VENDOR DOC.NO : DOC.TITLE :


SCT-G65-150
CLIENT DOC.NO : Level Transmitter-Datasheet
KG98-2-ONT-OMF-IN-7861-DS-150

Kayalvizhi
Digitally signed by Kayalvizhi
Date: 2021.12.16 11:42:30
+05'30'

3 11-Dec-21 REISSUED FOR REVIEW DOE RR UP


2 13-Nov-21 REISSUED FOR REVIEW DOE PL RR
1 18-Oct-21 REISSUED FOR REVIEW DOE PL RR
0 02-Dec-20 ISSUED FOR REVIEW DOE AJ SR
REV. DATE DESCRIPTION BY CHECKED APPROVED
CLIENT : ONGC M.R. NO : KG98/2-ONT-ME-OMF-MIS-00012

P.S. NO : KG98/2-ONT-ME-GEN-PS2-00011
P.O.NO. :7861

EPC Contractor: Design Engineering Consultant : VENDOR NAME :


Tata Projects Limited Kavin Engineering And Services
Private Limited

CONFIDENTIAL AGREEMENT: This document and the information it contains are property of SPARKLE CLEAN TECH PRIVATE
LIMITED. It shall not be used for any purpose other than for which it was supplied. Not to disclose without Authorization
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 2 / CODE-1

COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline KAVIN Comments Vendor Response Status
Date : 02-12-2021 Date: 11-12-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS-
1
150
CRS Sr 47 of Rev-01 IN Vessel spec. shall be SS316L Incorporated Closed
KG98-2-ONT-OMF-IN-7861-DS-
2
150
CRS Sr 47 of Rev-01 IN Dimension " MM " Missing Incorporated Closed

Vendor to confirm fluid properties with reference to


KG98-2-ONT-OMF-IN-7861-DS-
3
150
Sheet no. 21 of 26 IN the properties provided for Pre-treatment Hydroxide Incorporated Closed
dosing pump MDS as per the snapshot below
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 1 / CODE-2

COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
Typical Comments :
1. Vendor to ensure that all level transmitter tags are
covered in the datasheet as per latest P & ID - Rev 05. 1. It is ensured that all level transmitter tags are covered in the datasheet as
2. Vendor to ensure that all Tank height & Tank per latest P & ID - Rev 05.
KG98-2-ONT-OMF-IN-7861-DS- Instrument Nozzle shall be as per Approved Tank GAD 2. It is ensured that all Tank height & Tank Instrument Nozzle shall be as per
1 sheet no. 5 of 26 IN Noted and Closed
150 & accordingly to consider the Calibration range. Approved Tank GAD & accordingly to consider the Calibration range.
3. Vendor to ensure that accuracy of instrument shall be 3. It is ensured that accuracy of instrument shall be as per OEM standard with
as per OEM standard with inline with tender inline with tender specifications
specifications

KG98-2-ONT-OMF-IN-7861-DS-
2 sheet no. 5 of 26 IN T-N79505 tank description to be write properly Incorporated Noted and Closed
150
KG98-2-ONT-OMF-IN-7861-DS-
3 sheet no. 5 of 26 IN T-N79505 MOC is CS-EP as per P&ID Rev.05 Incorporated Noted and Closed
150

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
4 sheet no. 5 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS-
5 Sheet no. 6 of 26 IN T-N79505 MOC is CS-EP as per P&ID Rev.05 Incorporated Noted and Closed
150

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
6 Sheet no. 6 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- T-N79509 tank description sall be UF FILTRATE


7 Sheet no. 7 of 26 IN Incorporated Noted and Closed
150 WATER TANK
KG98-2-ONT-OMF-IN-7861-DS-
8 Sheet no. 7 of 26 IN T-N79508 shall be CLOSED Incorporated Noted and Closed
150

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
9 Sheet no. 7 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS-
10 Sheet no. 7 of 26 IN Vendor to confirm the fluid properties Checked from PFD Rev.04 & incorporated Noted and Closed
150
KG98-2-ONT-OMF-IN-7861-DS-
11 Sheet no. 8 of 26 IN Vendor to confirm the fluid properties Checked from PFD Rev.04 & incorporated Noted and Closed
150

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
12 Sheet no. 8 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- Sludge collection sump is a flat roof sump as per


13 Sheet no. 9 of 26 IN Incorporated Noted and Closed
150 P&ID rev.5. Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS-
14
150
Sheet no. 9 of 26 IN T-N79511 description tank shall be properly written Incorporated Noted and Closed
Please check as per P&ID rev.5, UF Backwash waste
KG98-2-ONT-OMF-IN-7861-DS-
15
150
Sheet no. 9 of 26 IN & UF Reject tank is a closed tank with fixed conical Incorporated Noted and Closed
roof and flat bottom with slope
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
16 Sheet no. 9 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS-
17
150
Sheet no. 9 of 26 IN 1030 kg/m3 as per rev.4 PFD Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- Supernatant collection sump is a flat roof sump as
18 Sheet no. 10 of 26 IN Incorporated Noted and Closed
150 per P&ID rev.5. Vendor to check and update
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 1 / CODE-2

COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS-
19
150
Sheet no. 10 of 26 IN Sump Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- Sludge collection sump is a flat roof sump as per
20 Sheet no. 10 of 26 IN Incorporated as per P&ID Rev.05 Noted and Closed
150 P&ID rev.5. Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS-
21
150
Sheet no. 10 of 26 IN 1030 kg/m3 as per rev.4 PFD Incorporated Noted and Closed

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
22 Sheet no. 10 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS-
23
150
Sheet no. 11 of 26 IN Avoid spelling errors Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- PAC Dosing tank is a flat roof sump as per P&ID
24
150
Sheet no. 11 of 26 IN Tank type incorporated as per P&ID Rev.05 Noted and Closed
rev.5. Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
25 Sheet no. 11 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per poly aluminum chloride dosing pump MDS
26
150
Sheet no. 11 of 26 IN Vendor shall provide fluid properties Noted and Closed
. (Self comment)
KG98-2-ONT-OMF-IN-7861-DS-
27
150
Sheet no. 12 of 26 IN T-N79516 tank description write properly Incorporated Noted and Closed

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
28 Sheet no. 12 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per polymer (PE) dosing pump MDS . (Self
29 Sheet no. 12 of 26 IN Vendor shall provide fluid properties Noted and Closed
150 comment)
KG98-2-ONT-OMF-IN-7861-DS-
30
150
Sheet no. 13 of 26 IN For N79-LZT-372 write description properly Incorporated Noted and Closed

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
31 Sheet no. 13 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per polymer (PE) dosing pump MDS . (Self
32 Sheet no. 13 of 26 IN Vendor shall provide fluid properties Noted and Closed
150 comment)
KG98-2-ONT-OMF-IN-7861-DS- For T-N79517 service should be Dewatering
33 Sheet no. 14 of 26 IN Incorporated Noted and Closed
150 polymer
KG98-2-ONT-OMF-IN-7861-DS- Dewatering polymer Dosing tank is a flat roof sump
34 Sheet no. 14 of 26 IN Checked & Incorporated Noted and Closed
150 as per P&ID rev.5. Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
35 Sheet no. 14 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- Provides fluid properties as per dewatering polymer dosing pump MDS .
36 Sheet no. 14 of 26 IN Vendor to provide and confirm fluid properties Noted and Closed
150 (Self comment)
KG98-2-ONT-OMF-IN-7861-DS- T-N79518 equipment description shall include UF
37 Sheet no. 15 of 26 IN Incorporated Noted and Closed
150 CEB HYPO
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
38 Sheet no. 15 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 1 / CODE-2

COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS- T-N79519 eqipment description shall include UF CEB
39 Sheet no. 16 of 26 IN Incorporated Noted and Closed
150 HYDROXIDE
KG98-2-ONT-OMF-IN-7861-DS- UF CEB Hydroxide dosing tank is a flat top and
40 Sheet no. 16 of 26 IN Incorporated Noted and Closed
150 bottom (Sloped) tank. Kindly check and update
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
41 Sheet no. 16 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

Vendor to confirm fluid properties with reference to


KG98-2-ONT-OMF-IN-7861-DS-
42
150
Sheet no. 16 of 26 IN the properties provided for UF CEB Hydroxide dosing Checked & incoporated Noted and Closed
pump MDS as per the snapshot below
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
43 Sheet no. 17 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- 1.87 as per MDS for UF CEB acid dosing pump.


