NO. Malfunction Display Method of Indoor Unit Display Method of Outdoor Unit A/C status Possible Causes
Name Dual-8 Indicator Display (during Indicator has 3 kinds of
Code blinking, ON 0.5s and OFF 0.5s) display status and during
Display blinking, ON 0.5s and OFF 0.5s
Operation Cool Heating Yellow Red Green
Indicator Indicator Indicator Indicator Indicator Indicator
1 High E1 OFF 3s During cooling and drying Possible reasons:
and blink operation, except indoor 1. Refrigerant was
pressure once fan operates, all loads stop superabundant;
protection of operation. During heating 2. Poor heat exchange
system operation, the complete unit (including and bad radiating
stops. environment );
Ambient temperature is too
high.
2 Antifreezing E2 OFF 3S OFF 1S During cooling and drying 1. Poor air-return in indoor
and blink and blink operation, compressor and unit;
protection twice 3 times outdoor fan stop while indoor 2. Fan speed is abnormal;
fan operates. 3. Evaporator is dirty.
3 In defect of F0 OFF 1S The Dual-8 Code Display will 1.In defect of refrigerant;
And blink show F0 and the complete 2.Indoor evaporator
refrigerant 9 times unit stops. temperature
sensor works abnormally;
3.The unit has been plugged
up somewhere.
4 High E4 OFF 3S OFF 1S During cooling and drying Please refer to the
and blink 4 and blink operation, compressor and malfunction analysis
discharge times 7 times outdoor fan stop while indoor (discharge protection,
temperature fan operates. During heating overload).
protection of operation, all loads stop.
compressor
5 Overcurrent E5 OFF 3S OFF 1S During cooling and drying 1. Supply voltage is unstable;
and blink and blink operation, compressor and 2. Supply voltage is too low
protection 5 times 5 times outdoor fan stop while indoor and load is too high;
fan operates. During heating 3. Evaporator is dirty.
operation, all loads stop.
6 Communication E6 OFF 3S Always During cooling operation, Refer to the corresponding
and blink 6 ON compressor stops while malfunction analysis.
Malfunction times indoor fan motor operates.
During heating operation, the
complete unit stops.
7 High E8 OFF 3S OFF 1S During cooling operation: Refer to the malfunction
and blink 8 and blink compressor will stop while analysis (overload, high
temperature times 6 times indoor fan will operate. temperature resistant).
resistant During heating operation, the
protection complete unit stops.
8 EEPROM EE OFF 3S OFF 1S During cooling and drying Replace outdoor control panel
And blink and blink operation, compressor will AP1
malfunction 15 times 11 times stop while indoor fan will
operate; During heating
operation, the complete unit
will stop
9 Limit/ EU OFF 3S OFF 3S All loads operate normally, Discharging after the
and blink 6 and blink 6 While operation frequency complete unit is de-energized
decrease times times for compressor is decreased for 20mins, check whether the
frequency thermal grease on IPM
due to high Module of outdoor control
panel AP1 is sufficient and
temperature of wheter the radiator is inserted
module tightly. If its no use, please
replace control panel AP1.
10 Malfunction C5 OFF 3S Wireless remote receiver and 1. No jumper cap insert on
and blink 15 button are effective, but can mainboard.
protection of times not dispose the related 2. Incorrect insert of jumper
jumper cap command cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit
of mainboard.
11 Gathering Fo OFF 3S OFF 3S OFF 3S When the outdoor unit Nominal cooling mode
and blink 1 and blink 1 and blink receive signal of Gathering
refrigerant times times 17 times refrigerant the system will be
forced to run under cooling
mode for gathering
refrigerant
12 Indoor F1 OFF 3S During cooling and drying 1. Loosening or bad contact
and blink operation, indoor unit of indoor ambient temp.
ambient once operates while other loads sensor and mainboard
temperature will stop; during heating terminal.
sensor is operation, the complete unit 2. Components in mainboard
will stop operation. fell down leads short circuit.
open/short 3. Indoor ambient temp.
circuited sensor damaged.(check with
sensor resistance value chart)
4. Mainboard damaged.
13 Indoor F2 OFF 3S AC stops operation once 1. Loosening or bad contact
and blink reaches the setting of Indoor evaporator temp.
evaporator twice temperature. Cooling, drying: sensor and mainboard
temperature internal fan motor stops terminal.
sensor is operation while other loads 2. Components on the
stop operation; heating: AC mainboard fall down leads
open/short stop operation short circuit.
