P.S. NO : KG98/2-ONT-ME-GEN-PS2-00011
P.O.NO. :7861
CONFIDENTIAL AGREEMENT: This document and the information it contains are property of SPARKLE CLEAN TECH PRIVATE
LIMITED. It shall not be used for any purpose other than for which it was supplied. Not to disclose without Authorization
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 2 / CODE-1
COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline KAVIN Comments Vendor Response Status
Date : 02-12-2021 Date: 11-12-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS-
1
150
CRS Sr 47 of Rev-01 IN Vessel spec. shall be SS316L Incorporated Closed
KG98-2-ONT-OMF-IN-7861-DS-
2
150
CRS Sr 47 of Rev-01 IN Dimension " MM " Missing Incorporated Closed
COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
Typical Comments :
1. Vendor to ensure that all level transmitter tags are
covered in the datasheet as per latest P & ID - Rev 05. 1. It is ensured that all level transmitter tags are covered in the datasheet as
2. Vendor to ensure that all Tank height & Tank per latest P & ID - Rev 05.
KG98-2-ONT-OMF-IN-7861-DS- Instrument Nozzle shall be as per Approved Tank GAD 2. It is ensured that all Tank height & Tank Instrument Nozzle shall be as per
1 sheet no. 5 of 26 IN Noted and Closed
150 & accordingly to consider the Calibration range. Approved Tank GAD & accordingly to consider the Calibration range.
3. Vendor to ensure that accuracy of instrument shall be 3. It is ensured that accuracy of instrument shall be as per OEM standard with
as per OEM standard with inline with tender inline with tender specifications
specifications
KG98-2-ONT-OMF-IN-7861-DS-
2 sheet no. 5 of 26 IN T-N79505 tank description to be write properly Incorporated Noted and Closed
150
KG98-2-ONT-OMF-IN-7861-DS-
3 sheet no. 5 of 26 IN T-N79505 MOC is CS-EP as per P&ID Rev.05 Incorporated Noted and Closed
150
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
4 sheet no. 5 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS-
5 Sheet no. 6 of 26 IN T-N79505 MOC is CS-EP as per P&ID Rev.05 Incorporated Noted and Closed
150
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
6 Sheet no. 6 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
9 Sheet no. 7 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS-
10 Sheet no. 7 of 26 IN Vendor to confirm the fluid properties Checked from PFD Rev.04 & incorporated Noted and Closed
150
KG98-2-ONT-OMF-IN-7861-DS-
11 Sheet no. 8 of 26 IN Vendor to confirm the fluid properties Checked from PFD Rev.04 & incorporated Noted and Closed
150
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
12 Sheet no. 8 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS-
17
150
Sheet no. 9 of 26 IN 1030 kg/m3 as per rev.4 PFD Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- Supernatant collection sump is a flat roof sump as
18 Sheet no. 10 of 26 IN Incorporated Noted and Closed
150 per P&ID rev.5. Vendor to check and update
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 1 / CODE-2
COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS-
19
150
Sheet no. 10 of 26 IN Sump Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- Sludge collection sump is a flat roof sump as per
20 Sheet no. 10 of 26 IN Incorporated as per P&ID Rev.05 Noted and Closed
150 P&ID rev.5. Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS-
21
150
Sheet no. 10 of 26 IN 1030 kg/m3 as per rev.4 PFD Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
22 Sheet no. 10 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS-
23
150
Sheet no. 11 of 26 IN Avoid spelling errors Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- PAC Dosing tank is a flat roof sump as per P&ID
24
150
Sheet no. 11 of 26 IN Tank type incorporated as per P&ID Rev.05 Noted and Closed
rev.5. Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
25 Sheet no. 11 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per poly aluminum chloride dosing pump MDS
26
150
Sheet no. 11 of 26 IN Vendor shall provide fluid properties Noted and Closed
. (Self comment)
KG98-2-ONT-OMF-IN-7861-DS-
27
150
Sheet no. 12 of 26 IN T-N79516 tank description write properly Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
28 Sheet no. 12 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per polymer (PE) dosing pump MDS . (Self
29 Sheet no. 12 of 26 IN Vendor shall provide fluid properties Noted and Closed
150 comment)
KG98-2-ONT-OMF-IN-7861-DS-
30
150
Sheet no. 13 of 26 IN For N79-LZT-372 write description properly Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
31 Sheet no. 13 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per polymer (PE) dosing pump MDS . (Self
32 Sheet no. 13 of 26 IN Vendor shall provide fluid properties Noted and Closed
150 comment)
