DHOS-CS-PC-2108
C O N N E C TA B L E D E V I C E S
Various types of equipment in a building
can be controlled by a single controller.
Smart Devices
Connect to a wide variety of smart devices, Other
12%
ranging from IP cameras to locks and sensors, and
Office
access all of them from just one Reiri app.
Device HVAC
16%
48%
Lighting
24%
1
Energy Saving
SCHEDULING
SETBACK
When automatic changeover is enabled, cooling and heating changed to cooling mode. If room temperature is below heat
operations of each room will automatically be changed based on setpoint and indoor units are in cooling mode, operation mode Vote Mode
setpoint and room temperature. This function operates a group will be automatically changed to heating mode. For Vote mode, each indoor unit in a group will be
of indoor units to change cooling/heating mode automatically at assigned weight (from 0 to 3) which will then be used to
the same time and can register up to 40 groups. In the case of There is also a Guard Timer function which prevents the decide cool/heat change based on each unit’s setpoint
heat pump/heat recovery VRV, the group will consist of all indoor automatic changeover from activating too frequently in case and room temperature. This mode also includes a Heat
units of the VRV system. the room temperature keeps fluctuating above and below the Override function.
setpoint.
Generally, if room temperature is above cool setpoint and indoor
units are in heating mode, operation mode will be automatically Heat Pump
Vote Mode (without Heat Override) Outdoor Unit
Changeover Group
Fix Mode
For Fix mode, a fixed target indoor unit’s setpoint and
room temperature is used to decide cooling/heating
mode change for all other units. This fixed target indoor
unit can be different from the cool/heat master unit.
Heat Pump Heat
Outdoor Unit Override
Changeover Group Weight 3 2 1 0 1
Unit A Unit B Unit C Unit D Unit E
(Not Evaluated)
• When the room temperature falls below the heat • When Heat Override is switched on, the air-conditioning
Unit D setpoint temperature of the target unit, cooling mode is units will automatically change to heating mode regardless
automatically changed to heating mode. of the weighted outcome.
Energy and water consumption data will be captured and In addition, indoor air quality can also be monitored via trend The PPD function accurately calculates indoor unit power
displayed in user-friendly graphs. Users are able to select graphs for indoor environmental changes such as humidity, CO 2 consumption from outdoor unit power consumption divided by It is easy to export PPD data.
PPD data can be exported in CSV format
desired devices and parameters to monitor energy and water and PM2.5 levels. each indoor unit's operation information. This data is utilised to to any PC to be easily managed and
consumption and ensure effective energy management. calculate air-conditioning usage fees for respective tenants in analysed.
a building and is also useful for energy management. Building
owners are also able to configure price settings for different
timings accordingly.
Trend Graph Energy Management Water Management
As such, this function is able to keep track of power distribution
for each indoor unit and perform air-conditioning billing
calculations swiftly and automatically.
Tenant A
HIGH Operational information
of individual indoor units
Automatic calculation of total power
consumption of individual indoor units
Tenant C
MEDIUM Invoice
Invoice Invoice
Billing
In addition to VRV systems, Reiri can also connect to Split and integrate with other building equipment with WAGO I/O modules Users can monitor and control all connected air-conditioners
SkyAir units, making it the ultimate smart air-conditioning and Modbus devices, and also allow wireless connections to and smart devices from the Reiri app on their smartphones,
control. Depending on the building type, Reiri is also able to Z-Wave devices and even voice command assistants such as tablets or PCs as long as there is internet connection. With
Google Home. everything conveniently accessible from a single app, users can
enjoy greater convenience and energy savings.
Reiri for Office /
Reiri for Office (Touchscreen Controller) /
Reiri for Home
Split*
Outdoor unit
Indoor unit
SkyAir*
Reir i
Remotely control air-
Smoke conditioning units and
Roller Curtain Detector Smart Plug Light
lightings from the Reiri app
WAGO node
Lighting, pump, C O M P L I A N T W I T H C Y B E R - S E C U R I T Y S TA N D A R D ( E N 3 0 3 6 4 5 )
fan, keycard switch,
window contact switch,
sensors (temperature,
humidity, CO2, lux,
occupancy...)
Reiri has achieved the EN 303 645 certification, which
guarantees a safe and reliable platform for users regardless of
location. Privacy and security are of the utmost importance and
all data will be securely stored accordingly.
