Point of ● Run CPU ● DI120-150

TCD 200 CNET Communication Error(ERR_CNET_SYNC) Application


Detection ○ Speed CPU ● DI180-420

[Meaning] When DPRAM communication is not possible between CLN[C-NET LON] [Actions to take]
and 1960 for 3 or more consecutive cycles(240ms). 1. Check LED6[Green]-CNL in DOC-200 PCB for flickering status.
(Normally, flickers at 500ms interval)
2. Turn Off and On MAIN contactor.
[Diagram] 3. Replace DOC-U50(CNL) ROM in DOC-200 PCB.
4. Replace DOC-U22 EEPROM in DOC-200 PCB.
LonDpramCntl.sync_ok[CNET] +1 err_count 5. Replace DOC-U12,13 FLASH ROM in DOC-200 PCB.

0 err_count

err_count >= 4 TCD 200

C-NET
LON Reset

※Communication between 1960 and CNL[C-NET LON], a kind of data communication(DPRAM WRITE)
is made through DPRAM in a TOKEN exchanging way by the TOKEN possessed side. So if TOKEN
is missed by any side, DPRM communication becomes impossible.

[Symptoms]

• LED6[GREEN]-CNL in DOC-200 does not flicker at 500ms interval.


• LED-LD1 in DCL-240 on the side of CAR MAIN OPB does not flicker at 300ms interval.
• All output and input are impossible on the CAR MAIN OPB side.
• E/L will not operate.
• If LED6[GREEN]-CNL in DOC-200 flickers at 500ms interval and LED-LD1 in DCL-240
on the side of CAR MAIN OPB flickers at 300ms interval, the CAR LON communication
is normal.
Point of ● Run CPU ● DI120-150
TCD 201 GNET Communication Error( ERR_GNET_SYNC) Application
Detection ○ Speed CPU ● DI180-420

[Meaning] When DPRAM communication is not possible between GLN[C-NET LON] [Actions to take]
and 1960 for 3 or more consecutive cycles(240ms).
1. Check LED5[Green]-CNL in DOC-200 PCB for flickering status.
(Normally, flickers at 500ms interval)
[Diagram] 2. Turn Off and On MAIN contactor.
3. Replace DOC-U44(GNL) ROM in DOC-200 PCB.
LonDpramCntl.sync_ok[GNET] +1 err_count 4. Replace DOC-U22 EEPROM in DOC-200 PCB.
5. Replace DOC-U12,13 FLASH ROM in DOC-200 PCB.

0 err_count

err_count >= 4 TCD 201

G-NET
LON Reset

※Communication between 1960 and GNL[C-NET LON], a kind of data communication(DPRAM WRITE)
is made through DPRAM in a TOKEN exchanging way by the TOKEN possessed side. So if TOKEN
is missed by any side, DPRM communication becomes impossible.

[Symptoms]

• LED5[GREEN]-GNL in DOC-200 does not flicker at 500ms interval.


• LED-LD1 in DHL-2XX on the HALL side does not flicker at 300ms interval.
• All output reset and hall side input are impossible on the HALL side.
• E/L will not operate.
• If LED5[GREEN]-GNL in DOC-200 flickers at 500ms interval and LED-LD1
in DCL-240 on the side of HALL flickers at 300ms interval, the HALL LON
communication is normal.
Point of ● Run CPU ● DI120-150
TCD 202 Car Communication Error(ERR_CAGE) Application
Detection ○ Speed CPU ● DI180-420

[Meaning] [Actions to take]


Front Main OPB( OPB ID = 1 ) CAR LON Communication Error
1. Check the flickering status of LED6[GREEN]-CNL in
DOC-200 PCB. (Normal at 500ms interval)
2. Check the flickering status of LED-LD1in FRONT MAIN OPB
side DCL-240 PCB. (Normal at 300ms interval)
[Explanation]
3. Check the input voltage between No. 4 and 3 pin of
DCL-240 PCB CCN1 connector on the side of front MAIN OPB.
(DC22V)
*Cage_Node_Down & 0x01 4. Verify if connectors for C-NET LON communicator are
S
TCD 202 connected well.
0x7814 Measure the resistance between Pin 1 and Pin 2 of Y1
connector.(If the resistance value is beyond 10±4 Ohm,
check for disconnection)
5. Check the terminal resistance (DIP SW8) setting in the
OPB side DCL-240 PCB.
(Refer to terminal resistance setting criteria)
※ CNL(C-NET LON) sends the results of communication with CLON board in each OPB to 1960 through
DPRAM, and 1960 checks the CLON board responding status by referring OPB installation SPEC and 6. Verify if OPB ID is 1(DIP 1 ‘ON’).
stores them by bit. The variable is *Cage_Node_Down(0x7814). (Refer to OPB ID setting criteria)
OPB for each Bit is shown as below. The OPB is normal if the bit is ‘0’ and is abnormal if the bit
is ‘1’. 1 2 3 4 5 6 7 8

