Edg Check List (061-Edg-1001a)

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 20

DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 4/10/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 10.05 WITA

2 Stop Time 10.35 WITA

3 Engine Speed < 1725 RPM 1580

4 Load % 49.93

5 Lube Oil Pressure > 3.5 Bar 5.94

6 Lube Oil Temperature < 97 0


C 78.7

7 Bearing DE Temp. (PT7) < 85 0


C 60.6

8 Bearing NDE Temp. (PT8) < 85 0


C 44.4

9 Fuel Oil Pressure - Bar 8.12

10 Fuel Oil Temperature - C 53.2

11 Fuel Oil Filter dP 1 Bar -

12 Jacket Water Temperature < 102 0


C 82.4

13 Inter cooler water Temp < 75 0


C 44.8

0.94*fnormal <
14 Frequency fmeasured < Hz 49.9
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 80

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 35

19 Running Hours - Hours 3067

Comments:
Battery 26 Volt DC Name: Imron
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 5/10/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 09.30

2 Stop Time 09.45

3 Engine Speed < 1725 RPM 1499

4 Load % 50

5 Lube Oil Pressure > 3.5 Bar 6.12

6 Lube Oil Temperature < 97 0


C 77

7 Bearing DE Temp. (PT7) < 85 0


C 37.8

8 Bearing NDE Temp. (PT8) < 85 0


C 38.8

9 Fuel Oil Pressure - Bar 8.11

10 Fuel Oil Temperature - C 49.2

11 Fuel Oil Filter dP 1 Bar 0

12 Jacket Water Temperature < 102 0


C 82.7

13 Inter cooler water Temp < 75 0


C 44.3

0.94*fnormal <
14 Frequency fmeasured < Hz 49.96
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 75

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 44.2

19 Running Hours - Hours 3308

Comments:
Battery 26 Volt DC Name: Ikram
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 6/10/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 09.40

2 Stop Time 10.00

3 Engine Speed < 1725 RPM 1499

4 Load % 50 904 kW

5 Lube Oil Pressure > 3.5 Bar 6.51

6 Lube Oil Temperature < 97 0


C 79

7 Bearing DE Temp. (PT7) < 85 0


C 54

8 Bearing NDE Temp. (PT8) < 85 0


C 41

9 Fuel Oil Pressure - Bar 8.11

10 Fuel Oil Temperature - C 50.2

11 Fuel Oil Filter dP 1 Bar 0

12 Jacket Water Temperature < 102 0


C 80.9

13 Inter cooler water Temp < 75 0


C 40.3

0.94*fnormal <
14 Frequency fmeasured < Hz 49.96
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 75

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 31

19 Running Hours - Hours 3309

Comments:
Battery 26 Volt DC Name: Afrialsyah/Edi
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 10/07/2017 & 14/07/2017 (take data)

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 9.13

2 Stop Time 9.43

3 Engine Speed < 1725 RPM 1499

4 Load % 50

5 Lube Oil Pressure > 3.5 Bar 6.1

6 Lube Oil Temperature < 97 0


C 82.3

7 Bearing DE Temp. (PT7) < 85 0


C 58

8 Bearing NDE Temp. (PT8) < 85 0


C 42.8

9 Fuel Oil Pressure - Bar 8.11

10 Fuel Oil Temperature - C 57.6

11 Fuel Oil Filter dP 1 Bar 0

12 Jacket Water Temperature < 102 0


C 80.5

13 Inter cooler water Temp < 75 0


C 44.9

0.94*fnormal <
14 Frequency fmeasured < Hz 49.95
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 75

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 27.8

19 Running Hours - Hours 3310

Comments:
Battery 26 Volt DC Name:
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 10/8/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 14:30

2 Stop Time 15:00

3 Engine Speed < 1725 RPM 1498

4 Load % 50

5 Lube Oil Pressure > 3.5 Bar 6.27

6 Lube Oil Temperature < 97 0


C 79.5

7 Bearing DE Temp. (PT7) < 85 0


C 53.4

8 Bearing NDE Temp. (PT8) < 85 0


C 42.8

9 Fuel Oil Pressure - Bar 8.1

10 Fuel Oil Temperature - C 50.5

11 Fuel Oil Filter dP 1 Bar 0

12 Jacket Water Temperature < 102 0


C 78.5

13 Inter cooler water Temp < 75 0


C 42.9

0.94*fnormal <
14 Frequency fmeasured < Hz 49.95
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 75

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 29

19 Running Hours - Hours 3310

Comments:
Battery 26 Volt DC Name: Akhmad Bagus / EdiS
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 9/10/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 10.03

2 Stop Time 10.23

3 Engine Speed < 1725 RPM 1499

4 Load % 50

5 Lube Oil Pressure > 3.5 Bar 6.28

6 Lube Oil Temperature < 97 0


C 79.8

7 Bearing DE Temp. (PT7) < 85 0


C 52

8 Bearing NDE Temp. (PT8) < 85 0


C 39.8

9 Fuel Oil Pressure - Bar 8.09

10 Fuel Oil Temperature - C 51.5

11 Fuel Oil Filter dP 1 Bar 0

12 Jacket Water Temperature < 102 0


C 77.7

13 Inter cooler water Temp < 75 0


C 40.3

0.94*fnormal <
14 Frequency fmeasured < Hz 49.92
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 74

