Professional Documents
Culture Documents
Industrial Refrigeration Best Practice Guide
Industrial Refrigeration Best Practice Guide
December 2004
Prepared by
Cascade Energy Engineering, Inc.
6½ N. Second Ave, Suite 310
Walla Walla, Washington 99362
www.cascadeenergy.com
Primary Authors
Marcus Wilcox, Rob Morton, Dan Brown: Cascade Energy Engineering
Technical Illustration
Elaine Giraud: SeeFigureOne
Technical Reviewers
Greg Jourdan: Wenatchee Valley College
Anthony Radspieler and Steve Greenberg: Lawrence Berkeley National Laboratory
Doug Reindl: Industrial Refrigeration Consortium
Michael Steur: Hixson, Inc.
Copyright
© 2004 Northwest Energy Efficiency Alliance, Inc. All rights reserved. Northwest Energy Efficiency Alliance grants
permission to reproduce this material in whole or in part only for information or education purposes.
ISBN: 0-9721077-9-7
Disclaimer
This Guide was prepared by Cascade Energy Engineering for the Northwest Energy Efficiency Alliance. Neither the
Northwest Energy Efficiency Alliance nor any of its contractors, subcontractors, or employees, makes any warranty,
expressed or implied, or assumes any legal liability of responsibility for the accuracy, completeness, or usefulness of any
information, apparatus, product, or process disclosed within this Guide. This Guide and any examples described herein are
intended to be general information and guidelines concerning the subject matter, and are not recommendations with respect
to any specific project or application.
[CD]
Introduction
Courtesy of Frick
Background
This Guide identifies and discusses best practices for making industrial refrigeration systems both
energy-efficient and productive. The highest levels of efficiency in these systems are achieved
through a combination of design, construction, commissioning, operation, and maintenance. This
Guide provides insights into approaches to industrial refrigeration systems that cost less to operate,
are reliable, can maintain accurate and consistent temperatures in refrigerated spaces, help ensure
that processing equipment operates consistently, and can meet varying production needs.
This Guide was developed with the support of the Northwest Energy Efficiency Alliance. The
Alliance is a non-profit corporation supported by electric utilities, public benefits administrators,
state governments, public interest groups and energy efficiency industry representatives. These
entities work together to make affordable, energy-efficient products and services available in the
marketplace.
The Alliance is committed to programs that will cause market transformation, wherein energy users
are influenced by example, education, and experience to increasingly consider and make choices in
favor of energy-efficient products and services.
Goals
Ultimately, market transformation for energy efficiency in industrial refrigeration is achieved by
changing the business practices of food processing companies, cold-storage and refrigerated
warehouses, and the trade allies that support and serve them. Design standards and operation-and-
maintenance practices that increase and maintain energy efficiency can also be adopted by users of
industrial refrigeration and their engineering consultants and contractors.
In this context, the goals of this Best Practices Guide are:
To identify opportunities to increase electrical energy efficiency in industrial refrigeration
systems The Guide specifically focuses on energy savings measured in kilowatt-hours (kWh).
Attribute Criteria
Size: 100 tons or larger
Refrigerant: Ammonia (R-717) in the vast majority of cases, with some R-22 applications
System Type: Centralized and built-up, as opposed to commercial refrigeration equipment
which is simpler, more modular, and distributed
Load Temperatures: -60°F to 55°F with normally at least one load below 40°F
Function: Primarily storage and processing of food products
Industries: Refrigerated warehouses, including controlled atmosphere
Fruit and vegetable processors ranging from fresh product storage to highly
processed pre-prepared meals
Breweries and wineries
Dairy and ice cream processors
Meat, poultry, and fish processors
Although most of this Best Practices Guide will be of interest to all readers, some sections will be of
particular interest to specific audiences. The chapters of the Guide and how each audience may find
them valuable are outlined below and illustrated in . We hope that you will find useful information
on best practices for your refrigeration system for energy efficiency, to control operating costs, and
to realize productivity benefits—fundamentally, to improve your bottom line.
Chapter 2: Best Practices
Overview, beginning on
page 5, includes an overview
of design, operation, and
maintenance best practices, an
outline of the major categories
of improvement, and a guide
on how to obtain best
practices in industrial
refrigeration systems.
Chapter 3: Refrigeration
System Basics, beginning on
page 10, reviews refrigeration
Figure 1: Suggested road map to this Guide for various audiences
basics and, if needed, will help
familiarize you with industrial
refrigeration concepts and equipment. If you are already familiar with refrigeration systems and
related components you may want to skip this section, but it may be useful for reference. You may
also want to skip this chapter if you are looking for a higher level view of best practices. You can
refer to this chapter as needed.
Chapter 4: Best Practices for Equipment, Systems, and Controls, beginning on page 46, describes
energy-efficient concepts, equipment, controls, and system types. This chapter features
recommended best practices. If you are an owner, plant engineer, or operator, we recommend that
you understand these best practices and consider them, if feasible, for your facility. This chapter
also highlights the benefits beyond energy cost savings that are often associated with increased
Design
Designing the facility to reduce loads
Selecting energy-efficient equipment and controls
Integrating that equipment into a system that is optimized for efficiency at both peak loads and
typical loads
Operation
Trained and certified operators with a conceptual knowledge of energy-efficient practices and
an understanding of refrigeration cycles
Scheduled or regular review and documentation of key set points and operational strategies
required for energy-efficient operation
Using a control system to review operations to confirm efficient operation and to automate
complex control strategies
Observing equipment and gauge readings to confirm efficient operation
Maintenance
Trained and certified maintenance staff and contractors
Preventive maintenance practices
Routine calibration of sensors, controls, and actuators that indicate system performance
Routine cleaning and maintenance of evaporators, condensers and heat exchangers
Commissioning
Implementing commissioning for new construction, for major retrofits, and periodically for all
systems to ensure that the system, equipment, and controls meet process and energy-efficiency
objectives
Life-Cycle Costs
Best practices encompass much more than just energy performance. In the broadest sense, best
practices could be defined as follows:
Design, operational, and maintenance practices that help minimize life-cycle costs to the system
owner are based upon factors that include:
Initial capital investment
The expected life of the equipment
Ideally, all of these costs and their interactions would be well understood, and selecting the “best
practices” for a given situation would be straightforward. Real situations, however, are more
complicated and have more unknowns, but we contend that in most cases, a system that is designed,
operated, and maintained in an energy-efficient manner will typically have low life-cycle costs.
There is no single set of best practices that is ideal for every situation. We do not suggest that every
conceivable energy-efficient option should be integrated into every system. The optimum design for
a system that operates continuously at relatively high load will be different than the design for a
system with a short season with highly variable loads. Instead, we believe that it is warranted to
consider a range of energy-efficiency choices when designing a new refrigeration system or
modifying an existing system. Existing system constraints, energy rates, and utility or government
incentives can all significantly influence which best practices are economically viable for a specific
system.
System Commissioning
Develop and execute a commissioning plan to assure that the system, equipment, and
controls meet their process and energy-efficiency objectives.
Think of commissioning as a way to ensure that you are getting what you are paying for in
your refrigeration system project, not as an additional cost without benefit.
Introduction
In this chapter, we explain the basic refrigeration cycle and describe the equipment typically used in
industrial refrigeration systems. We discuss the various features and characteristics of this energy-
using equipment and review system-control and variable-frequency drive (VFD) technology.
If you are already familiar with industrial refrigeration, this chapter can serve as a refresher or as
background reference information. If you are unfamiliar with refrigeration, this chapter will
introduce and explain critical basic concepts and terms that underlie best practices for energy
efficiency. In any case, this chapter can serve as the basis of a common understanding of industrial
refrigeration among the parties of various duties, responsibilities, and expertise—managers,
maintenance staff, system operators, vendors, contractors, and so on.
Purpose of Refrigeration
The purpose of refrigeration is to remove heat from some
medium—a fluid or solid—and transfer that heat elsewhere. In
most systems, heat is removed from air (for example, a
refrigerated warehouse), water or glycol (for example, a water
chiller), or a food product (for example, ice cream), and
transferred outdoors to the ambient environment. Although
industrial refrigeration is also used in the chemical industry and
in unique applications such as cooling the concrete during dam
construction, the fundamental purpose and operation is the
same.
If you are familiar with the basics of a refrigeration cycle, you Figure 2: Refrigeration transfers
can skip some or all of the following sections. However, this heat from a medium to the
chapter may be a valuable refresher on the processes and ambient environment
equipment.
Refrigerants
The purpose of refrigeration is to remove heat from a fluid or solid. Because heat transfer is driven
by a temperature difference, to remove heat from something, we need to put it in contact with
some medium at a lower temperature. In the case of industrial refrigeration, this medium is a liquid
refrigerant at a low temperature.
Many naturally occurring substances can be used as a refrigerant,
including air, ammonia, water, and carbon dioxide. There are For food processing and
also man-made refrigerants, such as R-11, R-12, R-22, and R-502. storage, ammonia is the most
Modern replacements for these refrigerants include R-123, R-134,
and R-404, and many new refrigerants are being developed. The efficient refrigerant.
type of refrigerant chosen for a particular application is
determined by the pressure and temperature ranges required by
the application. For typical food-processing and storage applications, ammonia offers the highest
efficiency of any refrigerant. (In certain situations, R-22 is also an appropriate choice.) For building
Evaporation
Imagine we have a cold liquid refrigerant, such as ammonia, at
0 psig (atmospheric pressure) and -28°F. The liquid ammonia is
located in an evaporator coil. Air that is warmer than the
refrigerant, at say -10°F, is blown across the evaporator by fans.
When that air passes over the fins on the evaporator, it is cooled
by the -28°F ammonia inside the evaporator. As the ammonia
absorbs heat from the air stream, it boils (at a constant pressure
and temperature) and the air exits the evaporator at a colder
temperature than it entered, say -20°F.
Figure 3: The basic refrigeration
The processes within the evaporator in any particular application cycle
are essentially the same. Instead of air blowing over a coil, water
could be flowing through the tubes of a heat exchanger, or a food product such as ice cream could
be opposite a heat-exchange surface from the ammonia. In any case, the result is refrigerant that has
absorbed heat, boiled, and made something else colder, thus achieving the refrigeration effect the
system was designed for.
We now have a volume of ammonia that is still at -28°F and 0 psig, but is now a vapor. So that it
can do more refrigeration, we must return it to a cold, low-pressure condition. To do this, we first
need to raise the temperature of the refrigerant so we can get rid of the heat outside, where the
temperature is likely much higher than -28°F.
