STUD WALL DESIGN (TYPICAL)

LABEL Brg. Wall (Typ.) LOADING


HEIGHT 9 ft DL LL TRIB W
DEFLECTION L/ 240 ROOF 16 20 16 576
WIND INTERIOR ZONE 17.0 psf FLOOR 16 40 0 0
WIND END ZONE 19.0 psf WALL 17 0 9 153
EARTHQUAKE PRESSURE 5 psf OTHERS 20 0 0
LL ON ROOF SNOW? N W= 729 plf
LUMBER TYPE 2 ( DF No. 2 )

LOAD CASES
D + L + Lr D + L + Wint + Lr D + L + Wend + Lr D + L + EQ + Lr
Cd = 1.25 1.60 1.60 1.60
FcE (psi) = 565 565 565 565
F'c (psi) = 526 536 536 536
fc (psi) = 185 OK 185 OK 185 OK 185 OK
M (lb-ft) = 0 205 229 60
Fb' (psi) = 1941 2484 2484 2484
fb (psi) = 0 OK 802 OK 896 OK 236 OK
CSR = 0.12 OK 0.60 OK 0.66 OK 0.26 OK
Dmax (in.) = 0.425 0.425 0.425 0.425
D (in.) = 0.000 OK 0.217 OK 0.243 OK 0.091 OK

TRIMMER: KING STUD Wind Interior Zone:


Trimmer supports only vertical load ... King stud supports only bending ...
Pcap (lbs) = 2762 Mcap (lb-ft) = 634
trib width capacity (ft) = 4.13 for M < Mcap
trib width capacity (ft) = 2.61 for D < L / 240

KING STUD Wind End Zone: KING STUD Earth Quake:


King stud supports only bending ... King stud supports only bending ...
Mcap(lb-ft) = 634 Mcap (lb-ft) = 634
cap (ft) = 3.69 for M < Mcap trib width capacity (ft) = 14.04 for M < Mcap
cap (ft) = 2.33 for D < L / 240 trib width capacity (ft) = 6.21 for D < L / 240

INTERIOR ZONE USE: 2 X 4 @ 16 " O.C.


END ZONE USE: 2 X 4 @ 16 " O.C.

DHLA/NRG Revised 04-01-09