PRODUCT LINE-UP
Flagship model
Reiri for Office
Touchscreen Controller
DCPF04
Weekly
Schedule Up to 300 patterns (including yearly calendar) can be set
Schedule
DCPF01 Yearly
Calendar A pattern set as calendar has high priority than a pattern which is set as day of a week.
Chart on the environmental changes (e.g. Temperature, Humidity or CO2 levels) along different points of
Data Management Trend Graph*
intervals (6h/12h/24h/48h/7 days/specific period within 7 days).
WAGO I/O System
Energy Graph* Bar chart on energy and other meter value, up to 4 energy categories excluding the recycled category.
Up to 10 nodes Split* Real Time Energy Daily/Monthly real time energy consumption status on screen.
Display
Power Proportional Power Proportional Distribution results available at 60 min interval. Power consumption data for cooling
Distribution (P.P.D.)* and heating mode are available.
Multi-tenant Generate Bill for individual tenants by using P.P.D. data, up to 256 tenants with maximum 256 indoor units
Management^ registered under each tenant.
SkyAir* P.P.D. Billing
Lighting Pump Fan Sensor Number of electricity price variation in a day: 5 time zones can be set with different currency.
The system supports data output in CSV format, and printout function.
Access through mobile application/ Web browser. Up to 80 accounts (Admin and User account) can
Account Management be registered.
Screens and operation accessible to general users can be restricted by admin account
Supported languages English, Spanish, Portuguese, Simplified Chinese, Traditional Chinese, Vietnamese, Bahasa (Indonesia), Thai
Notification Push notification in cases: 1) Error/alert detected 2) Specified management point started 3) Version
update messages
DCPF05 Reiri for Office (Controller Extension) Expansion Controller Detecting PM2.5, CO2, VOC, temp. & RH, Modbus RS485
Controller DCPE01S IAQ Sensor AC
interface (100~240VAC Power Supply)
DCPF10 Reiri for Office (Multisite Extension) Multi-site controller
IAQ Sensor for Reiri
DCPA01 Adaptor for Reiri Up to 64 indoor units can be managed Detecting PM2.5, CO2, VOC, temp. & RH, Modbus RS485
DCPE02S IAQ Sensor DC
interface (24VAC/VDC power supply)
BRP072B42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
A/C Connection
Interface Adaptor BRP072C42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
BRP072C42-1 Daikin Mobile Controller Adaptor (for SA units) For individual SA Indoor unit
Power supply:
787-712; 787-1112
OPTIONAL SOFTWAR E
*Use with 750-362 only. Not applicable with 750-862.
Management points
Description
Icon
A simple office building solution with a secured, cloud- Icons show the operation status of equipment
F E AT U R E S Monitoring
View
enabled platform and a dedicated touch panel. Monitoring and Screen
• Modern Touch Screen for Centralised Control Functions Layout Maximum 50 screen can be registered;
View Background image size should be less than 512kB
Control
• Energy Management Remote Control
Individually prohibit operation of each local remote-control function
Prohibition
• IAQ Management
• Mobile Control of Air-conditioning Units Setpoint Range Limitation To limit setpoint range for each indoor unit management point
• Automatic Control
• Scalability Automatic changeover Number of changeover groups: 100
Modbus Devices • User-friendly App Interface Off Timer Off timer duration can set from 5min to 120min with every 5min interval
• Complete control of all connected devices
Reir i • Easy installation and configuration Setback Setback setpoint can be selected within 24-35°C in cooling mode and 5-20°C in heating mode.
• Push Notification
• Compliant with Cyber-security standard Number of programmes: 100
Scene Up to 20 actions can be registered per pattern.
(EN303645)
Automation Control
IAQ Sensor Smart Meter Functions Number of programmes: 100
Up to 20 actions can be registered per pattern.
Schedule Weekly Schedule Up to 300 patterns (including yearly calendar) can be set.
DCPF04
Yearly Calendar A pattern set as calendar has high priority than a pattern which is set as day of a week.
History Management point operation, management point status change, management point error/alert message,
function execution and system information are recorded for one year.
Report* Operation data (latest information and operation report) and error report on daily/monthly basis.
DCPA01 Chart on the environmental changes (e.g. Temperature, Humidity or CO2 levels) along different points of
Data Management Trend Graph*
intervals (6h/12h/24h/48h/7 days/specific period within 7 days)
Smartphone Wi-Fi Router
Energy Graph* Bar chart on energy and other meter value, up to 4 energy categories excluding the recycled category.
Real Time Energy Daily/Monthly real time energy consumption status on screen.