Compression
This is where compression comes in. A compressor is a piece of equipment that simply compresses
the refrigerant vapor, raising its pressure and therefore its temperature. In our example, the
compressor would receive the boiled ammonia vapor at -28°F, 0 psig (d in Figure 3), and compress
it to an elevated pressure and temperature, say 85°F and 150 psig (e in Figure 3). (In reality, the
discharge temperature is superheated, but we have used saturated conditions for the sake of
Condensing
The high-pressure, high-temperature refrigerant vapor now enters a piece of equipment called a
condenser, which, like an evaporator, is similar to a car radiator. The refrigerant vapor at 85°F and
150 psig enters the condenser (ein Figure 3). Fans blow cooler ambient air at, say 70°F, across the
condenser. Within the condenser, the warm refrigerant vapor heats the air. The air leaves the
condenser at a higher temperature, say 80°F, while the refrigerant cools down and condenses from a
vapor to a liquid (f in Figure 3).
We now have a volume of ammonia that is still at 85°F and 150 psig, but is now a liquid. But we
still need to turn this into a low-temperature, low-pressure liquid. For this, we turn to expansion.
Expansion
When a liquid refrigerant at high pressure passes through a restriction such as a narrowed tube or a
barely open valve, the liquid loses pressure. That loss of pressure causes a small portion of the liquid
to vaporize. That vaporization absorbs energy from the remaining liquid refrigerant, causing it to
cool down. This process is called expansion, and in industrial refrigeration systems is achieved using
a piece of equipment called an expansion valve.
In our example, our 85°F, 150 psig liquid enters an expansion valve, and its pressure drops to 0 psig.
The liquid refrigerant temperature drops to -28°F, and we find ourselves back where we started.
Our cold liquid refrigerant is again ready to do more
refrigeration (c in Figure 3).
Two-stage refrigeration is more
Two-Stage Cycle efficient than single-stage in
In applications where a very low temperature (for example, less low-temperature applications.
than -25°F for ammonia) is required, two stages of refrigeration
can be used. A two-stage system (Figure 4) is essentially two
standard cycles stacked on top of each other (with an “intercooler” in between). The first stage of
compression is performed by a “first-stage,” “low-stage,” or “booster” compressor, and the second
stage is performed by a “second-stage” or “high-stage” compressor.
The booster compressor discharges
“superheated” refrigerant vapor—that is, vapor
that is above the saturation temperature (the
threshold boiling temperature) of the
refrigerant. Because compression is most
efficient when the entering refrigerant is at
saturation, the superheated vapor from the first
stage must be cooled down to saturation before
moving on to the second stage. This is where
the intercooler comes in. The booster
compressor discharges its superheated vapor at
the bottom of a vessel—the intercooler—filled
with liquid ammonia. The gas bubbles up
through this liquid, is cooled back to Figure 4: Thermodynamic process associated with
saturation, and is then drawn into the high- two-stage compression
stage compressor.
Expansion can also occur in two stages.
The following sections discuss these in greater detail and address issues of performance ratings,
capacity control, and design and selection.
Evaporators
Introduction
All cooling within the refrigeration cycle occurs in a piece of equipment called an evaporator. There
are two primary types of evaporators:
Refrigerant-to-air coils
Heat exchangers Refrigerant-to-air evaporator
coils are most common.
There are two main types of heat exchangers:
Refrigerant-to-secondary fluid
Direct-contact
Refrigerant-to-Air Coils
Overview
The most common evaporator configuration is the refrigerant-to-air coil (also called an evaporator
fan coil), in which the cooled refrigerant is passed through tubes, and air is drawn over the tubes to
refrigerate it. The tubes typically have attached fins to improve heat transfer. Figure 5 shows an
example.
Axial Fans
Most evaporator coils use axial fans that either
push or pull air through the coil. In larger
evaporator coil applications, the fan motors are
standard NEMA frame units and are normally
mounted to a rigid mounting plate with four
bolts in the motor base. In smaller applications
with fractional horsepower motors, there is Figure 8: Evaporator coils in a penthouse
often a belly-band mount, in which the fan
shroud wraps around the body of a footless (often special OEM) motor, and is cinched around the
motor body. This is important because these special motors are inefficient and create challenges
with VFD installations.
Two-Speed
Evaporator fan motors can have two speeds, allowing full- and
(typically) half-speed operation.
Courtesy of Vilter
Normally, the capacity of evaporator coils is controlled by controlling the flow or pressure of the
liquid refrigerant to achieve temperature control.
The following sections describe each method and explain how evaporator capacity is controlled in
each.
Flooded
In a flooded system, low-pressure, low-temperature liquid
refrigerant is held in an adjacent vessel called an accumulator.
The accumulator is physically located above the coil, and
refrigerant simply flows to the coil due to gravity. As the
refrigerant boils, the vapor bubbles rise through the coil to the
top of the accumulator, where the vapor is drawn away by the
compressors.
In a flooded system, a pressure regulator is located on the
accumulator. The refrigerant pressure (and hence temperature) is Figure 11: Flooded evaporator
varied in the accumulator by throttling the gas returning in the
suction line of the compressors. When the regulator is wide open, the refrigerant essentially sees the
full suction pressure of the compressors and the refrigerant is at low temperature, thus maximizing
capacity. As the regulator closes, the pressure rises in the coil, with a commensurate increase in
boiling temperature and decrease in temperature difference between refrigerant and entering air.
Direct Expansion
In a direct-expansion system, high-pressure
liquid refrigerant is piped from the high-
pressure receiver to the evaporator coil. A
thermal-expansion valve meters refrigerant flow
to maintain a target superheat for refrigerant
leaving the evaporator coil.
Similar to a recirculated system, a direct-
expansion system uses a liquid solenoid to turn Figure 12: Direct expansion refrigerant transport
refrigerant flow to the thermal expansion valve
on and off.
Types of Defrost
There are four common methods of frost removal and a fifth
hybrid method.
Hot-Gas Defrost
In a hot-gas defrost system, high-pressure, high-temperature,
refrigerant vapor is discharged from the compressor and routed
to and passed through the evaporator coil. The gas is often
managed by a pressure regulator at the coil outlet, maintaining a
pressure of 65 to 95 psig within the coil. In addition, there may
be a master pressure regulator on the main hot-gas line that
reduces pressure to about 100 psig. Any liquid or vapor
refrigerant leaving the coil is typically returned in the coil Figure 13: Frosted evaporator
suction line. coil
Water Defrost
In a water defrost system, warm water (typically 40 to 80°F) is sprayed over the coil surface.
Although well or city water is sometimes used directly, there is usually a tank or pit where defrost
water is stored. In a few cases, the water is heated by steam or electric resistance, but normally, it is
heated using heat recovered from the refrigeration system. In most cases, a remote condenser sump
serves double-duty as a defrost water tank, and water is heated
during condenser operation.
Hybrid Defrost
Although uncommon, some systems use a simultaneous combination of hot-gas and water defrost.
A typical application would be a freeze tunnel where completely eliminating all frost quickly is
critical to productivity.
Defrost Control
Defrost can be initiated manually, through simple local controls, or through a centralized
computer-control system.
The need for defrost is a function of air flow, the coil temperature, and the amount of moisture in
the air (which can vary seasonally or by product type). In cooled spaces that are seldom accessed
and contain covered or sealed food products, defrost requirements are minimal. Defrost introduces
significant heat to the refrigerated spaces through convection, radiation, and sublimation, so
minimizing defrost cycles while keeping coils frost-free and efficient is a goal of defrost controls.
Heat Exchangers
The second major category of evaporators is the heat exchanger. There are two main categories of
heat-exchange methods and several types of heat exchangers that are appropriate for each:
Heat-Exchange Methods
Direct-Contact Freezers
In this method, refrigerant is used to cool a food product such as juice or milk. This is usually done
with a plate-and-frame, shell and tube, or other specialty heat exchanger. Also, scraped-surface
exchangers are used for high-viscosity or hardening products such as puree, ice cream, or flake ice.
In other systems, refrigerant cools a plate or surface that is directly opposite a hardening product
such as cartons of ice cream or fish fillets. This is usually done with a plate freezer. Also, batch ice-
cube makers rely on contact between a refrigerated surface and freezing water.
Courtesy of Mueller
Figure 15: Heat exchangers: Shell-and-tube, inside (left top) and outside (left bottom); Plate-and-frame
(center); Falling-film (right)
Plate Freezers
A plate freezer (Figure 16) is
commonly used to harden or Courtesy of Cherry-Burrell (left) and APV (right)
freeze food products such as
cartons of ice cream or fish Figure 16: Scraped-surface heat exchanger (left) and plate freezer
fillets. The product is placed (right)
on a flat horizontal surface
Compressors
Introduction
The purpose of a compressor is to increase the pressure and
temperature of refrigerant vapor returning from the evaporators.
There are three primary types of compressors:
Reciprocating
Rotary screw
Rotary vane
Courtesy of Vogt
Reciprocating and rotary screw compressors are most common.
Although rotary vane compressors are rarely installed today, Figure 18: Cube ice maker
many are still in use.
This section describes the configuration, operation, and control of reciprocating, screw, and rotary
vane compressors.
Configuration
Reciprocating compressors use pistons to
compress refrigerant vapor within a cylinder.
Most compressors have 2 to 16 cylinders.
Figure 19 shows a 12-cylinder compressor.
The pistons are driven by a crankshaft which is
driven either directly, by an electric motor, or
indirectly, via a belt drive connected to a
motor. An inlet valve opens and low-pressure,
low-temperature refrigerant vapor is drawn
into the cylinder as the piston lowers. The inlet
valve then closes and the piston rises,
compressing the vapor. As the gas pressure Courtesy of Vilter
increases, it exits the cylinder through the Figure 19: Twelve-cylinder reciprocating compressor
exhaust valve. Figure 20 shows an internal
view.
In some uncommon applications, a “compound” compressor provides multiple stages of
compression in a single machine. For example, four cylinders might provide a first stage of
compression, and another two cylinders may provide a second stage. Compound compressors are
used to improve efficiency and to extend the operable pressure range of the machine.
Capacity Control
All reciprocating compressors use a form of
cylinder unloading to control capacity. The
inlet valve is held open (either by oil pressure
or discharge-gas pressure), preventing the
cylinder from compressing. Although the
piston still draws suction gas on its downward
stroke, it simply pushes the gas back into the
suction line during the upward stroke. Most
compressors have simple unloading stages (such
as an 8-cylinder machine unloading to 75%,
50%, and 25%).
In general, electric solenoids activate unloaders. Figure 20: Cut-away view of compressor
The electric solenoids can be managed by
pressure switches mounted directly on the compressor, by remote electro-mechanical switches, or
by a modern computer-control system.
Cylinder unloading is an efficient form of capacity control, with a nearly proportional reduction in
capacity and power (see Figure 21).
Power
supplied from an adjacent 50%
0%
costly in terms of water use 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Control
As mentioned before, reciprocating compressors are often provided with simple pressure switches
for cylinder unloading and safety cut-outs. Microprocessor-based controls are rarely provided for
reciprocating compressor packages.
Advantages Disadvantages
Low Cost Frequent Maintenance
Simple Maintenance High Maintenance Cost
Efficient Unloading Limited Capacity/Size
Compact Discrete Unloading
Many Moving Parts
Configuration
Screw compressors come in two designs: twin
and single screw.
Twin Screw
A twin screw has a male and female rotor
which rotate and mesh together (see Figure 22).
Refrigerant vapor is drawn into the space
between the rotors, and as the rotors turn and
mesh, the vapor is trapped. As the rotors
continue to rotate, the vapor is compressed and Courtesy of Frick
pushed to the opposite end of the compressor.
The vapor is then opened to the discharge port, Figure 23: Screw compressor package
and pushed from the compressor.
The screw compressor package relies on oil to seal the rotors during compression. In addition, oil is
pumped through bearings for lubrication. After compression, the refrigerant vapor and oil are
mixed and must be separated. The compressor and driving motor are commonly mounted on top of
an oil separator, as shown in Figure 23. The oil separator has coalescing elements that trap the
entrained oil from the refrigerant vapor stream.
Single Screw
The single-screw design is
relatively new and has a single
rotor and two gate rotors, one
on each side (see Figure 24).
The center female rotor is
driven by the motor and the
two male gate rotors mesh
with, and turn alongside, the
female rotor. The resulting
compression is similar to that
Courtesy of Vilter (right)
of a twin screw.
Figure 24: Single-screw compressor
Figure 26: Diagram of slide valve unloading (left) and Photograph of slide valve (right)
Cooling
Screw compressors use oil for lubrication and cooling during the compression process, so heat must
be removed from the oil continuously. There are several methods of cooling screw compressors,
including:
Liquid injection
Thermosiphon
Water or glycol cooling
Direct cooling
Liquid injection cooling imposes a small capacity penalty, and can impose a power penalty of 1% to
10% or more. The power penalty results from the need to recompress the refrigerant that was
injected into the compression process. In general, the power penalty increases with pressure ratio,
and is greatest in single-stage applications with a low suction pressure.
An additional disadvantage of liquid injection is
the need to elevate condensing pressure to
ensure adequate pressure to inject properly.
Older designs had a minimum pressure
requirement of 100 to 125 psig, although
modern designs with electronic expansion
valves are capable of operating at lower
pressures.
In a small number of applications, the injection
occurs in the compressor discharge line. This
eliminates the power penalty, but requires a
booster pump. A small liquid pump boosts
liquid pressure sufficiently to allow injection
into the compressor discharge piping. Figure 29
shows one manufacturer’s discharge injection
system.
Courtesy of Vilter
Direct-Contact Cooling
A recently developed
technology is direct-contact
cooling between the
refrigerant and oil. A layer of
liquid refrigerant is
maintained on top of the oil
within the oil separator. The
refrigerant boils in the
separator, cooling the oil. A
mixture of oil and liquid
refrigerant is injected into the
discharge end of the rotor Courtesy of Vilter
Beginning of Compression
Discharge
set manually through mechanical adjustment. 120
Pressure
Pressure (psi)
The location and shape of the discharge port is 100 Overcompression
End of Compression
80
Undercompression
Why does the VI matter? It can significantly 40
Compression Process
system, overcompression or undercompression
occurs (Figure 32).
Figure 32: Diagram of overcompression and
In the case of undercompression, the gas within undercompression
the compressor does not rise to the pressure
outside the discharge port. As the rotors turn and open to the discharge port, gas actually rushes
into the compressor from the discharge line. This gas must be recompressed and discharged from
the machine. This results in inefficiency.
In the case of overcompression, the gas within the compressor
rises to a pressure higher than that outside the discharge port.
Unnecessary work on the gas within the compressor also results
in inefficiency.
Ideally, the gas pressure within the compressor perfectly matches
the pressure outside the discharge port. Correctly selecting a
fixed-VI compressor, adjusting a manual VI port, or upgrading to
an auto-VI feature will improve efficiency (see Screw Compressor
Volume Ratio on page 68 for details).
Compressor Control
Virtually all new screw compressors are controlled by a
microprocessor panel mounted on the compressor package (see
Courtesy of Frick
Figure 33).
Figure 33: Compressor control
Although many older packages were originally equipped with panel
simple electro-mechanical controls, these can be upgraded to a
modern panel for additional features and improved integration with a central computer-control
system.
Advantages Disadvantages
Long maintenance intervals High initial cost
Available in large capacity Factory-level service requirements
Slide valve with infinite control Inefficient unloading
Few moving parts Large package size
Cooling
In many rotary vane booster applications, no cooling is required because of the very low operating
suction temperature. However, water cooling is used when needed.
Control
Virtually all applications are operated manually or with simple pressure switches or a computer-
control system.
Advantages Disadvantages
High-volume capacity No or limited capacity control
Compact Susceptible to vane damage
Noisy
Performance Ratings
Full-Load Ratings
All compressors are rated for capacity and power at various suction and discharge pressures and
temperatures. Ratings are often available as a table, performance curves, or through factory-
provided software.
Capacity is rated in tons of refrigeration (TR), where 1 TR = 12,000 BTU/hour. Power is
universally rated in brake horsepower (BHP), the input power required at the shaft. Table 6 shows
sample ratings.
There are three general rules that can be applied to any set of full-load compressor ratings:
Raising suction pressure increases compressor capacity.
Lowering discharge pressure decreases power.
In all cases, raising suction or lowering discharge pressure improves BHP/TR.
These rules will be used in later sections to improve compressor and system efficiency (see
Increasing Suction Pressure, page 46 and Reducing Discharge Pressure, page 49).
Part-Load Ratings
Traditionally, full-load ratings have been the focus for designing and assessing the overall
performance of compressors. Only recently has part-load performance become prominent,
particularly in response to increased energy awareness. Unfortunately, part-load ratings for
compressors are developed and presented less consistently than full-load ratings, making it difficult
to compare the part-load performance of equipment from different manufacturers.
Historically, only general part-load ratings were published. That is, performance at specific
operating conditions was not rated. In addition, manufacturers would “take liberties” with
performance curves, for example, claiming reduced discharge pressure when unloaded to mask
inefficiency. It was difficult to accurately assess compressor performance at reduced load.
These rules will be used in later sections to improve compressor and system efficiency (see
Improving Compressor Part-Load Performance, page 59).
Courtesy Imeco (left), Evapco (center), and Baltimore Air Coil (right)
Figure 37: Forced-draft, axial fan condenser (left); Induced-draft, axial fan condenser (center); Forced-draft,
centrifugal fan condenser (right)
Capacity Ratings
Full Load
All evaporative condensers are rated at nominal conditions (in thousands of Btu/hr, or MBH), and
are corrected based on condensing temperature and entering wet-bulb temperature. These
correction factors are virtually universal across all manufacturers and models.
Dry Operation
If a condenser must be operated without water (conditions below freezing), the fans can be operated
alone. In this situation, heat transfer is very poor. Condenser manufacturers provide ratings for dry
operation, but, as discussed in Wet vs. Dry Operation (page 64), dry operation is very inefficient
and should be avoided unless absolutely necessary.
Introduction
Some important components of an industrial refrigeration system do not use energy directly but
nonetheless affect the overall energy efficiency of the system. Examples include vessels, valves, heat
exchangers, purgers, and other miscellaneous equipment. It is important to be familiar with these
components and their role in system efficiency.
Vessels
Low-Pressure Receivers
A low-pressure receiver (LPR) is an insulated
tank that holds low-pressure, low-temperature
liquid ammonia to be sent to evaporators
(Figure 38). The liquid is pumped to the coils,
and some of it (typically 1/4 to 1/3) boils in the
evaporator coil. The mixture of vapor and
liquid returns to the LPR where the gas rises to
the top and is drawn away by the compressor
suction. Since only some of the refrigerant is Figure 38: Low-pressure receiver (LPR) with
boiled in the evaporator, this system is often insulation and liquid pump
called “overfeed” or “liquid recirc.”
We address the LPR and its piping and valves in Chapter 4:Best Practices for Equipment, Systems,
and Controls because overfeed rates and other related issues can affect efficiency.
Accumulators
An accumulator is also an insulated tank that holds low-pressure, low-temperature liquid ammonia.
It is located above an evaporator coil or heat exchanger, and the liquid ammonia level is held about
midway in the accumulator and thus completely floods the evaporator below it. Virtually all
accumulators have a manual, dual-position, or motorized pressure regulator between the vessel and
the compressor suction line that manages ammonia pressure and temperature within the coil.
We address adjusting and controlling pressure regulators on these coils in Optimum Evaporator
VFD Control and Set Points on page 57.
High-Pressure Receivers
A high-pressure receiver (HPR) is an
uninsulated tank that holds the high-pressure
liquid draining from the condensers (Figure 40).
Virtually all refrigeration systems have some
kind of HPR. It is usually located in the engine
room, but it is sometimes located on the roof
immediately below the condensers, or outdoors
adjacent to the engine room. These vessels can
be horizontal or vertical designs.
Controlled-Pressure Receivers
Figure 40: High-pressure receiver (HPR)
A few systems use a gas-pressure design, where
compressor discharge gas is used to move liquid refrigerant throughout the coils and between
vessels. In lieu of a high-pressure receiver, these systems use a controlled-pressure receiver (CPR). In
a system with a standard HPR, the pressure inside the vessel floats with system condensing pressure.
With a CPR, pressure in the vessel is held at a constant level, typically 65 to 100 psig. Gas-pressure
systems are often inefficient, and the CPR often presents a bottleneck to reducing condensing
pressure.
Valves
Liquid Solenoids
A liquid solenoid is a valve
that opens and closes to
manage liquid )or gas)
refrigerant flow (Figure 41,
left). Almost all refrigeration
Courtesy of Hansen
systems include liquid
solenoids. A liquid solenoid Figure 41: Liquid solenoid (left); Metered liquid solenoid (right)
opens and closes to manage
the flow of liquid refrigerant. Solenoids are commonly used for evaporator feed in recirculated
systems, for make-up liquid to LPRs and intercoolers, and for miscellaneous applications such as
compressor liquid injection.
Valves Figure 42: Hand expansion valve (left); Thermal expansion valve (right)
Thermal expansion valves are
used on the rare applications that include a direct-expansion evaporator coil, on screw-compressor
liquid-injection systems (Figure 42, center, right), and on less common applications. Older thermal-
expansion valves use a classic bulb-and-diaphragm design, although new electronic versions are
becoming increasingly popular for greater flexibility and control.
Pressure Regulators
Pressure regulators maintain a
steady pressure at their inlet
or outlet (Figure 43).
