# Factor of safety for Overturning 1.

10

SOIL CONDITIONS

Characteristic Angle of
Depth to Water table Unit Weight of Allowable Bearing
# Soil Condition Internal Friction, φk
(m) Soil, γs (kN/m ) Capacity of Soil (kN/m2)
3
(Degrees)

1 Class 2A >2.0 30.0 17.0 350

Notes:
The loads applied loads during pole structural design are factored loads and therefore the base reactions are ultimate reaction.
The safety factor therefore is 1.1 for these calculations
Factor of Safety for loads applied on pole 1.5
Safety factor for loads on foundation 1.1
Factor of safety for resistance 1.5 Minimum
Global Factor of Safety is atleast: 2.5 As required
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SS3-12 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SS3-12 Suspension Type
Top Pole Diameter dt mm 260
Bottom Pole Diameter db mm 649
Pole Total Height Lp m 16.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate

Pole diameter at outcrop top dout mm 880 Base Plate Diameter


Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 42.00 Shear
Design Horizontal Load on Pole Hd kN 50.82 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 515.00 Moment
Design Overturning Moment at GL Md kN.m 623.15 Factored Moment
Characteristic Vertical load Vk kN 28.00 Axial
The Moment to Shear Ratio, e e m 12.26
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C25
Length of the Caisson Lc m 3.5 For Overturning Resistance
Diameter of Caisson Dc m 1.100 Provide 1100 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.10
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 76.3 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 935.6 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 1.60 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 1.60 O.K, >/= 1.5
Volume of Caisson Vc m3 3.69 Caisson Concrete + Outcrop
B: Bearing Capacitry:
Diameter of Base B m 1.10 1100 mm
Bearing Area of pad Abase m2 0.95
Dead weight of foundation Gf kN 88.64 Caisson Weight
Total Vertical load P kN 128.31 Factored
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 135 Maximum Base Pressure

Ratio sallowable /sapplied 2.59 O.K


Concrete Volume of Required for Foundation Vtotal m3 3.69 For Each Pole
SS3-12: Page 1 of 2
SINOTEC-GTSCC JV
REINFORCEMENT DESIGN CALCULATION AS PER BS 8110
Date Modified: 5/12/2022
Pole Type SS3-12 Suspension
Description Symbol Value Unit Remarks
Design Data
Design Soil Class Class 2A
Unit Weight of Soil γs 1733 kg/m3
Rankine Passive Earth Pressure Coeff. Kp 3.0
unit Weight of concrete γc 2446 kg/m3
The Characteristic Strength of Concrete Fck 25 MPa
The Characteristic Strength of Reinforcement Fy 460 MPa
Disturbed Soil Thickness a 0.00 m
Additional Load Factor for Foundation Design Ff 1.50
Additional Load Factor for Steel Members Design Fsm 1.50
Design Forces & Safety Factors
Design Overturning Moment at GL M 63522 kg.m
Design Horizontal Load on Pole Hd 5180 kg
Charateristic vertical load Vk 2854 kg
Design vertical load Vd 4281 kg
Design vertical load Vd 42000 N
Foundation Dimensions
Diameter of Caisson Dc 1.10 m
Length of the Caisson Lc 3.50 m
Cover to Reinforcemnt Cover 0.075 m
Pier Steel Design Check
Pier Check for Axial Compression
Area of Steel Required of Shear Braced Column (As Per BS-8110 CL3.8.4.3), (Vd*Fsm*0.81-0.4* Pier Axial Compression
Asac -2528145 mm2
γc*π/4*Dc^2)/(0.8Fy) Steel is not Required
Location of the Mmax below the top of the Caisson,Ym=SQRT((2*HD)/(3*γs*Kp*Dc)) Ym 0.777 m
Maximum Bending Moment, Mmax=M+QYm-(QYm)/3 Mmax 66206 kg.m
Maximum Bending Moment Mmax 649478958 N.mm
Num. of Bar 1 Provided for Pier No. 14
Dia. Of Main Bar 1 Provided for Pier Dia1 20 mm
Diameter of Stirrups Dia2 10 mm
Min. Spacing of Steel (As Per CL.3.12.11) Not Less than Dia of Bar or 25mm Spmin 25 mm
Max. Spacing of Steel (As Per CL.3.12.11.2.7) Not Less than Dia of Bar or 25mm Spmax 300 mm
Spacing of Reinforcement, Pie*(Dc-2*Cover)/No1*1000 Spa 213 mm O.K
Total Area of Steel, (Pie/4*Dia^2)*No1 Asc 4400 mm2
The Area of the Concrete, (pie/4)*Dc^2 Ac 950714 mm2
Required Max. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmax 6.00%
As Per CL.3.12.6.2 of BS-8110
Required Min. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmin 0.40%
As Per Table 3.25 of BS-8110
Percentage of Steel Bar Provided, Asc/(Dc^2*pie/4) Psa 0.46% O.K
Relative Effective Height of Concrete Compression Zone Xr 0.166
Max.Relative Effective Height of Concrete Comp. Zone Xmax 0.196
Relative Calculation Variation, 0.5-0.8*Xr K1 0.367
Sqrt(0.25-k1^2) K2 0.340
K2/Sqrt(K1^2+K2^2) sinθ 0.679
The Effective Height of the Circular Section d 1005 mm
Ultimate Moment of the Part of the Concrete, 4/(3Pie)*(0.25*sinθ-2*K2*K1^2)*0.567* γ c*d*Ac McO 450468078 N.mm
Ultimate Axial Force of the Part of the Concrete, 4/Pie*(0.25-K1*K2))*0.567* γ c*Ac FcO 210427641 N
Area of Steel Asi 314 mm
SUM(fsiAsi) SUM(fsiAsi) 2024000
SUM(Fsi*Asi*esi) SUM(Fsi*Asi*esi) 716988517
Ultimate Moment Capacity for Pier, McO+SUM(fsiAsiesi) Mrd 1167456595 N.mm O.K
Ultimate axial Comp. Capacity for Pier, FcO+SUM(fsiAsi) Nrd 169961313 N O.K
SS3-12: Page 2 of 2
RESISTING MOMENT MOBILIZED BY REINFORCEMENT
Fsi Asi Ysi ei No. Fsi*Asi*ei cover 75 mm
1 460 314.28571 95 -101 1 -14566534.52 Dia. stirrups 10 mm
2 460 314.28571 140 -56 2 -16121640.48 Main Bar Dia 20 mm
3 460 314.28571 266 70 2 20310359.52 Main Bar dia/2 10 mm
4 460 314.28571 449 253 2 73223502.38 Pier Dia. 1100 mm
5 460 314.28571 651 455 2 131630359.5 d = 1005 mm
6 460 314.28571 834 638 2 184543502.4 Asbar = 314.2857 mm2
7 460 314.28571 960 764 2 220975502.4 No. = 14
8 460 314.28571 1005 809 1 116993465.5 fy 460 MPa
Ts = 1922800 N
fck 25 MPa
Depth of stress block = 166 mm
Arae Comp. = 90485 mm2
Cc 1922800 N
Ts-Cc 0.00 N
sum(Fsi*Asi*esi) 716988516.7 N.mm Depth to Neutral Axis 196 mm
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SS3-15 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SS3-15 Suspension Type
Top Pole Diameter dt mm 260
Bottom Pole Diameter db mm 724
Pole Total Height Lp m 19.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate

Pole diameter at outcrop top dout mm 950 Base Plate Diameter


Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 45.00 Shear
Design Horizontal Load on Pole Hd kN 54.45 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 650.00 Moment
Design Overturning Moment at GL Md kN.m 786.50 Factored Moment
Characteristic Vertical load Vk kN 35.00 Axial
The Moment to Shear Ratio, e e m 14.44
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C25
Length of the Caisson Lc m 3.6 For Overturning Resistance
Diameter of Caisson Dc m 1.200 Provide 1200 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.20
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 79.1 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 1142.8 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 1.50 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 1.50 O.K, >/= 1.5
Volume of Caisson Vc m3 4.51 Caisson Concrete + Outcrop
B: Bearing Capacitry:
Diameter of Base B m 1.20 1200 mm
Bearing Area of pad Abase m2 1.13
Dead weight of foundation Gf kN 108.35 Caisson Weight
Total Vertical load P kN 157.68 Factored
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 139 Maximum Base Pressure

Ratio sallowable /sapplied 2.51 O.K


Concrete Volume of Required for Foundation Vtotal m3 4.51 For Each Pole
SS3-15: Page 1 of 2
SINOTEC-GTSCC JV
REINFORCEMENT DESIGN CALCULATION AS PER BS 8110
Date Modified: 5/12/2022
Pole Type SS3-15 Suspension
Description Symbol Value Unit Remarks
Design Data
Design Soil Class Class 2A
Unit Weight of Soil γs 1733 kg/m3
Rankine Passive Earth Pressure Coeff. Kp 3.0
unit Weight of concrete γc 2446 kg/m3
The Characteristic Strength of Concrete Fck 25 MPa
The Characteristic Strength of Reinforcement Fy 460 MPa
Disturbed Soil Thickness a 0.00 m
Additional Load Factor for Foundation Design Ff 1.50
Additional Load Factor for Steel Members Design Fsm 1.50
Design Forces & Safety Factors
Design Overturning Moment at GL M 80173 kg.m
Design Horizontal Load on Pole Hd 5550 kg
Charateristic vertical load Vk 3568 kg
Design vertical load Vd 5352 kg
Design vertical load Vd 52500 N
Foundation Dimensions
Diameter of Caisson Dc 1.20 m
Length of the Caisson Lc 3.60 m
Cover to Reinforcemnt Cover 0.075 m
Pier Steel Design Check
Pier Check for Axial Compression
Area of Steel Required of Shear Braced Column (As Per BS-8110 CL3.8.4.3), (Vd*Fsm*0.81-0.4* Pier Axial Compression
Asac -3008701 mm2
γc*π/4*Dc^2)/(0.8Fy) Steel is not Required
Location of the Mmax below the top of the Caisson,Ym=SQRT((2*HD)/(3*γs*Kp*Dc)) Ym 0.770 m
Maximum Bending Moment, Mmax=M+QYm-(QYm)/3 Mmax 83023 kg.m
Maximum Bending Moment Mmax 814456592 N.mm
Num. of Bar 1 Provided for Pier No. 16
Dia. Of Main Bar 1 Provided for Pier Dia1 20 mm
Diameter of Stirrups Dia2 10 mm
Min. Spacing of Steel (As Per CL.3.12.11) Not Less than Dia of Bar or 25mm Spmin 25 mm
Max. Spacing of Steel (As Per CL.3.12.11.2.7) Not Less than Dia of Bar or 25mm Spmax 300 mm
Spacing of Reinforcement, Pie*(Dc-2*Cover)/No1*1000 Spa 206 mm O.K
Total Area of Steel, (Pie/4*Dia^2)*No1 Asc 5029 mm2
The Area of the Concrete, (pie/4)*Dc^2 Ac 1131429 mm2
Required Max. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmax 6.00%
As Per CL.3.12.6.2 of BS-8110
Required Min. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmin 0.40%
As Per Table 3.25 of BS-8110
Percentage of Steel Bar Provided, Asc/(Dc^2*pie/4) Psa 0.44% O.K
Relative Effective Height of Concrete Compression Zone Xr 0.177
Max.Relative Effective Height of Concrete Comp. Zone Xmax 0.208 O.K
Relative Calculation Variation, 0.5-0.8*Xr K1 0.359
Sqrt(0.25-k1^2) K2 0.348
K2/Sqrt(K1^2+K2^2) sinθ 0.696
The Effective Height of the Circular Section d 1105 mm
Ultimate Moment of the Part of the Concrete, 4/(3Pie)*(0.25*sinθ-2*K2*K1^2)*0.567* γ c*d*Ac McO 635060369 N.mm
Ultimate Axial Force of the Part of the Concrete, 4/Pie*(0.25-K1*K2))*0.567* γ c*Ac FcO 249798948 N
Area of Steel Asi 314 mm
SUM(fsiAsi) SUM(fsiAsi) 2313143
SUM(Fsi*Asi*esi) SUM(Fsi*Asi*esi) 907508101
Ultimate Moment Capacity for Pier, McO+SUM(fsiAsiesi) Mrd 1542568470 N.mm O.K
Ultimate axial Comp. Capacity for Pier, FcO+SUM(fsiAsi) Nrd 201689673 N O.K
SS3-15: Page 2 of 2
RESISTING MOMENT MOBILIZED BY REINFORCEMENT
Fsi Asi Ysi ei No. Fsi*Asi*ei cover 75 mm
1 460 314.28571 95 -113 1 -16289315.09 Dia. stirrups 10 mm
2 460 314.28571 133 -75 2 -21591201.6 Main Bar Dia 20 mm
3 460 314.28571 243 35 2 10214512.68 Main Bar dia/2 10 mm
4 460 314.28571 407 199 2 57633941.25 Pier Dia. 1200 mm
5 460 314.28571 600 392 2 113438512.7 d = 1105 mm
6 460 314.28571 793 585 2 169243084.1 Asbar = 314.2857 mm2
7 460 314.28571 957 749 2 216662512.7 No. = 16
8 460 314.28571 1067 859 2 248468227 fy 460 MPa
9 460 314.28571 1105 897 1 129727827.8 Ts = 2197486 N
fck 25 MPa
Depth of stress block = 177 mm
Arae Comp. = 103411 mm2
Cc 2197486 N
Ts-Cc 0.00 N
sum(Fsi*Asi*esi) 907508101.5 N.mm Depth to Neutral Axis 208 mm
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SSZ3-14 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SSZ3-14 Suspension Type
Top Pole Diameter dt mm 300
Bottom Pole Diameter db mm 750
Pole Total Height Lp m 21.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate

Pole diameter at outcrop top dout mm 1000 Base Plate Diameter


Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 50.00 Shear
Design Horizontal Load on Pole Hd kN 60.50 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 842.00 Moment
Design Overturning Moment at GL Md kN.m 1018.82 Factored Moment
Characteristic Vertical load Vk kN 43.00 Axial
The Moment to Shear Ratio, e e m 16.84
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C25
Length of the Caisson Lc m 3.8 For Overturning Resistance
Diameter of Caisson Dc m 1.250 Provide 1250 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.25
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 84.7 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 1427.0 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 1.50 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 1.50 O.K, >/= 1.5
Volume of Caisson Vc m3 5.16 Caisson Concrete + Outcrop
B: Bearing Capacitry:
Diameter of Base B m 1.25 1250 mm
Bearing Area of pad Abase m2 1.23
Dead weight of foundation Gf kN 123.75 Caisson Weight
Total Vertical load P kN 183.43 Factored
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 149 Maximum Base Pressure

Ratio sallowable /sapplied 2.34 O.K


Concrete Volume of Required for Foundation Vtotal m3 5.16 For Each Pole
SSZ3-14: Page 1 of 2
SINOTEC-GTSCC JV
REINFORCEMENT DESIGN CALCULATION AS PER BS 8110
Date Modified: 5/12/2022
Pole Type SSZ3-14 Suspension
Description Symbol Value Unit Remarks
Design Data
Design Soil Class Class 2A
Unit Weight of Soil γs 1733 kg/m3
Rankine Passive Earth Pressure Coeff. Kp 3.0
unit Weight of concrete γc 2446 kg/m3
The Characteristic Strength of Concrete Fck 25 MPa
The Characteristic Strength of Reinforcement Fy 460 MPa
Disturbed Soil Thickness a 0.00 m
Additional Load Factor for Foundation Design Ff 1.50
Additional Load Factor for Steel Members Design Fsm 1.50
Design Forces & Safety Factors
Design Overturning Moment at GL M 103855 kg.m
Design Horizontal Load on Pole Hd 6167 kg
Charateristic vertical load Vk 4383 kg
Design vertical load Vd 6575 kg
Design vertical load Vd 64500 N
Foundation Dimensions
Diameter of Caisson Dc 1.25 m
Length of the Caisson Lc 3.80 m
Cover to Reinforcemnt Cover 0.075 m
Pier Steel Design Check
Pier Check for Axial Compression
Area of Steel Required of Shear Braced Column (As Per BS-8110 CL3.8.4.3), (Vd*Fsm*0.81-0.4* Pier Axial Compression
Asac -3264647 mm2
γc*π/4*Dc^2)/(0.8Fy) Steel is not Required
Location of the Mmax below the top of the Caisson,Ym=SQRT((2*HD)/(3*γs*Kp*Dc)) Ym 0.795 m
Maximum Bending Moment, Mmax=M+QYm-(QYm)/3 Mmax 107126 kg.m
Maximum Bending Moment Mmax 1050901604 N.mm
Num. of Bar 1 Provided for Pier No. 16
Dia. Of Main Bar 1 Provided for Pier Dia1 20 mm
Diameter of Stirrups Dia2 10 mm
Min. Spacing of Steel (As Per CL.3.12.11) Not Less than Dia of Bar or 25mm Spmin 25 mm
Max. Spacing of Steel (As Per CL.3.12.11.2.7) Not Less than Dia of Bar or 25mm Spmax 300 mm
Spacing of Reinforcement, Pie*(Dc-2*Cover)/No1*1000 Spa 216 mm O.K
Total Area of Steel, (Pie/4*Dia^2)*No1 Asc 5029 mm2
The Area of the Concrete, (pie/4)*Dc^2 Ac 1227679 mm2
Required Max. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmax 6.00%