ON
*Cage_Node_Down(0x7814)

Bit 7 6 5 4 3 1 2 0

REAR REAR WHEEL WHEEL FRONT FRONT


OPB PDL SUB MAIN CHAIR CHAIR SUB MAIN 7. Verify if data in address 0x0018 is FFH on the SPEC READ
SUB MAIN MODE. If the data is 00H, correct the data into FFH on the
SPEC WRITE MODE.
[Symptoms] 8. Replace DOC-U50 ROM in DOC-200.
9. Replace DCL-U2 ROM in FRONT MAIN OPB side
DCL-240 PCB.
•LED-LD1 in DCL-240 on the MAIN OPB side does not flicker at 300ms interval.
• All output reset and input are impossible on the CAR MAIN OPB side.
• E/L will not operate.
Point of ● Run CPU ● DI120-150
TCD 203 SUB Run Operating Board Communication Error(ERR_SUB_OPB) ○ Speed CPU Application
Detection ● DI180-420

[Meaning] Front Sub OPB( OPB ID = 2 ) CAR LON Communication Error [Actions to take]
1. Check the flickering status of LED6[GREEN]-CNL in
DOC-200 PCB. (Normal at 500ms interval)
2. Check the flickering status of LED-LD1in FRONT SUB OPB
side DCL-240 PCB. (Normal at 300ms interval)
[Explanation]
3. Check the input voltage between No. 4 and 3 pin of
DCL-240 PCB CCN1 connector on the side of Front SUB OPB.
(DC22V)
*Cage_Node_Down & 0x02 4. Verify if connectors for C-NET LON communicator are
S
TCD 203 connected well.
0x7814 Measure the resistance between Pin 1 and Pin 2 of Y1
connector.(If the resistance value is beyond 10±4 Ohm,
check for disconnection)
5. Check the terminal resistance (DIP SW8) setting in the
OPB side DCL-240 PCB.
(Refer to terminal resistance setting criteria)
※ CNL(C-NET LON) sends the results of communication with CLON board in each OPB to 1960 through
DPRAM, and 1960 checks the CLON board responding status by referring OPB installation SPEC and 6. Verify if OPB ID is 2(DIP 2 ‘ON’).
stores them by bit. The variable is *Cage_Node_Down(0x7814). (Refer to OPB ID setting criteria)
OPB for each Bit is shown as below. The OPB is normal if the bit is ‘0’ and is abnormal if the bit
1 2 3 4 5 6 7 8
is ‘1’.
ON
*Cage_Node_Down(0x7814)

Bit 7 6 5 4 3 2 1 0

REAR REAR WHEEL WHEEL FRONT FRONT


OPB PDL SUB MAIN CHAIR CHAIR SUB MAIN 7. Verify if data in address 0x0019 is FFH on the SPEC READ
SUB MAIN MODE. If the data is 00H, correct the data into FFH on the
SPEC WRITE MODE.
[Symptoms] 8. Replace DOC-U50 ROM in DOC-200.
9. Replace DCL-U2 ROM in FRONT SUB OPB side
DCL-240 PCB.
•LED-LD1 in DCL-240 on the FRONT SUB OPB side does not flicker at 300ms interval.
• All output reset and input are impossible on the CAR FRONT SUB OPB side.
Operation Board for Disabled Person MAIN Run Communication Error Point of ● Run CPU ● DI120-150
TCD 204 Application
(ERR_WHEEL_MAIN) Detection ○ Speed CPU ● DI180-420

[Meaning] [Actions to take]


