Point of ● Run CPU ● DI120-150

TCD 170 Running Direction Error Application


Detection ○ Speed CPU ● DI180-420

[Meaning] [Actions to take]


When there is a discrepancy between running commanded direction and
running direction detected by R/E at 8 m/min E/L speed for 520msec.

1. Check ØA, ØB phase of ENCODE and R, S, T phase of motor


[Diagram] by means of ENCODE-MOTOR CHECK MODE(A86E) of
ANN (Refer to Annunciator manual)
Prev_Enco_Old-Prev_Enco

Make_on_off_history(x11pl,on) 2.Check R/E ØA, ØB.


1) If detected during trial operation, try exchanging ØA, ØB
wiring with each other.
Make_on_off_history(x11pl,on) 2) ØA:40T1/22, ØB:40T1/20

Prev_Enco Old_Prev_Enco 3. Check MOTOR rotation.


1) When motor operates reversely at start-up,
(1) if motor operates reversely at trial operation, exchange U,
RUNNING C1ST (*Elevator_State==RUN)
V wiring of motor belt with each other
0x558F 0x501F 0x7600==0x0008 (2) If motor operates reversely after delivered to customer,
check or replace MAIN IGBT,DPP-XXX,DPC-1XX PCB
since the reversion is coming from the main circuit fault.
RUN_500MS
UP_RUN VX12PL CUR_V_8
TV4HT 2 When motor operates in the normal direction.
0x558D 0x572E 0x5703 0x36A1 0x3403
Replace DOC-200 PCB.
DOWN_RUN VX11PL

0x558E 0x572D

TV47T AIS_ENCO_MOTOR_CHECK
TCD170

0x3431 0x513A