Aertronic Aerzener g2 V107dokumen - Tips Manuel Profibus
Aertronic Aerzener g2 V107dokumen - Tips Manuel Profibus
Profibus - Manual
AERtronic AS 300 V1.07 and later
The Profibus EM5 Module works with 64 word input and 8 word output data.
9. Byte –
16. Byte Free
With an active shut down the corresponding Bit is set =1. In the attached list all possible shut downs
or trips are detailed. Which ones are selected depends on the type of machine (i.e. Blower,
Compressor single stage, or two stage) and the chosen configuration.
Principle:
- Trip signals must lead to the shutdown of the drive motor
- The designation 2 indicates a 2 stage machine
- All configured analog inputs have an alarm sensor (signal failure)
- All configured analog inputs with limit values have an alarm or shut down signal
Warning / alarm:
With an active alarm the corresponding Bit is set =1. In the attached list all possible alarms are
detailed. Which ones are selected depends on the type of machine (i.e. Blower, Compressor single
stage, or two stage) and the chosen configuration.
Principle:
- Alarm and warning signals don’t lead to a shutdown of the drive motor
- The designation 2 indicates a 2 stage machine
- All configured analog inputs have an alarm sensor (signal failure)
- All configured analog inputs with limit values have an alarm or warning signal
Maintenance:
If a maintenance required or necessary the corresponding Bit is set = 1. The maintenance message is
so long active until the reset in the menu “acknowledge maintenance”
Status display:
Status:
Bit 6: System in ramp down (shut down operation) Bit is set = 1, when the
shut-down operation is
active and the machine
is in unload. The
machine switches into
standby mode when the
“Min. run-on time” is
expired (main motor off)
Bit 7: System in soft ramp down Bit is set = 1, when the
machine is within the
“switch off time”. The
machine stop is
activated but it remains
running in idle mode for
a present time before the
main motor is stopped.
24. Byte: Bit 0: Control ON/OFF enabled over Profibus Bit is set = 1. when the
parameter “remote
on/off” is set to
“Profibus” and the
release Bit 7 from
Byte 2 is set to 1
Bit 1: Control Load enabled over Profibus Bit is set = 1, when the
parameter
“remote load/idle” is set
to “Profibus” and the
release Bit 7 from
Byte 3 is set to 1
Bit 2: System is initiate (start command) Bit is set = 1, when the
machine is initiate. In
this case the machine
can be running or is in
standby mode
Bit 3: System main motor running Bit is set = 1, when the
main motor is running
Bit 4: System re-start block active Bit is set = 1, when the
re-start is blocked (max
starts, start-up temp.,
etc.)
Bit 5: System maintenance active Bit is set = 1, when a
maintenance is needed
Bit 6: System warning / alarm active Bit is set = 1, when a
warning or an alarm is
active
Bit 7: System shut down active Bit is set = 1, when a
shut down is active
Digital Inputs:
Digital outputs:
Analog input:
The configured and connected analog inputs will be transmitted as (16Bit) integer. The information
[0,1 %] refers to the decimal point. In that case the value must divide by 10.
(Example 457% / 10 = 45,7%)
37. Byte: \ Actual set value for variable speed drive [0,1 %] Value divide by 10
38. Byte: /
73. Byte: \ Vibration 1S1 / 3S1 [%] Only the highest value
74. Byte: / will transmitted
77. Byte: \ Vibration 1S2 / 3S2 [%] Only the highest value
78. Byte: / will transmitted
Hours:
81. Byte: \
82. Byte: \ Operating hours [h]
83. Byte: /
84. Byte: /
85. Byte: \
86. Byte: \ Loaded hours [h]
87. Byte: /
88. Byte: /
89. Byte: \
90. Byte: \ Idle / no load hours [h]
91. Byte: /
92. Byte: /
93. Byte: \
94. Byte: \ Rented hours [h]
95. Byte: /
96. Byte: /
Maintenance interval:
101. Byte: \ Maintenance interval cooling air in / out remaining time [h]
102. Byte: /
107. Byte: \ Maintenance interval pressure relief valve remaining time [h]
108. Byte: /
119. Byte: \ Maintenance interval water condensate drain remaining time [h]
120. Byte: /
123. Byte: \ Maintenance interval main inspection remaining time [10h] Value must be
124. Byte: / multiplied by 10
Communication status: