Professional Documents
Culture Documents
RCS-985TS Instruction Manual Standard V1.02 (En YJBH2008.0086.0003)
RCS-985TS Instruction Manual Standard V1.02 (En YJBH2008.0086.0003)
RCS-985TS Instruction Manual Standard V1.02 (En YJBH2008.0086.0003)
Transformer Protection
Instruction Manual
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Before carrying out any work on the equipment the user should be familiar with the contents of this
manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER means that dearth, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means that dearth, severe personal or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high -voltage equipment must
be observed. Noncompliance may result in dearth, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, c heck that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
Version : RCS-985TS NANJING NARI-RELAYS ELECTRIC CO., LTD.
Manual: V1. 02 69 Suyuan Avenue, Jiangning, Nanjing 211102, China
P/N: EN_YJBH2008.0086.0003 Tel: 86-25-87178185, Fax: 86-25-87178208
Copyright © NR 200 9. All rights reserved Website: www.nari-relays.com
Email: international@nari-relays.com
We reserve all rights to this document and to the information
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.
Table of Content
Preface.............................................................................................................................................. i
Introduction .............................................................................................................................. i
3.11.1 Application........................................................................................................... 41
Chapter 1 Introduction
1.1 Application
Figure 1.1-1 to Figure 1.1-4 show typical applications of RCS-985TS. The relay is suited to be wall
surface mounted or flush mounted into a control panel.
Figure 1.1-2, Figure 1.1-3 and Figure 1.1-4 are typically applied for step-down transformer of
start-up/standby transformer of power plant.
l n ab cn
RCS-985TS
*
Main transformer
* *
l n ab c
Step-down transformer
l n ab cn
* RCS-985TS
*
*
ab c
l n a b c
a bc
a bc
1.2 Functions
1.3 Features
On the premise of 24 samples per cycle, all data measurement, calculation and logic
discrimination could be finished within one sampling period. The event recording and protection
logic calculation also can be finished simultaneously.
Duplicate CPUs hardware means the device is equipped with two CPU modules. One is called
CPU module and the other is called MON module. The two modules have independent low pass
filters, analog-digital converters, calculation and logic outputting respectively.
There are independent general fault detectors in MON module, which will connect power supply to
output relays when operate, besides protective fault detectors in the CPU module used for various
protective functions. The relay could drive a tripping output contact only when the fault detectors in
the CPU module and the fault detectors in the MON module operate simultaneously. This kind of
independent supervision of tripping outputs using fault detectors can avoid any maloperation
possibly caused by any hardware component fails.
Main and backup protection are integrated in one set of protection equipment. Protection
information such as sampled data and binary inputs is shared by all elements. The equipment can
record all relevant waveforms of any fault.
Elaborately designed tripping logic makes it possible of operation circuit to suit for various circuit
breakers.
The percent differential protection adopts variable slope restraint characteristics and actual
unbalanced differential current effect can be simulated. In order to prevent unwanted operation of
differential protection due to CT saturation, m easures to discriminate CT saturation are provided
for phase current at every side.
Amplitude correction and phase shift compensation of current from CT of each side have been
done for differential protection in program automatically by configuring corresponding settings.
Based on the operation sequence of DPFC restraint current element and DPFC differential current
element of differential protection, external with CT saturation or internal fault can be distinguished
correctly. In case of internal fault, the relay will operate immediately. While in case of external fault
with CT saturation, the criterion of current waveform is adopted then. The relay will not operate in
case of persisting external fault with CT saturation as soon as no less than 5ms and operate
There are logic settings provided to configure operating characteristic of voltage related protection
when VT circuit failure is distinguished.
After the fault detector pickup, the device can record all analog components, differential current
and time sequence protection elements operation. Latest 8 pieces of fault waveform can be
recorded with up to 15s each one. The format of event or fault report is compatible with
international COMTRADE file.
SOE capacity: 64 pieces of fault report, 256 pieces of binary input changes report,64 pieces of
alarm report of equipment self check or operation and 64 pieces of user operating report.
The HMI interface with a LCD and a 9-button keypad on the front panel is very friendly to the user.
Two rear RS-485 ports and two (or three) Ethernet ports with SAS or RTU. The Ethernet
interfaces are optional: electrical or optical.
Various GPS clock synchronizations: second/minute pulse via binary input, or RS-485 message
via communication ports and IRIG-B synchronization.
Two options are available for rated secondary current of CT inputs: 1A or 5A.
Four options are available for rated auxiliary voltage: 250V, 220V, 125V, 110V.
The Ethernet interfaces are optional: electrical or optical and three Ethernet or two Ethernet
are optional too.
Enclosure dimensions
213.1×266.0×203.0 (unit: mm)
(W×H×D)
Trepanning dimensions
225mm×268.0, M5 screw (1/2 6U)
(W×H)
Mounting Way Flush mounted
Weight per device Approx. 5kg
Small control module: 3 LED indicators, a 9-key keypad and a
Local control panel
160×80-dot LCD
Display language English
Housing material Aluminum
Housing color Silver grey
Communication
Parameters
medium
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or MODBUS
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or MODBUS
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
RS-485 (EIA) Port number 1
2.3.3 Telesignal
Resolution of telesignals ≤ 2 ms
Input of telesignals Potential-free contact
Resolution of SOE ≤ 1ms
2.4 Certification
ISO9001: 2000
ISO14001:2004
OHSAS18001: 1999
ISO10012:2003
CMMI L3
3.1 Overview
The equipment protection is composed of current differential protection as main protection, and
following protections as backup protection, such as voltage controlled overcurrent protection of
each side, zero sequence overcurrent protection of each side, gap earth fault protection and
overload protection. VT/CT failure supervision function is also included.
Protection theory is introduced from the following three parts in the chapter, general fault detector,
protective fault detector and protection element. The equipment has independent general fault
detectors in MON module, which pick up to connect positive pole of power supply of output relays.
Every protection has its own fault detector in CPU module picking up to make the program jump to
fault calculation from normal calculation. The equipment output relays will operate to trip only if the
general fault detector and protective fault detector pick up and the corresponding protective
element operates simultaneously.
Any one of the following fault detectors operation will make power supply of output relays be
switched on for 500 ms to make it ready to send a tripping signal.
This fault detector will pick up to when the differential current reaches pickup setting of transformer
differential protection.
Where:
I d is differential current.
Restricted earth fault protection is also called zero-sequence differential protection. There are
three restricted earth fault protection elements of side 1, side 2 and side 3 respectively are
The fault detector of each side will pick up if the zero-sequence differential current is greater than
the setting [I_Pkp_PcntREF_S1(S2,S3)].
Where:
I 0 cdqd is the pickup setting of percent zero-sequence differential protection of the corresponding
NOTE: In the manual, side 1, side 2 and side 3 mean HV side, MV side and LV side
respectively.
The fault detector of each side will pick up when the maximum three-phase current reaches its
setting of overcurrent protection of corresponding side. Here each side means side1, side2 and
side 3.
The fault detector of each side will pick up when following two criteria of corresponding side are
satisfied.
(1) Maximum three-phase current of one side reaches setting of this protection.
(2) Corresponding voltage control element picks up.
This fault detector of each side will pick up when zero sequence current reaches setting of
zero-sequence overcurrent protection of corresponding side.
The fault detector will pick up if the zero sequence current from air-gap CT is higher than its
setting.
The fault detector will pick up if the zero sequence voltage from broken-delta winding of VT is
higher than its setting.
Operation of each fault detector makes the program jump to fault calculation of the protection
element for 500 ms.
Each protective fault detector has same operation criterion as the corresponding general fault
detector has.
By applying the Ampere-turn balance on different transformer vector groups, the RCS-985TSC
relay forms the current differential equations.
During the normal operation, the magnitude and angle of secondary currents of each side of
transformer are different due to different CT ratios, different voltage levels and different
transformer vector groups. This kind of current difference shall be eliminated during normal
operation, which is realized by correction coefficient compensation and phase shift compensation
in program.
