Earthing - Above Ground Riser Comparison
Earthing - Above Ground Riser Comparison
Earthing - Above Ground Riser Comparison
(Typical Configuration considered = 1 No. 33KV Incomer + 2 No. 33/11kV Transformer + 4 No. 11kV Outgoing Feeder)
EDRC Estimate (m) Site Estimate (m)
S. No. Equipment Unit Qty Sub-Total Remarks
Riser/unit Total Riser Riser/unit Total Riser
1 33kV outdoor VCB (3ph) Nos 3 7.39 22.17
Tower/Structure should be earthed at bottom
2 VCB - MB Nos 3 2.77 8.31 39.48 14.5 43.50 only. Running earth flat for full length of
3 VCB - Structure Nos 3 3 9.00 structure/tower not required.
15 ISO-MB Nos 1 1.5 1.50 14.86 19 19.00 Seaparate earthing not requird for structure since
the same is already covered in T/G