Wheel Chair Main OPB( OPB ID = 3 ) CAR LON Communication Error
1. Check the flickering status of LED6[GREEN]-CNL in
DOC-200 PCB. (Normal at 500ms interval)
2. Check the flickering status of LED-LD1in WHEEL CHAIR MAIN
OPB side DCL-240 PCB. (Normal at 300ms interval)
[Explanation]
3. Check the input voltage between No. 4 and 3 pin of
DCL-240 PCB CCN1 connector on the side of WHEEL CHAIR
MAIN OPB. (DC22V)
*Cage_Node_Down & 0x04 4. Verify if connectors for C-NET LON communicator are
S
TCD 204 connected well.
0x7814 Measure the resistance between Pin 1 and Pin 2 of Y1
connector.(If the resistance value is beyond 10±4 Ohm,
check for disconnection)
5. Check the terminal resistance (DIP SW8) setting in the
OPB side DCL-240 PCB.
(Refer to terminal resistance setting criteria)
※ CNL(C-NET LON) sends the results of communication with CLON board in each OPB to 1960 through
DPRAM, and 1960 checks the CLON board responding status by referring OPB installation SPEC and 6. Verify if OPB ID is 3(DIP 3 ‘ON’).
stores them by bit. The variable is *Cage_Node_Down(0x7814). (Refer to OPB ID setting criteria)
OPB for each Bit is shown as below. The OPB is normal if the bit is ‘0’ and is abnormal if the bit
is ‘1’. 1 2 3 4 5 6 7 8

ON
*Cage_Node_Down(0x7814)

Bit 7 6 5 4 3 2 1 0

REAR REAR WHEEL WHEEL FRONT FRONT


OPB PDL SUB MAIN CHAIR CHAIR SUB MAIN 7. Verify if data in address 0x001A is FFH on the SPEC READ
SUB MAIN MODE. If the data is 00H, correct the data into FFH on the
SPEC WRITE MODE.
[Symptoms] 8. Replace DOC-U50 ROM in DOC-200.
9. Replace DCL-U2 ROM in WHEEL CHAIR MAIN OPB side
DCL-240 PCB.
•LED-LD1 in DCL-240 on the WHEEL CHAIR MAIN OPB side does not flicker
at 300ms interval.
• All output reset and input are impossible on the CAR WHEEL CHAIR MAIN OPB side.
Operating Board for Disabled Person SUB Run Communication Error Point of ● Run CPU ● DI120-150
TCD 205 Application
(ERR_WHEEL_SUB) Detection ○ Speed CPU ● DI180-420

[Meaning] Wheel Chair Sub OPB( OPB ID = 4 ) CAR LON Communication Error [Actions to take]
1. Check the flickering status of LED6[GREEN]-CNL in
DOC-200 PCB. (Normal at 500ms interval)
2. Check the flickering status of LED-LD1in WHEEL CHAIR SUB
OPB side DCL-240 PCB. (Normal at 300ms interval)
[Explanation]
3. Check the input voltage between No. 4 and 3 pin of
DCL-240 PCB CCN1 connector on the side of WHEEL CHAIR
SUB OPB. (DC22V)
*Cage_Node_Down & 0x08 4. Verify if connectors for C-NET LON communicator are
S
TCD 205 connected well.
0x7814 Measure the resistance between Pin 1 and Pin 2 of Y1
connector.(If the resistance value is beyond 10±4 Ohm,
check for disconnection)
5. Check the terminal resistance (DIP SW8) setting in the
OPB side DCL-240 PCB.
(Refer to terminal resistance setting criteria)
※ CNL(C-NET LON) sends the results of communication with CLON board in each OPB to 1960 through
DPRAM, and 1960 checks the CLON board responding status by referring OPB installation SPEC and 6. Verify if OPB ID is 4(DIP 4 ‘ON’).
stores them by bit. The variable is *Cage_Node_Down(0x7814). (Refer to OPB ID setting criteria)
OPB for each Bit is shown as below. The OPB is normal if the bit is ‘0’ and is abnormal if the bit
is ‘1’. 1 2 3 4 5 6 7 8

ON
*Cage_Node_Down(0x7814)

Bit 7 6 5 4 3 2 1 0

REAR REAR WHEEL WHEEL FRONT FRONT


OPB PDL SUB MAIN CHAIR CHAIR SUB MAIN 7. Verify if data in address 0x001B is FFH on the SPEC READ
SUB MAIN MODE. If the data is 00H, correct the data into FFH on the
SPEC WRITE MODE.
8. Replace DOC-U50 ROM in DOC-200.
[Symptoms]
9. Replace DCL-U2 ROM in WHEEL CHAIR SUB OPB side
DCL-240 PCB.
•LED-LD1 in DCL-240 on the WHEEL CHAIR SUB OPB side does not flicker
at 300ms interval.
• All output reset and input are impossible on the CAR WHEEL CHAIR SUB OPB side.
Point of ● Run CPU ● DI120-150
TCD 206 Operating Board for Back-side MAIN Run Communication Error Application
(ERR_REAR_MAIN) Detection ○ Speed CPU ● DI180-420

[Meaning] [Actions to take]