Sn
I b 1n (Equation 3.4-1)
3U b1n
Where:
U b1 n is the rated phase-to-phase voltage at the calculated side of the transformer (i.e. setting
I
I b 2 n b1 n (Equation 3.4-2)
nbLH
Where:
I b1n is the rated primary current at the calculated side of transformer.
nbLH is the ratio of CT at the calculated side of transformer.
When viewing settings and values of current differential protection in the relay, user will find the
unit “Ie”(transformer secondary rated current). The current in differential protection calculation is
not actual secondary value but per unit value which can be got by actual secondary value of each
side of transformer divided by transformer secondary current of each side.
I
K ph N (Equation 3.4-3)
I b2n
Where:
Ib 2 n is the rated secondary current at the calculated side.
IN is the rated secondary current of each side CT of transformer.
The currents used in the following analysis have been corrected, that means the currents for
following calculation are the products of the actual secondary current of each side multiplying its
By defining which particular connection group the protected transformer belongs to, the proper
calculation routine will be applied.
Polarity of each secondary winding of CT is as same as shown in Figure 1.1-1 ~ Figure 1.1-4.
The secondary current phase shift compensation for all CTs are achieved by software, Y→ Δ
transform method is used for this purpose. For connection Y/Δ-11, the correction equations are as
follows:
At Y side:
'
I A (I A I B ) / 3
'
Where:
I A , I B , I C are the secondary currents of CT at Y side.
I ' A , I ' B , I ' C are the corrected current of each phase at side Y.
For other connection type,the current can be calculated according to the equations listed above.
The connection type can be selected by logic settings [Cfg_ConnGrp] (refer to section 7.2 system
settings).
[Cfg_ConnGrp] for user to select different vector group of transformer, which almost
covers common connection groups. If user has especially requirement, please inform us
before place an order.
Following analysis is based on the assumption that amplitude and phase shift compensation have
been done.
The Low setting percent differential protection with low pickup setting and restraint slope is also
called sensitive percent differential protection and is much more sensitive to operate when a slight
internal fault occurs. Three blocking elements, CT saturation, inrush current and CT circuit failure
(optional) have also been included for the protection in order to prevent it from unwanted
operation during an external fault.
m
Ii
rI i1
2
m
I d Ii
i1
Where:
I cdqd is the pickup setting of steady state percent differential protection, which is also setting of
k bl 1 is the first slope of percent differential protection [Slope1_PcntDiff] with setting range 0.05 –
k bl 2 is the second slope of percent differential protection [Slope2_PcntDiff] with setting range
A percent differential protection with high slope and high setting is equipped with the equipment.
This protection, also called an insensitive differential protection, is blocked only by an inrush
current criterion and CT circuit failure (optional).
Insensitive percent differential protection can prevent influence of steady state and transient CT
saturations during an external fault, and can operate correctly and quickly during an internal fault
even with CT saturated. Operation criterion of this insensitive percent differential protection is
I d 1.2 I e
(Equation 3.4-6)
I d 1.0 I r
Where:
NOTE: Parameters of this protection have been fixed in program and do not need to be
configured by user.
The aim of unrestrained instantaneous differential protection for transformer is to accelerate the
trip speed for transformer’
s inner fault. Therefore the element does not need any blocking element,
but the setting should be greater than the maximum inrush current.
Unrestrained differential element shall operate to trip breakers at all sides of transformer when any
phase differential current is higher than its setting. Its operation criterion is:
Where:
I cdqd is the setting of the unrestrained instantaneous differential protection, i.e. [I_InstDiff].
Id
operation area of unrestrained
instantaneous differential protection
Icdsd
.0
differential protection
ot ta o w
=1
K
pr en f l
Kbl2
ec ge
al c o
on
ti er ea
ti
en p r a
e r ng n
i ff ti i o
d et rat
s e
op
Kbl1
Icdqd
0 Ie 1.2Ie nIe Ir
Please refer to above sections for detailed description of, I d , I r , I e , K bl 1 , K bl 2 , I cdqd , and I cdsd in
above figure.
(1) Sensitive percent differential protection element will send tripping signal after CT saturation,
CT circuit failure (optional), inrush currents, and overexcitation have been excluded. It can ensure
sensitivity of protection and avoid unwanted operation when CT is saturated during an external
fault. Its operation area is the tint shadow area in the figure above.
(2) Insensitive percent differential protection element will send the tripping signal only after the CT
circuit failure (optional) and inrush current have been excluded. It eliminates influence of transient
and steady saturation of CT during an external fault and ensures reliable operation even if CT is in
saturation condition during an internal fault by means of its percentage restraint characteristic. Its
operation area is a deep shadow area in the figure above.
(3) Unrestrained instantaneous differential protection element will send tripping signal without
any blocking if differential current of any phase reaches its setting. Its operation area is over the
above two areas with no shadow.
In the equipment, the second harmonic of differential current can be used to distinguish inrush
current. Its operation criterion is:
Where:
Where:
The differential CT circuit failure is divided into two kinds: differential CT circuit abnormality (refer
to section 3.13.2) without pickup of fault detector of differential protection and differential CT circuit
failure (refer to section 3.13.3) with the fault detector pickup.
CT circuit failure blocking function can be configured by logic setting [En_CTSBlkDiff]. Please refer
to section 3.13.3 for details.
When a transformer is overexcited, the exciting current will increase sharply which may result in
unwanted operation of differential protection. Therefore the overexcitation shall be discriminated to
block the current differential protection. The fifth harmonic of differential current is used as criterion
of overexcitation discrimination.
Where:
differential current.
Where:
Id_max is the maximum value of differential currents.
Flg_FD_Diff is the internal flag indicating that the fault detector of differential current picks up.
Flg_Op_SensPcntDiff is the internal flag indicating that sensitive percent differential protection
operates.
[En_PcntDiff] is the logic setting used to enable percent differential protection function.
[En_InstDiff] is the logic setting used to enable instantaneous differential protection function.
Flg_Inrush is the internal flag indicating inrush current is distinguished.
Flg_CTS is the internal flag indicating current transformer circuit failure is distinguished.
Restricted earth fault protection is also called zero-sequence differential protection, which include
zero-sequence percent differential protection element and unrestrained instantaneous
zero-sequence differential protection element. There are three restricted earth fault protection
elements are equipped in the relay for the three sides of a transformer respectively.
If CTs used for REF have different ratios, then the CT ratio compensation is carried out in the
program automatically. Following gives the criteria of calculating correction coefficient.
There are two correction coefficients set for restricted earth fault protection (also called
zero-sequence differential protection) of each side. One is the correction coefficient of the
calculated side (i.e. three-phase CT input side) of each side, and the other is the correction
coefficient of neutral point side (i.e. zero-sequence CT on the neutral point) of each side.
K
K 0CrCa CT
K CT _ B
(Equation 3.5-1)
KCT _ B
K0 CrNP 1
KCT _ B
Where:
K 0 CrCa is the correction coefficient of the calculated side (i.e. three-phase current input side) of
K 0CrNP is the correction coefficient of the neutral point side of certain side of a transformer.
If the correction coefficient of the calculated side is not greater than 3, the actual calculated value
from (Equation 3.5-1) will be adopted as correction coefficient of the calculated side. If the
correction coefficient of the calculated side is greater than 3, the 3 will be adopted as correction
coefficient of the calculated side and the correction coefficient of the neutral point side will be
reduced proportionally. The criteria of calculating the two correction coefficients will change to the
following equation.
K 0CrCa 3
(Equation 3.5-2)
1
K 0 CrNP
K 0 CrCa / 3
The currents used in calculation of restricted earth fault are based on the two assumptions.
The currents for following calculation are the products of the actual secondary current of
each side multiplying its corresponding correction coefficient respectively.
I 0d I 0cdqd
I K I
0d 0 b1 0r
Where:
[I_Pkp_PcntREF_S1(S2,S3)].
When the above equation is satisfied the zero-sequence percent differential protection will
operate.
DANGER: Before restricted earth fault protection of some side is put into operation on
site, polarity of zero-sequence current transformers (CT) on neutral point of the side must
have been checked right by an energizing test of the side of a transformer or a test of
simulating an external fault of the side in primary system. Otherwise a maloperation may
occur during an external earth fault.