44
150
Sheet no. 17 of 26 IN Checked & incoporated Noted and Closed
Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS-
45
150
Sheet no. 18 of 26 IN For N79-LT-394 write description properly Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- Conical fixed roof and flat bottom as per rev. 5 P&ID.
46
150
Sheet no. 18 of 26 IN Checked & incoporated Noted and Closed
Vendor to check and update
KG98-2-ONT-OMF-IN-7861-DS-
47
150
Sheet no. 18 of 26 IN Vessel spec. shall be SS316L Incorporated Open
KG98-2-ONT-OMF-IN-7861-DS-
48
150
Sheet no. 18 of 26 IN lenth shuold be in mm Incorporated Noted and Closed

KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
49 Sheet no. 18 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

KG98-2-ONT-OMF-IN-7861-DS- T-N79522 name shall be POWDER ACTIVATED


50 Sheet no. 19 of 26 IN Incorporated Noted and Closed
150 (PACT) CARBON DOSING TANK
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
51 Sheet no. 19 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
52 Sheet no. 20 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
Vendor to confirm fluid properties with reference to
KG98-2-ONT-OMF-IN-7861-DS-
53
150
Sheet no. 20 of 26 IN the properties provided for Pre-treatment Hydroxide Checked & incoporated Noted and Closed
dosing pump MDS as per the snapshot below
KG98-2-ONT-OMF-IN-7861-DS-
54
150
Sheet no. 21 of 26 IN T-N79528 service shall be HYDROXIDE (NaOH) Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
55 Sheet no. 21 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
Vendor to confirm fluid properties with reference to
KG98-2-ONT-OMF-IN-7861-DS-
56
150
Sheet no. 21 of 26 IN the properties provided for Pre-treatment Hydroxide Checked & incoporated Open
dosing pump MDS as per the snapshot below
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
57 Sheet no. 22 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS- 0.72 as per flash Mixer Tank MDS. Vendor to check
58
150
Sheet no. 22 of 26 IN Checked & incoporated Noted and Closed
and confirm
Document Title: Level Transmitter Datasheet
Onshore Terminal for KG DWN 98/2 Development Project
Document No.:KG98-2-ONT-OMF-IN-7861-DS-150
Rev. No.: 1 / CODE-2

COMMENT RESOLUTION SHEET Vendor Name: Sparkle Clean Tech Pvt. Ltd.
Equip.Tag No./ Name: A-N79070 / Supply of ETP Package for Onshore
Terminal KG DWN 98/2 Development Project
S.No. Ref Doc No./ Title Ref. Clause Discipline TPL Comments Vendor Response Status
Date : 29-10-2021 Date: 13-11-2021 Closed/ Open
KG98-2-ONT-OMF-IN-7861-DS- N79-LZT-385 description shall be FLOCCULATION
59 Sheet no. 23 of 26 IN Incorporated Noted and Closed
150 TANK (T-N79503)
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
60 Sheet no. 23 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.
KG98-2-ONT-OMF-IN-7861-DS-
61
150
Sheet no. 24 of 26 IN Zone 1, Group IIA/B, Temp Class T3 Incorporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS-
62
150
Sheet no. 25 of 26 IN unit shall in mm. Kindly check and update Checked & incoporated Noted and Closed
KG98-2-ONT-OMF-IN-7861-DS- As Per P&ID Rev.05 design pressure shall be Full of water & same topic
63 Sheet no. 25 of 26 IN Design Pressure shall be 3.5 kg/cm2g Noted and Closed
150 discussed on 02 november 2021 in teams meeting.

For N79-LZT-371 & N79-LT-388 specific gravity shall be 0.8 instead of 1 &
KG98-2-ONT-OMF-IN-7861-DS-
64
150
Sheet no. 12 of 26 IN - density shall be 800 kg/m3 instead of 1000 kg/m3 as per POLYMER Noted and Closed
dosing pump MDS . (Self comment)

For N79-LZT-372 & N79-LT-389 specific gravity shall be 0.8 instead of 1 &
KG98-2-ONT-OMF-IN-7861-DS-
65
150
Sheet no. 13 of 26 IN - density shall be 800 kg/m3 instead of 1000 kg/m3 as per POLYMER dosing Noted and Closed
pump MDS . (Self comment)

For N79-LZT-373 & N79-LT-390 specific gravity shall be 1.022 to 1.05


KG98-2-ONT-OMF-IN-7861-DS-
66
150
Sheet no. 14 of 26 IN - instead of 1 & density shall be 1022 to 1050 kg/m3 instead of 1000 kg/m3 Noted and Closed
as per DEWATERING POLYMER dosing pump MDS . (Self comment)
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER SHEET 5-23 DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 2 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
TATA PROJECTS KAVIN ENGINEERING AND SPARKLE CLEAN TECH
7861 -
LIMITED SERVICES PRIVATE LIMITED PRIVATE LIMITED.

CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20
REVISION RECORD SHEET

REV. NO. PURPOSE LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY

0 ISSUED FOR REVIEW FIRST ISSUE

1 REISSUED FOR REVIEW SECOND ISSUE

2 REISSUED FOR REVIEW THIRD ISSUE

3 REISSUED FOR REVIEW FOURTH ISSUE


DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER SHEET 5-23 DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 3 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
TATA PROJECTS KAVIN ENGINEERING AND SPARKLE CLEAN TECH
7861 -
LIMITED SERVICES PRIVATE LIMITED PRIVATE LIMITED.

CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

NOTES SHEET
1) Documentation required :- Calibration Certificate,Material Certificates, weather proof
Pressure test procedure/Report, NDT Procedure/ report, Operating & Maintenance Instructions & Spare Parts List.
2) All equipment shall remain unaffected by radio transmissions (Levels of permissible RFI shall be as per IEC 60801). Band-pass
and / or band stop filers shall be fitted, as necessary. All instruments shall be immune to EM interference.
3) All electronic transmitters shall be 24 V DC loop-powered ‘Smart type’ with 4 –20 mA output signal with In-built HART Protocol.
Electronic Transmitters shall have integral LCD display.
4) Transmitter shall be certified by bodies such as EC/FM/UL/BASEEFA/CENELEC/CSA/PTB/ATEX/CIMFR for use in Class 1,
Zone 1, Group II A/B, T3 hazardous area.
5) Tag plate of SS 316 with following details shall be provided - Manufacturer’s Name, model No. & Serial No. , Calibration Span Range
Body & Element material, Certification
6) The Radar type Tank Level system shall satisfy requirements of API MPMS Chapter 3, Section 1 B.
7) The Antenna unit shall be designed as per API standard. MOC shall be SS316L with protective sealing.
8) Use of asbestos or asbestos-bearing materials shall be avoided.