KG98-2-ONT-OMF-IN-7861-DS- For T-N79517 service should be Dewatering
33 Sheet no. 14 of 26 IN Incorporated Noted and Closed
150 polymer
KG98-2-ONT-OMF-IN-7861-DS- Dewatering polymer Dosing tank is a flat roof sump
34 Sheet no. 14 of 26 IN Checked & Incorporated Noted and Closed
150 as per P&ID rev.5. Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
35 Sheet no. 14 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per dewatering polymer dosing pump MDS .
36 Sheet no. 14 of 26 IN Vendor to provide and confirm fluid properties Noted and Closed
150 (Self comment)
KG98-2-ONT-OMF-IN-7861-DS- T-N79518 equipment description shall include UF
37 Sheet no. 15 of 26 IN Incorporated Noted and Closed
150 CEB HYPO
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
38 Sheet no. 15 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 1 / CODE-2
COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS- T-N79519 eqipment description shall include UF CEB
39 Sheet no. 16 of 26 IN Incorporated Noted and Closed
150 HYDROXIDE
KG98-2-ONT-OMF-IN-7861-DS- UF CEB Hydroxide dosing tank is a flat top and
40 Sheet no. 16 of 26 IN Incorporated Noted and Closed
150 bottom (Sloped) tank. Kindly check and update
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
41 Sheet no. 16 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
49 Sheet no. 18 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS- N79-LZT-385 description shall be FLOCCULATION
59 Sheet no. 23 of 26 IN Incorporated Noted and Closed
150 TANK (T-N79503)
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
60 Sheet no. 23 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS-
61
150
Sheet no. 24 of 26 IN Zone 1, Group IIA/B, Temp Class T3 Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS-
62
150
Sheet no. 25 of 26 IN unit shall in mm. Kindly check and update Checked & incoporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
63 Sheet no. 25 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
For N79-LZT-371 & N79-LT-388 specific gravity shall be 0.8 instead of 1 &
KG98-2-ONT-OMF-IN-7861-DS-
64
150
Sheet no. 12 of 26 IN - density shall be 800 kg/m3 instead of 1000 kg/m3 as per POLYMER Noted and Closed
dosing pump MDS . (Self comment)
For N79-LZT-372 & N79-LT-389 specific gravity shall be 0.8 instead of 1 &
KG98-2-ONT-OMF-IN-7861-DS-
65
150
Sheet no. 13 of 26 IN - density shall be 800 kg/m3 instead of 1000 kg/m3 as per POLYMER dosing Noted and Closed
pump MDS . (Self comment)
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20
REVISION RECORD SHEET
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20
NOTES SHEET
1) Documentation required :- Calibration Certificate,Material Certificates, weather proof
Pressure test procedure/Report, NDT Procedure/ report, Operating & Maintenance Instructions & Spare Parts List.
2) All equipment shall remain unaffected by radio transmissions (Levels of permissible RFI shall be as per IEC 60801). Band-pass
and / or band stop filers shall be fitted, as necessary. All instruments shall be immune to EM interference.
3) All electronic transmitters shall be 24 V DC loop-powered ‘Smart type’ with 4 –20 mA output signal with In-built HART Protocol.
Electronic Transmitters shall have integral LCD display.
