Professional Documents
Culture Documents
Orifice Measurement - Josh Kinney
Orifice Measurement - Josh Kinney
In Figure 6, the solid points are the uncorrected orifice The Achilles heel of most DP meter wet gas corrections is
meter gas flow predictions and the hollow points show the that the liquid mass flow rate is required to be known
prediction after the application of the Chisholm equation: before it can be applied. The Chisholm correlation is no
. different. This information is not at all easy to come by in
. m g Apparent real applications. Two common methods for obtaining
mg = (3)
1 + CX LM + X LM
2 the liquid flow rate in natural gas production are to either
use test separator history or apply a wet gas tracer dilution
where technique. Here, tracer chemicals (usually fluorescent
1 1
⎛ρ ⎞ 4 ⎛ ρl ⎞ 4
dyes) are injected into a wet gas at a known rate. At a
C = ⎜⎜ g ⎟⎟ + ⎜ ⎟ (3a) distance judged suitably far downstream to have allowed
⎜ ⎟
⎝ ρl ⎠ ⎝ ρg ⎠ fully-mixed flow to be achieved, samples are taken. The
relative intensity of the fluorescence of the liquid sample
It can be seen that without the Chisholm equation and the injection tracer provides an indication of the
correction, some of the higher Lockhart-Martinelli liquid flow rate. Further details of this technique are
parameter value datasets have over-readings up to outside the scope of this paper.
approximately +35%. After the Chisholm correction is
applied, all the data are corrected to less than ±5% error in Worked Example of Applying the Chisholm Correction
the gas flow rate. The majority of the data are corrected
to within ±2%. Chisholm produced his correction factor The following example shows how the Chisholm wet gas
by modeling separated flow. It should be noted that the orifice plate equation can be applied in the field for the
data that have a “corrected” result >+2% are for flow case of a known liquid mass flow rate. An actual test
patterns that are described as annular mist flows and that point from a 4” diameter, schedule 40, 0.5 beta ratio
have DPs >500” Water Column (“WC”). This is a orifice plate meter tested at the CEESI wet gas test loop is
relatively large DP and, in practice, if an orifice meter used.
experiences DPs >500” WC, the beta ratio should be
increased to reduce the DP to <500” WC. If this is done, This wet natural gas at 43.8 bara (635.3 psia) and 306°K
the Chisholm equation corrects the over-reading to give a (910F) has a gas density ( ρ g ) of 32.9 kg/m3 (2.06
gas flow rate within ±2% of the actual gas flow rate value.
In Figure 6, the only exception to this rule is the lowest lbm/ft3) and a liquid density ( ρ l ) of 718.2 kg/m3 (44.84
pressure (or gas-to-liquid density) tested. Here, it was the lbm/ft3). An operator in the field would know such
lowest velocities at the lowest pressure that produced the information. The liquid injection reference meter
poorest results. A camera at CEESI identified the indicates that the liquid mass flow rate is 1.98 kg/s (4.37
problem to be slugging flow in the test section. That is, lbm/s). In the field, this would be information obtained
this was an unsteady flow and all meters would give some independently from the orifice plate meter and Chisholm
error under this inherently unsteady flow pattern. This equation (e.g., from the test separator history or a tracer
was a poor flow condition to attempt to measure. dilution technique). The reference gas meter indicates
that the actual gas mass flow rate is 1.60 kg/s (3.53
Chisholm’s wet gas correction for orifice meters, lbm/s). A meter operator in the field would not know this
therefore, worked if the DPs were kept below 500” WC gas flow rate information. The resulting differential
(i.e., a reasonable request in the field) and the wet gas pressure produced across the orifice plate meter by the
flow was steady. It should be noted, however, that wet gas flow is measured as 44,160 Pa (177.6” WC).
Chisholm’s correction was formulated from test data for Applying the standard dry gas calculation method with
orifice meters in wet gas where the meter diameter was this differential pressure gives a gas mass flow reading
. Comments on the Published Research and his Worked
(i.e., m g , Apparent ) of 2.14 kg/s (4.72 lbm/s). Here, we see Example
that the presence of the liquid has caused the meter to
over-read the actual gas mass flow rate. The difference Note the measured differential pressure was 177.6” WC.
between the uncorrected gas mass flow rate prediction Steven, et al. [11], suggest the Chisholm equation is only
and the actual (or reference) gas mass flow rate is 33.7%. applicable if the differential pressure is less than 500”
Of course, in the field, the operator only knows the gas WC, so this example is within this limit.