Figure 3.5-1 shows operation characteristic of this zero-sequence percent differential protection.
The operation of this protection shall trip all breakers at all sides of a transforme r when any
unrestrained zero-sequence differential current is greater than its setting. Its operation criterion is:
Where:
I 0 cdsd is the setting of the unrestrained instantaneous zero-sequence differential protection, i.e.
[I_InstREF_S1(S2,S3)].
Please refer to above sections for detailed description of I 0 d , I 0 r , K 0 bl , I 0 cdqd and I 0cdsd in
above figure.
Difference of transient characteristic and saturation of various CT will result in erroneous zero
sequence differential current during an external three-phase short circuit fault or transformer
energization.
In order to eliminate the effect of it, positive sequence current restraint blocking criterion is used.
When zero sequence current of each side zero-sequence differential protection is greater than 0
times positive sequence current, it is decided that zero sequence current is caused by fau lt and
release zero sequence differential protection. Positive sequence current restraint blocking criterion
is showed below.
Where:
0 is a proportional coefficient.
At the same time, second harmonic of phase current of each side of zero-sequence differential
protection is adopted to distinguish CT saturation to block zero-sequence differential protection.
proportional coefficient.
Zero-sequence differential CT circuit abnormality alarm function is equipped and please refer to
section 3.13.3 for detailes.
Where:
Flg_FD_REF_S1 is the internal flag indicating that the fault detector of zero-sequence differential
protection of side 1 picks up.
protection of HV side.
3.6.1 Application
Following functions of three-stage definite time overcurrent relay can be selected by configuring
corresponding logic settings:
Choose which stage is controlled by voltage control element (stage 1 and 2).
Choose being controlled by which side voltage control element (stage 1 and 2)
The voltage control element is an element which will operate if phase-to-phase voltage is lower
than its setting or negative sequence voltage is higher than its setting. Each side of transformer
has its own voltage control element for controlling overcurrent protection of local side or other side
by configuring corresponding logic setting.
Criteria:
Where:
Stage 1 and stage 2 of definite time overcurrent protection can be controlled by voltage element by
configuring related logic settings [En_VCE_OC1_S1] and [En_VCE_OC2_S1]). Stage 1 or 2 can
be blocked by voltage control element of side1, side 2 or side 3 by configuring logic setting
[En_S1.VCE_OC_S1], [En_S2.VCE_OC_S1], or [En_S3.VCE_OC_S1].
When logic setting [En_S2.VCE_OC_S1] is set as “1”, voltage element of side 2 will pick up
following two cases:
Case 1: If voltage element of side 2 reaches its setting and current of side 2 is higher than 0.04 In
Case 2: If voltage element of side 2 reaches its setting and current of side 2 and side 3 both are
lower than 0.04 In.
When logic setting [En_S3.VCE_OC_S1] is set as “1”, voltage element of side 3 will pick up
following two cases:
Case 1: If voltage element of side 3 reaches its setting and current of side 3 is higher than 0.04 In .
Case 2: If voltage element of side 3 reaches its setting and current of side 2 and side 3 both are
lower than 0.04 In.
Logic setting [Opt_VTS_OC_S1] is used to configure action of voltage control element during VT
circuit failure. When this logic setting is set as “1”, if VT circuit failure is detected, the voltage
control element cannot pick up.
When this logic setting is set as “0”, if this side VT circuit failure is detected and voltage control
element reaches its setting, voltage control element will pickup and the voltage controlled
overcurrent protection will becomes a pure overcurrent protection.
When VT of some side is out of service for maintenance, the corresponding binary input
[BI_Out_VT1], [BI_Out_VT2] or [BI_Out_VT3] is needed to be energized to make overcurrent
protection of corresponding side operate correctly.
If binary input [BI_Out_VT1] is energized, voltage control element of side 1 can not pickup
anymore but voltage controlled overcurrent protection of the side can still operate in following two
cases:
Case 1: Overcurrent protection of side 1 reaches its setting, logic setting [En_S2.VCE_OC_S1] is
energized and voltage control element of side 2 pickups.
Case 2: Overcurrent protection of side 1 reaches its setting, logic setting [En_S3.VCE_OC_S1] is
energized and voltage control element of side 3 pickups.
For a self and parallel-excited generator, current decreases so quick during short-circuit fault that it
may be lower than overcurrent protection setting before tripping signal is issued. Therefore, after
current memory function is equipped to remember fault current so that the voltage controlled
overcurrent protection can operate reliably. Logic setting [En_Mem_Curr] is used for configuration
of this function.Current memory function is only applied for voltage control overcurrent protection.
Each side of transformer has its own voltage control element for controlling overcurrent protection
of local side other other side. Here voltage control elment of side 1 is taken as an example to show
the logic.
Where:
Flg_VTS_S1 is the internal flag indicating that voltage transformer circuit failure of side 1 is
distinguished.
[Opt_VTS_OC_S1] is the logic setting of selecting side 1 overcurrent protection how to response
when VT circuit fails.
Flg_VCE_S1 is the internal flag indicating that voltage control element (VCE) of side 1 picks up.
Stage 1 and stage 2 of overcurrent protection have similar logic diagrams and stage 1 is taken as
example to show the logic scheme diagram.
& ≥1
[En_Mem_Curr]
Imax>[I_OC1 _S1]
Flg_VCE _S1
[En_VCE_OC1 _S1] &
[En_S1.VCE_OC_S1]
&
Flg_VCE _S2 ≥1 & [t_OC1_S1] [Op_OC1_S1]
& ≥1
[En_S2.VCE_OC_ S1 ]
Flg_VCE _S3
&
[En_S3.VCE_OC_ S1 ]
[EBI_PPF_S1]
&
[En_PPF_S1]
Flg_FD_OC1_S1
Flg_VCE_S1 is the internal flag indicating that voltage control element (VCE) of side 1 picks up.
Flg_VCE_S2 is the internal flag indicating that voltage control element (VCE) of side 2 picks up.
Flg_VCE_S3 is the internal flag indicating that voltage control element (VCE) of side 3 picks up.
Flg_FD_OC1_S1 is the internal flag indicating that the fault detector of stage 1 of overcurrent
protection of side 1 picks up.
Stage 3 of overcurrent protection is pure overcurrent protection without voltage control element
blocking.
Flg_FD_OC1_S1 is the internal flag indicating that the fault detector of stage 3 of overcurrent
protection of side 1 picks up.
Protection of Side 1
3.7.1 Application
This protection is applied as backup protection of earth fault for transformer with neutral point
earthed, which comprises two-stage definite time overcurrent protection element with own
settings and definite time delays. Setting is provided for voltage control element for the user to
choose certain sensitivity.
Following functions of three-stage definite time zero-sequence overcurrent relay can be selected
by configuring corresponding logic settings:
Whether or not use calculated zero sequence current (stage1 and 2).
Logic setting [Opt_Dir_ROC_S1] is used to select the direction of every stage of zero sequence
overcurrent protection. If this logic setting is set as “1”, the direction is transformer and reach angle
is 225º. If this logic setting is set as “0”, the direction is power system and reach angle is 75º.
Figure 3.7-1 shows operating characteristic of directional protection where the hatched area is
operation zone.
Io
Io
NOTE: The zero sequence voltage and current used by directional relay is definitely the
calculated voltage and current. The direction mentioned above is based on the
assumption that positive polarity of CT being at the side of busbar.
Logic setting [Opt_3I0_ROC_S1] is used to select whether zero sequence current is used by stage
1 or 2 of zero-sequence overcurrent relay. If the logic setting is set as “1”, internally calculated zero
sequence current is used for the stage. If it is set as “0”, directly measured zero sequence current
is used.
When VT of side 1 is out of service for temperate maintenance, it is needed to energize the binary
input [BI_Out_VT1] and then the directional element pickups.
Stage 1 and stage 2 have similar logic diagrams with independent settings and stage 1 is taken as
example to show the logic scheme diagram.
Where:
Flg_Dir_ROC_S1 is the internal flag indicating the zero sequence directional element picks up.