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 24

19 Running Hours - Hours 3310

Comments:
Battery 26 Volt DC Name: Afrialsyah/Muhammad Ikram
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 10/10/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 9:00

2 Stop Time 9:20

3 Engine Speed < 1725 RPM 1498

4 Load % 50

5 Lube Oil Pressure > 3.5 Bar 6.85

6 Lube Oil Temperature < 97 0


C 77.6

7 Bearing DE Temp. (PT7) < 85 0


C 58

8 Bearing NDE Temp. (PT8) < 85 0


C 45.2

9 Fuel Oil Pressure - Bar 8.09

10 Fuel Oil Temperature - C 43.6

11 Fuel Oil Filter dP (A109) 1 Bar 0

12 Jacket Water Temperature < 102 0


C 68

13 Inter cooler water Temp < 75 0


C 66

0.94*fnormal <
14 Frequency fmeasured < Hz 49.8
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 74

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 30

19 Running Hours - Hours 3311

Comments:
Battery 26 Volt DC Name: Aat Safaat/Paris
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 11/10/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 14:05

2 Stop Time 14:27

3 Engine Speed < 1725 RPM 1498

4 Load % 50

5 Lube Oil Pressure > 3.5 Bar 6.15

6 Lube Oil Temperature < 97 0


C 81.3

7 Bearing DE Temp. (PT7) < 85 0


C 58.2

8 Bearing NDE Temp. (PT8) < 85 0


C 47.6

9 Fuel Oil Pressure - Bar 8.07

10 Fuel Oil Temperature - C 59.3

11 Fuel Oil Filter dP (A109) 1 Bar 0

12 Jacket Water Temperature < 102 0


C 79.8

13 Inter cooler water Temp < 75 0


C 49.9

0.94*fnormal <
14 Frequency fmeasured < Hz 49.94
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 80

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 35

19 Running Hours - Hours 3312

Comments:
Battery 26 Volt DC Name: Suparno/Ikram
Lube Oil Filter (0031845301) Total: 5 Ea.
Fuel Oil Filter (X00042421) Total: 2 Ea
Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date 12/10/2017

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time 8:48

2 Stop Time 9:09

3 Engine Speed < 1725 RPM 1498

4 Load % 75

5 Lube Oil Pressure > 3.5 Bar 6.2

6 Lube Oil Temperature < 97 0


C 73.3

7 Bearing DE Temp. (PT7) < 85 0


C 52.4

8 Bearing NDE Temp. (PT8) < 85 0


C 45.2

9 Fuel Oil Pressure - Bar 7.97

10 Fuel Oil Temperature - C 59.3

11 Fuel Oil Filter dP (A109) 1 Bar 0

12 Jacket Water Temperature < 102 0


C 79.1

13 Inter cooler water Temp < 75 0


C 49.1

0.94*fnormal <
14 Frequency fmeasured < Hz 49.96
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 % 80

16 Engine Oil level (LSL-227) > 70 % 80

17 Engine Mode - R/L L

18 Ambient Temperature < 40 0


C 30

19 Running Hours - Hours 3312

Comments: Very
minol oil spill accumulated under the oil filter. It has been cleaned before engine running. Name: Bagus / Akmal

Signature
DONGGI SENORO LIQUEFIED NATURAL GAS

EMERGENCY DIESEL GENERATOR (061-EDG-1001A/B/C)


UNIT NO : 061-EDG-1001 A Date

Engine Model/Type : 16V 4000 G63/ Engine No:527 109 120

Power Rating : 1965 KW

Year Made : 2011

Manufacturer : MTU

Note: Reading to be Taken after 30 Minutes of on Load Running or 5-10 Minutes before Engine stop on no Load Running

No TAG NO / DESCRIPTION REF. VALUE VALUE REMARKS

1 Start Time

2 Stop Time

3 Engine Speed < 1725 RPM

4 Load %

5 Lube Oil Pressure > 3.5 Bar

6 Lube Oil Temperature < 97 0


C

7 Bearing DE Temp. (PT7) < 85 0


C

8 Bearing NDE Temp. (PT8) < 85 0


C

9 Fuel Oil Pressure - Bar

10 Fuel Oil Temperature - C

11 Fuel Oil Filter dP 1 Bar

12 Jacket Water Temperature < 102 0


C

13 Inter cooler water Temp < 75 0


C

0.94*fnormal <
14 Frequency fmeasured < Hz
1.15*fnormal

15 Diesel day tank level (TK-11) > 70 %

16 Engine Oil level (LSL-227) > 70 %

17 Engine Mode - R/L

18 Ambient Temperature < 40 0


C

19 Running Hours - Hours

Comments:
Name:

Signature

You might also like