4) Transmitter shall be certified by bodies such as EC/FM/UL/BASEEFA/CENELEC/CSA/PTB/ATEX/CIMFR for use in Class 1,
Zone 1, Group II A/B, T3 hazardous area.
5) Tag plate of SS 316 with following details shall be provided - Manufacturer’s Name, model No. & Serial No. , Calibration Span Range
Body & Element material, Certification
6) The Radar type Tank Level system shall satisfy requirements of API MPMS Chapter 3, Section 1 B.
7) The Antenna unit shall be designed as per API standard. MOC shall be SS316L with protective sealing.
8) Use of asbestos or asbestos-bearing materials shall be avoided.
HOLD:
1) Level range and Nozzle Height in Tentative and shall be confirmed later.
2) C-C length will be confirm afetr finalizing the vessel GA drawing.
3) Tank & Nozzle height will be confirm after finalizing the GA
4) Tank size to be confirmed later
5) Calibration / Transmitter range will be confirm after finalizing the tank GA.
6) SIL Rating shall be confirmed after SIL study report, However SIL 2 is considered.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER SHEET 5-23 DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20
INDEX SHEET
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 AJ 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20
INDEX SHEET
2 EQUALIZATION TANK T-N79501 EQUALIZATION TANK T-N79501 COOLING TOWER FEED TANK T-N79505
Equipment:
3 Service : PRODUCED WATER PRODUCED WATER PRODUCED WATER
GENERAL
CIRCULAR WITH FIXED CONICAL ROOF CIRCULAR WITH FIXED CONICAL ROOF CIRCULAR WITH FIXED CONICAL ROOF
7
Tank Type (CLOSED) (CLOSED) (CLOSED)
12 Suspended Solids NA NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM
16 Upper
Density Kg/ mᶟ 962 962 962
17 Lower
18 Upper Fluid Viscosity cP
0.50 0.50 0.50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA
33 Probe Type Rigid Single Lead (13mm) Rigid Single Lead (13mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA NA
38 Still Well NA NA NA
39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#
42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC 24 V DC
± 0.12 in. (3 mm) or 0.03% of measured ± 0.12 in. (3 mm) or 0.03% of measured ± 0.12 in. (3 mm) or 0.03% of measured
51 Accuracy
distance, whichever is greatest distance, whichever is greatest distance, whichever is greatest
5301HS1S1V4BM00410CAI1M1C1Q4Q8Q
53 5301HS1S1V4BM00410CAI1M1C1Q4Q8QT 5301HS1S1V4AM00260CAI1M1C1Q4Q8QT
Model No: T
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
SUPPLY OF ETP PACKAGE FOR ONSHORE
TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 06 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH PRIVATE
TATA PROJECTS LIMITED AND SERVICES
LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
11 Interface NA NA NA
12 Suspended Solids NA NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM
kg/cm2g
14 Temperature (Design / Operating) (˚C) 85 / 57.2 85 / 35 85 / 35
16 Upper
Density Kg/ mᶟ 962 994 994
17 Lower
18 Upper Fluid Viscosity cP
0.50 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA NA
38 Still Well NA NA NA
39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#
42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC
52 Manufacturer
5301HS1S1V4AM00251CAI1M1C1Q4Q8 5301HS1S1V4AM00251CAI1M1C1Q
53 5301HS1S1V4AM00260CAI1M1C1Q4Q8QT
Model No: QT 4Q8QT
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
2 UF CIP TANK T-N79508 UF CIP TANK T-N79508 UF FILTRATE WATER TANK T-N79509
Equipment:
3 CIP CHEMICAL CIP CHEMICAL UF PERMEATE WATER
Service :
GENERAL
11 Interface NA NA NA
12 Suspended Solids NA NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM
kg/cm2g
14 Temperature (Design / Operating) (˚C) 85 / 35 85 / 35 85 / 35