[Opt_VTS_ROC_S1] is the logic setting of selecting zero sequence overcurrent protection how to
act during VT circuit failure.
[EBI_EF_S1] is the binary input of enabling earth fault protection of side 1 (i.e. voltage supervised
directional zero-sequence protection of side 1).
Flg_FD_ROC1_S1 is internal flag indicating that the fault detector of stage 1 of zero-sequence
overcurrent protection picks up.
One stage “gap” zero-sequence overcurrent protection with two delays and one stage
zero-sequence overvoltage protection with two delays are provided as backup protection of side 1
of transformer with neutral point ungrounded, or grounded through small reactor or gap.
Considering that ground overcurrent via air gap and zero -sequence overvoltage may appear
alternatively during air gap broken down process, once zero-sequence overcurrent or
zero-sequence overvoltage protection operates, the operations of these two elements are “OR”
relation. Therefore operation of the “gap”protection is reliable.
Logic scheme
Where:
Flg_FD_ROV_Gap is the internal flag indicating that the fault detector of gap zero-sequence
overvoltage protection picks up.
Flg_FD_ROC_Gap is the internal flag indicating that fault detector of gap zero-sequence
overcurrent protection picks up.
3.9.1 Application
This protection is applied as backup protection of transformer, LV busbar and neighboring lines,
which comprises two-stage definite time overcurrent protection element with own settings and
time delays. The two stages can be controlled by voltage control element by configuring logic
settings. Settings are provided for voltage control element for the user to choose certain sensitivity
Voltage controlled overcurrent protections of side 2 and 3 have similar logic schemes with
independent settings to control the protection. Here side 2 is taken as an example.
Following functions of two-stage definite time overcurrent relay can be selected by configuring
corresponding logic settings:
Choose which stage is controlled by voltage control element (stage 1 and 2).
Voltage control elements of side 2 and side 2 are similar to that of side 1 with the independent
settings of each side, and please refer to section 3.6.3 for operation criteria.
Stage 1 and stage 2 of definite time overcurrent protection can be controlled by voltage control
element of local side by configuring related logic settings [En_VCE_OC1_S2(S3)] and
[En_VCE_OC2_S2(S3)].
Logic setting [Opt_VTS_OC_S2] is used to configure action of voltage control element during VT
circuit failure. When this logic setting is set as “1”, if VT circuit failure is detected, the voltage
control element cannot pick up and the protection will not operate. When this logic setting is set
as “0”, if this side VT circuit failure is detected and voltage control element reaches its setting,
voltage control element will pickup and the voltage controlled overcurrent protection will becomes
a pure overcurrent protection.
When VT of some side is out of service for maintenance, the corresponding binary input
If binary input [BI_Out_VT2] is energized, voltage control element of side 2 can not pickup to
release the voltage blocking of this side or other side.
During switching on process of power supply of the power plant, tripping of stage 2 of this
protection shall be accelerated in order to prevent expansion of fault during following ceases,
such as fault occurs during switching on process or switching onto fault condition.
This function shall be enabled by a binary input during a short period of the transformer being
switched on and disabled when the transformer operates normally. When this function is disabled,
stage 2 will operate with its own time delay.
Logic setting [En_OC2_SOTF_S2] is used to configure this function. If this logic setting is set as
“1”, stage 2 of overcurrent protection will operate with short time delay, when the current
reaches its setting during a short period of the standby transformer being witched on. When
current in branch presents longer than 5 s, accelerating tripping function will be disabled. If binary
input of enabling accelerating tripping is energized continuously more than 10 s, an alarm will be
issued and the accelerating function will be disabled.
Voltage control elements of side 2 and 3 have similar logic schemes as that of side 2 with the
independent settings of each side, and please refer to section 3.6.7.1 for the logic scheme of
voltage control element.
Side 2 and side 3 both have SOTF logics of stage 2 of local side by configuring corresponding
binary inputs and logic settings and their logic schemes are similar.
Flag_Cur_T5_Sx is the internal flag indicating that the duration of current of side 2 (or side 3) is
less than 5 seconds.
[BI_SOTF_Sx] is the binary input of accelerating tripping contact of side 2 (or side 3).
Flg_SOTF_T10_Sx is the internal flag indicating that the persisting time of the binary input of side
2 (or side 3) is less than 10s.
[En_OC2_SOTF_Sx] is the logic setting of enabling SOTF logic of side 2 (or side 3).
Flg_SOTF_Sx is the internal flag indicating that SOTF logic of stage 2 of side 2 (or side 3) picks
up.
Stage 1 of overcurrent protection of side 1 and that of side 2 have similar logic schemes.
Imax_Sx is the maximum value of three-phase current of side 2 (or side 3).
[I_OC1_Sx]: current setting of stage 1 of overcurrent protection of side 2 (or side 3).
[En_VCE _OC1_Sx] is the logic setting of enabling voltage control for stage 1 of overcurrent
protection of side 2 (or side 3).
[EBI_PPF_Sx] is the binary input of enabling the backup overcurrent protection of side 2 (or side
3).
[En_PPF_Sx] is the logic setting of enabling backup overcurrent protection of side 2 (or side 3).
Flg_FD_OC1_Sx is the internal flag indicating that the fault detector of overcurrent protection
stage 1 of side 2 (or side 3) picks up.
[t_OC1_Sx] is the time delay of stage 1 of overcurrent protection of side 2 (or side 3).
[Op_OC1_Sx] is the operation of stage 1 of overcurrent protection of side 2 (or side 3).
Where:
Flg_ SOTF_Sx, [EBI_PPF_Sx] and [En_PPF_Sx] please refer to above two sections description.
Imax_Sx is the maximum value of three-phase current of side 2 (or side 3).
[I_OC2_Sx] is the current setting of stage 2 of overcurrent protection of side 2 (or side 3)
Flg_FD_OC2_Sx is the internal flag indicating that the fault detector of overcurrent protection
stage 2 of side 2 (or side 3) picks up.
[t_OC2_Sx] is the delay setting of stage 2 of overcurrent protection of side 2 (or side 3)
[Op_OC2_Sx] is the operation of stage 2 of overcurrent element of side 2 (or side 3).
This protection is mainly used as backup protection of transformer with side 2 or 3 neutral point
grounded solidly, which consists of two-stages zero sequence overcurrent protection with time
delays. Zero sequence current used is usually taken from zero sequence CT on neutral point.
Logic scheme
Side 2 and 3 have similar logic schemes of zero sequence overcurrent protection, and stage 1
and 2 of zero sequence overcurrent protection also have similar logic schemes, so here stage 1 is
taken as an example to show logic diagram.
3.11.1 Application
When fault occurs on HVS of a main transformer or a step-down transformer, tripping is needed. If
breaking capacity of the corresponding breaker is not high enough, the breaker shall be blocked
until other related breakers are tripped firstly and the fault current is reduced to permit range. This
blocking process is described below.
(1) If the current is higher than the setting [I_CCE], related other breakers, which can be
configured by logic setting [TrpLog_CCE], will be tripped firstly. With a delay 20 ms, current is
checked again whether lower than the setting [I_CCE]. If it is, then the breaker is tripped, and
otherwise the breaker will not be tripped until the current lower than [I_CCE].
(2) If current floating through the breaker is lower than the setting [I_CCE], then the breaker will
be tripped with a delay 20 ms.
One normal-open contact is provided for the blocking element. The selective tripping function is
realized by cooperation of this contact with the tripping contact of mechanical protection.
If this blocking function is disabled, the circuit breaker will be tripped without delay.
This function can be configured to any side of transformer by configuring logic setting
[Cfg_CT_OvLd].
Where
Ia, Ib and Ic are phase A, B and C currents of one side of transformer in turn.
[I_CCE] is the current setting of current control element for breaking capacity blocking function.
Flg_TrpCmd is the internal flag indicating that tripping command is issued by protection.
BO_TrpOutp3 means that “TrpOutp3“(i.e. the 3rd group of tripping output relays) operates and
corresponding normally open contacts are closed. “TrpOutp3”is fixed as output relays for breaking
capacity blocking function.
