Point of ● Run CPU ● DI120-150

TCD 211 Other E/L Fault Application


Detection ○ Speed CPU ● DI180-420

[Actions to take]
[Meaning] Other E/L is failed.

1. Check the failed E/L

[Explanation] See if there are any failed E/Ls in the group.

An error is detected when ALIVE signal is not received from an E/L included in Check the value of variable(Balive_Member) ADDRESS
NPLEX(group for a certain period. 0x81D with ANNOUNCIATOR.
Here, an E/L whose bit is not set is judged to be a failed E/L.
All E/Ls in NPLEX group can diagnose the other E/Ls for faults by exchanging
ALIVE signal one another which are predetermined.
For example,
If ALIVE signal is not received regularly from a E/L, that E/L is judged to be failed. If 2 E/L is failed among 3 ones,
ADDR 0x81D2 value is 0x05.
But, an E/L that has never run does not affect failure detection though it belongs to If 2 and 3 E/Ls are failed among 3 ones,
NPLEX group. the value is 0x01.

2. If there’s no E/L failed,


verify that the communication line is well connected.

[Symptoms] If there’s no error found in all E/Ls and all E/Ls are masters,
the error may be from communication line disconnection.
An E/L failed is excepted from allocation.
Note) Master E/L check
If there’s no failed E/L found, bad signal output may occur
Check variable(I_am)ADDRESS 0x8000
on account of bad communication.
with ANNOUNCIATOR.
1) Only some E/Ls do hall call service, or
2) Master/slave selection is repeated, or
0xff : Master E/L
3) One or more E/L do back-up operation.
0x00: Slave E/L
0xf0: Master/Slave
Point of ● Run CPU ● DI120~150
TCD 212 RELAY MASTER FAULT Application
Detection ○ Speed CPU ● DI180~420

[Actions to take]
[Meaning] When there is an error in LON in charge of GNET of communication
board(DOL-200).
1. Verify that GNET terminal resistance of DIP SW8-1 is set
well in DOC-200 PCB.

[Explanation] 2. Verify that group control board and communication board


<< S/W SKELETON >> (DOL-200) are normal.
(Refer to group control related manuals.)
GIS_COMMON_POWER S
TCD 212 3. Referring connection diagram(3X03743 CTLC.[2]) of
0x50EF
communication line of communication board(DOL-200) at the,
group control board and control board, check the circuit
wiring system such as MIC connection failure, etc..
Especially, focus on power connection and communication line
connection status.
<< H/W SKELETON >>

NO.1 C.P
COMM-01 40T1-37 JOB SITE WIRING
40T2-37
COMM-02 40T1-38 40T2-38

DOR-200 DOA-100 DOR-200 DOA-100


MA

MA

CN2 CN2 40T1


MC-01 MC-01 COMM-06 -39
TO SVP
NO.2 C.P
MC-02 COMM-07
40T1 40T2-37
MC-02 -40
ANN ANN 40T2-38
MA

MA

TRX1 TRX2 TRX1 TRX2


DOC-200 DOC-200
(MPU1) (MPU2)
TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2

MD-01
MD-01

ME-02
ME-01
MD-02

MD-02
ME-02

MD-01

MD-02

ME-01

TRX1 TRX2 NO.8 C.P


DOL-200

40T2-37
40T2-38

TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2 TRX1 TRX2

Drawing No. : 3X03743 CTL C.[2]

* When communication PACKET DATA is not received from group control board or
GIS_COMMON_POWER (ADDR:0x50EF) is not set in communication PACKET
DATA.
Point of ● Run CPU ● DI120-150
TCD 213 RELAY SLAVE FAULT Application
Detection ○ Speed CPU ● DI180-420

[Actions to take]
[Meaning] LON in charge of HNET in communication board( DOL-200) is failed.
Check the communication board and take actions as stated below.

1. With an announciator, check the position of the hall master


[Explanation] where the error is detected
When an error occurs in LON in charge of HALL NET of communication board
For example, check
(relay board) belonging to NPLEX or communication line contact is bad.
Column 1 LON status: LED3 Column 1 COM Status: LED12
That is, an error occurs in communication between on HALL NET line and
Column 2 LON status: LED4 Column 2 COM status: LED13
communication board.