Examples include a suction-
pressure regulator on a
flooded evaporator coil, or a
hot-gas-defrost regulator.
Pressure regulators are
common in industrial
refrigeration systems. They
can either be manual (set to
maintain a fixed pressure), Courtesy of Hansen
Purgers
Systems operating with negative suction pressures (below atmospheric pressure) can draw air into
the system. Left unresolved, the added air results in increased condensing pressures. We discuss the
benefits of purgers (Figure 44) in Purgers on page 75.
Controls
Introduction
All industrial refrigeration systems must be controlled to keep temperatures, pressures, and other
critical variables within suitable ranges. Refrigeration controls affect production, safety, and
efficiency. The basic features of most computer-control systems are:
Evaporator liquid solenoid and pressure regulator control
Evaporator fan on/off control
Evaporator defrost control
Compressor on/off and unloading control
Condenser pump and fan on/off control
The presence of advanced control features depends on the control system capabilities and the
customer’s needs.
There are four basic categories of control systems:
Manual control
Electro-mechanical control
Simple programmable logic controllers (PLC)
Computer control
Manual Controls
Manual control is simply the complete management of equipment by attending personnel.
With manual control systems, system operators simply turn on equipment (such as a compressor,
condenser pump, or fan) and, in some cases, adjust capacity as needed. Simple push-button controls
or hand switches are most common for equipment start and stop. Manual control is increasingly
uncommon.
Electro-Mechanical Controls
Electro-mechanical controls use simple pneumatic or electronic circuitry to manage refrigeration
equipment.
Electro-mechanical controls are still relatively common, particularly for small systems where
computer control is not cost-effective, and with equipment such as reciprocating compressors where
pressure switches are often integrated with the equipment by the manufacturer.
Pressure Switches
Simple pressure switches are most often used to unload the cylinders in reciprocating compressors
and to control the cycling of condenser pumps and fans. There are two common types of pressure
switches:
Spring-loaded
Mercury
Thermostats
A thermostat senses temperature changes and activates a switch
that controls a piece of equipment. In refrigeration systems, they
are most often used to control evaporator coils and associated
liquid solenoids and fans. Figure 46 shows a sample application.
Simple Programmable
Logic Control (PLC)
Figure 47: Electro-mechanical control system
Small systems can be
controlled using simple programmable logic controllers, or PLCs (Figure 48). These types of
controllers perform the same basic functions as electro-mechanical controls, using solid-state
hardware in lieu of pneumatic, thermostatic, and electrical (relay) controls. Common PLCs include
the Honeywell Universal Digital Controller (UDC) series and the Allen-Bradley SLC 500. UDC
Computer Control
Introduction
Courtesy of Honeywell
Computer-control systems for refrigeration first became
Figure 48: Simple digital
available in the late 1980s and early 1990s. These systems were a
controller
remarkable leap forward in control, trending, alarms, and other
operations. Since these early systems, the capabilities of computer-based controls have expanded
dramatically, with easy-to-use graphical interfaces, remote access, and advanced features.
Control Software
In the earliest systems, computer control depended on Unix, DOS, Assembly Language, C++, and
other low-level languages. These systems were usually proprietary, and have mostly given way to
systems with modern, open software platforms such as Wonderware, Intellution, Allen Bradley,
GE, Think-N-Do, and others. However, there are still many systems that use proprietary or low-
level software for control. Advanced features, brought about by Microsoft Windows and its
graphical user interface, networking, and the Internet, have expanded the abilities of control
software. In general, there has been an evolution away from proprietary and low-level software
toward open architectures that require less arcane coding.
Introduction
Until the early 1990s, the use of variable frequency drives (VFDs) in industrial refrigeration was
rare. Throughout the 1990s, VFDs began to appear as a standard factory-offered option for other
equipment such as centrifugal water chillers. In the early 2000s, even rotary-screw air compressors
offered VFD options. Only relatively recently have manufacturers of industrial refrigeration
equipment embraced VFD technology. Now, virtually all prominent manufacturers of screw
compressors for industrial refrigeration offer VFD control as a factory option. It is also possible to
retrofit VFDs on many existing compressor systems. In addition, all prominent condenser
Standard Motors
Whether driving fans, pumps, or compressors, virtually all industrial refrigeration motors are three-
phase induction units that operate at fixed speeds of 900, 1200, 1800, or 3600 rpm. Motor speeds for
typical equipment are:
Evaporator Fans: 1200 or 1800 rpm
Compressors – Reciprocating: 1200 rpm (direct) or 1800 rpm (belt)
Compressors – Rotary Screw: 3600 rpm
Compressors – Rotary Vane: 900 or 1200 rpm
Condenser Fans: 1800 rpm
The operating speed of the motor is determined by the frequency of the line current (in North
America, 60 Hertz, or 60 cycles per second), and the winding configuration (number of poles) of the
motor. When running unloaded a motor turns at its nameplate-listed speed, slowing a few percent
as load is placed on the shaft. Equipment run by motors at a single, fixed speed meet peak loads
requirements, but do not accommodate part-load conditions well, which account for most operating
hours.
Waveform Sample - VFD Output Voltage Waveform Sample - VFD Output Current
1600 600
1200 400
800
200
400
Voltage
0
Amps
0
-200
-400
-400
-800
-1200 -600
-1600 -800
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
Time (milliseconds) Time (milliseconds)
VFDs are available in a wide range of capacities, from fractional horsepower to thousands of
horsepower. In the United States, virtually all industrial refrigeration applications are 480-volt,
although some 240 volt applications still exist. Although rare in refrigeration, medium voltage
units—2300 to 4160 volts—are also available. Figure 52 shows a VFD installation.
VFD Issues
Size of VFD
Need for bypass feature
Input reactor or
harmonic filtering
Output reactor or dV/dt
filtering
Grouping of multiple Figure 54: Graph of torque and power versus speed for a variable
motors torque load
Motor Issues
Cooling at reduced speed
Insulation dielectric capabilities
Current in bearings
Driven-Equipment Issues
Minimum and maximum allowed speeds
Resonant frequencies
Control Issues
Serial or discrete I/O for control
Control algorithms
Control set points
Alarms and faults
In the Best Practices chapters, we address these issues and the proper application of VFDs to
evaporator fans, screw compressors, and condenser fans; we identify inappropriate refrigeration
applications such as reciprocating compressors and condenser pumps; and we discuss proper control
algorithms.
Introduction
This chapter covers engineering opportunities to improve refrigeration system design, select
efficient components, and control the system optimally. The chapter methodically addresses the
“Big Picture” efficiency categories introduced in Chapter 2: Best Practices Overview:
Reducing Lift (below)
Improving Part-Load Performance (page 55)
Upgrading Equipment (page 65)
Improving System Design (page 72)
Reducing Refrigeration Loads (page 76)
At the end of this chapter, we highlight the importance of computer controls (page 79) and provide
three checklists (page 80) pertaining to evaporators, compressors, and condensers that help tie
together these concepts.
Reducing Lift
Introduction
“Lift” in a refrigeration system is the difference between suction pressure and discharge pressure at
the compressor. Reducing lift by raising suction pressure or lowering discharge pressure improves
compressor efficiency. Three general rules apply to lift:
Increasing suction pressure increases compressor capacity.
Reducing discharge pressure decreases power.
Increasing suction or reducing discharge pressure reduces BHP/TR (brake horsepower per ton
refrigeration) and thereby increases efficiency.
This section presents methods for reducing lift, discusses some of the barriers to doing so, and
presents the potential energy savings. Note that suction and discharge pressure are often referred to
as temperatures, as there is a direct, proportional and consistent relationship between the pressure
and temperature of saturated ammonia vapor. This section will sometimes use one or the other
description. Table 7 describes the relationship between pressure and temperature for ammonia.
Table 7: Relationship between pressure and temperature for ammonia at sea level
In both Seattle and Miami, these conditions correspond to the dry-bulb temperature ranges from
44°F and below. In Seattle, there are 2,907 hours—about one-third of the year—when the system
could operate at 90 psig. In Miami, however, there are only 24 hours—about 0.3% of the year—
when the system could operate at 90 psig.
As this example shows, trying to reduce minimum condensing pressure to this 90-psig target will be
a more fruitful exercise in Seattle than in Miami.
Common Misperceptions
In addition to equipment or system barriers, there are also some common operational
misperceptions that limit efforts to reduce minimum condensing pressure. Some of the common
misperceptions are:
Concern About Increased Condenser Power In nearly all cases, reducing condensing pressure will
increase condenser pump and/or fan power. However, compressor energy savings will nearly
always exceed the increase in condenser energy consumption. Only when available condenser
capacity far exceeds operating compressor capacity (for example, in a processing facility in
“holding” mode on the weekend) could increased energy use by the condenser outweigh compressor
savings. In this case, applying a wet-bulb approach algorithm will operate an adequate amount of
condenser.
Issues of Screw Compressor Volume Ratio A screw compressor with a fixed internal volume ratio
(VI) can experience overcompression or undercompression when external pressure ratios do not
match the internal design of the compressor. Although this reduces the adiabatic or isentropic
efficiency of the compressor, compressor efficiency (in terms of brake horsepower per ton, or
BHP/TR) always increases when suction increases and discharge pressure decreases. Compressor VI
should never be used to justify maintaining an artificially high discharge pressure.
Operator Tradition Unfortunately, the preferences or traditions of system operators may result in
high condensing pressure. System operators often mark “target” or “acceptable” pressure levels on
master discharge pressure gauges in the engine room. When they grow accustomed to seeing system
pressure steady at some elevated value, they can find it disconcerting to see condensing pressure fall
to unprecedented levels during cool weather, even though that may be a perfectly reasonable
condition under a newly implemented control strategy. Ultimately, as system operators become
more familiar with new operating parameters and strategies, they will become more comfortable
with variations in operating conditions.
Introduction
In the simplest and least efficient scenario, evaporator fans operate non-stop at full speed except
during defrost. All evaporator capacity control (and hence, space temperature management) is
achieved with liquid solenoids (in recirculated or direct-expansion systems) or pressure regulators
(in flooded systems). Energy use of the evaporator fan is constant. Because of this, any reduction in
fan energy use through improved part-load operation has the added benefit of reducing space
refrigeration load from fan and motor energy. This can be done with fan cycling, two-speed fans, or
with VFDs.
Best Practices:
Fan Cycling Evaporator Fan Control
Computer controls for refrigeration systems
can allow evaporator fans to cycle—that is, turn Evaporator fan VFD control is the most efficient
off and on periodically. The most common option.
strategy is to cycle all evaporator fans off when Use VFD-rated motors or protect existing
the desired space temperature is reached.