BO_TrpOutp_Config means that othergroups of tripping output relays are selected to be tripped
first by configuring the logic setting [TrpLog_CCE].
RCS-985TS is also equipped with thermal overload alarm, cooling initiation, on-load tap change
blocking during overload and overcurrent output function, which can be enabled or disabled by
configuring the corresponding logic setting. This function can be configured to any side of
transformer by configuring logic setting [Cfg_CT_OvLd].
One NO (normaly open)output contact for overload initiating cooling system, one NC (normaly
closed) contact for on-load tap change blocking during overload and one NO contact for
overcurrent output are provided respectively.
Furthermore, one stage of zero-sequence overvoltage alarm is also equipped as earth fault alarm
and the zero sequence voltage for it is input through terminals 221-222.
Where:
I 0 is the zero sequence current of one side.
I n is rated secondary current of CT.
I max is the maximum value of three-phase current of one side.
If the current of any side of transformer meets the above criterion, CT circuit abnormality alarm of
this side will be issued after 10s .The abnormality alarm will be reset after 10 s if equipment returns
to normal condition.
Where
I d is differential current.
[I_Alm_Diff] is setting of differential current abnormality alarm
I res is the restraint current
K bj is percentage restraint coefficient.
This function is enabled only when differential protection is enabled by setting logic setting
[En_Diff] as “1”. If the criterion is met, differential circuit abnormality alarm will be issued after 10 s
but related differential protection will not be blocked. When the differential current eliminates and
the equipment return to normal condition, the alarm will be reset after 10 s.
If zero-sequence differential current is greater than its alarm setting fixed in program and lasted
longer than 10 s, alarm of zero-sequence differential current alarm will be issued without blocking
the zero-sequence percent differential protection.
CT circuit failure discrimination will function after pickup of fault detector of differential protection, if
both logic setting and binary input of enabling differential protection are set as “1”.
If internal fault occurs, at least one of following conditions will occur after fault detector of
(2) Maximum phase current is higher than 1.2 Ie (Ie is secondary calculated rated current of
transformer);
If none of those conditions occurs, it will be judged as CT circuit failure. If the logic setting
[Opt_CTSBlkDiff] is set as “1”, the percent differential protection will be blocked with an alarm
signal being issued. If this logic setting is set as “0”, an alarm signal will be issued without blocking
percent differential protection.
If the alarm is issued, the alarm signal can be reset only when the failure is removed and the
equipment is reset by pressing “RESET”button on panel via energizing binary input [BI_RseTarg]
(423).
NOTE: Do not press key ”RST”on the front faceplate to remove CT circuit failure signal,
(1) Positive sequence voltage is higher than 18V and any phase current is higher than 0.04 IN . (IN
is rated secondary current of current transformer.)
(2) Three times negative sequence voltage 3U2 is higher than 8V.
If any one criterion is met, VT circuit failure alarm will be issued after 10s. The alarm signal will be
reset automatically after 10s if equipment returns to normal condition.
Case1: Voltage control element of side 1 is not enabled to block overcurrent protection of side 1
and zero sequence directional relay of side 1 is not enabled.
Case1: Voltage control element of side 2 is not enabled to control overcurrent protection of side 2.
Case1: Voltage control element of side 3 is not enabled to control overcurrent protection of side 3.
Though the protection system is in non-operating state under normal conditions, it is waiting for a
power system fault to occur at any time and must operate for the fault without fail. When the
equipment is in energizing process before the LED “HEALTHY”is on, the equipment needs to be
checked to ensure there are no errors. Therefore, the automatic supervision function, which
checks the health of the protection system when startup and during normal operation, plays an
important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a fatal fault is detected during automatic supervision, the equipment will be blocked out. It
means that relay is out of service. Before you must re-energize the relays or reset CPU module
and MON module to make relay back into service, please find out the cause and inform the
factory.
The DSP, RAM, ROM chips on the CPU module are continuously to ensure whether they are
damaged or have some errors. If any one of them is detected damaged or having error, alarm
signal [Alm_Fail] and the corresponding hardware alarm signals will be issued with equipment
being blocked, and “HEALTHY”LED will be extinguished at the same time.
The secondary voltage level of the built-in DC/DC converter is monitored and checked whether the
DC voltage is within a prescribed range.
If a failure is detected in the DC power supply circuit, the alarm signal [Alm_Pwr _DC] will be
issued with equipment being blocked, and “HEALTHY”LED will be extinguished at the same time.
If a power supply failure is detected in the built-in MON module, the alarm signal [Alm_Pwr_MON]
will be issued with equipment being blocked, and “HEALTHY”LED will be extinguished at the
same time.
Chips controlling the output relays in the output circuit are continually monitored. If any error or
damage is detected in these chips, the alarm signal [Alm_TrpOut] will be issued with equipment
being blocked, and “HEALTHY”LED will be extinguished at the same time.
This relay has 4 setting groups, while only one is active at the same time. The settings of active
setting group are checked to ensure they are reasonable. If the settings in CPU module are
checked to be invalid, the alarm signal [Alm_Setting] will be issued with equipment being blocked,
and “HEALTHY”LED will be extinguished at the same time.
If the settings in the MON module are checked to be invalid, the alarm signal [Alm_Set_MON] will
be issued with equipment being blocked, and “HEALTHY”LED will be extinguished at the same
time.
Zero point of voltage and current may drift influenced by variation of temperature or other
environment condition. The equipment continually automatically traces the drift and adjusts it to
normal value.
If the fault detector in MON module keeps picking up for 10s, equipment will issue abnormality
alarm [Alm_FD_MON] without equipment being blocked, and the “ALMAR”LED will be lit at the
same time.
The communication between CPU module and MON is monitored to ensure reliable data
exchange. If communication fails, the alarm signal [Alm_Comm_MON] will be issued with
equipment being blocked, and “HEALTHY”LED will be extinguished at the same time.
The main purpose of the current transformer (CT) circuit failure supervision function is to detect
faults in the secondary circuits of CT and avoid influence on the operation of corresponding
protection functions. The CT failure supervision (CTS) function will be always processed all the
time, which includes following two aspects
The VTS logic in the relay is designed to detect the voltage failure and automatically adjust the
configuration of protective elements whose stability would otherwise be compromised. A
time-delay alarm output is also available.
Equipment hardware circuits and software working conditions are always monitored by the relay. If
any abnormality occurs, the corresponding alarm message will be issued on the LCD of the
equipment.
Some failures will result in some protective function being blocked. Some server failures of
hardware or software will result in the equipment being blocked and the contacts of equipment
failure will operate at same time. During that condition, the protection relay has to be out of service
for maintenance.
NOTE :If alarm signal is issued with equipment being blocked, please try to make a fault
diagnosis by referring the issued alarm messages but not to simply reboot or re-power the
relay. If user cannot find the failure reason on site, please inform manufacturer for
maintenance.
Handling suggestion
2. Modify and check settings of CT ratio to improve differential protection performance. (No.10)
3. Modify and check setting cell [Cfg_ConnGrp] in system settings submenu. (No.11)
4. Please refer to other alarm messages to ensure the failure cause. (No.12)
During equipment normal operation, VT and CT circuit and some binary input circuits are always
monitored by the relay. If any abnormality of them occurs or any alarm element operates, the
corresponding alarm message will be issued on the LCD of the equipment without blocking
equipment.
When this kind of alarm messages are issued, user need to find the abnormality reason, and then
take corresponding measures to eliminate the alarm message to make the equipment return to the
normal operation.
Handling suggestion
3. Check current sample value and the wiring of the CT secondary circuit of the corresponding
side. (No.4~No.6)
4. Check current sample value and the wiring of the VT secondary circuit of the corresponding
side. (No.7~No.9)
6. De-energize the binary input [EBI_Diff], and check the wiring of differential CT secondary
circuit. After the equipment returns to a normal condition, please reset the equipment and
energize the binary input [EBI_Diff]. (No.11)
8. Please refer to other alarm messages to ensure the abnormality cause. (No.17)
The relay also provides some auxiliary functions, such as real-time data metering, binary input
status recording, event and disturbance recording, etc. All these make the relay meet the
demands of the modern power grid requirements.