As Per CL.3.12.6.2 of BS-8110
Required Min. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmin 0.40%
As Per Table 3.25 of BS-8110
Percentage of Steel Bar Provided, Asc/(Dc^2*pie/4) Psa 0.41% O.K
Relative Effective Height of Concrete Compression Zone Xr 0.174
Max.Relative Effective Height of Concrete Comp. Zone Xmax 0.205
Relative Calculation Variation, 0.5-0.8*Xr K1 0.361
Sqrt(0.25-k1^2) K2 0.346
K2/Sqrt(K1^2+K2^2) sinθ 0.692
The Effective Height of the Circular Section d 1155 mm
Ultimate Moment of the Part of the Concrete, 4/(3Pie)*(0.25*sinθ-2*K2*K1^2)*0.567* γ c*d*Ac McO 706486917 N.mm
Ultimate Axial Force of the Part of the Concrete, 4/Pie*(0.25-K1*K2))*0.567* γ c*Ac FcO 271170364 N
Area of Steel Asi 314 mm
SUM(fsiAsi) SUM(fsiAsi) 2313143
SUM(Fsi*Asi*esi) SUM(Fsi*Asi*esi) 972669956
Ultimate Moment Capacity for Pier, McO+SUM(fsiAsiesi) Mrd 1679156873 N.mm O.K
Ultimate axial Comp. Capacity for Pier, FcO+SUM(fsiAsi) Nrd 218786806 N O.K
SSZ3-14: Page 2 of 2
RESISTING MOMENT MOBILIZED BY REINFORCEMENT
Fsi Asi Ysi ei No. Fsi*Asi*ei cover 75 mm
1 460 314.28571 95 -110 1 -15830984.87 Dia. stirrups 10 mm
2 460 314.28571 135 -70 2 -20096255.46 Main Bar Dia 20 mm
3 460 314.28571 250 45 2 13155173.11 Main Bar dia/2 10 mm
4 460 314.28571 422 217 2 62887744.54 Pier Dia. 1250 mm
5 460 314.28571 625 420 2 121583744.5 d = 1155 mm
6 460 314.28571 828 623 2 180279744.5 Asbar = 314.2857 mm2
7 460 314.28571 1000 795 2 230012316 No. = 16
8 460 314.28571 1115 910 2 263263744.5 fy 460 MPa
9 460 314.28571 1155 950 1 137414729.4 Ts = 2197486 N
fck 25 MPa
Depth of stress block = 174 mm
Arae Comp. = 103411 mm2
Cc 2197486 N
Ts-Cc 0.00 N
sum(Fsi*Asi*esi) 972669956.3 N.mm Depth to Neutral Axis 205 mm
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SSZ3-17 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SSZ3-17 Suspension Type
Top Pole Diameter dt mm 300
Bottom Pole Diameter db mm 803
Pole Total Height Lp m 24.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate

Pole diameter at outcrop top dout mm 1050 Base Plate Diameter


Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 53.00 Shear
Design Horizontal Load on Pole Hd kN 64.13 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 902.00 Moment
Design Overturning Moment at GL Md kN.m 1091.42 Factored Moment
Characteristic Vertical load Vk kN 49.00 Axial
The Moment to Shear Ratio, e e m 17.02
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C25
Length of the Caisson Lc m 3.8 For Overturning Resistance
Diameter of Caisson Dc m 1.350 Provide 1350 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.35
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 90.7 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 1544.2 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 1.50 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 1.50 O.K, >/= 1.5
Volume of Caisson Vc m3 6.01 Caisson Concrete + Outcrop
B: Bearing Capacitry:
Diameter of Base B m 1.35 1350 mm
Bearing Area of pad Abase m2 1.43
Dead weight of foundation Gf kN 144.34 Caisson Weight
Total Vertical load P kN 212.68 Factored
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 149 Maximum Base Pressure

