ABOVE GROUND RISER (50x6mm GI EARTH FLAT) ESTIMATION

(Typical Configuration considered = 1 No. 33KV Incomer + 2 No. 33/11kV Transformer + 4 No. 11kV Outgoing Feeder)
EDRC Estimate (m) Site Estimate (m)
S. No. Equipment Unit Qty Sub-Total Remarks
Riser/unit Total Riser Riser/unit Total Riser
1 33kV outdoor VCB (3ph) Nos 3 7.39 22.17
Tower/Structure should be earthed at bottom
2 VCB - MB Nos 3 2.77 8.31 39.48 14.5 43.50 only. Running earth flat for full length of
3 VCB - Structure Nos 3 3 9.00 structure/tower not required.

4 CT (3ph) Set 3 13.24 39.72


Since CT is mounted on common structure, each
of the earthing terminal (1&2) can be combined &
earthed through two separate risers.
5 CT console box Nos 1 1.5 1.50 50.22 33 99.00 Tower/Structure should be earthed at bottom
only. Running earth flat for full length of
structure/tower not required.
6 CT -Structure Set 3 3 9.00

7 33kV Isolator (3Ph) with Earth Switch Nos 1 8.244 8.24


(33kV Line side)
Tower/Structure should be earthed at bottom
8 ISO-MB Nos 1 1.5 1.50 14.24 19 19.00 only. Running earth flat for full length of
9 ES-MB Nos 1 1.5 1.50 structure/tower not required.
10 33kV ISO-structure Nos 1 3 3.00

11 33kV Isolator (3Ph) without Earth Switch Nos 3 8.244 24.73


(Pedestal Mounted)
Tower/Structure should be earthed at bottom
12 ISO-MB Nos 3 1.5 4.50 38.23 19 57.00 only. Running earth flat for full length of
structure/tower not required.

13 33kV ISO-structure Nos 3 3 9.00

14 33kV Isolator (3Ph) without Earth Switch Nos 1 13.36 13.36


(Beam mounted)

15 ISO-MB Nos 1 1.5 1.50 14.86 19 19.00 Seaparate earthing not requird for structure since
the same is already covered in T/G

16 33kV ISO-structure Nos 0 0 0.00

33kV LA (3 Ph.) LA should be earthed only at one point. Multiple


17 (Near Line takeoff & Transformer side) Set 3 12.175 36.53 36.53 * 50.00 earthing should be avoided
33kV LA (3 Ph.) LA should be earthed only at one point. Multiple
18 (Near Station Transformer side) Set 1 10.65 10.65 10.65 * 30.00 earthing should be avoided
19 PT (3 Ph.) Set 1 7.98 7.98
9.48 12 12.00 Structure earthing is covered in T1A
20 PT-JB Nos 1 1.5 1.50
21 33kV AB Switch Nos 1 4.4 4.40 Tower/Structure should be earthed at bottom
7.40 11 11.00 only. Running earth flat for full length of
22 33kV AB Switch- Structure Nos 1 3 3.00 structure/tower not required.
23 33kV HG Fuse Nos 1 4.4 4.40 Tower/Structure should be earthed at bottom
7.40 11 11.00 only. Running earth flat for full length of
24 33kV HG Fuse - Structure Nos 1 3 3.00 structure/tower not required.
25 POWER TRANSFORMERS Nos 2 15.00 30.00
33.00 28.00 56.00 2nos. For Tank; 2 no. for neutral
26 POWER TRANSFORMER- MB Nos 2 1.5 3.00
27 STATION TRANSFORMER Nos 1 11.9 11.90 11.90 8 8.00
11kV LA (3 ph.)
28 (Near Trafo 11kV side) Set 2 6.625 13.25 Tower/Structure should be earthed at bottom
19.25 10 20.00 only. Running earth flat for full length of
29 T3- 11kV Cable supporting Structure Nos 2 3 6.00 structure/tower not required.
(Near Trafo)
30 11kV LA (outgoing side) (3 Ph.) Set 4 11.58 46.32 LA should be earthed only at one point. Multiple
31 11kV Isolator (3 Ph.) Nos 4 15.6 62.40 120.72 55 220.00 earthing should be avoided. Tower/Structure
should be earthed at bottom only. Running earth
flat for full length of structure/tower not required.
32 11kV DP Structure Nos 4 3 12.00

Tower/Structure should be earthed at bottom


33 T1A/T2A Tower Nos 6 1.5 9.00 9.00 12 72.00 only. Running earth flat for full length of
structure/tower not required.
34 BMK Nos 1 2.8 2.80 2.80 2 2.00
35 Receptacle Panel Nos 1 2.1 2.10 2.10 3 3.00
36 LTDB panel for Station trafo Nos 1 5.4 5.40 5.40 8 8.00
37 33KV PANEL Set 1 3 3.00 3.00 6 6.00
38 11KV PANEL Set 1 3 3.00 3.00 18 18.00
39 ACDB, DCDB, ILDB,MLDB, RTU Set 1 15 15.00 15.00 15 15.00
40 Cable trench Set 1 185 185.00 185.00 215 215.00
Missing Item :
41 T1/T2 Tower Nos 5
Total 639 995
Quantity recommended 650 1000