5.2 Metering
Equipment samples 24 points per cycle. Calculate the RMS value in each interval and LCD will be
updated every 0.5 second. The following system quantities are displayed in RMS values of the
secondary side of CT and VT. This device has double CPU system (i.e. CPU and MON module),
so the sampled values of both modules will be displayed on LCD through different access menu.
NOTE: Ie and In mentioned in following sections are units. Ie is secondary rated current of
NOTE: The quantities listed in following tables are to be displayed on LCD for RCS-985TM,
but for a certain application, some of these quantities may be eliminated due of the
scheme user required, so please look up the devices on site for actual quantities
displayed.
Table 5.2-6 Relevant quantities of earth fault and gap earth fault protections
All the binary input changes are recorded in the relay, and can be displayed on LCD locally printed
or sent to automation system of substation via communication channel.
5.4.1 Introduction
Event recording
Present recording
All the recording information can be viewed on local LCD (except waveform) or by printing o.
Please see the detailed steps in section 8.7.
The equipment can store the latest 64 trip reports, the latest 64 equipment operation alarm reports,
the latest 64 self-check alarm reports, the latest 64 user operating reports and the latest 256
sequence of event (SOE) reports respectively. All the records are stored in non-volatile memory,
and when the available space is exhausted, the oldest report is automatically overwritten by the
latest one
Any operation of protection elements, either pickup of tripping, will be logged as an event record.
Please refer to Table 8.3-1 for details.
Any abnormality alarm being detected during relay self-check supervision will also be logged as
individual events. Please refer to Table 4.2-1 for details.
Under a normal operation, some alarm signals occurred due of secondary circuit abnormality or
protection alarm element operating will be record in the equipment. Please refer to Table 4.2-2 for
details.
Whatever the user does any operation to the equipment, such as modifying the settings or clearing
reports, will be recorded by the equipment.
SOE records
Here “SOE report “includes following kinds of record, such as protection elements and alarm
elements operation and dropping off, and binary input being energized or de-energized. SOE
reports are also called binary input changing reports.
(1) When a protection element operates, its state changes from “0”to “1”, and when the element
drops off, its state changes from “1”to “0”. (Refer to Table 8.3-1 for all the events).
(2) When an alarm element picks up to issue alarm signal, its state changes from “0”to “1”, and
when the element drops off, its state changes from “1”to “0”. (Refer to and Table 4.2-1 and
Table 4.2-2 for all the events).
(3) When a binary input is energized, its state changes from “0”to”1”, and when the binary input is
de-energized, its state changes from “1”to “0”. (Refer to Table 5.3-1 for all the events).
The equipment can store 64 pieces of trip report and the latest 8 waveform in non-volatile memory.
If a new fault occurs when 64 fault records or 8 fault waveform records have been stored, the
oldest will be overwritten by the latest one. The equipment stores actual samples that are taken at
a rate of 24 samples per cycle.
One total waveform is composed of 3 cycles’waveform before pickup of fault detector and five
cycles’waveform after pickup of fault detector. If there is anyone protection element operating,
then the recording duration will be prolonged to show 3 cycles’waveform before and 5 cycles’
waveform after the protection element trips. The duration of one waveform recording can be 15
second at most.
In modern protective schemes it is often desirable to synchronize the relays real time clock so that
events from different relays can be placed in chronological order. This can be done using the
IRIG-B input, if fitted, RS-485 message via the communication interface connected to the
substation control system, or second/minute pulse via binary input.
Pulsing this input will result in the real time clock snapping to the nearest minute. The
recommended pulse duration is 20ms to be repeated no more than once per minute. An example
of the time synchronization function is shown bellow.
Symbol “”will be viewed on right head of single line diagram on LCD when equipment detects
synchronization signal from binary input.
The modular design of the RCS-985TS allows the relay to be easily upgraded or repaired by a
qualified service person. The faceplate is hinged to allow easy access to the configurable modules,
and back-plugging structure design makes it easy to repair or replace any modules.
There are several types of hardware modules in the RCS-985TS and each module takes a
different part in the equipment. The RCS-985TS mainly consists of PWR module (power supply
module), CPU module, MON module, AI modules (analog inputs module, VTs and CTs), BO
modules and HMI module. Following figure shows the block diagram of the RCS-985TS.
CPU module with a powerful microchip processor, two serial interfaces and up to three
Ethernet interfaces for SAS or RTU, one interface for the local printer, and one clock
synchronization interface.
HMI module with a 160×80-dot matrix backlight LCD, a 9-key keypad, 3 LED indicators.
No.3 PWR module power supply module with 20 regular optical insulation inputs and 5
special optical insulation inputs, and a built-in extension module of the interfaces of the CPU
module.
No.4 BO module with 8 contact outputs for tripping, 5 contact outputs for local signal and 4
contact outputs for alarm.
No.5 BO module with 12 contact outputs for tripping, 5 contact outputs for remote signal.
NOTE: No.1 AI module configuration must have been definitely declared in the technical
scheme.
The Figure 6.1-2 and Figure 6.1-3 and shows the front view and rear view of the RCS-985TS.
T
RS
ESC
Besides HMI module, CPU module and MON module, RCS-985TS comprises the following 5
plug-in module, the arrangement of modules has been showed in the following table.
The basic enclosure for the RCS-985TS is an electronic equipment rack with an adequate number
of slots for the No.1 AC module, No.2 AC module, No.3 PWR module, No.4 BO module and No.5
BO module. The basic rack is equipped with a back plane (mother board), and the CPU module
equipped with the basic rack. Moreover, MON module is equipped with CPU module. The back
plane provides some back plane lines for distributing signals within the enclosure.
There are 10 slots in the rack of RCS-985TS equipped with above mentioned five plug-in modules.
Protection calculations
The CPU module can calculate protective elements (such as differential protection,
overcurrent element, zero sequence overcurrent etc.) based on the analog inputs form the AI
module and binary inputs from the PWR module, and then judges that whether the device
need to trip.
Communication management
The CPU module can effectively manage the communication procedure, and reliably send out
some useful information through its various communication interfaces. Two serial interfaces
for SAS or RTU, up to three Ethernet interfaces for SAS or RTU and one serial interface for
the printer are contained in this module. A 20-pin interface for the connection with the HMI
module is contained in this module too. If an event is occurred (such as SOE, protective
tripping event etc.), this module will send out the relevant event information through these
interfaces, and make it be easily observed by the user.
Auxiliary calculations
Basing on the analog inputs, the CPU module also can calculate out the measurement values,
such as active power, reactive power and power factor etc. All these values can be sent to a
SAS or a RTU through the communication interfaces.
Clock Synchronization
This module has a local clock chip and an interface to receive clock synchronized signals
from external clock source. These signals include PPS (pulse per second) signal and IRIG-B
signal. Basing on the timing message (from SAS or RTU) and the PPS signal, or basing on
the IRIG-B signal, this module can make the local clock synchronize with the standard clock.
There are some jumpers on this module for various purposes. The jumpers JP1 (“ARM-JTAG”) is
used to connect with an ARM simulator, and the jumper J6 (“DSP-JTAG”) is used to connect with a
DSP simulator. The jumper J5 (“CPLD”) is used to program the CPLD chip on this module. The
jumper JP8 (“CONSOLE”) is used to debug the ARM program of this module.
All above jumpers are reserved for the manufacturer to develop and debug the relevant programs
of this module; the user needn’
t use anyone of them.
NOTE: In a regular application, anyone of the above jumpers must be kept the state that
has been set by the manufacturer. Any change of the configuration of the above jumpers
is not permitted.
The jumper JP2 and JP3 are used to download the relevant programs of the CPU module. When
the jumper JP2 is connected, writing the DSP program to the corresponding flash memory is
permitted. When the jumper JP3 is connected, downloading the ARM program to the CPU module
is permitted.
NOTE: In a regular application, the jumper JP2 and JP3 are unconnected. The two
jumpers are only reserved for the manufacturer to refresh the programs of the CPU
module.
