Loadbreak Connectors

Catalog Data COOPER POWER


SERIES
Effective March 2015
CA650014EN Supersedes TD650006EN August 2014

200 A 35 kV class three-phase


loadbreak junction
General
Eaton's Cooper Power™ series 200 A, 35 kV Class
three-phase loadbreak junction pro­vides two, three
or four 21.1/36.6 kV loadbreak interfaces that are
internally bused together and meet all require-
ments of IEEE Std 386™-2006 standard – 200 A
Loadbreak Interface No. 1A, 21.1/36.6 kV (large 35
kV Class interface). Loadbreak junc­tions are used
in pad-mounted apparatus, under­ground vaults,
and other ap­pa­ra­tus to sectionalize, establish
loops, taps and splices, and to facilitate ap­pa­ra­tus
change-outs. Sec­tion­al­izing a cable run to find and
isolate a cable fault is made easy when a loadbreak
junction is used with large interface 35 kV Class
21.1/36.6 kV three-phase loadbreak elbows and
other ac­ces­so­ries meeting the re­quire­ments of
IEEE Std 386™-2006 standard
The 21.1/36.6 kV three-phase rated loadbreak
junction should not be used with 21.1 kV single-
phase rated loadbreak elbow connectors or
grounding elbows. For quick identification, Eaton's
Cooper Power series 21.1/36.6 kV three-phase
rated loadbreak junctions are color coded with
purple nose pieces. Mating 21.1/36.6 kV three-phase
loadbreak elbow connectors (Document 500‑41,
200 A 35 kV Class Three-Phase (Purple Cuff)
Loadbreak Elbow Connector) have a molded purple
cuff. Single-phase rated products are color coded
with tan nose pieces and molded cuffs. When
mated with compara­bly rated prod­ucts, the junction
provides a fully shielded, sub­mers­ible, sepa­rable
connection for loadbreak operation.
The loadbreak junction is available with an
adjustable stainless steel bracket for mounting
flat or at a 45° angle. Stainless steel "U" straps are
available for direct wall mounting.
Catalog Data CA650014EN 200 A 35 kV class three-phase loadbreak junction
Effective March 2015

LOCKING GROOVE GAS VALVE


Spring-loaded gas valve CONTACT SPRING
Nose piece locking Zinc-plated beryllium copper con-
groove is made of traps arc-extinguishing
gases in bushing gas tact spring provides current path
high strength plastic from copper piston to
that secures mating chamber during switching
operations. copper housing.
accessories to
loadbreak junction.

PISTON STOP SEMI-CONDUCTIVE SHIELD


Full circum­fer­ence piston stop Molded semi-conductive
limits piston travel during fault close. peroxide-cured EPDM shield
meets requirements of IEEE Std
592™-2007 standard.
GAS SEALS
Multiple gas seals
further limit the
amount of gases
expelled.

CONTACT TUBE
Contact assembly
is replaceable in
the field. ARC INTERRUPTER RETAINER PINS
Arc interrupter is made of Retainer pins secure
specially formulated ablative piston during normal
material with superior switching operations.
de-ionizing properties. During fault close, the
COPPER PISTON pins shear to allow piston
Moveable copper to move forward quickly.
FINGER CONTACTS piston is forced
The silver-plated copper forward quickly to EPDM INSULATION
finger contacts are threaded engage elbow probe High quality peroxide-cured
into the copper housing. by gas pressure EPDM insulation is mixed and
generated during formulated in-house for
fault close. complete control of raw rubber
char­ac­ter­is­tics.

Figure 1. Three-phase loadbreak junction cutaway shown.


NNote: Dimensions given are for reference only.

Installation Table 1. Voltage Ratings and Characteristics


No special tools are required. Junctions are bolted to the mounting Description kV
surface. Refer to Service Information S500-15-1 200 A 35 kV Class Standard Voltage Class 35
Loadbreak Junction Installation Instructions for details.
Maximum Rating Phase-to-Phase 36.6
Maximum Rating Phase-to-Ground 21.1
Production tests
AC 60 Hz 1 Minute Withstand 50
Tests conducted in accordance with IEEE Std 386™-2006 standard: DC 15 Minute Withstand 103
• ac 60 Hz 1 Minute Withstand BIL and Full Wave Crest 150
• 50 kV Minimum Corona Voltage Level 26
• Minimum Corona Voltage Level Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.
• 26 kV
Table 2.  Current Ratings and Characteristics
Tests are conducted in accordance with Eaton requirements.
Description Amperes
• Physical In­spec­tion
Continuous 200 A rms
• Periodic Dissection
Switching 10 operations at 200 A rms at 36.6 kV
• Periodic Fluoroscopic (X-ray) Analysis 10,000 A rms symmetrical at 36.6 kV for 0.17 s after 10
Fault Closure switching operations
10,000 A rms symmetrical for 0.17 s
Short Time
3,500 A rms symmetrical for 3.0 s
Current ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.

2 www.cooperpower.com
200 A 35 kV class three-phase loadbreak junction Catalog Data CA650014EN
Effective March 2015

ADJUSTABLE BRACKET
GROUND CONNECTOR Adjustable Stainless Steel
Grounding Connector Bracket can be mounted flat 3.7"
accommodates wire up to or at a 45° tilt from mount- (94 mm)
5/8 inch in diameter. 5.0" ing surface.
(127 mm)
PARKING STANDS
Parking Stands accommodate
insulated standoff bushings or
S10 portable feedthrus. (only one
provided on 2 way junction)
S11

S7

S9
B
C
D
6.2"
A (158 mm)

5/8 X 7/8" OBROUND


MOUNTING HOLES
S Dim. in (mm)
S7 1.02 (25.8)
S9 5.46 (139)
S10 11.52 (292.7)
S11 13.79.(350.2)

Figure 2. Three-phase junction shows mounting dimensions for 2-, 3- and 4-way interfaces. See Table 5 for dimensional information.
NNote: Dimensions given are for reference only.

Ordering information Table 5.  Dimensional Information


To order a 35 kV Class (21.1/36.6 kV) three-phase loadbreak junction, Mounting Dimensions in./mm
specify the appropriate product from Table 3. Number of
Interfaces A B C D
Each kit contains: 23.1 8.8 15.0 19.0
• Loadbreak Junction (with mounting bracket or straps, depending 2
(587) (223) (381) (483)
on product ordered)
33.3 13.8 15.0 19.0
• Shipping Caps (not for energized operation) 3
(846) (350) (381) (483)
• Installation Instruction Sheet
38.5 18.8 20.0 24.0
4
(978) (477) (508) (610)
Table 3.  Loadbreak Junctions NNote: C and D are minimum and maximum stud centerline separations for
Number of Junction with Junction with mounting.
Interfaces Junction Only U-Straps Bracket

2 LJ235C2 LJ235C2U LJ235C2B


3 LJ235C3 LJ235C3U LJ235C3B 5.2 "
(132 mm)
4 LJ235C4 LJ235C4U LJ235C4B

Table 4.  Replacement Parts


Description Catalog Number Hole Size
0.375 "
Contact Tube 2637407B04B (10 mm)

Contact Tube Replacement Tool 2637585B01


4.3 " min.
U-Strap Kit with Hardware (1 strap) 2637570A01B (108 mm)

Stainless Steel Bracket Assembly (2-way) 2604688B01B


Figure 3. Stainless steel U-Strap for direct wall mount.
Stainless Steel Bracket Assembly (3-way) 2604688B02B
Stainless Steel Bracket Assembly (4-way) 2604688B03B NNote: Dimensions given are for reference only.

www.cooperpower.com 3
Catalog Data CA650014EN 200 A 35 kV class three-phase loadbreak junction
Effective March 2015

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

Eaton’s Cooper Power Systems Division Eaton and Cooper Power are valuable
2300 Badger Drive trademarks of Eaton in the U.S. and other
Waukesha, WI 53188 countries. You are not permitted to use these
United States trademarks without the prior written consent
Cooperpower.com of Eaton.
IEEE Std 592™-2007 and Std 386™-2006 For Eaton’s Cooper Power series
© 2015 Eaton standards are trademarks of the Institute of loadbreak junction product
All Rights Reserved Electrical and Electronics Engineers, Inc.,
Printed in USA (IEEE). This publication is not endorsed or information call 1-877-277-4636
Publication No. CA650014EN approved by the IEEE. or visit: www.cooperpower.com.