Other E/L Fault
Other E/L Fault
[Actions to take]
[Meaning] Other E/L is failed.
An error is detected when ALIVE signal is not received from an E/L included in Check the value of variable(Balive_Member) ADDRESS
NPLEX(group for a certain period. 0x81D with ANNOUNCIATOR.
Here, an E/L whose bit is not set is judged to be a failed E/L.
All E/Ls in NPLEX group can diagnose the other E/Ls for faults by exchanging
ALIVE signal one another which are predetermined.
For example,
If ALIVE signal is not received regularly from a E/L, that E/L is judged to be failed. If 2 E/L is failed among 3 ones,
ADDR 0x81D2 value is 0x05.
But, an E/L that has never run does not affect failure detection though it belongs to If 2 and 3 E/Ls are failed among 3 ones,
NPLEX group. the value is 0x01.
[Symptoms] If there’s no error found in all E/Ls and all E/Ls are masters,
the error may be from communication line disconnection.
An E/L failed is excepted from allocation.
Note) Master E/L check
If there’s no failed E/L found, bad signal output may occur
Check variable(I_am)ADDRESS 0x8000
on account of bad communication.
with ANNOUNCIATOR.
1) Only some E/Ls do hall call service, or
2) Master/slave selection is repeated, or
0xff : Master E/L
3) One or more E/L do back-up operation.
0x00: Slave E/L
0xf0: Master/Slave
Point of ● Run CPU ● DI120~150
TCD 212 RELAY MASTER FAULT Application
Detection ○ Speed CPU ● DI180~420
[Actions to take]
[Meaning] When there is an error in LON in charge of GNET of communication
board(DOL-200).
1. Verify that GNET terminal resistance of DIP SW8-1 is set
well in DOC-200 PCB.
NO.1 C.P
COMM-01 40T1-37 JOB SITE WIRING
40T2-37
COMM-02 40T1-38 40T2-38
MA
MA
MD-01
MD-01
ME-02
ME-01
MD-02
MD-02
ME-02
MD-01
MD-02
ME-01
40T2-37
40T2-38
TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2
* When communication PACKET DATA is not received from group control board or
GIS_COMMON_POWER (ADDR:0x50EF) is not set in communication PACKET
DATA.
Point of ● Run CPU ● DI120-150
TCD 213 RELAY SLAVE FAULT Application
Detection ○ Speed CPU ● DI180-420
[Actions to take]
[Meaning] LON in charge of HNET in communication board( DOL-200) is failed.
Check the communication board and take actions as stated below.
[Actions to take]
[Meaning] Hall button jam occurs
Check the floor indicated on the hall button where the button jam
occurs, direction call chime/kong, etc. and maintain hall buttons.
[Explanation]
[Symptoms]
[Actions to take]
[Meaning] Two or more masters occur in NPLEX connected to communication line.
The error is designed to be removed automatically. If it is
repeatedly detected, power OFF one of the two E/L and power
ON after 30sec.
[Explanation]
Check communication line.
When two or more master E/Ls occur to be selected at the same
time.
[Symptoms]
[Actions to take]
[Meaning] When two or more masters repeat in NPLEX connected with communication
line.
Check communication line.
[Explanation]
[Symptoms]
[Meaning] When at least one HLON board communication is failed. [Actions to take]
1. Check errors for the SIDE, calling chime, and floor HLON
board communication by means of ANN - A21E(Back-up
Ram Referring Mode).
[Explanation] ※ Example
Enter the followings on ANN board.
Group_Net_Err_Status->Node[fl_side][call_type][fl_zone] TCD 214 K: A21E
ADDR:DAT K : 1040E
0x1040
If 1040=x02(0000 0010),
SIDE1,K-type calling, absolute floor 2nd floor HLON
※ CNL(C-NET LON) sends the results of communication with HLON on each HALL side to 1960 through board fault.
DPRAM, and 1960 checks the HLON board responding status by referring HALL installation SPEC and
If 1040=x30(0011 0000),
stores them by bit. The variable is Group_Net_Err_Status->Node[fl_side][I][fl_zon] (0x1040).
HALL HLON board for each corresponding Bit is as shown below. The HLON is normal if the bit is ‘0’ and SIDE1,K-type calling, absolute floor 5,6th floor button
the HLON is abnormal if the bit is ‘1’. board fault.
Group_Net_Err_Status->Node[fl_side][call_type][fl_zone]
To see 8th or higher floor, enter KEY-PAD ‘0’(INC) on the
ANN board.
Side Side1 Side2 2. Check the failed floor for DHL-2XX board LED-LD1 flickering
Calling Floor Address Floor Address status.
57~64 Floor 0x1060 57~64 Floor 0x1080 (Normally, at 300ms interval)
N
type ∫ ∫ ∫ ∫ 3. Verify that connectors for G-NET LON are connected well.
1~8 Floor 0x1059 1~8 Floor 0x1079 4. Check the voltage between No. 4 and 3 pin plug of DHL-2XX
57~64 Floor 0x1058 57~64 Floor 0x1078 board HA of the failed floor. (DC22V)
M
type ∫ ∫ ∫ ∫ 5. Check the terminal resistance(DIP SW No.14) setting of
1~8 Floor 0x1051 1~8 Floor 0x1071 DHL-2XX board on the failed side.
57~64 Floor 0x1050 57~64 Floor 0x1070 (Refer to terminal resistance setting criteria)
L
∫ ∫ ∫ ∫ 6. Check the DHL-2XX board side, calling chime, and floor ID of the
type
1~8 Floor 0x1049 1~8 Floor 0x1069 failed floor. (Refer to HALL ID setting criteria)
57~64 Floor 0x1048 57~64 Floor 0x1068 7. Measure the resistance between No. 1 and 2 pin of DHL-2XX
K
type ∫ ∫ ∫ ∫ board HA connector of the failed floor. If the resistance value
1~8 Floor 0x1040 1~8 Floor 0x1061 is beyond 6 ±0.5 Ohm, pulse transformer(PST) is judged to
be bad.
8. Replace DOC-U50 ROM of DOC-200.
[Symptoms]
9. Replace DHL-U2 ROM in DHL-2XX of the failed floor.
•LED-LD1 in DHL-2XX board on the side of the HALL does not flicker at 300ms interval.
• All output reset, input, or output control is impossible on the side of the HALL.
Point of ● Run CPU ● DI120-240
TCD 215 HLON FAULT (Entire) Application
Detection ○ Speed CPU ● DI180-420
[Explanation] 2. Separate HAP and HAP1 MIC and check DC22V HLON power.
• 8FL or below height : HA P 2-1
All_Hall_Button_Dead TCD 215 • 16FL or below height : HA P 4-3
• 24FL or below height : HA P 6-5
• 32FL or below height : HA P 8-7
• 40FL or below height : HA P1 2-1
• 48FL or below height : HA P1 4-3
• 56FL or below height : HA P1 6-5
• 62FL or below height : HA P1 8-7
[Symptoms]
•LED-LD1 in DHL-2XX board on the side of every HALL does not flicker at 300ms interval.
• All output reset, input, or output control is impossible on the side of every HALL.
Point of ● Run CPU ● DI120-150
TCD 216 HALL SIDE ERROR Application
Detection ○ Speed CPU ● DI180-420
[Symptoms]