CALCULATION 

OF WATER REQUIREMENT, PIPE SZES & NUMBER OF NOZZLE
FOR OIL TANKS

Attachment: Markedup Flow Diagram

DATE: 20‐APR‐2022
SUBMITTED BY: ASHIM KUMAR DAS

SIGNATURE:

Page 1 of 5
CALCULATION OF WATER REQUIREMENT, PIPE SIZES AND NUMBER OF NOZZLES
TANK NO.‐1 (ATF)
Description Value Unit Refernce/Note
Diamter 12 m
Height 8.75 m
Volume 989.1 m3
Surface Area of Tank Shell 329.7 m2
Cooling Water Desity 3 lpm/m2 Cl. 4.3.2.1 (i), OISD‐117
Cooling Water Requirement 59.3 m3  / hr
Number of riser Header 2 no.
Number of working riser Header 1 no.
Flow through Riser header 59.35 m3  / hr
No. of Ring Header 3 nos.
Flow Through each Ring header 20 m3  / hr
Flow Through riser sub‐header 39.56 m3  / hr
Water Velocity  5 m/s Cl. 4.3.2.1 (i), OISD‐117
Size of each Riser header 64.81 mm
Selected Riser Header 65 NB IS:1239 (Heavy Gr.)
Size of each Riser sub header 52.92 mm
Selected Riser Sub‐Header size 50 NB IS:1239 (Heavy Gr.)
Size of each Ring header 37.42 mm
Selected Ring Header size 40 NB IS:1239 (Heavy Gr.)

Selection of Number of Spray Nozzle
Spray Nozzle considered 120 Degree
Sprayer Location from Tank Shell 550 mm Cl. 11.4.3 (b), OISD‐235
Max. Coverage length along the curved surface 2230 mm
Number of nozzle for one ring 17 nos.
Number Ring considered 3
Total No. of Spray nozzle 51 nos.
Flow Throguh each nozzle 1.16 m3  / hr

Page 2 of 5
CALCULATION OF WATER REQUIREMENT, PIPE SIZES AND NUMBER OF NOZZLES 
TANK NO.‐2 (ATF)
Description Value Unit Refernce/Note
Diamter 10 m
Height 10 m
Volume 785 m3
Surface Area of Tank Shell 314 m2
Cooling Water Desity 3 lpm/m2 Cl. 4.3.2.1 (i), OISD‐117
Cooling Water Requirement 56.5 m3  / hr
Number of riser Header 2 no. as provided
Number of working riser Header 1 no.
Flow through each Riser header 56.52 m3  / hr
Flow Through each riser sub‐header 37.68 m3  / hr
Water Velocity  5 m/s Cl. 4.3.2.1 (i), OISD‐117
Size of each Riser header 63.25 mm
Selected Riser Header 65 NB IS:1239 (Heavy Gr.)
Size of each Riser sub header 51.64 mm
Selected Riser Sub‐Header size 50 NB IS:1239 (Heavy Gr.)
No of Ring Header 3 no.
Flow through each Ring Hender 18.84
Size of each Ring header 36.51 mm
Selected Ring Header size 40 NB IS:1239 (Heavy Gr.)

Selection of Number of Spray Nozzle
Spray Nozzle considered 120 Degree
Sprayer Location from Tank Shell 550 mm Cl. 11.4.3 (b), OISD‐235
Max. Coverage length along the curved surface 2444 mm
Number of nozzle for one ring 13 nos.
Number Ring considered 3
Total No. of Spray nozzle 39 nos.
Flow Throguh each nozzle 1.45 m3  / hr

Page 3 of 5
CALCULATION OF WATER REQUIREMENT, PIPE SIZES AND NUMBER OF NOZZLES 
TANK NO.‐3 & 4 (CLASS‐B)
Description Value Unit Refernce/Note
Diamter 14 m
Height 11 m
Volume 1692.46 m3
Surface Area of Tank Shell 483.56 m2
Cooling Water Desity 3 lpm/m2 Cl. 4.3.2.1 (i), OISD‐117
Cooling Water Requirement 87.04 m3  / hr
Number of riser Header 2 no.
Number of working riser Header 1 no.
Flow through each Riser main header 87.04 m3  / hr
No. of ring header 3 no.
Flow Through each ring header 29 m3  / hr
Flow Through each riser sub‐header 29.01 m3  / hr
Water Velocity  5 m/s Cl. 4.3.2.1 (i), OISD‐117
Size of Riser header 78.49 mm
Selected Riser Header 80 NB IS:1239 (Heavy Gr.)
Size of Riser sub header 64.08 mm
Selected Riser Sub‐Header size 65 NB IS:1239 (Heavy Gr.)
Size of each Ring header 45.31 mm
Selected Ring Header size 50 NB IS:1239 (Heavy Gr.)

Selection of Number of Spray Nozzle
Spray Nozzle considered 120 Degree
Sprayer Location from Tank Shell 550 mm Cl. 11.4.3 (b), OISD‐235
Max. Coverage length along the curved surface 2218 mm
Number of nozzle for one ring 20 nos.
Number Ring considered 3
Total No. of Spray nozzle 60 nos. For each tank
3
Flow Throguh each nozzle 1.45 m  / hr

Page 4 of 5
Data Sheet of Spray Nozzle
Description Value Unit
Total Number of Spray Nozzle 210 nos
Effective Working Pressure 1.4 to 3.5 Bar
Maximum working Pressure 12 Bar
K Factor by Vendor
Angle of Discharge 120 Degree
Number of Nozzle
End Connection by Vendor
Material
Body SS304
Scroll SS304
Spray angle 65 to 150 Degree
Range at Min Pr. by Vendor
Effective coveragre at Min Pr. by Vendor
Flow through each nozzle (max) 1.45 m3 / hr

Page 5 of 5
ATTACHMENT

50 50 50 50
50 50

50 65 50
65 65 65

50 50
80 80 80
80

40 40 40 40
40 40

40 50 40
50 50 50

40 40
65 65 65 65