Rear Main OPB( OPB ID = 5 ) CAR LON Communication Error
1. Check the flickering status of LED6[GREEN]-CNL in
DOC-200 PCB. (Normal at 500ms interval)
2. Check the flickering status of LED-LD1in REAR MAIN OPB
side DCL-240 PCB. (Normal at 300ms interval)
[Explanation]
3. Check the input voltage between No. 4 and 3 pin of
DCL-240 PCB CCN1 connector on the side of REAR MAIN
OPB. (DC22V)
*Cage_Node_Down & 0x10 4. Verify if connectors for C-NET LON communicator are
S
TCD 206 connected well.
0x7814 Measure the resistance between Pin 1 and Pin 2 of Y1
connector.(If the resistance value is beyond 10±4 Ohm,
check for disconnection)
5. Check the terminal resistance (DIP SW8) setting in the
OPB side DCL-240 PCB.
(Refer to terminal resistance setting criteria)
※ CNL(C-NET LON) sends the results of communication with CLON board in each OPB to 1960 through
DPRAM, and 1960 checks the CLON board responding status by referring OPB installation SPEC and 6. Verify if OPB ID is 5(DIP 1,3 ‘ON’).
stores themby bit. The variable is *Cage_Node_Down(0x7814). (Refer to OPB ID setting criteria)
OPB for each Bit is shown as below. The OPB is normal if the bit is ‘0’ and is abnormal if the bit
is ‘1’. 1 2 3 4 5 6 7 8

ON
*Cage_Node_Down(0x7814)

Bit 7 6 5 4 3 2 1 0

REAR REAR WHEEL WHEEL FRONT FRONT


OPB PDL SUB MAIN CHAIR CHAIR SUB MAIN 7. Verify if data in address 0x001A is FFH on the SPEC READ
SUB MAIN MODE. If the data is 00H, correct the data into FFH on the
SPEC WRITE MODE.
8. Replace DOC-U50 ROM in DOC-200.
[Symptoms]
9. Replace DCL-U2 ROM in REAR MAIN OPB side
•LED-LD1 in DCL-240 on the REAR MAIN OPB side does not flicker at 300ms interval. DCL-240 PCB.
• All output reset and input are impossible on the CAR REAR MAIN SUB OPB side.
Point of ● Run CPU ● DI120-150
TCD 207 Operating Board for Back-side SUB Run Communication Error Application
( ERR_REAR_SUB) Detection ○ Speed CPU ● DI180-420

[Meaning] Rear Sub OPB( OPB ID = 6 ) CAR LON Communication Error [Actions to take]
1. Check the flickering status of LED6[GREEN]-CNL in
DOC-200 PCB. (Normal at 500ms interval)
2. Check the flickering status of LED-LD1in REAR SUB OPB
side DCL-240 PCB. (Normal at 300ms interval)
[Explanation]
3. Check the input voltage between No. 4 and 3 pin of
DCL-240 PCB CCN1 connector on the side of REAR SUB
OPB. (DC22V)
*Cage_Node_Down & 0x20 4. Verify if connectors for C-NET LON communicator are
S
TCD 207 connected well.
0x7814 Measure the resistance between Pin 1 and Pin 2 of Y1
connector.(If the resistance value is beyond 10±4 Ohm,
check for disconnection)
5. Check the terminal resistance (DIP SW8) setting in the
OPB side DCL-240 PCB.
(Refer to terminal resistance setting criteria)
※ CNL(C-NET LON) sends the results of communication with CLON board in each OPB to 1960 through
DPRAM, and 1960 checks the CLON board responding status by referring OPB installation SPEC and 6. Verify if OPB ID is 6(DIP 2,3 ‘ON’).
stores them by bit. The variable is *Cage_Node_Down(0x7814). (Refer to OPB ID setting criteria)
OPB for each Bit is as shown below. The OPB is normal if the bit is ‘0’ and is abnormal if the bit
is ‘1’. 1 2 3 4 5 6 7 8

ON
*Cage_Node_Down(0x7814)

Bit 7 6 5 4 3 2 1 0

REAR REAR WHEEL WHEEL FRONT FRONT


OPB PDL SUB MAIN CHAIR CHAIR SUB MAIN 7. Verify if data in address 0x001A is FFH on the SPEC READ
SUB MAIN MODE. If the data is 00H, correct the data into FFH on the
SPEC WRITE MODE.
[Symptoms] 8. Replace DOC-U50 ROM in DOC-200.
9. Replace DCL-U2 ROM in REAR SUB OPB side
•LED-LD1 in DCL-240 on the REAR SUB OPB side does not flicker at 300ms interval. DCL-240 PCB.
• All output reset and input are impossible on the CAR REAR SUB OPB side.
Point of ● Run CPU ● DI120-150
TCD 223 One or More HLON Fault (ERR_1_HALL) Application
Detection ○ Speed CPU ● DI180-420