Ratio sallowable /sapplied 2.36 O.K


Concrete Volume of Required for Foundation Vtotal m3 6.01 For Each Pole
SSZ3-17: Page 1 of 2
SINOTEC-GTSCC JV
REINFORCEMENT DESIGN CALCULATION AS PER BS 8110
Date Modified: 5/12/2022
Pole Type SSZ3-17 Suspension
Description Symbol Value Unit Remarks
Design Data
Design Soil Class Class 2A
Unit Weight of Soil γs 1733 kg/m3
Rankine Passive Earth Pressure Coeff. Kp 3.0
unit Weight of concrete γc 2446 kg/m3
The Characteristic Strength of Concrete Fck 25 MPa
The Characteristic Strength of Reinforcement Fy 460 MPa
Disturbed Soil Thickness a 0.00 m
Additional Load Factor for Foundation Design Ff 1.50
Additional Load Factor for Steel Members Design Fsm 1.50
Design Forces & Safety Factors
Design Overturning Moment at GL M 111256 kg.m
Design Horizontal Load on Pole Hd 6537 kg
Charateristic vertical load Vk 4995 kg
Design vertical load Vd 7492 kg
Design vertical load Vd 73500 N
Foundation Dimensions
Diameter of Caisson Dc 1.35 m
Length of the Caisson Lc 3.80 m
Cover to Reinforcemnt Cover 0.075 m
Pier Steel Design Check
Pier Check for Axial Compression
Area of Steel Required of Shear Braced Column (As Per BS-8110 CL3.8.4.3), (Vd*Fsm*0.81-0.4* Pier Axial Compression
Asac -3807885 mm2
γc*π/4*Dc^2)/(0.8Fy) Steel is not Required
Location of the Mmax below the top of the Caisson,Ym=SQRT((2*HD)/(3*γs*Kp*Dc)) Ym 0.788 m
Maximum Bending Moment, Mmax=M+QYm-(QYm)/3 Mmax 114690 kg.m
Maximum Bending Moment Mmax 1125110154 N.mm
Num. of Bar 1 Provided for Pier No. 20
Dia. Of Main Bar 1 Provided for Pier Dia1 20 mm
Diameter of Stirrups Dia2 10 mm
Min. Spacing of Steel (As Per CL.3.12.11) Not Less than Dia of Bar or 25mm Spmin 25 mm
Max. Spacing of Steel (As Per CL.3.12.11.2.7) Not Less than Dia of Bar or 25mm Spmax 300 mm
Spacing of Reinforcement, Pie*(Dc-2*Cover)/No1*1000 Spa 189 mm O.K
Total Area of Steel, (Pie/4*Dia^2)*No1 Asc 6286 mm2
The Area of the Concrete, (pie/4)*Dc^2 Ac 1431964 mm2
Required Max. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmax 6.00%
As Per CL.3.12.6.2 of BS-8110
Required Min. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmin 0.40%
As Per Table 3.25 of BS-8110
Percentage of Steel Bar Provided, Asc/(Dc^2*pie/4) Psa 0.44% O.K
Relative Effective Height of Concrete Compression Zone Xr 0.197
Max.Relative Effective Height of Concrete Comp. Zone Xmax 0.232
Relative Calculation Variation, 0.5-0.8*Xr K1 0.342
Sqrt(0.25-k1^2) K2 0.364
K2/Sqrt(K1^2+K2^2) sinθ 0.729
The Effective Height of the Circular Section d 1255 mm
Ultimate Moment of the Part of the Concrete, 4/(3Pie)*(0.25*sinθ-2*K2*K1^2)*0.567* γ c*d*Ac McO 1044894223 N.mm
Ultimate Axial Force of the Part of the Concrete, 4/Pie*(0.25-K1*K2))*0.567* γ c*Ac FcO 316612327 N
Area of Steel Asi 314 mm
SUM(fsiAsi) SUM(fsiAsi) 2891429
SUM(Fsi*Asi*esi) SUM(Fsi*Asi*esi) 1281940683
Ultimate Moment Capacity for Pier, McO+SUM(fsiAsiesi) Mrd 2326834906 N.mm O.K
Ultimate axial Comp. Capacity for Pier, FcO+SUM(fsiAsi) Nrd 255603005 N O.K
SSZ3-17: Page 2 of 2
RESISTING MOMENT MOBILIZED BY REINFORCEMENT
Fsi Asi Ysi ei No. Fsi*Asi*ei cover 75 mm
1 460 314.28571 95 -137 1 -19754394.4 Dia. stirrups 10 mm
2 460 314.28571 123 -109 2 -31412788.8 Main Bar Dia 20 mm
3 460 314.28571 206 -26 2 -7413931.656 Main Bar dia/2 10 mm
4 460 314.28571 334 102 2 29596354.06 Pier Dia. 1350 mm
5 460 314.28571 496 264 2 76437496.92 d = 1255 mm
6 460 314.28571 675 443 2 128194068.3 Asbar = 314.2857 mm2
7 460 314.28571 854 622 2 179950639.8 No. = 20
8 460 314.28571 1016 784 2 226791782.6 fy 460 MPa
9 460 314.28571 1144 912 2 263802068.3 Ts = 2746857 N
10 460 314.28571 1227 995 2 287800925.5 fck 25 MPa
11 460 314.28571 1255 1023 1 147948462.7 Depth of stress block = 197 mm
Arae Comp. = 129264 mm2
Cc 2746857 N
Ts-Cc 0.00 N
sum(Fsi*Asi*esi) 1281940683 N.mm Depth to Neutral Axis 232 mm
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SSZ3-20 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SSZ3-20 Suspension Type
Top Pole Diameter dt mm 300
Bottom Pole Diameter db mm 869
Pole Total Height Lp m 27.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate

Pole diameter at outcrop top dout mm 1120 Base Plate Diameter


Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 56.76 Shear
Design Horizontal Load on Pole Hd kN 68.68 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 1072.02 Moment
Design Overturning Moment at GL Md kN.m 1297.14 Factored Moment
Characteristic Vertical load Vk kN 55.24 Axial
The Moment to Shear Ratio, e e m 18.89
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C25
Length of the Caisson Lc m 4.0 For Overturning Resistance
Diameter of Caisson Dc m 1.400 Provide 1400 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.40
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 99.8 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 1885.5 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 1.50 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 1.50 O.K, >/= 1.5
Volume of Caisson Vc m3 6.79 Caisson Concrete + Outcrop
B: Bearing Capacitry:
Diameter of Base B m 1.40 1400 mm
Bearing Area of pad Abase m2 1.54
Dead weight of foundation Gf kN 162.99 Caisson Weight
Total Vertical load P kN 240.06 Factored
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 156 Maximum Base Pressure