The MON module is an important part of this equipment, and contains a powerful microchip
processor and some necessary electronic elements. There are a set of fault detectors on MON
module, which function is to supervise the tripping outputs.
The HIM module is installed on the front panel of RCS -985TS (see Figure 6.2-2). It is used to
observe the running status and event information on the LCD, and configure the protection
settings and device operation mode. A 160×80-dot matrix backlight LCD, a 9-key keypad, Three
LED indicators are contained in this module. All these can help the user to know the status of the
equipment and detailed event information easily, and provide convenient and friendly access
interface for the user. For further details, see Chapter 6 “Human-machine Interface”.
The elements and their functions of the HMI module are listed as follow.
This LCD is used for monitoring status, fault diagnostics and setting, etc.
These LED indicators are used to denote the status of this protective system.
A 9-key keypad
6.2.5 AI Modules
The AI modules are analog input units. No.1 AI module contains 11 current transformers and 1
voltage transformers or 12 current transformers. No.2 AI module contains 8 voltage transformers
They can transform these AC input values to relevant micro AC voltage signals, which are suited
to the analog inputs of the CPU and MON module. It also can be thought as a bridge between the
two modules and the external analog signals that come into the relay. The transformers are used
both to step-down the currents and voltages to levels appropriate to the relay’
s electronic circuitry
and to provide effective isolation between the relay and the power system. A low pass filter circuit
is connected to each transformer (CT and VT) secondary circuit for reducing the noise of each
analog AC input signal.
NOTE: The rated value of the input current transformer is optional: 1A or 5A. The rated
value of the CT must be definitely declared in the technical scheme and the contract.
NOTE: Because the rated value of the input current transformer is optional, it is
necessary to check that whether the rated values of the current transformer inputs are
accordant to the demand of the practical engineering before putting the device into
operation.
Isolator transformer
Ia_ S1 101
102
Ian_ S1
Ib_S1 103
To LPF
Ibn_S1 104
Ic_S1 105
Icn_S1 106
101 102
Ia_S2 107
103 104 108
Ian_ S2
Ib_ S2 109
To LPF
105 106 Ibn _S2 110
Ic_S2 111
Icn_S2 112
107 108
Ia_ S3 113
109 110
114
Ian_ S3
Ib _S3 115
111 112 To LPF
Ibn _S3 116
Ic_S3 117
113 114
Icn_S3 118
I0_ S1 119
120
I0n_ S1
To LPF
I0 _S2
121
I0n _S2 122
U 0_Gap 123
To LPF
U0n _Gap 124
AI
Figure 6.2-3 Rear view and connector definition of the No.1 AI module
DANGER: Never allow the current transformer (CT) secondary circuit connected to this
equipment to be opened while the primary system is live. Opening the CT circuit will
produce a dangerously high voltage. If this safety precaution is disregarded, personal
dearth, severe personal injury or considerable equipment damage will occur.
NOTE: Terminals 123/124 are alternative to be as the input terminals of zero sequence
voltage for gap earth fault protection, or as input terminals of zero sequence current from
the zero-sequence CT 3 for the earth fault protection of side 3. Please refer to section
6.3.2 for the details.
Isolator transformer
Ua_S1 201
202
Uan_S1
Ub_S 1
201 202 203
To LPF
Ubn_ S1 204
Uc_ S1 205
203 204
206
Ucn_S1
205 206
Ua_S2
209
Ub_S3 To LPF
213 214 216
Uc_ S3 217
U0 _Delt 221
To LPF
222
U 0n_ Delt
AI
Figure 6.2-4 Rear view and connector definitionof the No.2 AI module
The power supply module is a DC/DC converter with electrical insulation between input and output,
and an output power of 30W. The power supply module has an input voltage range of 88 V DC to
288 V DC without any switching of ranges. The standardized output voltages are +3.3V, +5V, ±12V
and +24V DC. The tolerances of the output voltages are continuously monitored.
The +3.3V DC output provides power supply for the microchip processo rs, and the +5V DC output
provides power supply for all the electrical elements that need +5V DC power supply in the
RCS-985TS. The ±12V DC output provides power supply for A/D conversion circuits in this device,
and the +24V DC output provides power supply for the static relays on the operation circuits (BO
module).
The input of the power supply module is protected by a 3.15A / 250 V slow fuse. The current surge
when energizing the power supply module is limited to 3.15A. The use of an external miniature
circuit breaker is recommended. The circuit breaker must be in the on position when the device is
in operation and in the off position when the device is in cold reserve.
Twenty regular optical insulation binary inputs and five special optical insulation binary inputs are
contained in this module. The regular optical insulation binary inputs are used to monitor the
position of the regular binary signals; the special optical insulation binary inputs are used to
monitor the position of the special binary signals, which must be taken into account in the
protection calculations and communication management of the CPU module.
A built-in extension interfaces module of the CPU module is equipped on the PWR module. Two
EIA RS-485 standardized ports and three Ethernet ports are contained in the built-in module.
The Ethernet ports are optional: optical or electrical. For more information about the Ethernet ports,
please refer to section 2.1.5.
NOTE: In a built-in module with three Ethernet ports, the transmission rate of the third
Ethernet port is 10Mbit/s, and the transmission rate of the other two Ethernet ports are
100M/bit. In a built-in module with two Ethernet ports, the transmission rate of the two
Ethernet ports are 100M/bit.
There are two connectors on the front of the PWR module: a 12-pin connector and a 30-pin
connector. The terminal definition of the two connectors is described below.
GND 401
402
Pwr + 403
Power Input
Pwr - 404
EBI_Diff 406
COM1
415 BI_SOTF_S2 415 RS-485 B 302
416
BI_SOTF_S3 416 SHLD 303
417
418 RS-485 A 304
301 EBI_Resv2 417
419 C OM2
302
420 418 RS-485 B 305
303 EBI_Resv2
421
304 419 SHLD
422 BI_Out_VT1 306
305
423
306
sy nc hronization
EBI_REF_S3 426
BI_Resv1 427
PWR
BI_Resv2 428
BI_Resv3 429
BI_Resv4 430
Figure 6.2-5 Rear View and connector definitions of the No.3 PWR module
303 SHLD
304 A
No.2 serial port: EIA RS-485 standardized communication
305 COM2 B
interface for connecting with a SAS or a RTU.
306 SHLD
307 SYN+
CLK EIA RS-485 standardized interface for clock synchronization,
308 SYN-
SYN PPS and IRIG-B signals are permitted.
309 SHLD
310 RXD
Interface for connecting with a printer, the EPSON ® LQ-300K
311 PRT TXD
printer is recommended.
312 SGND
6.2.7 BO Modules
The BO modules consist of some necessary contact outputs, such as trip-outputs, signal outputs
etc. They can receive tripping commands from the CPU module, and then act according to these
commands. These modules also can send out some necessary binary output signals (dry contact)
to the SAS or RTU according to the relevant commands from the CPU module.
A 30-pin connector is fixed on the front of the No. 4 BO (or No.5 BO) module. The terminal
definition of the connector is described below.
501 Common
502 BO_Fail
503 BO_Alm_Abnor
504 BO_Diff
(latched)
505 BO_BakProt
(latched)
506 BO_REF
507
501 BO_TrpOutp_1-1
502 508
503
509
504
505 BO_TrpOutp_1-2
510
506
507 511
508 BO _TrpOutp_2-1
509 512
510
511 513
512 BO_TrpOutp_2-2
513 514
514
515
515
BO_TrpOutp_3-1
516
516
517
518 517
519 BO _TrpOutp_3-2
520 518
521
519
522
523 BO_TrpOutp_4-1
520
524
525
521
526
BO_TrpOutp_4-2
527 522
528
529 523
530 BO_CCE
524
525
BO_Alm _BlkOTLC
_OvLD
526
527
BO_Alm_InitCool
BO _OvLd
528
OUT
529
BO_Alm_ROV
530
Figure 6.2-6 Rear view and connector definition of the No.4 BO module
601 Common
602 BO_Fail
603 BO_Alm_Abnor
604 BO_Diff
605 BO_BakProt
606 BO_Alm_OvLd
607
601
BO_TrpOutp_5-1
602 608
603
604 609
605
BO_TrpOutp_5-2
606 610
607
611
608
609 BO _TrpOutp_6-1
612
510
611 613
612
BO_TrpOutp_6-2
613 614
614
615 615
616 BO_TrpOutp_7-1
617 616
618
617
619
620 BO _TrpOutp_7-2
618
621
622 619
623 BO_TrpOutp_8-1
624 620
625
621
626
627 BO_TrpOutp_8-2
622
628
629 623
630
624 BO_TrpOutp_9
625
BO_TrpOutp_10
626
627
BO BO_TrpOutp_11
628
OUT
629
BO_TrpOutp_12
630
Figure 6.2-7 Rear view and connector definition of the No.2 BO module
Logic setting of tripping matrix consists of sixteen binary digits but four hexadecimal digits can be
viewed through device LCD screen. Every bit represents a group of tripping relays. When a
protection element operates, the relay group will output if the corresponding bit is set as “1”and
will not output if the bit is set as “0”. Corresponding bit, relay group name and number of contacts
of s of tripping matrix are as follows.