A kind of Bit Set 2. Check LON status LED

If the LED does not flicker, communication board HNET LON


Variable ADDR Meaning is failed or the slot(Each column LON module) is badly inserted.
ErrHallMaster 0x82A7 Column 1~8 Hall Master Fault Replace the slot of the column on communication board.
0x82A8 Column 9~16 Hall Master Fault
0x82A9 Column 17~24 Hall Master Fault 3. Check communication status LED.

If LON status LED flickers but communication LED does not


[Symptom]
flicker, check the communication line.
All indicators of certain hall columns turn OFF and hall button stops.
4. As per above “3”, if the communication line is normal, replace
the board (LON module slot).

5. If all LEDs operate normally, check the communication line


between relay board and E/L control board.
Point of ● Run CPU ● DI120-150
TCD 217 Hall Button Jam Detection Application
Detection ○ Speed CPU ● DI180-420

[Actions to take]
[Meaning] Hall button jam occurs
Check the floor indicated on the hall button where the button jam
occurs, direction call chime/kong, etc. and maintain hall buttons.
[Explanation]

When a hall button is kept in jammed for 3 minutes or more.

UP Direction Button Jam Floor DOWN Direction Button Jam

Variable: ButtonJamUpFloor Variable: ButtonJamDnFloor


Bit Set Pattern Bit Set Pattern

ADDR : 0x8050 1~8 Fl ADDR : 0x8060 1~ 8 Fl


0x8051 9~16 Fl 0x8061 9~16 Fl
0x8052 17~24 Fl 0x8062 17~24 Fl
0x8053 25~32 Fl 0x8063 25~32 Fl
| | | |
0x805F ~ 128 Fl 0x806F ~ 128 Fl

[Symptoms]

Hall button where button jam occurs is restrained from input.


Point of ● Run CPU ● DI120-150
TCD 218 Master Selection Error Application
Detection ○ Speed CPU ● DI180-420

[Actions to take]
[Meaning] Two or more masters occur in NPLEX connected to communication line.
The error is designed to be removed automatically. If it is
repeatedly detected, power OFF one of the two E/L and power
ON after 30sec.
[Explanation]
Check communication line.
When two or more master E/Ls occur to be selected at the same
time.

[Symptoms]

When an error occurs in NPLEX control because of two master.


Point of ● Run CPU ● DI120-150
TCD 219 Master Selection Error Repetition Application
Detection ○ Speed CPU ● DI180-420

[Actions to take]
[Meaning] When two or more masters repeat in NPLEX connected with communication
line.
Check communication line.

[Explanation]

When two or more master E/L occur repeatedly.

[Symptoms]

No allocation control done


Point of ● Run CPU ● DI120-240
TCD 214 HLON Fault (One or More ) Application
Detection ○ Speed CPU ● DI180-420

[Meaning] When at least one HLON board communication is failed. [Actions to take]