Ratio sallowable /sapplied 2.25 O.K


Concrete Volume of Required for Foundation Vtotal m3 6.79 For Each Pole
SSZ3-20: Page 1 of 2
SINOTEC-GTSCC JV
REINFORCEMENT DESIGN CALCULATION AS PER BS 8110
Date Modified: 5/12/2022
Pole Type SSZ3-20 Suspension
Description Symbol Value Unit Remarks
Design Data
Design Soil Class Class 2A
Unit Weight of Soil γs 1733 kg/m3
Rankine Passive Earth Pressure Coeff. Kp 3.0
unit Weight of concrete γc 2446 kg/m3
The Characteristic Strength of Concrete Fck 25 MPa
The Characteristic Strength of Reinforcement Fy 460 MPa
Disturbed Soil Thickness a 0.00 m
Additional Load Factor for Foundation Design Ff 1.50
Additional Load Factor for Steel Members Design Fsm 1.50
Design Forces & Safety Factors
Design Overturning Moment at GL M 132227 kg.m
Design Horizontal Load on Pole Hd 7001 kg
Charateristic vertical load Vk 5631 kg
Design vertical load Vd 8446 kg
Design vertical load Vd 82860 N
Foundation Dimensions
Diameter of Caisson Dc 1.40 m
Length of the Caisson Lc 4.00 m
Cover to Reinforcemnt Cover 0.075 m
Pier Steel Design Check
Pier Check for Axial Compression
Area of Steel Required of Shear Braced Column (As Per BS-8110 CL3.8.4.3), (Vd*Fsm*0.81-0.4* Pier Axial Compression
Asac -4095172 mm2
γc*π/4*Dc^2)/(0.8Fy) Steel is not Required
Location of the Mmax below the top of the Caisson,Ym=SQRT((2*HD)/(3*γs*Kp*Dc)) Ym 0.801 m
Maximum Bending Moment, Mmax=M+QYm-(QYm)/3 Mmax 135964 kg.m
Maximum Bending Moment Mmax 1333809534 N.mm
Num. of Bar 1 Provided for Pier No. 20
Dia. Of Main Bar 1 Provided for Pier Dia1 20 mm
Diameter of Stirrups Dia2 10 mm
Min. Spacing of Steel (As Per CL.3.12.11) Not Less than Dia of Bar or 25mm Spmin 25 mm
Max. Spacing of Steel (As Per CL.3.12.11.2.7) Not Less than Dia of Bar or 25mm Spmax 300 mm
Spacing of Reinforcement, Pie*(Dc-2*Cover)/No1*1000 Spa 196 mm O.K
Total Area of Steel, (Pie/4*Dia^2)*No1 Asc 6286 mm2
The Area of the Concrete, (pie/4)*Dc^2 Ac 1540000 mm2
Required Max. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmax 6.00%
As Per CL.3.12.6.2 of BS-8110
Required Min. Percentage of Reinforcement due to Biaxial Moment and Axial Comp. Load Pcmin 0.40%
As Per Table 3.25 of BS-8110
Percentage of Steel Bar Provided, Asc/(Dc^2*pie/4) Psa 0.41% O.K
Relative Effective Height of Concrete Compression Zone Xr 0.194
Max.Relative Effective Height of Concrete Comp. Zone Xmax 0.228
Relative Calculation Variation, 0.5-0.8*Xr K1 0.345
Sqrt(0.25-k1^2) K2 0.362
K2/Sqrt(K1^2+K2^2) sinθ 0.725
The Effective Height of the Circular Section d 1305 mm
Ultimate Moment of the Part of the Concrete, 4/(3Pie)*(0.25*sinθ-2*K2*K1^2)*0.567* γ c*d*Ac McO 1149107786 N.mm
Ultimate Axial Force of the Part of the Concrete, 4/Pie*(0.25-K1*K2))*0.567* γ c*Ac FcO 340275922 N
Area of Steel Asi 314 mm
SUM(fsiAsi) SUM(fsiAsi) 2891429
SUM(Fsi*Asi*esi) SUM(Fsi*Asi*esi) 1363336338
Ultimate Moment Capacity for Pier, McO+SUM(fsiAsiesi) Mrd 2512444123 N.mm O.K
Ultimate axial Comp. Capacity for Pier, FcO+SUM(fsiAsi) Nrd 274533881 N O.K
SSZ3-20: Page 2 of 2
RESISTING MOMENT MOBILIZED BY REINFORCEMENT
Fsi Asi Ysi ei No. Fsi*Asi*ei cover 75 mm
1 460 314.28571 95 -133 1 -19298897.4 Dia. stirrups 10 mm
2 460 314.28571 125 -103 2 -29923509.1 Main Bar Dia 20 mm
3 460 314.28571 211 -17 2 -5057223.381 Main Bar dia/2 10 mm
4 460 314.28571 344 116 2 33398776.62 Pier Dia. 1400 mm
5 460 314.28571 513 285 2 82263919.48 d = 1305 mm
6 460 314.28571 700 472 2 136333633.8 Asbar = 314.2857 mm2
7 460 314.28571 887 659 2 190403348 No. = 20
8 460 314.28571 1056 828 2 239268490.9 fy 460 MPa
9 460 314.28571 1189 961 2 277724490.9 Ts = 2746857 N
10 460 314.28571 1275 1047 2 302590776.6 fck 25 MPa
11 460 314.28571 1305 1077 1 155632531.2 Depth of stress block = 194 mm
Arae Comp. = 129264 mm2
Cc 2746857 N
Ts-Cc 0.00 N
sum(Fsi*Asi*esi) 1363336338 N.mm Depth to Neutral Axis 228 mm
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES


DOCUMENT No.: P-SL-F00-007/CM/A0240/H/002/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SA3-12 Angle
Subject Symbol Unit Remarks
Safety Factor for Unfavourable Actions γActions 1.10 For Overturning Moment
Pole Properties:-Please Refer to Fabrication drawings
Pole Type A-Type SA3-12 Angle Pole
Top Pole Diameter dt mm 350
Bottom Pole Diameter db mm 616
Pole Total Height Lp m 18.00
Length of Pole Embeddment Le m 2.10
Pole diameter at ground line (GL) dGL mm 585
Pole diameter at outcrop top dout mm 582
Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 16.50 Shear
Design Horizontal Load on Pole Hd kN 19.97 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 5.67 Moment
Design Overturning Moment at GL Md kN.m 6.86 Factored Moment
Characteristic Vertical load Vk kN 206.61 Axial
The Moment to Shear Ratio, e e m 0.34
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C20
Length of the Caisson Lc m 2.1 For Overturning Resistance
Diameter of Caisson Dc m 0.900 Provide 900 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 0.90
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 87.0 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 29.9 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 4.36 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 4.36 O.K, >/= 1.5
Volume of Caisson Vc m3 0.86 Concrete Backfill + Outcrop
B: Bearing Capacitry:
Diameter of pad B m 1.10 1100 mm
Thickness of Base Concrete and Blinding Dp m 0.125 (75 mm Blinding)
Bearing Area of pad Abase m2 0.95
Volume of pad Vp m3 0.12
Dead weight of foundation Gf kN 23.55 Caisson + Pad
Total Vertical load P kN 259.06 Including Weight of Soil Over Pad
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 272 Maximum Base Pressure