HOLD:
1) Level range and Nozzle Height in Tentative and shall be confirmed later.
2) C-C length will be confirm afetr finalizing the vessel GA drawing.
3) Tank & Nozzle height will be confirm after finalizing the GA
4) Tank size to be confirmed later
5) Calibration / Transmitter range will be confirm after finalizing the tank GA.
6) SIL Rating shall be confirmed after SIL study report, However SIL 2 is considered.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER SHEET 5-23 DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 4 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
TATA PROJECTS KAVIN ENGINEERING AND SPARKLE CLEAN TECH
7861 -
LIMITED SERVICES PRIVATE LIMITED PRIVATE LIMITED.

CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

INDEX SHEET

SHEET NO. TITLE REV 0 REV 1 REV 2


1 COVER SHEET 02-Dec-20 18-Oct-21 13-Nov-21
2 INDEX SHEET 02-Dec-20 18-Oct-21 13-Nov-21
3 REVISION RECORD SHEET 02-Dec-20 18-Oct-21 13-Nov-21
4 NOTES SHEET 02-Dec-20 18-Oct-21 13-Nov-21
5 to 23 LEVEL TRANSMITTER. 02-Dec-20 18-Oct-21 13-Nov-21
24 & 25 LEVEL TRANSMITTER. 02-Dec-20 18-Oct-21 13-Nov-21
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER SHEET 5-23 DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 4 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
TATA PROJECTS KAVIN ENGINEERING AND SPARKLE CLEAN TECH
7861 -
LIMITED SERVICES PRIVATE LIMITED PRIVATE LIMITED.

CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 AJ 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

INDEX SHEET

SHEET NO. TITLE REV 0 REV 1


1 COVER SHEET 02-Dec-20 18-Oct-21
2 INDEX SHEET 02-Dec-20 18-Oct-21
3 REVISION RECORD SHEET 02-Dec-20 18-Oct-21
4 NOTES SHEET 02-Dec-20 18-Oct-21
5 to 23 LEVEL TRANSMITTER. 02-Dec-20 18-Oct-21
24 & 25 LEVEL TRANSMITTER. 03-Dec-20 18-Oct-21
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 05 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LT-351 N79-LZT-352 N79-LT-353

2 EQUALIZATION TANK T-N79501 EQUALIZATION TANK T-N79501 COOLING TOWER FEED TANK T-N79505
Equipment:
3 Service : PRODUCED WATER PRODUCED WATER PRODUCED WATER
GENERAL

KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017


4
SHEET: 03 OF 32 SHEET: 03 OF 32 SHEET: 06 OF 32
P&ID:
5 Vessel Spec. CS-EP CS-EP CS-EP

6 Tank Height (mm) 4000 4000 2500 mm

CIRCULAR WITH FIXED CONICAL ROOF CIRCULAR WITH FIXED CONICAL ROOF CIRCULAR WITH FIXED CONICAL ROOF
7
Tank Type (CLOSED) (CLOSED) (CLOSED)

8 Nozzle Height mm 150 mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA NA

12 Suspended Solids NA NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM

14 Temperature (Design / Operating) (˚C) 85 / 57.2 85 / 57.2 85 / 57.2

15 Specific gravity 0.962 0.962 0.962

16 Upper
Density Kg/ mᶟ 962 962 962
17 Lower
18 Upper Fluid Viscosity cP
0.50 0.50 0.50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA NA

32 Principle GWR GWR GWR

33 Probe Type Rigid Single Lead (13mm) Rigid Single Lead (13mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L SS316L


SENSOR

35 Probe length 4100 mm 4100 mm 2600 mm

36 Calibration Range (mm) 0 - 4000 0 - 4000 0 - 2500

37 Isolation Material NA NA NA

38 Still Well NA NA NA

39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 4000 mm 0 - 4000 mm 0 - 2500 mm

45 SIL Rating SIL-2 SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC 24 V DC

50 Cable Connection 1/2" NPT (F) 1/2" NPT (F) 1/2"NPT(F)

± 0.12 in. (3 mm) or 0.03% of measured ± 0.12 in. (3 mm) or 0.03% of measured ± 0.12 in. (3 mm) or 0.03% of measured
51 Accuracy
distance, whichever is greatest distance, whichever is greatest distance, whichever is greatest

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount) Emerson(Rosemount)


OTHERS

5301HS1S1V4BM00410CAI1M1C1Q4Q8Q
53 5301HS1S1V4BM00410CAI1M1C1Q4Q8QT 5301HS1S1V4AM00260CAI1M1C1Q4Q8QT
Model No: T

54 NOTES:- * - TO BE CONFIRMED BY VENDOR


55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.

KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
SUPPLY OF ETP PACKAGE FOR ONSHORE
TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 06 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH PRIVATE
TATA PROJECTS LIMITED AND SERVICES
LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 N79-LZT-354 N79-LT-355 N79-LZT-356


Tag No. :

CLARIFIED WATER/UF FEED TANK T- CLARIFIED WATER/UF FEED TANK T-


2 COOLING WATER FEED TANK T-N79505
N79507 N79507
Equipment:
3 PRODUCED WATER PRODUCED WATER PRODUCED WATER
Service :
GENERAL

KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017


4
SHEET: 06 OF 32 SHEET: 10 OF 32 SHEET: 10 OF 32
P&ID:
5 CS-EP CS-EP CS-EP
Vessel Spec.
6 2500 mm 2210 mm 2210 mm
Tank Height
7 Tank Type CIRCULAR WITH FIXED CONICAL ROOF CIRCULAR WITH FIXED CONICAL ROOF CIRCULAR WITH FIXED CONICAL
8 150 mm 150 mm 150 mm
Nozzle Height mm
9 Upper Fluid / Phase
LIQUID LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA NA

12 Suspended Solids NA NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM
kg/cm2g
14 Temperature (Design / Operating) (˚C) 85 / 57.2 85 / 35 85 / 35

15 Specific gravity 0.962 0.994 0.994

16 Upper
Density Kg/ mᶟ 962 994 994
17 Lower
18 Upper Fluid Viscosity cP
0.50 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA NA

32 Principle GWR GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L SS316L


SENSOR

35 Probe length 2600 mm 2510 mm 2510 mm

36 Calibration Range (mm) 0 - 2500 0 - 2210 0 - 2210

37 Isolation Material NA NA NA

38 Still Well NA NA NA

39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 2500 mm 0 - 2210 mm 0 - 2210 mm


45 SIL Rating SIL-2 SIL-2 SIL-2
TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2"NPT(F) 1/2"NPT(F)

± 0.12 in. (3 mm) or 0.03% of ± 0.12 in. (3 mm) or 0.03% of


± 0.12 in. (3 mm) or 0.03% of measured
51 Accuracy measured distance, whichever is measured distance, whichever is
distance, whichever is greatest
greatest greatest

Emerson(Rosemount) Emerson(Rosemount) Emerson(Rosemount)


OTHERS

52 Manufacturer
5301HS1S1V4AM00251CAI1M1C1Q4Q8 5301HS1S1V4AM00251CAI1M1C1Q
53 5301HS1S1V4AM00260CAI1M1C1Q4Q8QT
Model No: QT 4Q8QT
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.

KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 07 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 N79-LZT-357 N79-LT-358 N79-LT-359


Tag No. :

2 UF CIP TANK T-N79508 UF CIP TANK T-N79508 UF FILTRATE WATER TANK T-N79509
Equipment:
3 CIP CHEMICAL CIP CHEMICAL UF PERMEATE WATER
Service :
GENERAL

KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017


4
SHEET: 13 OF 32 SHEET: 13 OF 32 SHEET: 15 OF 32
P&ID:
5 FRP FRP CS-EP
Vessel Spec.
6 1500 mm 1500 mm 2000 mm
Tank Height
CIRCULAR FLAT TOP & BOTTOM CIRCULAR WITH FIXED CONICAL ROOF
7 CIRCULAR FLAT TOP & BOTTOM (CLOSED)
Tank Type (CLOSED) (CLOSED)

8 150 mm 150 mm 150 mm


Nozzle Height mm
9 Upper Fluid / Phase
LIQUID LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA NA

12 Suspended Solids NA NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM
kg/cm2g
14 Temperature (Design / Operating) (˚C) 85 / 35 85 / 35 85 / 35

15 Specific gravity 1.050 1.050 0.994

16 Upper
Density Kg/ mᶟ 1050 1050 0.994
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA NA

32 Principle NON-CONTACT GWR NON-CONTACT GWR GWR

33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L SS316L


SENSOR

35 Probe length NA NA 2130 mm

36 Calibration Range (mm) 0 - 1500 0 - 1500 0 - 2000

37 Isolation Material NA NA NA

38 Still Well NA NA NA

39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1500 mm 0 - 1500 mm 0 - 2000 mm

45 SIL Rating SIL-2 SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC

50 Cable Connection 1/2" NPT(F) 1/2" NPT(F) 1/2" NPT (F)


± 0.12 in. (3 mm) or 0.03% of
51 Accuracy ±2 mm ±2 mm measured distance, whichever is
greatest
52 Manufacturer Emerson(Rosemount) Emerson(Rosemount) Emerson(Rosemount)
OTHERS

5408F1SHS1I11R4AACAA4M5C1Q4Q8Q 5301HS1S1V4AM00213CAI1M1C1Q4Q8
53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
T QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.

KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 08 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-360 N79-LT-361 N79-LZT-362

2 UF FILTRATE TANK T-N79509 OFFSPEC TANK T-N79510 OFFSPEC TANK T-N79510


Equipment:
GENERAL

3 Service : UF PERMEATE WATER PRODUCED WATER PRODUCED WATER


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 15 OF 32 SHEET: 16 OF 32 SHEET: 16 OF 32
5 Vessel Spec. CS-EP CS-EP CS-EP

6 Tank Height 2000 mm 2000 mm 2000 mm


7 Tank Type CIRCULAR WITH FIXED CONICAL ROOF (CLOSED) CIRCULAR WITH FIXED CONICAL ROOF CIRCULAR WITH FIXED CONICAL ROOF
8 Nozzle Height mm 150 mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA NA

12 Suspended Solids NA NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM FULL OF WATER / ATM

14 Temperature (Design / Operating) (˚C) 85 / 35 85 / 35 85 / 35

15 Specific gravity 0.994 0.994 0.994

16 Upper
Density Kg/ mᶟ 0.994 994 994
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA NA

32 Principle GWR GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L SS-316L


SENSOR

35 Probe length 2130 mm 2130 mm 2130 mm

36 Calibration Range (mm) 0 - 2000 0 - 2000 0 - 2000

37 Isolation Material NA NA NA

38 Still Well NA NA NA

39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 2000 mm 0 - 2000 mm 0 - 2000 mm

45 SIL Rating SIL-2 SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC

50 Cable Connection 1/2" NPT (F) 1/2"NPT(F) 1/2"NPT(F)


± 0.12 in. (3 mm) or 0.03% of ± 0.12 in. (3 mm) or 0.03% of
± 0.12 in. (3 mm) or 0.03% of measured
51 Accuracy measured distance, whichever is measured distance, whichever is
distance, whichever is greatest
greatest greatest
52 Manufacturer Emerson(Rosemount) Emerson(Rosemount) Emerson(Rosemount)
OTHERS

5301HS1S1V4AM00213CAI1M1C1Q4Q8 5301HS1S1V4AM00213CAI1M1C1Q4Q
53 5301HS1S1V4AM00213CAI1M1C1Q4Q8QT
QT 8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV
SUPPLY OF ETP PACKAGE FOR ONSHORE
TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 09 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LT-363 N79-LZT-364 N79-LT-365

UF INTER. BACKWASH WASTE COLLECTION UF INTER. BACKWASH WASTE COLLECTION


2 SLUDGE COLLECTION SUMP T-N79511
TANK T-N79526 TANK T-N79526
Equipment:
3 Service : UF BACKWASH WASTE & UF REJECT UF BACKWASH WASTE & UF REJECT SLUDGE FROM CPI, DNF & SBR
GENERAL

KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017


4
SHEET: 17 OF 32 SHEET: 17 OF 32 SHEET: 18 OF 32
P&ID:
5 Vessel Spec. CS-EP CS-EP CS-EP

6 Tank Height 1000 mm 1000 mm 3000 mm


CLOSED TANK WITH FIXED CONICAL ROOF CLOSED TANK WITH FIXED CONICAL ROOF CLOSED TANK WITH FLAT ROOF &
7
Tank Type & FLAT BOTTOM WITH SLOP & FLAT BOTTOM WITH SLOP BOTTOM WITH SLOP
8 Nozzle Height mm 150 mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA NA

12 Suspended Solids NA NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 85 / 35 85 / 35 85 / 35

15 Specific gravity 0.994 0.994 1.030

16 Upper
Density Kg/ mᶟ 994 994 1030
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA NA

32 Principle GWR GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L SS316L


SENSOR

35 Probe length 1150 1150 3100 mm

36 Calibration Range mm 0 - 1000 0 - 1000 0 - 3000

37 Isolation Material NA NA NA

38 Still Well NA NA NA

39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316 ASTM A105

42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1000 mm 0 - 1000 mm 0 - 3000 mm

45 SIL Rating SIL-2 SIL-2 SIL-2

46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD
TRANSMITTER

47 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66


Enclosure Material / Enclosure Protection

48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC

50 Cable Connection 1/2" NPT (F) 1/2" NPT (F) 1/2" NPT (F)

± 0.12 in. (3 mm) or 0.03% of


± 0.12 in. (3 mm) or 0.03% of measured ± 0.12 in. (3 mm) or 0.03% of measured
51 Accuracy measured distance, whichever is
distance, whichever is greatest distance, whichever is greatest
greatest
Emerson(Rosemount) Emerson(Rosemount) Emerson(Rosemount)
OTHER

52 Manufacturer
S

5301HS1S1V4BM00310CAI1M1C1Q4Q
53 5301HS1S1V4AM00115CAI1M1C1Q4Q8QT 5301HS1S1V4AM00115CAI1M1C1Q4Q8QT
Model No: 8QT
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 10 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-366 N79-LT-367 N79-LZT-368

SUPERNATANT COLLECTION TANK SUPER NATANT COLLECTION TANK


2 SLUDGE COLLECTION SUMP T-N79511
T-N79512 T-N79512
Equipment:
3 Service : SLUDGE FROM CPI, DNF & SBR SUPERNATANT WATER SUPERNATANT WATER
GENERAL

KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017


4
P&ID: SHEET: 18 OF 32 SHEET: 19 OF 32 SHEET: 19 OF 32
5 Vessel Spec. CS-EP CS-EP CS-EP

6 Tank Height 3000 mm 1500 1500

CLOSED TANK WITH FLAT ROOF & BOTTOM CLOSED TANK WITH FLAT TOP & BOTTOM CLOSED TANK WITH FLAT TOP &
7
WITH SLOP WITH SLOP BOTTOM WITH SLOP
Tank Type
8 Nozzle Height mm 150 mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA NA
NA NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM ATM ATM