[Meaning] When at least one HLON board communication is failed. [Actions to take]
1. Check errors for the SIDE, calling bell, and floor HLON board
communication by means of ANN - A21E(Back-up Ram
Referring Mode).
※ Example
[Explanation]
Enter the followings on ANN board.
Group_Net_Err_Status->Hall_Node[fl_side][I][fl_zon] K: A21E
TCD 223
ADDR:DAT K : 1040E
0x1040 If 1040=x02(0000 0010),
SIDE1,K-type calling, absolute floor 2nd floor HLON board
※ CNL(C-NET LON) sends the results of communication with HLON on each HALL side to 1960 through fault.
DPRAM, and 1960 checks the HLON board responding status by referring OPB installation SPEC and If 1040=x30(0011 0000),
stores them by bit. The variable is Group_Net_Err_Status->Node[fl_side][I][fl_zon] (0x1040). SIDE1,K-type calling, absolute floor 5,6th floor button
HALL HLON board for each Bit is as shown below. The OPB is normal if the bit is ‘0’ and the OPB is
board fault.
abnormal if the bit is ‘1’.
To see 8th or higher floor, enter KEY-PAD ‘0’(INC) on the
Group_Net_Err_Status->Node[fl_side][I][fl_zon] ANN board.
Side Side1 Side2 2. Check the failed floor for DHL-2XX board LED-LD1 flickering
부름종 Floor Address Floor Address status.(Normally, at 300ms interval)
57~64 Floor 0x105F 57~64 Floor 0x107F 3. Verify that connectors for G-NET LON are connected well.
N종 ∫ ∫ ∫ ∫ 4. Check the voltage between No. 4 and 3 pin of DHL-2XX board
1~8 Floor 0x1058 1~8 Floor 0x1078 HA plug of the failed floor. (DC22V)
57~64 Floor 0x1057 57~64 Floor 0x1077 5. Check the terminal resistance(DIP SW1 No.4) setting of
M종 ∫ ∫ ∫ ∫ DHL-2XX board on the failed side.
1~8 Floor 0x1050 1~8 Floor 0x1070 (Refer to terminal resistance setting criteria)
57~64 Floor 0x104F 57~64 Floor 0x106F 6. Check the DHL-2XX board side, calling bell, and floor ID of the failed
L종 ∫ ∫ ∫ ∫ floor. (Refer to HALL ID setting criteria)
1~8 Floor 0x1048 1~8 Floor 0x1068 7. Measure the resistance between No. 1 and 2 pin of DHL-2XX
57~64 Floor 0x1047 57~64 Floor 0x1067 board HA connector of the failed floor. If the resistance value
K종 ∫ ∫ ∫ ∫ is beyond 6 ±0.5 Ohm, pulse transformer(PST) is judged to
1~8 Floor 0x1040 1~8 Floor 0x1060 be bad.
8. Replace DOC-U50 ROM of DOC-200.
9. Replace DHL-U2 ROM in DHL-2XX of the failed floor.
[Symptoms]

•LED-LD1 in DHL-2XX board on the side of the HALL does not flicker at 300ms interval.
• All output reset, input, or output control is impossible on the side of the HALL.
Date Prepared : 98/02/18
Revision No. : 0

Point of ● Run CPU ● DI120-150


TCD 224 Entire HLON Fault (ERR_ALL_HALL) Application
Detection ○ Speed CPU ● DI180-420

[Meaning] When entire HLON board communication is failed in HALL. [Actions to take]

1. Check for connection status of communication line from MD


connector of DOC-200 board to DHL-2XX HA connector
of each HALL.
[Explanation] 2. Separate HAP and HAP1 MIC and check the voltage of
DC22V HLON power.
• 8FL or Less Building: HA P 2-1
• 16FL or Less Building: HA P 4-3
• 24FL or Less Building : HA P 6-5
All_Hall_Button_Dead TCD 224 • 32FL or Less Building : HA P 8-7
• 40FL or Less Building : HA P1 2-1
• 48FL or Less Building : HA P1 4-3
• 56FL or Less Building : HA P1 6-5
• 62FL or Less Building : HA P1 8-7
3. Check the terminal resistance(DIP SW1 No.4) of HLON board.
(Refer to terminal resistance setting criteria)
4. Replace DOC-U50 ROM of DOC-200.

[Symptoms]

•LED-LD1 in DHL-2XX board on the side of every HALL does not flicker at 300ms interval.
• All output reset, input, or output control is impossible on the side of every HALL.