16 Upper
Density Kg/ mᶟ 1050 1050 0.994
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA
33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal) Rigid Single Lead (8 mm)
37 Isolation Material NA NA NA
38 Still Well NA NA NA
39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#
42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC
5408F1SHS1I11R4AACAA4M5C1Q4Q8Q 5301HS1S1V4AM00213CAI1M1C1Q4Q8
53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
T QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
11 Interface NA NA NA
12 Suspended Solids NA NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM
16 Upper
Density Kg/ mᶟ 0.994 994 994
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA NA
38 Still Well NA NA NA
39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#
42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC
5301HS1S1V4AM00213CAI1M1C1Q4Q8 5301HS1S1V4AM00213CAI1M1C1Q4Q
53 5301HS1S1V4AM00213CAI1M1C1Q4Q8QT
QT 8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
SUPPLY OF ETP PACKAGE FOR ONSHORE
TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 09 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
12 Suspended Solids NA NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM FULL OF WATER /ATM
16 Upper
Density Kg/ mᶟ 994 994 1030
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA NA
38 Still Well NA NA NA
39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#
42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD
TRANSMITTER
48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC
50 Cable Connection 1/2" NPT (F) 1/2" NPT (F) 1/2" NPT (F)
52 Manufacturer
S
5301HS1S1V4BM00310CAI1M1C1Q4Q
53 5301HS1S1V4AM00115CAI1M1C1Q4Q8QT 5301HS1S1V4AM00115CAI1M1C1Q4Q8QT
Model No: 8QT
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
CLOSED TANK WITH FLAT ROOF & BOTTOM CLOSED TANK WITH FLAT TOP & BOTTOM CLOSED TANK WITH FLAT TOP &
7
WITH SLOP WITH SLOP BOTTOM WITH SLOP
Tank Type
8 Nozzle Height mm 150 mm 150 mm 150 mm
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM ATM ATM
16 Upper
Density Kg/ mᶟ 1030 985 985
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA NA
38 Still Well NA NA NA
39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#
42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD
48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC
5301HS1S1V4AM00161CAI1M1C1Q4Q
53 5301HS1S1V4BM00310CAI1M1C1Q4Q8QT 5301HS1S1V4AM00161CAI1M1C1Q4Q8QT
8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
4
P&ID: SHEET: 20 OF 32 SHEET: 20 OF 32
5 Vessel Spec. FRP FRP
CIRCULAR WITH FIXED CONICAL ROOF & FLAT BOTTOM CIRCULAR WITH FIXED CONICAL ROOF & FLAT BOTTOM TANK
7
TANK (CLOSED) (CLOSED)
Tank Type
8 Nozzle Height mm 150 mm 150 mm
11 Interface NA NA
12 Suspended Solids NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
16 Upper
Density Kg/ mᶟ 1200 1200
17 Lower
18 Upper Fluid Viscosity cP
30 30
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Flexible Single Lead with weight Flexible Single Lead with weight
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
SIL-2 SIL-2
TRANSMITTER
45 SIL Rating
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
2 POLYMER CHEMICAL PRE TANK PE T-N79516 POLYMER CHEMICAL PRE TANK PE T-N79516
Equipment:
GENERAL
11 Interface NA NA
12 Suspended Solids NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM
16 Upper
Density Kg/ mᶟ 800 800
17 Lower
18 Upper Fluid Viscosity cP
100-150 100-150
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)
35 Probe length NA NA
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
51 Accuracy ±2 mm ±2 mm
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
16 Upper