circuited 3. Indoor evaporator temp.
sensor damaged.(check
temp. sensor value chart for
testing)
4. Mainboard damaged.
' Useful
( Not useful
:
14 Outdoor F3 OFF 3S OFF 1S During cooling and drying Outdoor temperature sensor
and blink and operating, compressor stops hasnt been connected well or
ambient 3 times blink 6 while indoor fan operates; is damaged. Please check it
temperature times During heating operation, by referring to the resistance
sensor is the complete unit will stop table for temperature sensor)
operation
open/short
circuited
15 Outdoor F4 OFF 3S OFF 1S During cooling and drying Outdoor temperature sensor
and blink 4 And blink operation, compressor stops hasnt been connected well or
condenser times 5 times while indoor fan will operate; is damaged. Please check it
temperature During heating operation, by referring to the resistance
sensor is the complete unit will stop table for temperature sensor)
operation.
open/short
circuited
16 Outdoor F5 OFF 3S OFF 1S During cooling and drying 1.Outdoor temperature sensor
and blink 5 And blink operation, compressor will hasnt been connected well or
discharge times 7 times stop after operating for about is damaged. Please check it
temperature 3 mins, while indoor fan will by referring to the resistance
sensor is operate; During heating table for temperature sensor)
operation, the complete unit 2.The head of temperature
open/short will stop after operating for sensor Hasn t been inserted
circuited about 3 mins. into the copper tube
17 Limit/ F6 OFF 3S OFF 1S All loads operate normally, Refer to the malfunction
and blink And blink While operation frequency analysis (overload, high
decrease for 6 times 3 times for compressor is decreased temperature resistant)
frequency
due to
overload
18 Decrease F8 OFF 3S OFF 1S All loads operate normally, The input supply voltage is
and blink 8 And blink While operation frequency too low;
frequency times once for compressor is decreased System pressure is too high
due to and overload
overcurrent
19 Decrease F9 OFF 3S OFF 1S All loads operate normally, Overload or temperature is
and blink 9 And blink While operation frequency too high;
frequency times twice for compressor is decreased Refrigerant is insufficient
due to Malfunction of electric
high air expansion valve (EKV)
discharge
20 Limit/ FH OFF 3S OFF 3S OFF 1S All loads operate normally, Poor air-return in indoor unit
and blink 2 and blink 2 And blink while operation frequency for or fan speed is too low
decrease times times 4 times compressor is decreased
frequency
due to
antifreezing
21 Voltage for PH OFF 3S OFF 1S During cooling and drying 1. Measure the voltage of
and blink And blink operation, compressor will position L and N on wiring
DC bus-bar 11 times 13 times stop while indoor fan will board (XT), if the voltage is
is too high operate; During heating higher than 265VAC, turn
operation, the complete unit on the unit after the supply
will stop operation. voltage is increased to the
normal range.
2.If the AC input is normal,
measure the voltage of
electrolytic capacitor C on
control panel (AP1), if its
normal, theres malfunction
for the circuit, please replace
the control panel (AP1)
22 Voltage of PL OFF 3S OFF 1S During cooling and drying 1. Measure the voltage of
and blink And blink operation, compressor will position L and N on wiring
DC bus-bar 21 times 12 times stop while indoor fan will board (XT), if the voltage is
is too low operate; During heating higher than 150VAC, turn on
operation, the complete unit the unit after the supply
will stop voltage is increased to the
normal range.
2.If the AC input is normal,
measure the voltage of
electrolytic capacitor C on
control panel (AP1), if its
normal, theres malfunction
for the circuit, please replace
the control panel (AP1)
23 Compressor P0 (during (during Showing during min. cooling
blinking, blinking, or min. heating test
Min ON 0.25s ON 0.25s
frequence in and OFF and OFF
test state 0.25s) 0.25s)
Magazines Podcasts
Sheet Music
:
TTA-TWE Catálogo (Inglés)
kuraimund
Electromechanical Engineering
Equipment
:
Hidden Figures: The American
Dream and the Untold Story of
the Black Women…
Margot Lee Shetterly
Mathematicians Who Helped
Win the Space Race
eh126.pdf
Rasiya Sulthana
Show more
:
About Support
Press Accessibility
Contact us Publishers
Invite friends
Social
Gids
Twitter
Legal
Facebook
Terms Pinterest
Privacy
Copyright
Cookie Preferences
Language: English