Display
WAGO I/O System
Power Proportional Power Proportional Distribution results available at 60 min interval. Power consumption data for cooling
Up to 10 nodes Split* Distribution (P.P.D.)* and heating mode are available.
Multi-tenant
Generate Bill for individual tenants by using P.P.D. data, up to 256 tenants with maximum 256 indoor units
Management^
registered under each tenant.
P.P.D. Billing
Number of electricity price variation in a day: 5 time zones can be set with different currency.
The system supports data output in CSV format, and printout function.
Access through mobile application/ Web browser. Up to 80 accounts (Admin and User account) can
SkyAir* Account Management be registered.
Lighting Pump Fan Sensor Screens and operation accessible to general users can be restricted by admin account
Supported languages English, Spanish, Portuguese, Simplified Chinese, Traditional Chinese, Vietnamese, Bahasa (Indonesia), Thai
*Additional Interface Adaptors may be required Push notification in cases: 1) Error/alert detected 2) Specified management point started 3) Version
Notification
update messages
17 | Reiri for Office (Touchscreen Controller) Reiri for Office (Touchscreen Controller) | 18
OPTIONAL ACCESSORIES
Controller DCPF10
DCPA01
Reiri for Office (Multisite Extension)
OPTIONAL HARDWAR E
OPTIONAL SOFTWAR E
L O C A L LY P R O C U R E D M O D U L E S
Type Specification
System modules:
750-600; 750-601; 750-602; 750-613; 753-620 (for DALI module) DCPF01 DCPA01
WAGO I/O System
Supported IO modules:
Di: 750-400,430,432,436,1405
Do: 750-504, 513, 513/000-001, 1504
Ai: 750-454,455,459,479,460,460/000-003,460/000-005,461,461/000-003,461/000-004,461/000-005,461/020-000 REQUIRED ACCESSORY
Ao: 750-554,555,559,560
Pulse counter module*: 750-638
DALI: 753-647 A/C CONNECTION HARDWARE
Power measurement: 750-495
Modbus Smart Meter Schneider PM5300 / PM5110 / PM5500 / iEM3100 / iEM3200 series
19 | Reiri for Office (Touchscreen Controller) Reiri for Office (Controller Extension) | 20
S P E C I F I C AT I O N S ( S O F T W A R E )
Category Functions Description
Monitoring and
Control Functions
Monitoring
Screen
Icon View
Layout
View
Icons show the operation status of equipment
Weekly DCPF10
Schedule Up to 300 patterns (including yearly calendar) can be set.
Schedule
Yearly
A pattern set as calendar has high priority than a pattern which is set as day of a week.
Calendar Head Office
Number of programmes: 500
Interlock Up to 10 management points can be registered as activation condition.
The delay timer of execution condition can be set within 0-120 mins after the activation conditions are satisfied.
Management point operation, management point status change, management point error/alert message, Wi-Fi Router
History
function execution and system information are recorded for one year.
Report* Operation data (latest information and operation report) and error report on daily/monthly basis.
Data Management Chart on the environmental changes (e.g. Temperature, Humidity or CO2 levels) along different points of
Trend Graph*
intervals (6h/12h/24h/48h/7 days/specific period within 7 days)
Site A
Energy Graph* Bar chart on energy and other meter value, up to 4 energy categories excluding the recycled category. Internet
Real Time Energy Display Daily/Monthly real time energy consumption status on screen.
Access through mobile application/ Web browser. Up to 200 accounts (Admin and User account) can be DCPF01 DCPA01
Account Management registered.
Screens and operation accessible to general users can be restricted by admin account.
Supported languages English, Spanish, Portuguese, Simplified Chinese, Traditional Chinese, Vietnamese, Bahasa (Indonesia), Thai
Push notification in cases: 1) Error / alert detected 2) Specified management point started 3) Version
Notification
update messages
Email Alert Malfunction Alert will be sent to preset email account Site D
Lighting Pump
*The system supports data output in CSV format.
OPTIONAL ACCESSORIES
21 | Reiri for Office (Controller Extension) Reiri for Office (Multisite Extension) | 22
S P E C I F I C AT I O N S ( S O F T W A R E )
Groups Maximum number of groups: 100 for each site Type Model Item Remarks
Setpoint Range Limitation To limit setpoint range for each indoor unit management point
Off Timer Off timer duration can set from 5min to 120min with every 5min interval
OPTIONAL ACCESSORY
Setback Setback setpoint can be selected within 24-35°C in cooling mode and 5-20°C in heating mode.