Density Kg/ mᶟ 800 800
17 Lower
18 Upper Fluid Viscosity cP
100-150 100-150
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance, whichever is
51 Accuracy
whichever is greatest greatest
KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 22 OF 32 SHEET: 22 OF 32
5 Vessel Spec. SS 316L SS-316L
CLOSED TANK WITH FIXED CONICAL ROOF & BOTTOM CLOSED TANK WITH FIXED CONICAL ROOF & BOTTOM WITH
7
WITH SLOP SLOP
Tank Type
8 Nozzle Height mm 150 mm 150 mm
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM
16 Upper
Density Kg/ mᶟ 1022 to 1050 1022 to 1050
17 Lower
18 Upper Fluid Viscosity cP
300 300
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)
35 Probe length NA NA
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
51 Accuracy ±2 mm ±2 mm
53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
2 UF CEB HYPO (NaOCL) DOSING TANK T-N79518 UF CEB HYPO (NaOCL) DOSING TANK T-N79518
Equipment:
GENERAL
11 Interface NA NA
12 Suspended Solids NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
16 Upper
Density Kg/ mᶟ 1150 1150
17 Lower
18 Upper Fluid Viscosity cP
1.7-2.0 1.7-2.0
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance, whichever is
51 Accuracy
whichever is greatest greatest
2 UF CEB HYDROXIDE (NaOH) DOSING TANK T-N79519 UF CEB HYDROXIDE (NaOH) DOSING TANK T-N79519
Equipment:
3 Service : SODIUM HYDROXIDE (NaOH) SODIUM HYDROXIDE (NaOH)
GENERAL
KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 24 OF 32 SHEET: 24 OF 32
5 Vessel Spec. SS 316L SS-316L
7 CLOSED TANK WITH FLAT TOP & BOTTOM (SLOPED) CLOSED TANK WITH FLAT TOP & BOTTOM (SLOPED)
Tank Type
8 Nozzle Height mm 150 mm 150 mm
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
16 Upper
Density Kg/ mᶟ 1480 TO 1500 1480 TO 1500
17 Lower
18 Upper Fluid Viscosity cP
54.4 to 78 54.4 to 78
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance,
51 Accuracy
whichever is greatest whichever is greatest
2 UF CEB ACID (HCL-30%) DOSING TANK UF CEB ACID (HCL-30%) DOSING TANK
Equipment:
GENERAL
11 Interface NA NA
12 Suspended Solids NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
16 Upper
Density Kg/ mᶟ 1150 1150
17 Lower
18 Upper Fluid Viscosity cP
1.87 1.87
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Rigid Single Lead (13mm) Rigid Single Lead (13mm)
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance,
51 Accuracy
whichever is greatest whichever is greatest
POWDER ACTIVATED CARBON (PACT - 10%) CHEMICAL POWDER ACTIVATED CARBON (PACT - 10%) CHEMICAL
2
PREPARATION TANK T-N79521 PREPARATION TANK T-N79521
Equipment:
GENERAL
6 4000 mm 3 4000 mm
Tank Height
7 Tank Type CONICAL FIXED ROOF & FLAT BOTTOM (CLOSED) CONICAL FIXED ROOF & FLAT BOTTOM (CLOSED)
8 Nozzle Height mm 150 mm 150 mm
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
15 Specific gravity 1 1
16 Upper
Density Kg/ mᶟ 1000 1000
17 Lower
18 Upper Fluid Viscosity cP
1.1 - 1.2 1.1 - 1.2
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)
35 Probe length NA NA
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
51 Accuracy ±2 mm ±2 mm
53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
POWDER ACTIVATED (PACT) CARBON DOSING TANK T- POWDER ACTIVATED (PACT) CARBON DOSING TANK T-
2
N79522 N79522
Equipment:
GENERAL
11 Interface NA NA
12 Suspended Solids NA NA
PROCESS CONDITIONS
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
15 Specific gravity 1 1
16 Upper
Density Kg/ mᶟ 1000 1000
17 Lower
18 Upper Fluid Viscosity cP
1.1 - 1.2 1.1 - 1.2
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
1 N79-LZT-398 N79-LT-397
Tag No. :
3 Service :
KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 32 OF 32 SHEET: 32 OF 32
5 SS-316L SS-316L
Vessel Spec.