Another strategy (used, for example, in motors with filters.
controlled-atmosphere fruit storage) is to Install temperature probes at worst-case
schedule fan cycling; for example, the fans are
locations to ensure uniform temperatures.
on for two hours and off for two hours. Some
systems even use an alternating strategy, where Tailor minimum speeds to the specific
every other evaporator fan operates for a set application.
period of time, and then the remaining fans
operate for the same duration. This is used in Benefits Beyond Energy
some fruit storage with the idea that the scheme
provides diversity in air flow patterns while More stable storage temperatures than with fan
saving energy. cycling.
Another strategy is to cycle fans off a few Lower moisture losses for exposed products.
minutes after shutting off refrigerant flow with Flexibility associated with continuous fan speed
the liquid solenoids. And some systems use a
“swirl” strategy where the evaporator fans adjustment.
operate periodically—say, 5 of every 30 More comfortable working environment when
minutes—to move air around. loads are low (lower air movement and
In some situations, entire coils or zones are quieter).
manually turned off by the system operator.
An example is a refrigerated dock in a food
distribution center, where dock cooling is not
needed for a season. A similar approach is to manually turn off one (or more) of several fans (often
using overloads or by pulling fuses). An example is a fruit storage facility in holding mode.
With any form of fan cycling, savings are maximized by operating as few fans for as little time as is
necessary to maintain the required space temperature. This is usually best accomplished using
computer-control systems that operate evaporator fans strictly as needed.
Two-Speed Fans
Two-speed fans can operate at three conditions—off, half speed, and full speed—and require special
two-speed starters. They offer a level of control between fan cycling and VFD control. At half
speed, fan power obeys the affinity (or cubic) laws and draw about 1/8 the power needed to run at
full speed while still moving about one-half the air.
1
Field measurements, which include motor and VFD losses, indicate that the “real-life” affinity-law exponent
is about 2.7 (instead of the theoretical 3.0). That is, fan power= (fraction of speed)2.7.
Some of the key design and implementation issues for a successful installation are discussed below.
Multiple / Small Motors A VFD can drive from two to more then thirty motors. In applications
with many small (<1 hp) motors, the total impedance seen by the VFD output circuitry can be
very high.
Harmonics and Input Reactors To limit harmonic feedback into the system and to protect the
input circuitry of the VFD, a 3% input reactor should be considered for all VFDs. Some VFDs offer
built-in reactors or harmonic filters.
Motor Protection with Output dV/dt Filters Because of the square-pulse waveform of the drive
voltage output and the fast switching of VFD transistors, the VFD and the motors it controls
exhibit a reflected-wave phenomena. This reflected wave can have voltage spikes above the rated
capacity of the motor insulation system. The increased potential between motor windings results in
corona that can break down winding insulation. Over time (anywhere from hours to years), the
breakdown will result in a ground fault within the motor. An output reactor or dV/dt filter should
be installed to reduce or eliminate this danger.
Introduction
The efficiency of all industrial refrigeration compressors degrades as they operate at a fraction of full
capacity. Figure 58 shows the relationship of power input and part-load fraction for a screw
compressor.
In general, the following
Sample Screw Compressor Part Load
strategies improve the
efficiency of the compressor 100%
system: 90%
80%
1 Limit part-load operation.
70%
compressor. 0%
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Capacity
Also, keep these part-load
characteristics in mind:
Figure 58: Typical part-load power for a constant-speed screw
Reciprocating compressor
compressors with
These criteria can help you configure equipment and select control algorithms to operate your
compressors efficiently.
Best Practices:
Improved Compressor Sequencing Compressor Sequencing
Basic control systems often stage compressors
in a fixed order. Although this method is Use computer control to manage compressor
popular because it is simple, it virtually sequencing.
guarantees that at least one compressor operates The control-system programmer must address
at partial capacity (and therefore inefficiently).
For example, consider a bank of three load variations in a way that avoids excessive
compressors of 100, 200, and 400 hp. Unless the motor starts and stops.
system operator manually selects compressors
Use a mix-and-match compressor sequencing to
or stages the control system, the larger
compressors could run significantly unloaded. best meet the load.
This situation is even worse for systems with Keep base-load compressors fully loaded.
identically sized compressors.
The trim compressor on each suction system
An alternative is to “mix and match” the should be a VFD-driven screw or reciprocating
combination of compressors that operate to
meet the varying load, as shown in Table 9. In compressor.
this strategy, each increment of required
compressor capacity is met as closely as Benefits Beyond Energy
possible with the best combination of available Less compressor run-time means less frequent
compressors. Compressor capacity is added in
100-hp increments—1/7 of the total capacity. maintenance and lower maintenance costs.
The penalty for part-load inefficiencies is
significantly reduced.
Stage Number
Unit
1 2 3 4 5 6 7
100 hp z z z z
200 hp z z z z
400 hp z z z z
Screw compressors benefit much more from improved sequencing than reciprocating compressors
which have excellent part-load performance characteristics.
In systems with both screw and reciprocating compressors, a good strategy is to use screw
compressors (operating continually at full capacity) for base loads, and use reciprocating
compressors to meet fluctuating loads as the trim compressor.
System operators often hesitate to have screw compressors (particularly large units) turn on and off
throughout the day. A compressor in disrepair may fail to restart when instructed by a control
system, or there may be anti-recycle issues that limit the effectiveness of the mix-and-match strategy.
Any barriers to implementing this mix-and-match strategy should be addressed.
Introduction
In the simplest configuration, the capacity of evaporative condensers is controlled by using simple
pressure switches or computers to cycle the pumps and fans of this equipment. In most cases,
pumps are turned on before fans. This section discusses ways to improve fan control and control-
system algorithms.
Two-Speed Fans
Manufacturers have offered two-speed fans for condensers for some time. One variation is a half-
speed pony motor driving the same shaft. In either configuration, the fans can be operated at full or
Best Practices:
Upgrading Equipment Evaporator Selection
Surface Air
Capacity Fan Total Efficiency
Option area Velocity
(TR) Configuration BHP (TR/BHP)
(sq ft) (fpm)
#1 52.3 15,627 595 4 × 2 hp 8 6.54
#2 48.7 11,313 647 4 × 2 hp 8 6.09
#3 49.8 14,650 615 4 × 2 hp 8 6.23
#4 49.5 12,503 632 4 × 2 hp 8 6.19
#5 51.1 12,067 625 4 × 2 hp 8 6.39
#6 47.5 11,722 655 4 × 2 hp 8 5.94
#7 47.6 15,627 595 4 × 2 hp 8 5.95
#8 51.5 11,722 733 5 × 2 hp 10 5.15
#9 52.8 11,313 725 5 × 2 hp 10 5.28
#10 54.3 14,650 682 5 × 2 hp 10 5.43
Refrigerant Feed
Liquid overfeed or flooded
evaporators are more efficient
than direct expansion (DX)
evaporators. There are three
reasons to avoid DX coils.
First, DX coils are derated
since some of the coil surface
area is not internally wetted.
Second, DX coils can limit the
reduction of condensing
pressure. Third, evaporator
fan VFDs are difficult to
implement on DX coils.
Figure 61: Graph of coil efficiency versus face velocity
Efficient Fan Blades
Some evaporator coils, particularly those with
small (less than 1 hp) fans, may have stamped-
steel fan blades of an older, inefficient design.
Modern alternatives provide the same fan
performance (in terms of air flow and pressure)
but require less shaft power.
In Figure 62, the fan blade on the right is the
original four-blade version provided with the
coil. The fan blade on the left performs nearly
identically, but uses about 1/3 less shaft power.
(In this example, the fan blade was teamed with
a premium-efficiency motor and VFD control Figure 62: Newer efficient fan-blade design (left)
for a package upgrade.) Purchased in bulk, the and older less efficient design (right)
new fans cost about $10 to $15 each. (It is
Penthouse Applications
Locating evaporator coils in a penthouse (Figure 8, page 14) offers many advantages, including
simplified maintenance. However, a penthouse design can be energy intensive for several reasons,
including:
Additional nozzles or ductwork increases pressure drop and fan power.
The coils are centrally-located, requiring additional air flow and velocity for proper air
movement.
The coils may discharge air perpendicular to aisles, requiring higher air velocity for air
movement.
For these reasons, you should evaluate penthouse designs by comparing them to ceiling-hung
evaporators based upon all quantifiable life-cycle costs. If you implement a penthouse design, use
fan-control strategies (for example, VFD control, simultaneous speed control) to minimize energy
use.
Best Practices:
Compressor Efficiency Screw Compressor Options
1.8
This figure shows that, for
BHP/TR
Table 11: Compressor capacity and power ratings at a condensing temperature of 85°F and various suction
temperatures for ammonia
Best Practices:
Condenser Efficiency Efficient Condenser Selection
manufacturer. Figure 65
MBH per Fan/Pump HP
300
shows an example of such a
graph that compares forced- 250
100
In general, centrifugal-fan
condensers are least efficient. 50
fan units are both more 5,000 10,000 15,000 20,000 25,000 30,000
When low-efficiency condensers are installed, the reason is usually that they cost less. The
condenser cost (in $/MBH) is the lowest at the greatest capacity for a given tube bundle size range
(that is, at the right end of the bands on the graph). Increased air flow is a relatively low-cost
method of adding capacity, albeit at the expense of efficiency.
It is important to compare condenser models or manufacturers at the same wet-bulb and condensing
temperatures. Some manufacturers use different nominal conditions, making direct comparison
difficult.
350
Traditionally, evaporative condensers have purger for systems that operate under vacuum.
relied on very simple spray nozzle designs. Use modern high-performance spray nozzles.
These metal or plastic nozzles were equipped
with a small hole for water spray, and would
Premium-Efficiency Motors
All major pieces of refrigeration equipment can be ordered with
premium-efficiency motors. Most evaporator and condenser
manufacturers offer two or three brands of motors, each
available with a premium-efficiency line. You can ask
manufacturers about their current products, and select the motor
with the highest efficiency.
Compressors are treated somewhat differently. Most motor
manufacturers offer a premium-efficiency series through the Courtesy of Frick
largest NEMA frame size (400 to 450 hp). Anything above this
Figure 66: High-performance
size is considered custom and often built to order. Premium- spray nozzles
efficiency motors cost more, so you should specify them with
care; the energy savings from the increased efficiency may not outweigh the higher initial
equipment cost.
Many motor manufacturers offer their Motor Efficiencies - 1800 rpm
premium line as their recommended inverter- 100
96
designation of “NEMA Premium” indicates a 94
92
84
energy use because of the affinity law. 82
ODP-Highest Available
ODP-EPACT
80
0 50 100 150 200 250 300 350 400 450 500
Motor Sizing
Power (hp)
It is important that a screw compressor motor Figure 67: Motor efficiencies – 1800 rpm
be adequately sized to prevent current-limiting.