Scene
Number of programmes: 100 for each site OPTIONAL SOFTWAR E
Up to 20 actions can be registered per pattern.
Number of programmes: 100 for each site Type Model Item Remarks
Automation Control
Functions Up to 20 actions can be registered per pattern.
Controller
Schedule Software DCPN005 Multi-site Branch Expansion To expand the multi-site control limit by 1 site
Weekly Schedule Up to 300 patterns (including yearly calendar) can be set.
Yearly Calendar A pattern set as calendar has high priority than a pattern which is set as day of a week.
Management point operation, management point status change, management point error/alert message,
History
function execution and system information for each site are recorded for one year.
Report* Operation data (latest information and operation report) and error report for each site on daily/monthly basis.
Data Management Trend Graph* Chart on the environmental changes for each site (e.g. Temperature, Humidity or CO2 levels) along different
points of intervals (6h/12h/24h/48h/7 days/specific period within 7 days).
Energy Graph* Bar chart on energy and other meter value, up to 4 energy categories excluding the recycled category for each site.
Power Proportional Power Proportional Distribution results available at 60 min interval for each site.
Distribution (P.P.D.)* Power consumption data for cooling and heating mode are available.
Multi-tenant
Management^ Generate Bill for individual tenants by using P.P.D. data, up to 256 tenants with maximum 256 indoor units
P.P.D. Billing registered under each tenant for each site.
Number of electricity price variation in a day: 5 time zones can be set with different currency.
The system supports data output in CSV format, and printout function.
Access through mobile application/ Web browser. Up to 200 accounts (Admin and User account) can
Account Management be registered.
Screens and operation accessible to general users can be restricted by admin account
Supported languages English, Spanish, Portuguese, Simplified Chinese, Traditional Chinese, Vietnamese, Bahasa (Indonesia), Thai
Notification Push notification in cases: 1) Error/alert detected 2) Specified management point started 3) Version
update messages
23 | Reiri for Office (Multisite Extension) Reiri for Office (Multisite Extension) | 24
Reiri for Hotel effectively saves
energy and cost while prioritizing
guests’ comfort and satisfaction.
With this smart hotel solution, energy
consumption is optimised without
compromising on the guests’ in-room
comfort. Hotel managers and staff
are also able to conveniently monitor
the status and manage the settings of
every room.
PRODUCT LINE-UP
Achieve the best of both worlds with this F E AT U R E S A/C CONNECTION HARDWARE
control solution that provides automatic aircon
• Guest Comfort Type Model Item Remarks
control to reduce energy consumption while
• Energy Management
ensuring an ideal level of comfort for guests • Easy installation and configuration DCPF01 Reiri for Office Building Controller
in every room. • Compliant with Cyber-security standard Controller DCPF04 Reiri for Office (Touchscreen Controller) Building controller
(EN303645)
DCPF05 Reiri for Office (Controller Extension) Office Building Expansion Controller
Check in Check in
DCPA01 Guest room air-conditioner Air-conditioner is controlled based on guest room status such as rent/unrent, occupied/unoccupied and
interlock window open/close signal, up to 10 signals in total.
Dry contact
Router
Window Sensor
DCPL01
OPTIONAL ACCESSORIES
Room B
BRP072B42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
A/C Connection
Interface Adaptor BRP072C42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
BRP072C42-1 Daikin Mobile Controller Adaptor (for SA units) For individual SA Indoor unit
Room C
Dry contact
Guest room air-conditioner Air-conditioner is controlled based on guest room status such as rent/unrent, occupied/unoccupied and window
interlock open/close signal, up to 10 signals in total.
Router
LAN Cable
DCPR01
Dry contact
OPTIONAL ACCESSORIES
Dry contact
DCPR01 DCPR01 A/C CONNECTION HARDWAR E
Dry contact Dry contact
Type Model Item Remarks
Dry contact Dry contact
DCPF01 Reiri for Office Centralised control for check in/out
DCPA01 Key Card Window Sensor
Controller DCPF04 Reiri for Office (Touchscreen Controller) Building controller
DCPA01 Key Card Window DCPA01 Key Card Window DCPF05 Reiri for Office (Controller Extension) Office Building Expansion Controller
Sensor Sensor
DCPA01 Adaptor for Reiri Up to 10 indoor units can be managed
BRP072B42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
A/C Connection BRP072C42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
Interface Adaptor
BRP072C42-1 Daikin Mobile Controller Adaptor (for SA units) For individual SA Indoor unit
DTA102A52 Interface adaptor for SkyAir For individual SkyAir Indoor Unit
SkyAir Connection
Interface Adaptor Interface adaptor for SkyAir
DTA112BA51 For individual SkyAir Indoor Unit
Residential Unit
Connection Interface KRP928BB2S Interface Adaptor for residential indoor unit For individual Indoor Unit
Adaptor
PRODUCT LINE-UP
Setback Setback setpoint can be selected within 24-35°C in cooling mode and 5-20°C in heating mode.
