resulting from an
accidental release of combustible material. However, visual flame detectors cannot
detect flames that are invisible to the naked eye such as hydrogen flames. Heavy
smoke also impairs the detector’s capacity to detect fire, since visible radiation from
the fire is one of the technology’s fundamental parameters.
A flame detector is an optical device and thus it needs to have a clear view of the
area to properly detect a fire.
Flame detectors have a 3-D cone of vision ranging from 90 degrees to 120 degrees.
Sensitivity of flame detectors diminishes at the edges of the cone of vision. There is
some blind spot at the edges of the cone. The detector would activate only when the
fire becomes larger (say about four times the surface area that needed at the center of
the cone)
Fig. : Field of view of flame detector – 3D
Blind spots
Blind spots
Since both sensitivity and range are related to fire size(surface area of fire), if the
detector is placed further away from (or closer to) the fire source, the detectable fire
size will vary according to the inverse square law.
So doubling the detection distance results in only ¼ of the radiant energy reaching the
detector, or conversely, for the same response time, the surface area of the fire then
needs to be 4 times larger.
A single detector with larger range is better compared with many detectors having
smaller range
Fig. : One 60 m IR3 Detector Verses
Seven 15 m IR/UV detectors
(Typical)
Gas detectors can be used to detect flammable and toxic gases and oxygen depletion.
Gas detectors may also be used to initiate specific precautions (for example plant
shutdown, evacuation, and operation of fire extinguishing procedures).
Flammable gas detecting apparatus may be used to monitor a gas atmosphere below
the lower flammable limit in circumstances where accumulation of gas may result in a
concentration of the gas/air mixture to potentially explosive levels.
Gas detectors are usually battery operated. They transmit warnings via a series of
audible and visible signals such as alarms and flashing lights, when dangerous levels
of gas vapours are detected. As detectors measure a gas concentration, the sensor
responds to a calibration gas, which serves as the reference point or scale. As a
sensor’s detection exceeds a preset alarm level, the alarm or signal will be activated.
As units, gas detectors are produced as portable or stationary devices.
Originally, detectors were produced to detect a single gas, but modern units may
detect several toxic or combustible gases, or even a combination of both types.
Basically the toxic gases or combustion gases can be detected using different
technologies like
IR technology
Pellistors are solid-state devices used to detect gases which are either combustible or
which have a significant difference in thermal conductivity to that of air. (The
detecting elements consist of small ‘pellets’ of catalyst-loaded ceramic whose
resistance changes in the presence of the target gas hence the term ‘pellistor’ being a
combination of ‘pellet’ and ‘resistor’)
Pellistors were originally developed for the mining industry during the early 1960’s;
Depending on the mode of operation in detecting gas, there are two types of pellistor,
namely
Catalytic type and
Thermal Conductivity (TC) type
The catalytic type sensor works by burning the target gas; the heat generated
producing a change in the resistance of the detecting element of the sensor
proportional to the gas concentration. Most of the pellister type gas detectors are of
catalytic type.
The thermal conductivity sensor works by measuring the change in heat loss (and
hence temperature/resistance) of the detecting element in the presence of the target
gas.
The earliest form of catalytic gas sensor used heated bare coils of platinum wire to
burn the gas. The heat generated by the burning process produced a change in the
resistance of the coil. This change was measured using a simple Wheatstone bridge
circuit. The low catalytic activity of the bare coil necessitated having to run the coils
at high temperatures (800 – 1000 °C) to be able to oxidise the target gas. At these
temperatures it was found that significant evaporation of the wire was taking place.
This produced a reduction in the wire diameter and a subsequent change in the
resistance. This produced a significant level of zero drift and a lifetime of as short as
several days.
The present day pellistor detectors consist of two matched platinum coils, each
embedded in a bead of alumina. The detecting element is coated with a catalyst which
promotes oxidation when in contact with flammable gases and the compensating
element is treated so that catalytic oxidation does not occur. The compensating
element is fitted to ensure that signals are not generated due to environmental effects
(eg changes in ambient temperature or gas flow rate).
Because pellistors are relatively high power devices, and as they operate at a
temperature that will ignite flammable gases they need to be sealed behind a flame
arrestor (sinter). Pellistors are typically fitted within stainless steel housing, mounted
on a Flameproof junction box.
• Correction factors can be applied so that the sensor can be scaled for a
particular substance.
• Pellistors are very simple devices; apart from calibration gas, no special
equipment is required for commissioning or maintenance.
Disadvantages of Pellistor Technology
• Pellistors must be operated behind a sinter (flame arrestor) which may become
blocked, thus preventing gas from reaching the sensor.
• Pellistors do not fail-safe; poisoned pellistors remain electrically operational;
thus the control system will continue to display zero gas when flammable gas
may be present.
• Pellistors require regular gas testing to ensure they are operational, and regular
calibration of offset signal loss due to poisoning or bead contamination.
Most gases absorb IR radiation at a characteristic wavelength and this behaviour is the
basis in IR type gas detection. When IR radiation transmitted is absorbed by a
particular gas, the strength of reflected IR radiation having wavelength corresponding
to the gas reduces at the receiving end. This difference in radiation intensity is
measured and processed for detecting the gas.
Infrared (IR) gas detectors overcome all of the limitations associated with pellistors to
provide fast and reliable detection of hydrocarbon gases. IR detectors provide rapid
gas detection and fail-safe operation.
Advantages of IR Technology
Disadvantages of IR Technology
a. Sensitivity
b. Reliability- the ability of the system and its components to be in proper
working condition at all times, so as to be ready to perform their intended
function.
c. Maintainability and
d. Stability - relates to its ability to sense fires over extended periods of time
with no change of sensitivity.
A practical detector must be robust, reliable and sensitive. It should also have long
life, should not give false alarms and should be easily tested and readily replaced.
Table shows the comparison of the performances of detectors
• Flame stage - Visible flame, more heat, often less or no smoke, particularly
with flammable liquids and gas fires.
• Heat stage - Large amounts of heat, flame, smoke and toxic gases are
produced. The transition from the previous stage can be very fast.
Fire detectors are designed to detect some characteristic effect of one or more of
these stages
Flame detector and optical type smoke detector are fast and can operate
without any time delay, but time delays are purposely inserted which may be 3
to 30 seconds. However, detection of fire is difficult in congested area or in
smoldering fires, as visibility of flame is needed to detect the fire.
Smoke detectors and gas fire detectors should not be provided in areas where
ambient temperature are likely to exceed 38 °C or fall below 0 °C, unless they are
specifically made for this purpose. Radioactive hazard/level should be less than
10 micro curies.
Fixed temperature type heat detectors will operate only when fourth stage of
fire has been reached (heat stage). They may take 1.5 to 1.75 minutes to operate
when fourth stage is reached and temperature changes at the rate of 20 °C/min.
Out of the fixed temperature type detectors, the slowest in operation may be
fusible alloy type and then bimetallic type.
Rate of rise type heat detector will respond quickly to fast heat rise ranging
from 6 to 12 °C/min when compared to fixed temperature type detectors.
Thermistor type have more faster response out of all the heat detectors.
Thermistor type and rate compensated type detectors can sense rate of rise
as slow as 3 °C/min.
Circulation of air near detectors affects their performance. Heat detectors are
not suitable for areas where ventilated air exist, as air circulation will constantly
remove the heat from the detection system. In such areas even the efficiency of
smoke detectors is dependent on amount of air change.
The effective area of smoke detectors based on the number of air changes
recommended by NFPA 72E-1978 is given in the table below