1. Check errors for the SIDE, calling chime, and floor HLON
board communication by means of ANN - A21E(Back-up
Ram Referring Mode).
[Explanation] ※ Example
Enter the followings on ANN board.
Group_Net_Err_Status->Node[fl_side][call_type][fl_zone] TCD 214 K: A21E
ADDR:DAT K : 1040E
0x1040
If 1040=x02(0000 0010),
SIDE1,K-type calling, absolute floor 2nd floor HLON
※ CNL(C-NET LON) sends the results of communication with HLON on each HALL side to 1960 through board fault.
DPRAM, and 1960 checks the HLON board responding status by referring HALL installation SPEC and
If 1040=x30(0011 0000),
stores them by bit. The variable is Group_Net_Err_Status->Node[fl_side][I][fl_zon] (0x1040).
HALL HLON board for each corresponding Bit is as shown below. The HLON is normal if the bit is ‘0’ and SIDE1,K-type calling, absolute floor 5,6th floor button
the HLON is abnormal if the bit is ‘1’. board fault.
Group_Net_Err_Status->Node[fl_side][call_type][fl_zone]
To see 8th or higher floor, enter KEY-PAD ‘0’(INC) on the
ANN board.
Side Side1 Side2 2. Check the failed floor for DHL-2XX board LED-LD1 flickering
Calling Floor Address Floor Address status.
57~64 Floor 0x1060 57~64 Floor 0x1080 (Normally, at 300ms interval)
N
type ∫ ∫ ∫ ∫ 3. Verify that connectors for G-NET LON are connected well.
1~8 Floor 0x1059 1~8 Floor 0x1079 4. Check the voltage between No. 4 and 3 pin plug of DHL-2XX
57~64 Floor 0x1058 57~64 Floor 0x1078 board HA of the failed floor. (DC22V)
M
type ∫ ∫ ∫ ∫ 5. Check the terminal resistance(DIP SW No.14) setting of
1~8 Floor 0x1051 1~8 Floor 0x1071 DHL-2XX board on the failed side.
57~64 Floor 0x1050 57~64 Floor 0x1070 (Refer to terminal resistance setting criteria)
L
∫ ∫ ∫ ∫ 6. Check the DHL-2XX board side, calling chime, and floor ID of the
type
1~8 Floor 0x1049 1~8 Floor 0x1069 failed floor. (Refer to HALL ID setting criteria)
57~64 Floor 0x1048 57~64 Floor 0x1068 7. Measure the resistance between No. 1 and 2 pin of DHL-2XX
K
type ∫ ∫ ∫ ∫ board HA connector of the failed floor. If the resistance value
1~8 Floor 0x1040 1~8 Floor 0x1061 is beyond 6 ±0.5 Ohm, pulse transformer(PST) is judged to
be bad.
8. Replace DOC-U50 ROM of DOC-200.
[Symptoms]
9. Replace DHL-U2 ROM in DHL-2XX of the failed floor.

•LED-LD1 in DHL-2XX board on the side of the HALL does not flicker at 300ms interval.
• All output reset, input, or output control is impossible on the side of the HALL.
Point of ● Run CPU ● DI120-240
TCD 215 HLON FAULT (Entire) Application
Detection ○ Speed CPU ● DI180-420

[Meaning] Entire hall HLON board communication error [Actions to take]

1. Verify that a communication line is linked between DOC-200


board MD connector to DHL-2XX HA connector in each hall.

[Explanation] 2. Separate HAP and HAP1 MIC and check DC22V HLON power.
• 8FL or below height : HA P 2-1
All_Hall_Button_Dead TCD 215 • 16FL or below height : HA P 4-3
• 24FL or below height : HA P 6-5
• 32FL or below height : HA P 8-7
• 40FL or below height : HA P1 2-1
• 48FL or below height : HA P1 4-3
• 56FL or below height : HA P1 6-5
• 62FL or below height : HA P1 8-7

3. Check the terminal resistance(DIP SW No.14) of HLON


terminal board. (Refer to terminal resistance setting criteria)

4. Replace DOC-U50 ROM of DOC-200.

[Symptoms]

•LED-LD1 in DHL-2XX board on the side of every HALL does not flicker at 300ms interval.
• All output reset, input, or output control is impossible on the side of every HALL.
Point of ● Run CPU ● DI120-150
TCD 216 HALL SIDE ERROR Application
Detection ○ Speed CPU ● DI180-420

[Meaning] [Actions to take]

Entire hall side error

1. Check the hall button power.


[Explanation]
2. Check communication line.
When all hall buttons in the specified hall side are failed, an error is detected and the
failed hall side is set with bit. 3. Check communication board.
Check the flickering status along with each hall button column.
If not flickering, check the slot insertion status of LON module
of each column. If LED 3~9 is flickering but LED11~LED17
Variable ADDR Meaning connected to LED 3~9 respectively are not flickering, check
Hall Line Dead 0x8740 1 ~ 8 Line fault communication line.
0x8741 9 ~16 Line fault
0x8742 17~24 Line fault If both of LED pair(e.x. Line 1 is composed of LED3 and
LED11) are not flickering but slots are well inserted, replace the
slots.

4. Check hall board.

[Symptoms]

The hall call registering of specified area is impossible.