Number of programmes: 30
IAQ Sensor Smart Meter Up to 20 actions can be registered per pattern.
Scene
Number of programmes: 30
DCPH01 DCPA01 Automation Control Up to 20 actions can be registered per pattern.
Functions
Split* Weekly Schedule Up to 50 patterns (including yearly calendar) can be set
Schedule
Yearly Calendar A pattern set as calendar has high priority than a pattern which is set as day of a week.
SkyAir*
Multi-split AC with
Number of programmes: 30
Daikin Mobile Controller
Interlock Up to 10 management points can be registered as activation condition.
The delay timer of execution condition can be set within 0-120 mins after the activation conditions are satisfied.
History Management point operation, management point status change, management point error/alert message,
RA
Compatible with: function execution and system information are recorded for one year.
BRP072C42
Report* Operation data (latest information and operation report) and error report on daily/monthly basis.
Data Management
SkyAir AC with Chart on the environmental changes (e.g. Temperature, Humidity or CO2 levels) along different points of
Trend Graph* intervals (6h/12h/24h/48h/7 days/specific period within 7 days)
Wi-Fi Router Daikin Mobile Controller
Energy Graph* Bar chart on energy and other meter value, up to 4 energy categories excluding the recycled category.
Access through mobile application/ Web browser. Up to 20 accounts (Admin and User account) can
Account
be registered.
Smartphone SkyAir Management
Screens and operation accessible to general users can be restricted by admin account
BRP072C42-1
LAN communication: AES-128-CBC with RSA 2048
*Additional Interface Internet communication: TLS 1.2
Adaptors may be required Security Account password storage: SHA256 hashing and AES-128-CBC together with other account information
System Setting Device login password storage: AES-128-CBC
IP Camera Supported languages English, Spanish, Portuguese, Simplified Chinese, Traditional Chinese, Vietnamese, Bahasa (Indonesia), Thai
Push notification in cases: 1) Error/alert detected 2) Specified management point started 3) Version
WAGO I/O System Notification update messages
Up to 5 nodes Email Alert Malfunction Alert will be sent to preset email account
Smart Home devices
Smoke
Roller Curtain Detector Smart Plug Light
Lighting Pump Fan Sensor
Door Lock
Motion
Flood Sensor Door Sensor Sensor
DCPA01 Adaptor for Reiri Up to 64 indoor units can be managed Setback, Setpoint Range, Remote Control Prohibition,
DCPN006 Residential Automatic Control Automatic Changeover functions for individual controller
Controller
BRP072B42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
Software Operation Report, Error Report functions for individual
DCPN007 Residential System Report controller
A/C Connection BRP072C42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
Interface Adaptor
BRP072C42-1 Daikin Mobile Controller Adaptor (for SA units) For individual SA Indoor unit
SkyAir Connection DTA102A52 Interface adaptor for SkyAir For individual SkyAir Indoor Unit
Interface Adaptor
DTA112BA51 Interface adaptor for SkyAir For individual SkyAir Indoor Unit
Residential Unit L O C A L LY P R O C U R E D M O D U L E S
Connection Interface KRP928BB2S Interface Adaptor for residential indoor unit For individual Indoor Unit
Adaptor Type Specification
OPTIONAL HARDWARE Modbus Smart Meter Schneider PM5300 / PM5110 / PM5500 / iEM3100 / iEM3200 series
Type Specification Aeotec: Nano Dimmer (ZW111), Nano Switch (ZW139), Door/Window Sensor 7 Pro (ZWA012), Tri Sensor (ZWA005),
Home Energy Meter Gen5 (ZW095), Smart Switch 6 (ZW096)
DCPE01S (IAQ Sensor AC) Smart Home Z-wave MCO Home: PM2.5 Monitor (MH10-PM2.5-WD), Multi-Sensor (A8-7/A8-9), Smart Plug (PS-UK)
IAQ Sensor for Reiri Devices (Other Brands) Popp Smoke Sensor (Ei650)
DCPE02S (IAQ Sensor DC)
Yale Digital Door Lock (models supporting Security 2 DSK (zws2dsk))
Samsung Digital Door Lock (models supporting HMDM-100)
Dimmer 2: FGD-212 Roller Shutter 3: FGR-223
Flood Sensor: FGFS-101 RGBW Controller: FGRGBW-442
Smoke Sensor: FGSD-002 Door/Window Sensor: FGDW-002 D-Link: DCS-F4602 (dome 2MP), DCS-F4702 (bullet 2MP), DCS-F4604 (dome 4MP), DCS-F4704 (bullet 4MP) [All Hardware Version B]
Smart Home
CO Sensor: FGCD-001 Motion Sensor:FGMS-001 Uniview: IPC21Series, IPC22Series, IPC23Series, IPC24Series, IPC25Series, IPC26Series, IPC31Series, IPC32Series, IPC33Series,
Z-wave Devices
Single Switch 2: FGS-213 Smart Plug: FGWPG-111 Compatible IP Cameras IPC35Series, IPC36Series, IPC54Series, IPC56Series, IPC62Series, IPC63Series, IPC64Series, IPC66Series, IPC67Series, IPC68Series,
( Fibaro )
Double Switch 2: FGS-223 Smart Implant:FGBS-222 IPC74Series, IPC76Series, IPC81Series, IPC85Series, IPC86Series, IPC2ASeries, IPC2CSeries, TIC22Series, TIC25Series, TIC68Series,
Smart Module : FGS-214 The Button: FGPB-101 TIC76Series
Double Smart Module: FGS-224
Monitoring Screens
Maximum number of groups: 5
Setpoint Range Limitation To limit setpoint range for each indoor unit management point
The best smart air-conditioner controller for homeowners to F E AT U R E S
achieve maximum comfort and energy savings. Automatic changeover Number of changeover groups: 5
• User-friendly App Interface
• Complete control of all air-conditioners Off Timer Off timer duration can set from 5min to 120min with every 5min interval
• Easy installation and configuration Setback Setback setpoint can be selected within 24-35°C in cooling mode and 5-20°C in heating mode.
• Push Notification Automation Control
Functions Number of programmes: 10
• Compliant with Cyber-security standard
Up to 20 actions can be registered per pattern.
(EN303645)
Schedule Weekly Schedule Up to 10 patterns (including yearly calendar) can be set.
Yearly Calendar A pattern set as calendar has high priority than a pattern which is set as day of a week.
Management point operation, management point status change, management point error/alert message,
History
function execution and system information are recorded for one year.
Data Management
Report* Operation data (latest information and operation report) and error report on daily/monthly basis.
Access through mobile application/ Web browser. Up to 10 accounts (Admin and User account) can be registered.
Account Management
Screens and operation accessible to general users can be restricted by admin account.
DIII - NET
LAN communication: AES-128-CBC with RSA 2048
Security Internet communication: TLS 1.2
Account password storage: SHA256 hashing and AES-128-CBC together with other account information
Device login password storage: AES-128-CBC
DCPA01 System Setting
Supported languages English, Spanish, Portuguese, Simplified Chinese, Traditional Chinese, Vietnamese, Bahasa (Indonesia), Thai
Notification Push notification in cases: 1) Error/alert detected 2) Specified management point started 3) Version update messages
OPTIONAL ACCESSORIES
DCPH02
Max. 30 A/C CONNECTION HARDWARE
indoor units
in total Type Model Item Remarks
BRP072B42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
A/C Connection BRP072C42 Daikin Mobile Controller Adaptor (for RA units) For individual RA Indoor Unit
Interface Adaptor
Wi-Fi Router
BRP072C42-1 Daikin Mobile Controller Adaptor (for SA units) For individual SA Indoor unit
SkyAir Connection DTA102A52 Interface adaptor for SkyAir For individual SkyAir Indoor Unit
Interface Adaptor
DTA112BA51 Interface adaptor for SkyAir For individual SkyAir Indoor Unit
Residential Unit
Connection Interface KRP928BB2S Interface Adaptor for residential indoor unit For individual Indoor Unit
Adaptor
37 | Reiri for Home (Lite Version) Reiri for Home (Lite Version) | 38
Daikin Holdings
Singapore Pte Ltd
ADDRESS
10 Ang Mo Kio Industrial Park 2,
Singapore 569501
MAIN LINE
6583 8888
EMAIL
dhos.support@daikin.com.sg