Current-limiting occurs when a motor exceeds its full-load amps (FLA) rating, and operates into the
service factor. Virtually all modern screw compressors use forced unloading to protect the motor
from overheating. A compressor that is current-limiting is inefficient (since it is unloaded), and may
cause another compressor to start to satisfy the load. You should carefully assess both maximum
discharge pressure and suction pressure to prevent current-limiting.
Liquid Subcooling
Liquid subcooling is a process of cooling liquid refrigerant below
the saturated condensing temperature for the purposes of Figure 69: Two-stage system
increased capacity and efficiency. Whenever multistaging or with multiple temperature levels
economizers are applied, subcooled liquid is available. Serving
loads with subcooled liquid increases efficiency by reducing the total amount of refrigerant that
must be supplied and compressed from evaporator loads. Hence, additional stages of subcooling,
and using subcooled liquid whenever possible are two methods of increasing efficiency.
In the previous example of five suction levels, the +35°F system could serve liquid to the +5°F
system. The +5°F system could then serve the -65°F, -45°F, and -35°F systems. These lowest
suctions would benefit from two stages of subcooling, substantially increasing efficiency.
In applications with single-stage economized screw compressors, the economizer port on an
unloaded screw compressor will become inactive as the compressor unloads (for example, at 70%
capacity). Unless there are other operating economized compressors or a stand-alone subcooling
system, efficiency will suffer due to diminished or eliminated liquid subcooling.
2
Detailed explanations of these systems are beyond the scope of this guide.
Best Practices:
Hot-Gas Defrost Hot-Gas Defrost
In the Reducing Lift section of this chapter
Only defrost when needed.
(page 46), we addressed the importance of
avoiding high condensing pressures for defrost. Only defrost for as long as needed.
Four other basic tenets apply to energy- Return hot gas defrost to the highest available
efficient defrost:
suction system.
1 Use free sources of heat for defrost (hot gas
or water). Avoid any form of electric Benefits Beyond Energy
resistance heating.
Reduces system loads, which frees compressor
2 Only defrost when needed.
capacity and reduces compressor run time.
3 Only defrost for as long as needed. Results in more stable operation.
4 Return hot gas defrost to the highest
available suction system.
Water defrost has relatively little effect on system efficiency. Since the evaporator coils are heated
during every defrost, minimizing the frequency of defrosts will maximize efficiency.
On the other hand, hot-gas defrost can have a significant effect on system efficiency. Ideally, all hot
gas entering the evaporator coil would condense and return to the engine room as liquid to be used
in the refrigeration cycle. In practice, hot gas passes through the coil and defrost pressure regulator
toward the end of the defrost cycle, returning to a compressor suction line. This gas must be
recompressed in the engine room, often placing a significant load on the compressors. Obviously,
using computer controls to minimize the frequency and duration of defrost will save energy.
Heat Recovery
Heat recovery, particularly for food processing facilities, is popular. Many systems use hot
compressor discharge gas for underfloor heating (using glycol), boiler makeup water, or plant
cleanup water. The greatest opportunity to recover heat is through a desuperheater, where water
can be heated as high as 100 to 120°F in a circulating loop. Unfortunately, about 10% or less of total
compressor heat rejection is superheat, so the total heat (Btus) available for recovery is limited.
If a condensing heat exchanger is installed, water temperature is limited to the condensing
temperature which, at 90 psig for ammonia, is only 58°F. Although most of the total rejected
compressor heat is released in condensing, the quality of the heat recovery is limited by saturated
condensing temperature. In this case, the water could not be heated higher than the 58°F
temperature of the condensing ammonia.
The economics of heat recovery often depend on the relative costs of electricity and natural gas or
other fossil fuels. In some situations, it may be cost-effective to operate at elevated discharge
pressure to increase heat recovery. In most cases, however, the energy cost savings from reduced
condensing pressure outweighs the savings afforded by increasing heat recovery. In addition, any
analysis should include the effect on compressor energy of the pressure drop on the ammonia side
of the heat exchanger.
In some multicompressor applications, one or more compressors can be operated at increased
discharge pressure to act as heat pumps. An example would be a large vegetable processor that uses
steam or other sources to heat defrost water. In this case, heat recovery from the refrigeration
system may be cost-effective, because compressor heat pumps can produce water temperatures up to
85 or 90°F.
Best Practices:
Purgers Non-condensable Purger
Refrigeration systems operating with a suction
Install an automatic purger for systems that
pressure below atmospheric pressure inevitably
pull air into the system. The air ultimately ends operate in a vacuum some or all of the time.
up in the condenser, where, as an ideal gas, it As a non-condensable gas check, the computer-
drives up condensing pressure (due to partial
pressures of the mixed air and ammonia vapor)
control system should monitor the temperature
and therefore decreases efficiency. One way to of the high-pressure liquid ammonia draining
gauge the effect of air in the system is to from the condenser.
measure the pressure within the condenser, and
measure the liquid temperature leaving the Benefits Beyond Energy: Effective
condenser. With no air in the system, the Non-condensable Gas Purge
condensing temperature and liquid temperature
should be the same. An increasing difference Effective purging helps avoid overloading or
between these two values indicates the buildup current-limiting the compressor motors, which
of air in the system.
can reduce production or product quality.
The effect of air in the system is increased
condensing pressure during summer months,
and possibly increased condenser fan and pump energy during winter months.
Automatic purgers can be installed to remove air from the system. Even if the air adds only a few
pounds to condensing pressure, the entire compressor system discharging to the condenser is
Best Practices:
Building Upgrades Fast-Acting Doors
Figure 70: Strip curtain (left), fast-folding door (center), and vestibule-style door (right) for infiltration
control
3
These heaters use more energy than is wasted from infiltration through a fully open doorway.
Chapter 3: Refrigeration System Basics outlines various control system types. We recommend that
you refer to that chapter to review the options. Although there are several variations on computer
control, we generally recommend that the control solution have these three attributes:
It is designed and built by a firm that specializes in industrial refrigeration control. These
systems consistently have the highest level of functionality. Their designers have typically already
encountered and addressed many issues that are specific to industrial refrigeration. Control systems
put together by generalists can work just as well, but the design process will likely be less efficient.
If you use a generalist, make sure a knowledgeable refrigeration consultant, either in-house or
contracted, is on the team.
It is designed and built by a control-system firms that is willing to customize the system for the
specific application. Every system is different and although most control solutions have already
been developed, there are almost always some control issues that are unique to a given project.
It has extensive trend-logging capabilities Extensive trend-logging, including the ability to export
data, are valuable for commissioning, O&M, and evaluating capital projects.
Efficiency Checklist
In this chapter, we have separated best practices into the several categories (listed under Energy
Efficiency—“The Big Picture” on page 6). However, most of these practices and the systems they
affect are interactive, so treating them separately may result in missed opportunities or in solutions
that are less than optimal. To foster a comprehensive approach, the following tables pull together
all of the major concepts related to compressors, evaporators, and condensers from the preceding
sections. The tables also preview the effects of proper maintenance procedures, which are addressed
in the next chapter.
Introduction
This chapter discusses best practices for achieving energy efficiency through the operation,
maintenance, and commissioning of refrigeration systems.
Operation and maintenance (O&M) can be defined as maintaining originally-specified equipment
performance through proper service at the specified intervals. Even the most efficient system design
and equipment can be rendered inefficient by inadequate operation and maintenance. It is important
that proper O&M practices be followed throughout the life of the system.
Commissioning can be defined as the inspection, review and adjustment of set points, control
strategies, and equipment features, to ensure that the system achieves the design intent and meets
original specifications in a way that maximizes performance and efficiency. Systems should be
commissioned when they are built (or modified) and should be periodically recommissioned.
Tracking Equipment and System Performance Best practices include establishing habits and
procedures that allow the emerging problems to be identified and fixed before they impact process
or energy performance. This includes maintaining daily engine room logs, trend-logging control
points with a computer-control system, and comparing performance over time.
Seeking Optimization The operators that attain the highest levels of efficiency make regular
adjustments to control system settings and adjustments to equipment. These adjustments are
followed by observation or measurement to see how the system responds.
Being Well-trained Knowledgeable maintenance staff and operators have a better understanding of
all of the items on this list. They also have a better conceptual understanding of the overall
performance goals. Plus, training often is used to satisfy PSM requirements as per federally
mandated OSHA standards.
The following sections address some key O&M issues for evaporators, compressors, and condensers
that affect energy performance.
Evaporators
Clean Coils Clean evaporator coils regularly.
Pressure washing can remove dirt that
accumulates on evaporator fins and tubes. This
is especially true in dirty or dusty
environments.
Fix Leaking Valves Rebuild liquid and gas
valves when leaking or other improper
operation is detected. For example, a leaking
hot-gas defrost valve will impart false
refrigeration loads by leaking gas into the
suction line.
Calibrate Temperature Probes and Sensors
Calibrate temperature probes and sensors
regularly using a consistent and traceable
standard (for example, an ice bath).
Condensers
Clean Water-Spray Nozzles and Strainers
Proper flow and water distribution to
condenser tube bundles is critical. Check for
spray pattern and clean nozzles and strainers as
needed to ensure full flow and wetting of coil
surface.
Figure 73: Slide valve potentiometer
Clean Condensers Remove build-up of solids
and other foreign material from all condenser surfaces. In particular, a clean tube bundle is critical
to maximum heat transfer. Also, pressure-wash drift eliminators regularly, as they accumulate solids
that can reduce air flow.
Maintain Belt Drives Adjust and replace fan Best Practices:
belts as necessary. A slipping belt is not only Condenser Maintenance
inefficient, but results in less air flow and heat
transfer in the condenser. Stay on top of the three big threats to condenser
Prevent Recirculation and Saturation performance with proper maintenance at correct
Normally located on building roofs,
intervals:
evaporative condensers are susceptible to
recirculation between each other, where the Non-condensable gases.
warm, moist discharge air of one condenser Scale on the condenser tube bundle.
enters the inlet of a neighboring condenser. In
Poor spray water dispersion.
addition, food processing facilities often have
multiple sources of steam exiting stacks or
vents, such as blanchers, washers, and boiler
blow-down. Preventing or correcting warm, moist air from entering the condenser will ensure full
performance.
Treat Condenser Water Treating condenser
water is critical to equipment performance and
long life and to control potential
contamination. Condenser tube bundles are
particularly susceptible to solid build-up
because of the alternate wetting and drying of
surfaces. In addition, the warm water of a
condenser is an attractive environment for
biological growth.
