Foundation Design For 66kV Steel Poles Bo-Kenema-SOIL CLASS 2A-08-11-21
Foundation Design For 66kV Steel Poles Bo-Kenema-SOIL CLASS 2A-08-11-21
10
SOIL CONDITIONS
Characteristic Angle of
Depth to Water table Unit Weight of Allowable Bearing
# Soil Condition Internal Friction, φk
(m) Soil, γs (kN/m ) Capacity of Soil (kN/m2)
3
(Degrees)
Notes:
The loads applied loads during pole structural design are factored loads and therefore the base reactions are ultimate reaction.
The safety factor therefore is 1.1 for these calculations
Factor of Safety for loads applied on pole 1.5
Safety factor for loads on foundation 1.1
Factor of safety for resistance 1.5 Minimum
Global Factor of Safety is atleast: 2.5 As required
SINOTEC-GTSCC JV
LOT 2 - DESIGN, SUPPLY, INSTALLATION, AND COMMISIONING OF ONE (1) 33kV OVERHEAD TRANSMISSION LINE
BETWEEN BO AND KENEMA AND REHABILITATION OF 11kV AND 0.4 kV DISTRIBUTION NETWORK
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SS3-12 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SS3-12 Suspension Type
Top Pole Diameter dt mm 260
Bottom Pole Diameter db mm 649
Pole Total Height Lp m 16.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SS3-15 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SS3-15 Suspension Type
Top Pole Diameter dt mm 260
Bottom Pole Diameter db mm 724
Pole Total Height Lp m 19.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SSZ3-14 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SSZ3-14 Suspension Type
Top Pole Diameter dt mm 300
Bottom Pole Diameter db mm 750
Pole Total Height Lp m 21.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SSZ3-17 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SSZ3-17 Suspension Type
Top Pole Diameter dt mm 300
Bottom Pole Diameter db mm 803
Pole Total Height Lp m 24.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REINFORCED CONCRETE FOUNDATION DESIGN CALCULATION SHEET FOR 66kV STEEL POLES
DOCUMENT No.: P-SL-F00-007/CM/A0240/H/005/A
Date Modified: 5/12/2022 Prepared by: Alex Bawa
Pole Type SSZ3-20 Suspension
Subject Symbol Unit Remarks
Safety Factor γActions 1.10 The Ultimate loads are applied
Pole Properties:-Please Refer to Fabrication drawings
Pole Type S-Type SSZ3-20 Suspension Type
Top Pole Diameter dt mm 300
Bottom Pole Diameter db mm 869
Pole Total Height Lp m 27.00
Length of Pole Embeddment Le m 0.00 Poles on Base Plate
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL
REPUBLIC OF SIERRA
ELECTRICITY LEONE AND SUPPLY AUTHORITY (EDSA)
DISTRIBUTION
CLIENT:
CONTRACTOR: SINOTEC-GTSCC JV
CONSULTANT: TRACTEBEL