Ratio sallowable /sapplied 1.28 O.K


Concrete Volume of Required for Foundation Vtotal m 3
1.96 For Double Poles
SA3-12: Page 1 of 1
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES


DOCUMENT No.: P-SL-F00-007/CM/A0240/H/002/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SA3-15 Angle
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type A-Type SA3-15 Angle Pole
Top Pole Diameter dt mm 350
Bottom Pole Diameter db mm 667
Pole Total Height Lp m 21.30
Length of Pole Embeddment Le m 2.40
Pole diameter at ground line (GL) dGL mm 631
Pole diameter at outcrop top dout mm 628
Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 11.41 Shear
Design Horizontal Load on Pole Hd kN 13.81 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 14.33 Moment
Design Overturning Moment at GL Md kN.m 17.34 Factored Moment
Characteristic Vertical load Vk kN 206.61 Axial
The Moment to Shear Ratio, e e m 1.26
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C20
Length of the Caisson Lc m 2.4 For Overturning Resistance
Diameter of Caisson Dc m 0.900 Provide 900 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 0.90
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 86.8 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 109.0 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 6.29 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 6.29 O.K, >/= 1.5
Volume of Caisson Vc m3 0.86 Concrete Backfill + Outcrop
B: Bearing Capacitry:
Diameter of pad B m 1.10 1100 mm
Thickness of Base Concrete and Blinding Dp m 0.125 (75 mm Blinding)
Bearing Area of pad Abase m2 0.95
Volume of pad Vp m3 0.12
Dead weight of foundation Gf kN 23.74 Caisson + Pad
Total Vertical load P kN 259.26 Including Weight of Soil Over Pad
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 273 Maximum Base Pressure

Ratio sallowable /sapplied 1.28 O.K


Concrete Volume of Required for Foundation Vtotal m 3
1.98 For Double Poles
SA3-15: Page 1 of 1
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES


DOCUMENT No.: P-SL-F00-007/CM/A0240/H/004/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SHA3-12 Heavy Angle
Subject Symbol Unit Remarks
Safety Factor for Unfavourable Actions γActions 1.10 For Overturning Moment
Pole Properties:-Please Refer to Fabrication drawings
Pole Type HA-Type SHA3-12 Heavy Angle Pole
Top Pole Diameter dt mm 380
Bottom Pole Diameter db mm 666
Pole Total Height Lp m 18.00
Length of Pole Embeddment Le m 2.10
Pole diameter at ground line (GL) dGL mm 633
Pole diameter at outcrop top dout mm 629
Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 26.39 Shear
Design Horizontal Load on Pole Hd kN 31.93 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 51.22 Moment
Design Overturning Moment at GL Md kN.m 61.98 Factored Moment
Characteristic Vertical load Vk kN 273.31 Axial
The Moment to Shear Ratio, e e m 1.94
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C20
Length of the Caisson Lc m 2.1 For Overturning Resistance
Diameter of Caisson Dc m 1.000 Provide 1000 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.00
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 58.4 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 113.4 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 1.83 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 1.83 O.K, >/= 1.5
Volume of Caisson Vc m3 1.10 Concrete Backfill + Outcrop
B: Bearing Capacitry:
Diameter of pad B m 1.20 1200 mm
Thickness of Base Concrete and Blinding Dp m 0.125 (75 mm Blinding)
Bearing Area of pad Abase m2 1.13
Volume of pad Vp m3 0.15
Dead weight of foundation Gf kN 29.84 Caisson + Pad
Total Vertical load P kN 339.93 Including Weight of Soil Over Pad
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 300 Maximum Base Pressure

Ratio sallowable /sapplied 1.16 O.K


Concrete Volume of Required for Foundation Vtotal m 3
2.49 For Double Poles
SHA3-12: Page 1 of 1
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES


DOCUMENT No.: P-SL-F00-007/CM/A0240/H/004/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SHA3-15 Heavy Angle
Subject Symbol Unit Remarks
Safety Factor for Unfavourable Actions γActions 1.10 For Overturning Moment
Pole Properties:-Please Refer to Fabrication drawings
Pole Type HA-Type SHA3-15 Heavy Angle Pole
Top Pole Diameter dt mm 380
Bottom Pole Diameter db mm 714
Pole Total Height Lp m 21.30
Length of Pole Embeddment Le m 2.40
Pole diameter at ground line (GL) dGL mm 676
Pole diameter at outcrop top dout mm 673
Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 2
350
Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated
Characteristic Horizontal Load on Pole Hk kN 19.47 Shear
Design Horizontal Load on Pole Hd kN 23.56 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 28.52 Moment
Design Overturning Moment at GL Md kN.m 34.51 Factored Moment
Characteristic Vertical load Vk kN 284.50 Axial
The Moment to Shear Ratio, e e m 1.46
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C20
Length of the Caisson Lc m 2.4 For Overturning Resistance
Diameter of Caisson Dc m 1.000 Provide 1000 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.00
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 91.2 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 133.6 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 3.87 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 3.87 O.K, >/= 1.5
Volume of Caisson Vc m3 1.13 Concrete Backfill + Outcrop
B: Bearing Capacitry:
Diameter of pad B m 1.20 1200 mm
Thickness of Base Concrete and Blinding Dp m 0.125 (75 mm Blinding)
Bearing Area of pad Abase m2 1.13
Volume of pad Vp m3 0.15
Dead weight of foundation Gf kN 30.75 Caisson + Pad
Total Vertical load P kN 353.24 Including Weight of Soil Over Pad
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 312 Maximum Base Pressure