Check and Purge Non-Condensable Gas To
test for non-condensable gas, measure the
temperature of liquid condensate draining from
each condenser circuit and compare it to the
Figure 74: Plugged condenser spray nozzles
saturated condensing temperature. Ideally, the
refrigeration control system would measure the average liquid temperature draining from the
Best Practices:
Commissioning System Commissioning
Evaporators
Coil Overfeed Rates Adjust overfeed or recirculated evaporator coils for the specified overfeed
rates. Proper overfeed rates are typically 3:1 to 4:1 (rates that maximize overall heat transfer). This
adjustment is particularly critical in gas pressure recirculation systems where excessive overfeed
rates can reduce system efficiency.
Adjust Pressure Regulators In some flooded systems, evaporator coil pressure regulators are
manually set to limit refrigerant pressure and temperature within the coil. This means that with the
regulator operating at 100% capacity, the refrigerant pressure within the coil is well above the
compressor suction pressure. These limitations are appropriate to avoid excessive temperature
differences that cause evaporators to frost rapidly. However, excessively high regulator settings
limit the capacity of the evaporator coil, and limit savings from evaporator fan cycling or VFD
control. Adjusting the pressure regulator for maximum capacity will increase capacity and
maximize efficiency.
Compressors
Adjust Economizers for Effectiveness On economized rotary screw compressors, the economizer
port should always be enabled to operate (valved open). Closing an economizer port can reduce
compressor efficiency by 5% to 10% or more. In addition, most economizer ports are equipped
with pressure regulators to maintain pressure in the subcooler or economizer vessel. Adjust these
regulators for the lowest possible pressure acceptable to the design.
Manually Adjust VI Properly For compressors with manually adjusted internal volume ratio,
review factory recommendations for proper setting at the given operating pressures. Improper VI
adjustment can reduce compressor efficiency, particularly after adjusting system pressures, or
reassigning the compressor to an alternative duty.
Investigate Current-Limiting Virtually all screw compressors implement a current-limiting feature
into the microprocessor panel. If motor load exceeds the nameplate capacity or the service factor,
the compressor can limit further loading or actually be forced to unload. This occurs most often
when a motor is undersized or a compressor is operating at elevated suction or discharge pressure
relative to design conditions. Since operating unloaded is inefficient, you may need to reassign the
Condensers
Review Purger Operation Inspect automatic system purgers for proper operation and capacity. If a
system has increased in size and capacity over time, a purger may not be capable of handling all
non-condensable load. Make sure that the foul-gas piping from the condenser circuits to the purger
does not trap liquid.
System
Review Crossover Piping and Valves Ensure that any crossover piping between various suction
systems is open or closed to best optimize energy efficiency. In general, every load should be served
by the highest possible suction unless part-load issues override the suction pressure advantage.
Optimize Underfloor Heating The underfloor heating system should use the lowest possible air or
glycol temperature required to prevent frost heaving. Due to the slow thermal response of the slab
and underfloor system, you should experiment slowly and carefully.
Controls
Maximize Suction Pressure Set Point Set the suction pressure as high as possible. Maximum
pressure is often dictated by one bottleneck load, such as a low-temperature zone or process.
Compressor Sequencing Carefully review and optimize compressor sequencing set points,
including order and criteria for starting and stopping compressors.
Remote vs. Local Compressor Control Ensure that the computer is in full control of all
compressor functions, including start/stop and load/unload. Leaving compressor microprocessors
in Local control mode prevents centralized suction pressure control and compressor sequencing.
Minimize Condensing Pressure Set Point Set the minimum condensing pressure as low as possible,
until problems are encountered. Recognize that advice on condensing pressure from manufacturers,
contractors, and technicians is often very conservative. When a barrier is encountered, assess the
cost and energy savings that are possible by correcting it.
Optimize Condenser Staging Operate evaporative condensers wet as often as possible. In addition,
stage condensers in order of decreasing efficiency, using axial-fan and integral sump units first,
before other units without these features. Finally, stage condensers as entire units. That is, avoid the
temptation to stage all pumps online first, then all fans. Rather, implement a pump-fan-pump-fan
strategy. If VFDs are used, follow the staging recommendations discussed in Improving Condenser
Part-Load Performance on page 62.
Ambient Temperature Probe Location Locate ambient-temperature and relative-humidity probes
in locations that are unaffected by direct sun or humidity sources. Check temperature and humidity
relative to nearby weather stations. Accurate measurement of ambient conditions is important for
successful implementation of wet-bulb approach condenser control.
Maximize Zone Temperatures Set all freezer or cooler zones to the highest acceptable temperature
set point allowed by product, customer, or corporate temperature criteria.
Introduction
This chapter provides a variety of tools, information, and approaches that can help you to
understand and control your refrigeration system energy costs.
The common element of these tools is that they are geared toward raising awareness of energy use
and operating costs. All plant staff should have full knowledge of the costs of running the
refrigeration system—from plant engineers, process operators, to maintenance personnel. And
owners and plant management also need to see energy costs as a variable rather than a fixed expense.
We believe that if you are aware of your energy use, the related energy costs, and the options
available to control them, you are more likely to select efficient choices that minimize life-cycle cost
and maximize profits.
This section includes the following:
A self-assessment questionnaire that allows you to consider how all aspects of your refrigeration
system can influence operating costs. This includes equipment choices, control methods, system
design, operation and maintenance, and management techniques.
An overview of life-cycle cost analysis.
An example of how to estimate the annual energy cost of your refrigeration system.
An overview of the techniques and benefits of refrigeration energy-efficiency studies.
A discussion of energy-accounting practices and their benefits.
A reference section that includes a variety of sources for information on industrial refrigeration
engineering and operation.
Score
2 The controls for our system allow space temperatures to pull down below the required
temperature by more than 2°F.
Points
Yes ........................................................................................................................ 0
No ........................................................................................................................ 1
Score
3 Which of the following descriptions best describes your system:
Points
We maintain our suction pressure below its design suction level
to be conservative and run all evaporator fans at full speed. ........................... 0
We maintain our suction pressure at its design suction pressure
and run all fan evaporator fans at full speed. ................................................... 1
We allow our suction pressure to float above the design suction
pressure while running all evaporator fans ...................................................... 2
We operate at the highest allowable suction pressure that still
allows some fan cycling or fan-speed reduction. .............................................. 3
Score
Score
5 We have expanded our system. After the expansion, we see noticeably more pressure drop in
our suction lines; or, sometimes we have trouble maintaining temperature in zones far from the
compressor room.
Points
Yes ........................................................................................................................ 0
No ........................................................................................................................ 1
Score
Section Score
Score
7 Our peak summer condensing pressure is about:
Points
above 180 psig ...................................................................................................... 0
170–180 psig ......................................................................................................... 1
160–170 psig ......................................................................................................... 2
150–160 psig ......................................................................................................... 3
below 150 psig ...................................................................................................... 4
Score
8 We have direct expansion (DX) evaporators or other DX loads in our system.
Points
Yes ........................................................................................................................ 0
No ........................................................................................................................ 1
Score
4
Questions in this section are geared toward the Pacific Northwest region of the United States.
Score
Section Score
Score
Section Score
Score
12 Which of the following best describes the typical unloading of our compressors?
Points
It is common to have two or more screw compressors operating
at less than 100% capacity on the same suction system. ................................ 0
All operating compressors remain fully loaded, but operate at
lower than necessary suction pressures. .......................................................... 2
Our control system fully loads our “base-load” compressors with
one screw compressor acting as “trim” compressor by
unloading the slide valve to maintain suction pressure at set
point. ............................................................................................................... 4
Our control system fully loads our “base-load” compressors with
either a reciprocating compressor or VFD-driven screw
compressor acting as the "trim" compressor. .................................................. 6
Score
Section Score
Score
14 We operate our condenser fans first and our pumps second.
Points
Yes ........................................................................................................................ 0
No ........................................................................................................................ 2
Score
15 We run our system dry for several months each winter, which often includes a month or more
when the weather is above freezing.
Points
Yes ........................................................................................................................ 0
No ........................................................................................................................ 2
Score
Section Score
Score
17 Our screw compressors are cooled with liquid injection.
Points
Yes ........................................................................................................................ 0
No ........................................................................................................................ 3
Score
Score
19 Our system has no suction systems below -30°F saturated suction temperature that are not
served with a two-stage system.
Points
True ...................................................................................................................... 0
False ...................................................................................................................... 3
Score
20 We have refrigeration computer-control system.
Points
False ...................................................................................................................... 0
True ...................................................................................................................... 3
Score
Section Score
Score
Section Score
Score
23 We measure the liquid ammonia temperature returning from our condenser. It is normally
within 2°F of the saturation temperature corresponding to the discharge pressure.
Points
False ...................................................................................................................... 0
True ...................................................................................................................... 2
Score
24 We check, clean, and replace condenser nozzles, water distribution trays, and strainers such
that system is clog-free and our water spray coverage is complete.
Points
False ...................................................................................................................... 0
True ...................................................................................................................... 2
Score
25 We calibrate temperature sensors, pressure sensors, and slide valves at least once a year.
Points
False ...................................................................................................................... 0
True ...................................................................................................................... 2
Score
26 We routinely clean our evaporator coils and condensers tube bundles.
Points
False ...................................................................................................................... 0
True ...................................................................................................................... 2
Score
27 We practice preventive maintenance on our compressors including regularly scheduled oil
changes, filter changes, oil analysis, vibration analysis, and clearance checks.
Points
False ...................................................................................................................... 0
True ...................................................................................................................... 2
Score
28 We routinely inspect our hot gas solenoid valves to confirm that no gas is leaking through to
the suction system.
Points
False ...................................................................................................................... 0
True ...................................................................................................................... 2
Score
Score
30 Which of the following best describes our use of our computer-control system for control?
Points
We either don't have a computer-control system or we have
overridden and disabled most/all of its control functions. .............................. 0
Our control system provides most/all of the control for our
system, but we largely rely on the original settings......................................... 1
We consider the control system a tool for active use. We
routinely make control changes with a particular emphasis on
minimizing energy use. ................................................................................... 2
Score
31 Which of the following describes the use of our computer system for "trend-logging"? Trend-
logging is defined as storing important system variables (space temperatures, system pressures,
etc.) that can be reviewed in graphs or tables.
Points
We either do not have a control system, or we have a control
system that we do not use for trend-logging.................................................... 0
We use the trend-logging capability of our computer on an
occasional basis................................................................................................. 1
We review trend-logging on a regular basis and trend most/all of
the control points that the system allows. ....................................................... 2
Score
Section Score
Score
Section Score
Score
34 We have installed electrical submetering of our refrigeration system and we use it as a tool to
optimize energy use and identify emerging trends.
Points
No ........................................................................................................................ 0
Yes ........................................................................................................................ 1
Score
35 During the course of our plant construction or last expansion, we had contractors provide bids
on energy efficiency upgrades and evaluated incremental investments in energy efficiency. We
selected options with low life-cycle costs that met our return on investment criteria.