14 Temperature (Design / Operating) (˚C) 85 / 35 85 / 35 85 / 35

15 Specific gravity 1.030 0.985 0.985

16 Upper
Density Kg/ mᶟ 1030 985 985
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA NA

32 Principle GWR GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L SS316L


SENSOR

35 Probe length 3100 mm 1610 mm 1610 mm

36 Calibration Range (mm) 0 - 3000 0 - 1500 0 - 1500

37 Isolation Material NA NA NA

38 Still Well NA NA NA

39 Mounting position Tank Top mounted Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material ASTM A105 SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 3000 mm 0 - 1500 mm 0 - 1500 mm

45 SIL Rating SIL-2 SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD YES - Integral LCD

47 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66


Enclosure Material / Enclosure Protection

48 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3
Area Classification
49 Power Supply 24 V DC 24 V DC 24 V DC

50 Cable Connection 1/2" NPT (F) 1/2"NPT(F) 1/2"NPT(F)

± 0.12 in. (3 mm) or 0.03% of


± 0.12 in. (3 mm) or 0.03% of measured ± 0.12 in. (3 mm) or 0.03% of measured
51 Accuracy measured distance, whichever is
distance, whichever is greatest distance, whichever is greatest
greatest

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount) Emerson(Rosemount)


OTHERS

5301HS1S1V4AM00161CAI1M1C1Q4Q
53 5301HS1S1V4BM00310CAI1M1C1Q4Q8QT 5301HS1S1V4AM00161CAI1M1C1Q4Q8QT
8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 11 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-370 N79-LT-387

2 PAC DOSING TANKT-N79514 PAC DOSING TANKT-N79514


Equipment:
3 Service : POLY ALUMINUM CHLORIDE (PAC) POLY ALUMINUM CHLORIDE (PAC)
KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
GENERAL

4
P&ID: SHEET: 20 OF 32 SHEET: 20 OF 32
5 Vessel Spec. FRP FRP

6 Tank Height 8000 8000

CIRCULAR WITH FIXED CONICAL ROOF & FLAT BOTTOM CIRCULAR WITH FIXED CONICAL ROOF & FLAT BOTTOM TANK
7
TANK (CLOSED) (CLOSED)
Tank Type
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA

12 Suspended Solids NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1.2 - 1.37 1.2 - 1.37

16 Upper
Density Kg/ mᶟ 1200 1200
17 Lower
18 Upper Fluid Viscosity cP
30 30
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle GWR GWR

33 Probe Type Flexible Single Lead with weight Flexible Single Lead with weight

34 Probe Material SS316L SS316L


SENSOR

35 Probe length 8150 mm 8150 mm

36 Calibration Range (mm) 0-8000 0-8000

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0-8000 mm 0-8000 mm

SIL-2 SIL-2
TRANSMITTER

45 SIL Rating

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2" NPT(F) 1/2"NPT(F)


± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance, whichever is
51 Accuracy
whichever is greatest greatest
52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)
OTHE
RS

53 Model No: 5301HS1S1V5AM00815CAI1M1C1Q4Q8QT 5301HS1S1V5AM00815CAI1M1C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.

KG98-2-ONT-OMF-IN-7861-DS-150
Level Transmitter-Datasheet REFER BELOW
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 12 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH PRIVATE
TATA PROJECTS LIMITED AND SERVICES
LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-371 N79-LT-388

2 POLYMER CHEMICAL PRE TANK PE T-N79516 POLYMER CHEMICAL PRE TANK PE T-N79516
Equipment:
GENERAL

3 Service : POLYMER (PE) POLYMER (PE)


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 21 OF 32 SHEET: 21 OF 32
5 Vessel Spec. SS-316L SS-316L

6 Tank Height 4000 mm 4000 mm


7 Tank Type CONICAL FIXED ROOF (CLOSED) CONICAL FIXED ROOF (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA

12 Suspended Solids NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 0.8 0.8

16 Upper
Density Kg/ mᶟ 800 800
17 Lower
18 Upper Fluid Viscosity cP
100-150 100-150
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle NON-CONTACT GWR NON-CONTACT GWR

33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)

34 Probe Material SS316L SS316L


SENSOR

35 Probe length NA NA

36 Calibration Range (mm) 0 - 4000 0 - 4000

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 4000 mm 0 - 4000 mm


TRANSMITTER

45 SIL Rating SIL-2 SIL-2

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2"NPT(F)

51 Accuracy ±2 mm ±2 mm

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHE
RS

53 Model No: 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 13 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LT-389 N79-LZT-372

2 POLYMER DOSING TANK T-N79515 POLYMER DOSING TANK T-N79515


Equipment:
GENERAL

3 Service : POLYMER (PE) POLYMER (PE)


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 21 OF 32 SHEET: 21 OF 32
5 Vessel Spec. SS-316L SS 316L

6 Tank Height 1250 mm 1250 mm


7 Tank Type CIRCULAR FLAT TOP & BOTTOM (CLOSED) CONICAL FIXED ROOF & FLAT BOTTOM
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 0.8 0.8

16 Upper
Density Kg/ mᶟ 800 800
17 Lower
18 Upper Fluid Viscosity cP
100-150 100-150
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L


SENSOR

35 Probe length 1390 mm 1390 mm

36 Calibration Range mm 0 - 1250 0 - 1250

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1250 mm 0 - 1250 mm

45 SIL Rating SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2" NPT(F)

± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance, whichever is
51 Accuracy
whichever is greatest greatest

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHE
RS

53 Model No: 5301HS1S1V4AM00139CAI1M1C1Q4Q8QT 5301HS1S1V4AM00139CAI1M1C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 14 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-373 N79-LT-390

DEWATERING POLYMER DOSING TANK DEWATERING POLYMER DOSING TANK


2
T-N79517 T-N79517
Equipment:
DEWATERING POLYMER
3 Service : DEWATERING POLYMER
GENERAL

KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 22 OF 32 SHEET: 22 OF 32
5 Vessel Spec. SS 316L SS-316L

6 Tank Height 4000 mm 4000 mm

CLOSED TANK WITH FIXED CONICAL ROOF & BOTTOM CLOSED TANK WITH FIXED CONICAL ROOF & BOTTOM WITH
7
WITH SLOP SLOP
Tank Type
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1.022 - 1.05 1.022 - 1.05

16 Upper
Density Kg/ mᶟ 1022 to 1050 1022 to 1050
17 Lower
18 Upper Fluid Viscosity cP
300 300
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle NON-CONTACT GWR NON-CONTACT GWR

33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)

34 Probe Material SS316L SS316L


SENSOR

35 Probe length NA NA

36 Calibration Range (mm) 0 - 4000 0- 4000

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0- 4000 mm 0- 4000 mm


TRANSMITTER

45 SIL Rating SIL-2 SIL-2

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2" NPT(F) 1/2"NPT(F)

51 Accuracy ±2 mm ±2 mm

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHERS

53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 15 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-374 N79-LT-391

2 UF CEB HYPO (NaOCL) DOSING TANK T-N79518 UF CEB HYPO (NaOCL) DOSING TANK T-N79518
Equipment:
GENERAL

3 Service : SODIUM HYPOCHLORITE (NaOCL) SODIUM HYPOCHLORITE (NaOCL)


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 23 OF 32 SHEET: 23 OF 32
5 Vessel Spec. FRP FRP

6 Tank Height 1500 mm 1500 mm


7 Tank Type FLAT TOP & BOTTOM (CLOSED) FLAT TOP & BOTTOM (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA

12 Suspended Solids NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1.150 1.150

16 Upper
Density Kg/ mᶟ 1150 1150
17 Lower
18 Upper Fluid Viscosity cP
1.7-2.0 1.7-2.0
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS316L


SENSOR

35 Probe length 1700 mm 1700 mm

36 Calibration Range (mm) 0 - 1500 0 -1500

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1500 mm 0 - 1500 mm

45 SIL Rating SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2" NPT(F) 1/2"NPT(F)

± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance, whichever is
51 Accuracy
whichever is greatest greatest

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHE
RS

53 Model No: 5301HS1S1V4AM00170CAI1M1C1Q4Q8QT 5301HS1S1V4AM00170CAI1M1C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 16 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-375 N79-LT-392

2 UF CEB HYDROXIDE (NaOH) DOSING TANK T-N79519 UF CEB HYDROXIDE (NaOH) DOSING TANK T-N79519
Equipment:
3 Service : SODIUM HYDROXIDE (NaOH) SODIUM HYDROXIDE (NaOH)
GENERAL

KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 24 OF 32 SHEET: 24 OF 32
5 Vessel Spec. SS 316L SS-316L

6 Tank Height 1500 mm 1500 mm

7 CLOSED TANK WITH FLAT TOP & BOTTOM (SLOPED) CLOSED TANK WITH FLAT TOP & BOTTOM (SLOPED)
Tank Type
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1.48 TO 1.50 1.48 TO 1.50

16 Upper
Density Kg/ mᶟ 1480 TO 1500 1480 TO 1500
17 Lower
18 Upper Fluid Viscosity cP
54.4 to 78 54.4 to 78
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS316L SS-316L


SENSOR

35 Probe length 1610 mm 1610 mm

36 Calibration Range mm 0 - 1500 0 - 1500

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1500 mm 0 - 1500 mm

45 SIL Rating SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2" NPT(F) 1/2"NPT(F)

± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance,
51 Accuracy
whichever is greatest whichever is greatest

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHE
RS

53 Model No: 5301HS1S1V4AM00161CAI1M1C1Q4Q8QT 5301HS1S1V4AM00161CAI1M1C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 17 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-376 N79-LT-393

2 UF CEB ACID (HCL-30%) DOSING TANK UF CEB ACID (HCL-30%) DOSING TANK
Equipment:
GENERAL

3 Service : HYDROCHLORIC ACID (HCL) HYDROCHLORIC ACID (HCL)


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 25 OF 32 SHEET: 25 OF 32
5 Vessel Spec. FRP FRP

6 Tank Height 4000 4000


7 Tank Type CIRCULAR FLAT TOP & BOTTOM (CLOSED) CIRCULAR FLAT TOP & BOTTOM (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA

12 Suspended Solids NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1.16-1.5 1.16-1.5

16 Upper
Density Kg/ mᶟ 1150 1150
17 Lower
18 Upper Fluid Viscosity cP
1.87 1.87
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle GWR GWR

33 Probe Type Rigid Single Lead (13mm) Rigid Single Lead (13mm)

34 Probe Material SS316L SS-316L


SENSOR

35 Probe length 4150 mm 4150 mm

36 Calibration Range mm 0 - 4000 0 - 4000

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 4000 mm 0 - 4000 mm

45 SIL Rating SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2" NPT(F) 1/2"NPT(F)

± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance,
51 Accuracy
whichever is greatest whichever is greatest

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHE
RS

53 Model No: 5301HS1S1V4BM00415CAI1M1C1Q4Q8QT 5301HS1S1V4BM00415CAI1M1C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 18 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-377 N79-LT-394

POWDER ACTIVATED CARBON (PACT - 10%) CHEMICAL POWDER ACTIVATED CARBON (PACT - 10%) CHEMICAL
2
PREPARATION TANK T-N79521 PREPARATION TANK T-N79521
Equipment:
GENERAL

3 Service : POWDER ACTIVATED CARBON (PACT ) POWDER ACTIVATED CARBON (PACT )


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 26 OF 32 SHEET: 26 OF 32
5 Vessel Spec. SS 316L 3 SS-316L

6 4000 mm 3 4000 mm
Tank Height
7 Tank Type CONICAL FIXED ROOF & FLAT BOTTOM (CLOSED) CONICAL FIXED ROOF & FLAT BOTTOM (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1 1

16 Upper
Density Kg/ mᶟ 1000 1000
17 Lower
18 Upper Fluid Viscosity cP
1.1 - 1.2 1.1 - 1.2
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle NON-CONTACT GWR NON-CONTACT GWR

33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)

34 Probe Material SS316L SS-316L


SENSOR

35 Probe length NA NA

36 Calibration Range (mm) 0-4000 0 - 4000

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0- 4000 mm 0- 4000 mm


TRANSMITTER

45 SIL Rating SIL-2 SIL-2

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2" NPT(F) 1/2"NPT(F)

51 Accuracy ±2 mm ±2 mm

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHER
S

53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 19 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LT-378 N79-LZT-395

POWDER ACTIVATED (PACT) CARBON DOSING TANK T- POWDER ACTIVATED (PACT) CARBON DOSING TANK T-
2
N79522 N79522
Equipment:
GENERAL

3 Service : POWDER ACTIVATED CARBON POWDER ACTIVATED CARBON


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 26 OF 32 SHEET: 26 OF 32
5 Vessel Spec. SS-316L SS-316L

6 Tank Height 1500 mm 1500 mm


7 Tank Type CONICAL FIXED ROOF & FLAT BOTTOM (CLOSED) CONICAL FIXED ROOF & FLAT BOTTOM (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA

12 Suspended Solids NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1 1

16 Upper
Density Kg/ mᶟ 1000 1000
17 Lower
18 Upper Fluid Viscosity cP
1.1 - 1.2 1.1 - 1.2
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS-316L SS-316L


SENSOR

35 Probe length 1640 mm 1640 mm

36 Calibration Range mm 0 - 1500 0- 1500

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1500 mm 0 - 1500 mm

45 SIL Rating SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2"NPT(F)


± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance,
51 Accuracy
whichever is greatest whichever is greatest
52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)
OTHE
RS

53 Model No: 5301HS1S1V4AM00164CAI1M1C1Q4Q8QT 5301HS1S1V4AM00164CAI1M1C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-DS-
Level Transmitter-Datasheet REFER BELOW 150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 20 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH PRIVATE
TATA PROJECTS LIMITED AND SERVICES
LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 N79-LZT-398 N79-LT-397
Tag No. :

2 PRE-TREATMENT(NaOH) PREP TANK T-N79527 PRE-TREATMENT(NaOH) CHEMICAL PREP TANK T-N79527


Equipment:
HYDROXIDE(NAOH) HYDROXIDE(NAOH)
GENERAL

3 Service :
KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 32 OF 32 SHEET: 32 OF 32
5 SS-316L SS-316L
Vessel Spec.
6 1500 mm 1500 mm
Tank Height
7 Tank Type CIRCULAR FLAT TOP & BOTTOM TANK (CLOSED) CIRCULAR FLAT TOP & BOTTOM TANK (CLOSED)
8 150 mm 150 mm
Nozzle Height mm
9 Upper Fluid / Phase
LIQUID LIQUID
10 Lower Fluid / Phase

11 Interface NA NA

12 Suspended Solids NA NA
PROCESS CONDITIONS

13 Pressure (Design / Operating) FULL OF WATER /ATM FULL OF WATER /ATM


kg/cm2g
14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1.53 1.53

16 Upper
Density Kg/ mᶟ 1530 1530
17 Lower
18 Upper Fluid Viscosity cP
47 - 50 3 47 - 50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle NON-CONTACT GWR NON-CONTACT GWR

33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)

34 Probe Material SS-316L SS-316L


SENSOR

35 Probe length NA NA

36 Calibration Range (mm) 0 - 1500 0 -1500

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 -1500 mm 0 -1500 mm


TRANSMITTER

45 SIL Rating SIL-2 SIL-2

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2"NPT(F)

51 Accuracy ±2 mm ±2 mm
Emerson(Rosemount) Emerson(Rosemount)
OTHERS

52 Manufacturer

53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 21 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LZT-399 N79-LT-396

2 PRE-TREATMENT(NaOH) DOSING TANK T-N79528 PRE-TREATMENT(NaOH) DOSING TANK T-N79528


Equipment:
GENERAL

3 Service : HYDROXIDE (NaOH) HYDROXIDE (NaOH)


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 32 OF 32 SHEET: 32 OF 32
5 Vessel Spec. SS-316L SS-316L

6 Tank Height 1250 mm 1250 mm


7 Tank Type CIRCULAR FLAT TOP & BOTTOM TANK (CLOSED) CIRCULAR FLAT TOP & BOTTOM TANK (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER /ATM FULL OF WATER /ATM

14 Temperature (Design / Operating) (˚C) 65 / 35 65 / 35

15 Specific gravity 1.53 1.53

16 Upper
Density Kg/ mᶟ 1530 1530
17 Lower
18 Upper Fluid Viscosity cP
47 - 50 45 - 50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle GWR GWR

33 Probe Type Rigid Single Lead (8 mm) Rigid Single Lead (8 mm)

34 Probe Material SS-316L SS-316L


SENSOR

35 Probe length 1360 mm 1360 mm

36 Calibration Range mm 0 - 1250 0 - 1250

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1250 0 - 1250

45 SIL Rating SIL-2 SIL-2


TRANSMITTER

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2"NPT(F)

± 0.12 in. (3 mm) or 0.03% of measured distance, ± 0.12 in. (3 mm) or 0.03% of measured distance,
51 Accuracy
whichever is greatest whichever is greatest

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHE
RS

53 Model No: 5301HS1S1V4AM00136CAI1M1C1Q4Q8QT 5301HS1S1V4AM00136CAI1M1C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 22 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LT-382 N79-LZT-383

2 FLASH MIXER TANK T-N79502 FLASH MIXER TANK T-N79502


Equipment:
GENERAL

3 Service : PRODUCED WATER PRODUCED WATER


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 04 OF 32 SHEET: 04 OF 32
5 Vessel Spec. CS-EP CS-EP

6 Tank Height 1500 mm 1500 mm


7 Tank Type CIRCULAR WITH FIXED CONICAL ROOF (CLOSED) CIRCULAR WITH FIXED CONICAL ROOF (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM

14 Temperature (Design / Operating) (˚C) 85 / 57.2 85 / 57.2

15 Specific gravity 0.962 0.962

16 Upper
Density Kg/ mᶟ 962 962
17 Lower
18 Upper Fluid Viscosity cP
0.72 0.72
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle NON-CONTACT GWR NON-CONTACT GWR

33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)

34 Probe Material SS316L SS316L


SENSOR

35 Probe length NA NA

36 Calibration Range mm 0 - 1500 0 -1500

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 1500 mm 0 - 1500 mm


TRANSMITTER

45 SIL Rating SIL-2 SIL-2

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2"NPT(F)

51 Accuracy ±2 mm ±2 mm
Emerson(Rosemount) Emerson(Rosemount)
OTHERS

52 Manufacturer

53 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT
Model No:
54 NOTES:- * - TO BE CONFIRMED BY
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
KG98-2-ONT-OMF-IN-7861-
Level Transmitter-Datasheet REFER BELOW DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE


TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 23 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
SPARKLE CLEAN TECH
TATA PROJECTS LIMITED AND SERVICES
PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION

ONGC 0 DOE 02-Dec-20 AJ 02-Dec-20 SR 02-Dec-20 ISSUED FOR REVIEW


CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 12-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 02-Dec-20

UNITS:- FLOW : LEVEL- mm Temperature-°C PRESS.: kg/cm2g

1 Tag No. : N79-LT-384 N79-LZT-385

2 FLOCCULATION TANK T-N79503 FLOCCULATION TANK T-N79503


Equipment:
GENERAL

3 Service : PRODUCED WATER PRODUCED WATER


KG98-2-ONT-OMF-PR-7861-PID-017 KG98-2-ONT-OMF-PR-7861-PID-017
4
P&ID: SHEET: 04 OF 32 SHEET: 04 OF 32
5 Vessel Spec. CS-EP CS-EP

6 Tank Height 2500 mm 2500 mm


7 Tank Type CIRCULAR WITH FIXED CONICAL ROOF (CLOSED) CIRCULAR WITH FIXED CONICAL ROOF (CLOSED)
8 Nozzle Height mm 150 mm 150 mm

9 Upper Fluid / Phase


LIQUID LIQUID
10 Lower Fluid / Phase
11 Interface NA NA
NA NA
PROCESS CONDITIONS

12 Suspended Solids
13 Pressure (Design / Operating) kg/cm2g FULL OF WATER / ATM FULL OF WATER / ATM

14 Temperature (Design / Operating) (˚C) 85 / 57.2 85 / 57.2

15 Specific gravity 0.962 0.962

16 Upper
Density Kg/ mᶟ 962 962
17 Lower
18 Upper Fluid Viscosity cP
0.50 0.50
19 Lower Fluid Viscosity cP
20 Dielectric Constant upper/lower NA NA

21 Thermal Conductivity Liquid (Upper / lower) NA NA

32 Principle NON-CONTACT GWR NON-CONTACT GWR

33 Probe Type Cone Antenna (PTFE seal) Cone Antenna (PTFE seal)

34 Probe Material SS316L SS316L


SENSOR

35 Probe length NA NA

36 Calibration Range (mm) 0 - 2500 0 - 2500

37 Isolation Material NA NA

38 Still Well NA NA

39 Mounting position Tank Top mounted Tank Top mounted

40 Connection - Size (mm) & Rating 4" ANSI Flanged 150# 4" ANSI Flanged 150#

41 Flange Material SS316 SS316

42 Mounting Vertical - Top mounted Vertical - Top mounted

43 Output Signal 4 –20 mA with HART Protocol 4 –20 mA with HART Protocol

44 Transmitter Range/Span 0 - 2500 mm 0 - 2500 mm


TRANSMITTER

45 SIL Rating SIL-2 SIL-2

46 Indicator YES - Integral LCD YES - Integral LCD

47 Enclosure Material / Enclosure Protection 316 SS /Ex'i', IP-66 316 SS /Ex'i', IP-66

48 Area Classification Zone 1, Group IIA/B, Temp Class T3 Zone 1, Group IIA/B, Temp Class T3

49 Power Supply 24 V DC 24 V DC

50 Cable Connection 1/2"NPT(F) 1/2"NPT(F)

51 Accuracy ±2 mm ±2 mm

52 Manufacturer Emerson(Rosemount) Emerson(Rosemount)


OTHE
RS

53 Model No: 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT 5408F1SHS1I11R4AACAA4M5C1Q4Q8QT


54 NOTES:- * - TO BE CONFIRMED BY VENDOR
55 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
Level Transmitter-Datasheet REFER SHEET 25 KG98/2-ONT-OMF-IN-7861-DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 24 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME
KAVIN ENGINEERING
TATA PROJECTS LIMITED AND SERVICES SPARKLE CLEAN TECH PRIVATE LIMITED.
PRIVATE LIMITED 7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 03-Dec-20 AJ 03-Dec-20 MSR/RR 03-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 03-Dec-20
2 3
UNITS:- Pressure kg/cm g Flow: Gas: MMSCFD Sm3/hr m /hr kg/hr
0 3
Temp C Liquid: m /hr kg/hr Usgpm