Ratio sallowable /sapplied 1.12 O.K


Concrete Volume of Required for Foundation Vtotal m 3
2.56 For Double Poles
SHA3-15: Page 1 of 1
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES


DOCUMENT No.: P-SL-F00-007/CM/A0240/H/003/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SDE3-12 Deadend
Subject Symbol Unit Remarks
Safety Factor for Unfavourable Actions γActions 1.10 For Overturning Moment
Pole Properties:-Please Refer to Fabrication drawings
Pole Type DE-Type SDE3-12 Deadend Pole
Top Pole Diameter dt mm 380
Bottom Pole Diameter db mm 666
Pole Total Height Lp m 18.00
Length of Pole Embeddment Le m 2.10
Pole diameter at ground line (GL) dGL mm 633
Pole diameter at outcrop top dout mm 629
Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 350
2

Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated


Characteristic Horizontal Load on Pole Hk kN 26.39 Shear
Design Horizontal Load on Pole Hd kN 31.93 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 51.22 Moment
Design Overturning Moment at GL Md kN.m 61.98 Factored Moment
Characteristic Vertical load Vk kN 273.31 Axial
The Moment to Shear Ratio, e e m 1.94
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C20
Length of the Caisson Lc m 2.1 For Overturning Resistance
Diameter of Caisson Dc m 1.000 Provide 1000 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.00
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 58.4 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 113.4 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 1.83 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 1.83 O.K, >/= 1.5
Volume of Caisson Vc m3 1.10 Concrete Backfill + Outcrop
B: Bearing Capacitry:
Diameter of pad B m 1.20 1200 mm
Thickness of Base Concrete and Blinding Dp m 0.125 (75 mm Blinding)
Bearing Area of pad Abase m2 1.13
Volume of pad Vp m3 0.15
Dead weight of foundation Gf kN 29.84 Caisson + Pad
Total Vertical load P kN 339.93 Including Weight of Soil Over Pad
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 300 Maximum Base Pressure

Ratio sallowable /sapplied 1.16 O.K


Concrete Volume of Required for Foundation Vtotal m 3
2.49 For Double Poles
SDE3-12: Page 1 of 1
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK

REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:

CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL

ICB N°: EDSA/AFDB/DIST/ICB/01/REH/07/18


LOAN No.: P-SL-F00-007

CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES


DOCUMENT No.: P-SL-F00-007/CM/A0240/H/003/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SDE3-15 Deadend
Subject Symbol Unit Remarks
Safety Factor for Unfavourable Actions γActions 1.10 For Overturning Moment
Pole Properties:-Please Refer to Fabrication drawings
Pole Type DE-Type SDE3-15 Deadend Pole
Top Pole Diameter dt mm 380
Bottom Pole Diameter db mm 714
Pole Total Height Lp m 21.30
Length of Pole Embeddment Le m 2.40
Pole diameter at ground line (GL) dGL mm 676
Pole diameter at outcrop top dout mm 673
Soil Properties:-Please Refer to Geotechnical report for 66 and 33 kV Lines
Soil Class Class 2A Geotechnical Investigation Report
Depth to water table D.W.T m >2.0 Dry or Damp soil conditions
Characteristic Angle of Internal Friction φk ° 30.0
Partial Factor for Angle of Internal Friction γφ 1.00 EN1997-1:2004 Table 2.1
Design Angle of Internal Friction φd ° 30.0
Rankine Passive Earth Pressure Coeff. Kp 3.00 Kp = tan2(45+φd/2)
Unit Weight of Soil γs kN/m3 17.00
Earth pressure factor m kN/m2/m 51.0 Equals to; Kp.γs
Allowable Bearing Capacity of Soil sallowable kN/m 350
2

Loads:-Please Refer to Fabrication Drawings, Maximum Base Reactions are Indicated


Characteristic Horizontal Load on Pole Hk kN 19.47 Shear
Design Horizontal Load on Pole Hd kN 23.56 Factored Shear + P-Delta Effect
Characteristic Overturning Moment at GL Mk kN.m 28.52 Moment
Design Overturning Moment at GL Md kN.m 34.51 Factored Moment
Characteristic Vertical load Vk kN 284.50 Axial
The Moment to Shear Ratio, e e m 1.46
Foundation Resistances:-Lateral and Moment Resistances are Based on Broms' Equation for Cohesionless Soils
Unit Weight of Concrete γc kN/m3 24 C20
Length of the Caisson Lc m 2.4 For Overturning Resistance
Diameter of Caisson Dc m 1.000 Provide 1000 mm
Outcrop (Concete above GL) h m 0.20 For Corrosion Protection
Cone Diameter of the Outcrop w m 1.00
A: Ultimate Lateral Resistance Check Based on Broms' Approach
Ultimate Shear Resistance based on Broms' Hu kN 91.2 Hu=(0.5γsDf3KpB)/(e + Df)
Moment Resistance Mu kN.m 133.6 Hu.e
Ratio Hu/Hd (F.O.S) Hu/Hd 3.87 O.K, >/= 1.5
Ratio Mu/Md (F.O.S) Mu/Md 3.87 O.K, >/= 1.5
Volume of Caisson Vc m3 1.13 Concrete Backfill + Outcrop
B: Bearing Capacitry:
Diameter of pad B m 1.20 1200 mm
Thickness of pad Dp m 0.20
Bearing Area of pad Abase m2 1.13
Volume of pad Vp m3 0.24
Dead weight of foundation Gf kN 32.89 Caisson + Pad
Total Vertical load P kN 355.60 Including Weight of Soil Over Pad
Pressure on soil due to the vertical loads;
sapplied = 𝑃/(𝐴𝑏𝑎𝑠𝑒 ) sapplied kN/m2 314 Maximum Base Pressure

Ratio sallowable /sapplied 1.11 O.K


Concrete Volume of Required for Foundation Vtotal m 3
2.74 For Double Poles
SDE3-15: Page 1 of 1