6 1500 mm 1500 mm
Tank Height
7 Tank Type CIRCULAR FLAT TOP & BOTTOM TANK (CLOSED) CIRCULAR FLAT TOP & BOTTOM TANK (CLOSED)
8 150 mm 150 mm
Nozzle Height mm
9 Upper Fluid / Phase
LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
12 Suspended Solids NA NA
PROCESS CONDITIONS
16 Upper
Density Kg/ mᶟ 1530 1530
17 Lower
18 Upper Fluid Viscosity cP
47 - 50 3 47 - 50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)
35 Probe length NA NA
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
51 Accuracy ±2 mm ±2 mm
Emerson(Rosemount) Emerson(Rosemount)
OTHERS
52 Manufacturer
53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM
16 Upper
Density Kg/ mᶟ 1530 1530
17 Lower
18 Upper Fluid Viscosity cP
47 - 50 45 - 50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance,
51 Accuracy
whichever is greatest whichever is greatest
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM
16 Upper
Density Kg/ mᶟ 962 962
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)
35 Probe length NA NA
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
51 Accuracy ±2 mm ±2 mm
Emerson(Rosemount) Emerson(Rosemount)
OTHERS
52 Manufacturer
53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM
16 Upper
Density Kg/ mᶟ 962 962
17 Lower
18 Upper Fluid Viscosity cP
0.50 0.50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA
33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)
35 Probe length NA NA
37 Isolation Material NA NA
38 Still Well NA NA
40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#
43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol
47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66
48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
49 Power Supply 24 V DC 24 V DC
51 Accuracy ±2 mm ±2 mm
SUPPLY OF ETP PACKAGE FOR ONSHORE TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 24 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 03-Dec-20 AJ 03-Dec-20 MSR/RR 03-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 03-Dec-20
2 3
UNITS:- Pressure kg/cm g Flow: Gas: MMSCFD Sm3/hr m /hr kg/hr
0 3
Temp C Liquid: m /hr kg/hr Usgpm
CONTRO- 17 Df PI PID Ds
15 RATING OVER RANGE: 130% PF UPPER RANGE VALUE BODY RATING TO SUIT DESIGN COND.
ELEMENT
16 DIFF. RANGE FIXED ADJ. RANGE REF SHT 25 SET AT SHT 25
17 ELEVATION SUPPRESSION
18 PROCESS DATA FLUID REF SHT 25 DESIGN. TEMP. REF SHT 25 DESIGN. PR. REF SHT 25
22 INTEGRATOR
28 DIAPHRAGM SEAL NA
34
37 MANUFACTURER Emerson(Rosemount)
38 MODEL No. 2051CD3A22A1JS1I1M5D4DFQ4Q8+1199WDAB3AFFWG1DA00
OTHER
39 VALVE MANIFOLD MANUFACTURER NA
40 MODEL No. NA
41 NOTES:- * - TO BE CONFIRMED BY VENDOR
42 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
Level Transmitter-Datasheet REFER BELOW KG98/2-ONT-OMF-IN-7861-DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
SUPPLY OF ETP PACKAGE FOR ONSHORE TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 25 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
SEQUENTIAL BATCH
2051CD3A22A1JS1I1M5D4D KG98-2-ONT-OMF-PR-7861-
FULL OF REACTOR (SBR) TANK T-
1 N79-LT-379 FQ4Q8+1199WDAB3AFFWG -25492 to 25492 0 - 6000 ATM 35 85 2" #150 RF PID-017 SIL-2 2
WATER N79506A/PRODUCED
1DA00 SHEET: 7 OF 32
WATER
SEQUENTIAL BATCH
2051CD3A22A1JS1I1M5D4D KG98-2-ONT-OMF-PR-7861-
FULL OF REACTOR (SBR) TANK T-
2 N79-LT-380 FQ4Q8+1199WDAB3AFFWG -25492 to 25492 0 - 6000 ATM 35 85 2" #150 RF PID-017 SIL-2 2
WATER N79506B / PRODUCED
1DA00 SHEET: 7 OF 32
WATER
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34 NOTES:- * - TO BE CONFIRMED BY VENDOR
35 REFER NOTES SHEET
36
37
38