TCD 237

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Point of ● Run CPU ● DI120~150

TCD 237 CRT Communication Error Application


Detection ○ Speed CPU ● DI180~420

[Meaning] When an error occurs in communication with CRT monitoring board. [Actions to take]

1.Verify if G/A ID is correctly set to DIP SW(SW6)


in DOC-200 PCB.
[Diagram]
2.Verify if terminal resistance is correctly set to
DIP SW(SW2) in DOC-200 PCB.

3.Check wirings such as MIC contact error, etc..


Especially, check the power connection and
communication line connection status chiefly.
< Related H/W SKELETON >