Points
No ........................................................................................................................ 0
Yes ........................................................................................................................ 3
Score
Section Score
Total 100
This self-assessment tool is intended to give you an idea of where your refrigeration system stands in
terms of energy efficiency and potential. You’ve probably noted that more expensive or complex
options are represented by higher scores. In most circumstances this also indicates greater energy
efficiency. But there are many operation-and-maintenance options for reducing energy costs with
minimal investment.
This self-assessment tool was developed with a “typical” refrigeration system of cold storage
warehouse in mind. Remember that your refrigeration system is customized and unique to your
Technically:
kW = motor shaft power x .746 / motor efficiency
but a decent approximation is:
kW = Motor Nameplate hp x typical motor amps / motor full load amps * 0.8
Average shaft power should address control type (constant, fan cycle, or speed control).
A lower level of efficiency is cost-effective when one or more of these conditions are not met. An
energy study addresses the specific case and helps define what is economically feasible.
An energy study defines the capital costs and energy cost savings associated with various upgrades
(in the case of new construction) or retrofits (for existing systems). It also summarizes any utility
incentives or tax benefits that may be available and provides the proper rigorous analysis and
documentation required to obtain them. If possible, the study should list or quantify non-energy
benefits or costs. Financial results are presented in terms of simple payback, return on investment,
or annual net cash flow, depending on the preferences of decision makers.
The energy study should be conducted by someone with knowledge and experience in refrigeration,
energy, and analysis. A lack of refrigeration knowledge will result in missed opportunities and poor
recommendations. A lack of energy experience will miss the big picture in terms of energy baseline,
utility rate schedules, and incentives. Limited analysis experience will result in dubious savings
estimates.
Some larger food-processing facilities have developed (or may want to develop) energy-study
expertise in-house. More commonly, energy studies are contracted out to energy-efficiency
specialists. Often, energy-efficiency programs of electric utilities will provide partial or full funding
for these studies. However, even if the customer pays for the study, this investment is small relative
to the capital cost of the equipment and the lifetime energy costs of the system. In other words, it is
a “best practice” to invest in high-quality decision-making information.
At a more detailed level, an energy study includes the following:
An engineering model of the energy use of the refrigeration system This model would represent
the loads, equipment, and control of the system. Such models can be constructed for both existing
systems and for proposed new construction.
A baseline model is constructed that represents either “as-is” conditions (for an existing system)
or a “baseline design” model (for new construction).
Modified versions of the model are created to represent alternate system configurations. The
difference in annual energy use between the baseline and alternate models represents potential
energy and cost savings.
These models can be quite complex, due to a combination of factors including seasonal
variations in weather and production, interactions between energy-using equipment, nonlinear
equipment part-load, and control subtleties. To be an accurate representation, a comprehensive
model should address both full-load and part-load equipment operation and the full range of
Estimates of the cost of efficiency upgrades These costs can be estimated based upon similar
projects, but a better approach is to obtain contractor costs based upon the specific case. It is an
excellent management practice to ask contractors for cost estimates for efficiency alternates as part
of the bidding process for new construction.
Design details The study should provide enough detail on specific design details, necessary set
points, and control algorithms to ensure that the energy-efficiency goals will be achieved.
Measurement and verification plans It is a good idea to describe how the system will be
commissioned and how savings will be verified at this early stage, particularly if incentives are at
stake.
Table 12: Example summary of savings and cost from an energy study
1.90
2,500,000
1.85
2,000,000
1.80
kWh
1,500,000
kWh
1.75
1,000,000 2000
1.70
2001
2002
500,000 1.65
2003
- 1.60
- 2,000 4,000 6,000 8,000 10,000 12,000 45 50 55 60 65 70 75 80
Production (lb/month) Average Monthly Ambient Temperature (°F)
Figure 75: Examples of tracking energy use normalized to production (left) and temperature (right)
Energy accounting can help your facility staff understand how and where energy is used in your
plant, and can help motivate people to take actions that can significant reduce utility costs. To get
the most benefit from energy accounting, allocate sufficient staff resources to set up and maintain
the system, and to develop a system of communication with owners, managers, facilities staff, and
others whose decisions affect energy use.
These two software tools can help you determine the economics of premium-efficiency vs. standard
motors. They also include other features, such as a database of plant motors, calculation of motor
operating costs, and tracking of motor maintenance.
MotorMaster+:
www.oit.doe.gov/bestpractices/software_tools.shtml
em2, electric motor management software
www.em2solutions.com
Case Studies
This section contains short case studies that were selected to show how some of these Best Practices
have been implemented in the Pacific Northwest.
Henningsen Cold Storage
Oregon Freeze Dry
WestFarm Foods
Baseline
www.energy.state.or.us
350,000
Improved Electric Utility
300,000
Portland General Electric
Energy Use (kWh)
0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Month
BEST PRACTICES IN INDUSTRIAL REFRIGERATION
Background
The engineering staff at Oregon Freeze Dry believes plant
energy use is their responsibility. In 2002, they decided to
look at the ammonia-based refrigeration system, one of their
most energy-intensive systems. They invited Al Leake of
Pacific Power to discuss energy-efficiency projects and
available incentives.
Pacific Power arranged for Cascade Energy Engineering to
perform an energy study to find specific ways to improve
the efficiency of the refrigeration system. Their report
suggested three efficiency measures: 1) installing variable- Features
frequency drives (VFDs) on four of the eight compressors;
2) adding a new suction line between two plants, and n ABB variable frequency drives were installed on four
3) expanding computer screw compressors (two high stage and two booster
controls to manage the compressors). The remaining four compressors are now
VFDs. used for base loading and back-up.
The existing compressors n A Techni-Systems computer-control system manages
inefficiently varied capacity which compressors run and at what speeds to meet the
with slide valves. The VFDs refrigeration load with maximum efficiency.
would instead allow the n A 12-inch-diameter suction line supplements the old 8-
compressor motors to vary inch line.
speed to match refrigeration
loads. The existing
undersized suction line
created a large pressure drop
Replication
which required a lower (and
less efficient) system suction n In industrial refrigeration systems, VFDs are often cost
pressure. effective for screw compressors, evaporator fans, and
condenser fans. Generally, VFDs are useful where
Oregon Freeze Dry
equipment operates for long hours in systems with
management reviewed the
variable loads or light loads.
report, found the financial
n If a compressor operates at or near full speed most of the
payback and incentives
time, adding an adjustable speed drive will not be cost
attractive, and approved the
effective.
installation.
n A VFD may not always be the best way to control
capacity. Sequencing of multiple compressors or the use
of a reciprocating
Benefits compressor for trim are
other possibilities.
n VFDs and control system efficiently vary the capacity of n The use of VFDs is only
the refrigeration system with speed control rather than one way to save energy
with the less efficient slide valves. in industrial refrigeration
n Energy savings of 1,939,000 kilowatt hours/year (34 systems. Other ways
percent of base energy use) with no reductions in include refrigeration
production. computer control,
n Energy cost savings of $77,700/year. thermosiphon oil
n Reduced wear on motors and compressors due to soft cooling, high-speed
starts and fewer operating hours. energy efficiency doors,
n The VFDs and control system require minimal and bi-level lighting.
employee training.
CASE STUDY
BEST PRACTICES IN INDUSTRIAL REFRIGERATION
WestFarm Foods
PROJECT SUMMARY
Benefits
n Reduced energy cost
n Increased system capacity
n Improved control
n Improved trending and alarming
n Reduced evaporator fan noise
n Reduced condenser fan noise
Financial Overview
Incremental Installation Cost
$310,000
Oregon Business Energy Tax Credit
The Project $108,000
Portland General Electric Incentive
$127,000
WestFarm Foods is one of the largest dairy manufacturers in
Energy Savings
the nation, with 1,200 employees at 11 processing plants in
Washington, Oregon, Idaho and California. In early 1996, 40% of base energy use
WestFarm Foods began planning for an expansion and 2,000,000 kWh/year
modernization of their Portland, Oregon creamery. Energy Cost Savings
WestFarm engineers were designing a new Extended Shelf
$75,000/year
Life (ESL) processing line and the associated cooler space. Resources
Increased loads from the ESL process and cooler would Project Owner
require adding a 350-hp compressor to supplement the
WestFarm Foods
existing 350-hp and 600-hp screw compressors. This in turn
(206) 281-3456
would require another condenser.
www.WestFarm.com
WestFarm and their Portland General Electric account
Energy Consultant
representative arranged for Cascade Energy Engineering to
perform a detailed energy study, starting with data logging Cascade Energy Engineering, Inc.
of the existing refrigeration system. The data collected (503) 287-8488
included suction pressure, condensing pressure, and Rob Morton, P.E.
compressor slide valve position. Hour meters recorded run rob.morton@cascadeenergy.com
time for the liquid solenoid valves and power measurements Business Energy Tax Credit
were made on the primary refrigeration compressor. Oregon Department of Energy
Data logging revealed three major issues with the existing 1-800-221-8035 (inside Oregon)
systems. First, compressors operated unloaded much of the (503) 378-4040
time because they were sequenced manually, not by www.energy.state.or.us
computer control, to meet the wide range of plant loads. Electric Utility
Second, the high minimum condensing pressure of 140 psig,
which was required to ensure proper liquid ammonia flow
Portland General Electric (Incentives are now
throughout the sprawling plant, resulted in increased available through the Energy Trust of Oregon)
compressor power, particularly during the winter. Third, 1 (866) 368-7878 (inside Oregon)
the evaporator coil liquid solenoids in the milk cooler were (503) 493-8888
off much of the time, resulting in excessive fan power. www.energytrust.org
BEST PRACTICES IN INDUSTRIAL REFRIGERATION
800
Day
and the new ESL cooler. The
computer reduces fan speed
whenever space temperature
is satisfied.
Results
A new high-pressure Implemented measures reduced annual energy consumption
ammonia receiver with a at the WestFarm facility by more than 2,000,000
booster pump was installed kWh—nearly 40% of the
to ensure adequate liquid total refrigeration energy
pressure to sensitive loads. use. Annual operating costs
This allowed the minimum were reduced by about
condensing pressure to be $75,000.
reduced from 140 psig to 90
psig. The entire package of
improvements cost $310,000.
A larger, more efficient Although this represented an
condenser was specified, and attractive 4.2-year payback,
all condenser fans were incentives from Portland
equipped with VFD control General Electric and a 35%
to manage condenser tax credit from the Oregon
capacity with speed rather Department of Energy
than cycling. reduced the final customer
payback to one year.
Industrial Refrigeration Best Practices Guide 119
Industrial Refrigeration Best Practices Guide
December 2004
ISBN: 0-9721077-9-7