1 TAG No. SEE SHT.25 SERVICE SEE SHT.25

2 FUNCTION RECORD INDICATE CONTROL BLIND TRANS

3 HAZARDOUS AREA Zone 1, Group IIA/B, Temp Class T3

4 CASE 316 SS NOM SIZE COLOUR MFR STD


GENERAL
5 MOUNTING FLUSH SURFACE YOKE OTHER

6 ENCLOSURE CLASS GENERAL PURPOSE WEATHER PROOF TO IP 66 OTHER

7 TYPE OF PROTECTION INTRINSICALLY SAFE Ex 'i' EXPLOSION PROOF

8 POWER SUPPLY 120V 60Hz OTHER AC DC 24VDC(Loop powered)

9 CHART STRIP ROLL FOLD CIRCULAR TIME MARKS

RECORDER 10 CHART DRIVE SPEED POWER

11 SCALE TYPE RANGE 1 2 3 4

9 TRANSMITTER OUTPUT(2 WIRE) 4-20 mA 10-50 mA 20-100 kPa FIELD BUS


XMTR 10 TYPE SMART OTHER FOUNDATION FIELD BUS TYPE HART PROTOCOL

11 ACCURACY ±0.075 percent of Span

15 CONTROL MODES P=PROP(GAIN); I=INTEGRAL(AUTO RESET); D=DERIVATIVE(RATE)

16 SUB: s=SLOW;f=FAST: If P PD Is OTHERS

CONTRO- 17 Df PI PID Ds

LLER 18 ACTION ON MEASUREMENT INCREASE OUTPUT: INCREASES DECREASES

19 AUTO MANUAL SWITCH NONE MFR STD OTHER

20 SET POINT ADJUSTMENT MANUAL EXTERNAL OTHER REMOTE

21 MANUAL REGULATOR NONE MFR STD OTHER

22 OUTPUT 4-20 mA 10-50 mA 20-100kPa OTHER

12 SERVICE FLOW LEVEL DIFF. PRESSURE OTHER

13 ELEMENT TYPE DIAPHRAGM BELLOWS MERCURY OTHER D/P CELL

14 MATERIAL BODY / ELEMENT SS 316 Ber. COPPER OTHER

15 RATING OVER RANGE: 130% PF UPPER RANGE VALUE BODY RATING TO SUIT DESIGN COND.
ELEMENT
16 DIFF. RANGE FIXED ADJ. RANGE REF SHT 25 SET AT SHT 25

17 ELEVATION SUPPRESSION

18 PROCESS DATA FLUID REF SHT 25 DESIGN. TEMP. REF SHT 25 DESIGN. PR. REF SHT 25

19 PROCESS CONN. 1/2 in NPTF 1/4 in NPTM FLANGED

20 ALARM SWITCHES QUANTITY FORM RATING

SWITCH 21 FUNCTION PRESSURE DEVIATION CONTACTS TO ON INC. MEAS.

20 OPTIONS 5-VALVE MANIFOLD MATERIAL - SS316

21 YOKE MOUNTING BRACKET ADJ. DAMP INTEGRAL SQ.RT.EXT.

22 INTEGRATOR

23 OTHER INTEGRAL DIGITAL INDICATOR Ex'i'

24 CABLE ENTRY 1/2" NPT

25 LIGHTNING PROTECTOR DUAL CHAMBER TYPE

26 YOKE MOUNTING BRACKET SS316 FOR 2"NB PIPE STAND


OPTIONS 27 MONO FLANGE VALVE

28 DIAPHRAGM SEAL NA

29 DIAPHRAGM SEAL FLANGED WITH CAPILLARY

30 MATERIAL DIAPHRAGM: SS 316 FLANGES: SS 316

31 PROCESS CONNECTION: SEE SHT. 25 SEAL FILL FLUID: D.C. 200

32 CAPILLARY LENGTH: 6 Meters CAPILLARY MATERIAL: SS 316

33 FLUSH CHAMBER (NOTE-10)

34

37 MANUFACTURER Emerson(Rosemount)
38 MODEL No. 2051CD3A22A1JS1I1M5D4DFQ4Q8+1199WDAB3AFFWG1DA00
OTHER
39 VALVE MANIFOLD MANUFACTURER NA
40 MODEL No. NA
41 NOTES:- * - TO BE CONFIRMED BY VENDOR
42 REFER NOTES SHEET.
DOCUMENT TITLE ITEM/TAG No. DOCUMENT NO.
Level Transmitter-Datasheet REFER BELOW KG98/2-ONT-OMF-IN-7861-DS-150
PROJECT DESCRIPTION VENDOR DOC.NO : SHEET REV

SUPPLY OF ETP PACKAGE FOR ONSHORE TERMINAL KG DWN 98/2 DEVELOPMENT PROJECT (A-N79070) SCT-G65-150 25 OF 25 3
EPC CONTRACTOR CONSULTANT PURCHASE ORDER No. REQUISITION No. VENDOR NAME

KAVIN ENGINEERING AND


TATA PROJECTS LIMITED SPARKLE CLEAN TECH PRIVATE LIMITED.
SERVICES PRIVATE LIMITED
7861 -
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
ONGC 0 DOE 03-Dec-20 AJ 03-Dec-20 SR 03-Dec-20 ISSUED FOR REVIEW
CONTRACTOR REF. 1 DOE 18-Oct-21 PL 18-Oct-21 RR 18-Oct-21 REISSUED FOR REVIEW
2 DOE 13-Nov-21 PL 13-Nov-21 RR 13-Nov-21 REISSUED FOR REVIEW
3 DOE 11-Dec-21 RR 11-Dec-21 UP 11-Dec-21 REISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE
DOE 03-Dec-20
OPER. DESIGN FLANGE
ADJUSTABLE RANGE SET RANGE SIL
S.No TAG NO. MODEL No. PRESS. TEMP. PRESS. TEMP SIZE & LOCATION / SERVICE P&ID NO REV
RATING
mm mm kg/cm2g O
C kg/cm2g O
C RATINGS

SEQUENTIAL BATCH
2051CD3A22A1JS1I1M5D4D KG98-2-ONT-OMF-PR-7861-
FULL OF REACTOR (SBR) TANK T-
1 N79-LT-379 FQ4Q8+1199WDAB3AFFWG -25492 to 25492 0 - 6000 ATM 35 85 2" #150 RF PID-017 SIL-2 2
WATER N79506A/PRODUCED
1DA00 SHEET: 7 OF 32
WATER

SEQUENTIAL BATCH
2051CD3A22A1JS1I1M5D4D KG98-2-ONT-OMF-PR-7861-
FULL OF REACTOR (SBR) TANK T-
2 N79-LT-380 FQ4Q8+1199WDAB3AFFWG -25492 to 25492 0 - 6000 ATM 35 85 2" #150 RF PID-017 SIL-2 2
WATER N79506B / PRODUCED
1DA00 SHEET: 7 OF 32
WATER

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32
33
34 NOTES:- * - TO BE CONFIRMED BY VENDOR
35 REFER NOTES SHEET
36
37
38
39