and liquid densities, and the raw differential pressure and,
therefore, the uncorrected gas flow rate prediction Note that Chisholm created his correlation from orifice
. meter data with a pipe diameter range of 2.5” to 4.” This
( m g , Apparent ). He or she, as yet, does not know the example is for a 4” diameter meter. The effect of
actual gas mass flow rate. Now, if the liquid mass flow extrapolating the diameter value in either direction is not
rate is available through an independent source, the well understood. Chisholm used multiple datasets with
Chisholm equation can be applied to find the gas mass several types of liquid. Researchers currently believe that
flow rate. orifice plate meters are relatively resilient to the effect of
changing the liquid properties on wet gas flow over-
The gas to liquid density ratio is: readings. Hall, et al. [12], showed 2”, schedule 80, 0.515
beta orifice meter wet gas data for natural gas with
different mixes of water and hydrocarbon liquid. It was
2.06 lbm / ft 3
Density Ratio = = 0.0458 found that the liquid phase had little effect on the wet gas
44.84 lbm / ft 3 over-reading, but all the 2” diameter pipe data (regardless
of the ratio of water and hydrocarbon liquid) tended to
agree and give a smaller over-reading than the data for the
Applying Equation 3a gives: 2.5” to 4” diameter pipe data. This resulted in the
Chisholm correlation over correcting the gas flow rate to
1 1 1
give an under prediction. Figure 7 shows this result as
⎛ρ ⎞ 4 ⎛ ρl ⎞ 4
⎟⎟ + ⎜ ⎟ = (0.0458)4 + ⎛⎜
1 1 ⎞4
C = ⎜⎜ g ⎟ = 2.62 shown by Hall.
⎜ρ ⎟
⎝ ρl ⎠ ⎝ g⎠ ⎝ 0.0458 ⎠
60
200 psia Uncorrected
Now, with Equation 1 used in Equation 3 with this value 200 psia Chisholm Correction
of “C,” we get: 50 400 psia Uncorrected
2 30
⎛ .
⎞ ⎛ .
⎞
% Error
⎜ ml ρg ⎟ ⎜ ml ρg ⎟
1 + C⎜ . ⎟⎟ + ⎜⎜ . ⎟⎟
20
⎜ mg ρl ρl
⎝ ⎠ ⎝ mg ⎠ 10
+2%
0
.
Now, if we know m g , Apparent , ρ g , ρl , C , and if we -10
0 0.1 0.2 0.3 -2% 0.4 0.5
. Xlm
know the liquid mass flow rate, m l , we can iterate the
Chisholm equation for the only unknown, i.e., the actual Figure 7. BP 2” Diameter, 0.515 Beta Orifice Meter
. Wet Gas Data from CEESI - Uncorrected
gas mass flow rate, m g . That is: and with Chisholm Correction
. 4.72 Hall pointed out that Chisholm’s correlation is a data fit
mg = and, hence, new data fits can be made on the model
2
⎛ 4.37 1 ⎞⎟ ⎛⎜ 4.37 ⎞
1 + 2.62⎜ . 0.0458 ⎟
created by Chisholm for orifice meters out of Chisholm’s
+ .
⎜ 0.0458 ⎟ ⎜ m ⎟ data range. For Hall’s very limited 2” diameter data set, it
⎝ mg ⎠ ⎝ g ⎠ was found that the following correction factor worked
well:
.
The result is m g equals 3.57 lbm/s (i.e. 1.62 kg/s). That 1 1
⎛ρ ⎞ 5 ⎛ ρl ⎞ 5
is +0.9% difference from the reference gas meter, C = ⎜⎜ g ⎟⎟ + ⎜ ⎟ (3b)
⎜ ⎟
compared to an uncorrected +33.7% from the reference ⎝ ρl ⎠ ⎝ ρg ⎠
gas meter.
Figure 8 shows the performance of equation 3b with the Trace liquids in a gas flow can cause an under-reading of
uncorrected data shown in Figure 7. However, Hall the actual gas flow rate by up to 2%. However, there are
expressly stated that this was an example from only a no correction factors available in the literature.
small dataset and users should apply it to a 2” diameter Considerable liquid mass flow rate with the gas flow will
orifice meter wet gas flow situation at their own risk. cause an orifice meter to over-predict the gas flow rate.
More research is required to understand better the For a liquid mass flow rate known from another source,
response of smaller orifice meters to wet gas. there are correction factors published for horizontal meter
applications. The Chisholm correction factor is widely
considered to be the best, but users should be aware that
60
200 psia Uncorrected
this is for DPs ≤ 500” WC and for pipe diameters of
50
200 psia Corrected between 2 ½” and 4.” For within this range and with an
400 psia Uncorrected
accurately known liquid mass flow rate, the Chisholm
400 psia Corrected
40 800 psia Uncorrected correction is said to predict the gas flow rate to within
800 psia Corrected ±2% of the true value. Use of this correlation outside this
30
% Error
Josh Kinney