Some voltage and current input channels share the same position of isolating transformer on AI
module. Therefore, only one group channel can be used in this case.
(1) 123/124 as zero sequence voltage channel, which is derived from open-delta of VT and used
for gap zero-sequence overvoltage protection
(2) 123/124 as zero sequence current channel, which is derived from zero sequence CT 3 and
used for zero-sequence overcurrent protection of side 3.
NOTE: Only one kind channel can be used simultaneously, so the selection of above
Chapter 7 Settings
The settings are used to determine the characteristic of each protective element and operation
mode of the relay. It is necessary to configure the settings of this relay according to engineering
demands before putting this relay into service. If the settings aren’
t configured correctly, the relay
maybe work abnormally (such as communication interrupted, printing out unexpected codes etc.),
even sometimes much more serious accident will occur (such as unwanted operation, missing
operation).
The user can configure these settings or parameters manually. Remote modification is also
supported
The RCS-985TS has four setting groups for protection to coordinate with the mode of power
system operation, one of which is assigned to be active. However, system parameters and
equipment setup parameters are common for all setting groups.
Configuring principles for protection settings are different when the equipment is used to protect
main transformer, step-down transformer or start-up/standby transformer. That means common
configuring principle for system parameters and equipment setup parameters, but different for
protection settings.
NOTE: If a CPU or MON module is replaced, it is necessary to configure all the settings
. NOTE: All current settings in this chapter are secondary current converted from primary
This submenu is mainly used to set the parameters for communication, printing and etc. In
addition, password is set here too.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1. No.1— [Password]
2. No.2— [Comm_Addr]
3. No.3— [IP1_Byte_3]
Byte 3 of the IP1. Refer to the picture in the remark column of it.
4. No.4— [IP1_Byte_2]
Byte 2 of the IP1. Refer to the picture in the remark column of it.
5. No.5— [IP2_Byte_3]
Byte 3 of the IP2. Refer to the picture in the remark column of it.
6. No.6— [IP2_Byte_2]
Byte 2 of the IP2. Refer to the picture in the remark column of it.
7. No.7— [IP3_Byte_3]
Byte 3 of the IP3. Refer to the picture in the remark column of it.
8. No.8— [IP3_Byte_2]
Byte 2 of the IP3. Refer to the picture in the remark column of it.
9. No.9— [Mask_Byte_3]
Byte 3 of the subnet mask. Refer to the picture in the remark column of it.
Byte 2 of the subnet mask. Refer to the picture in the remark column of it.
Byte 1 of the subnet mask. Refer to the picture in the remark column of it.
Byte 0 of the subnet mask. Refer to the picture in the remark column of it.
Logic setting used to select baud rate of rear RS485 port 1 for communication.
Logic setting used to select baud rate of rear RS485 port 2 for communication.
All settings of transformer system parameters are accessible in the following path:
System settings are mainly used for configuring parameters of transformer, such as capacity,
voltage level, ratio of CT, connection mode, etc.
The purpose of Inputting primary voltage level and current ratio of every side of transformer is to
calculate the secondary rated current and to adjust phase angle of secondary current
automatically.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [Active_Grp]
Active setting group. There are four setting groups and can be configured separately according to
different operation mode of transformer.
2 No.2— [Sn]
Capacity of transformer, primary voltage of each side, CT ratio and logic setting of connection
group are used to calculate rated secondary current and correction coefficient of each side of
transformer.
3 No.3— [U1n_S1]
Rated primary voltage of side 1. It should be configured as its actual value (i.e. its tap changer in
normal position).
4 No.4— [U1n_S2]
Rated primary voltage of side 2. It should be configured as its actual value (i.e. its tap changer in
normal position).
5 No.5— [U1n_S3]
Rated primary voltage of side 3. It should be configured as its actual value (i.e. its tap changer in
normal position).
6 No.6— [I1n_CT_S1]
For example, if current ratio of CT is 600/5, it shall be configured as rated primary current 600 A,
rated secondary current 5 A.
7 No.7— [I2n_CT_S1]
For example, if current ratio of CT is 600/5, it shall be configured as rated primary current 600 A,
rated secondary current 5 A.
8 No.8— [I1n_CT_S2]
9 No.9— [I2n_CT_S2]
10 No.10— [I1n_CT_S3]
11 No.11— [I2n_CT_S3]
12 No.12— [I1n_CT1_ROC]
Rated primary current of zero-sequence CT of side 1. It should be configured as its actual value.
13 No.13— [I2n_CT1_ROC]
14 No.14— [I1n_CT2_ROC]
Rated primary current of zero-sequence CT of side 2. It should be configured as its actual value.
15 No.15— [I2n_CT2_ROC]
16 No.16— [I1n_CT3_ROC]
Rated primary current of zero-sequence CT of side 3. It should be configured as its actual value.
17 No.17— [I2n_CT3_ROC]
18 No.18— [Cfg_ConnGrp]
This is the logic setting used to select connection group of transformer for calculation inner the
equipment. There are eight kinds of connection group for selection.
For example, If this logic setting is set as”1”, it means the connection group of transformer is
Y/D/D-11, and if set as “0”, it means the connection group is Y/Y/Y-12. Connection group shows in turn
the connection on side 1/ side 2/ side 3. Connection group of transformer is determined by actual
connections on its three sides.
19 No.19— [Cfg_CT_OvLd]
This is the logic setting used to select zero-sequence CT for overload protection. That means
which side is equipped with overload protection.
“0”: no definition
20 No.20— [En_InstDrop_Trp5]
This is the logic setting used to enable the “Trpoutp 5”relays (i.e. the 5th group of tripping output
relays) to drop off instantly without any delay.
“0”: means “Trpoutp 5”relays drop off with 120ms time delay.
“1”: means “Trpoutp 5”relays drop off instantly without any delay.
21 No.11— [En_CT3_ROC]
This is the logic setting used to select that terminal 123/124 is defined as zero-sequence CT of
side 3 or zero-sequence VT with the differential hardwares of No.1 AI module respectively.
“0”: means terminal 123/124 is defined as zero-sequence VT and No.14 setting is invalid.
All settings of transformer system parameters are accessible in the following path:
This submenu is used to configure protection elements by following list logic settings. Only the
logical setting herein is set as “1”, corresponding function is enabled.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [En_Diff]
2 No.2— [En_PPF_S1]
This is the logic setting used to enable phase-to-phase fault protection of side 1.
3 No.3— [En_PPF_S2]
This is the logic setting used to enable phase-to-phase fault protection of side 2.
4 No.4— [En_PPF_S3]
This is the logic setting used to enable phase-to-phase fault protection of side 3.
5 No.5— [En_EF_S1]
This is the logic setting used to enable earth fault protection of side 1.
6 No.6— [En_EF_S2]
This is the logic setting used to enable earth fault protection of side 2.
7 No.7— [En_EF_S3]
This is the logic setting used to enable earth fault protection of side 3.
8 No.8— [En_EF_Gap]
This is the logic setting used to enable gap earth fault protection.
9 No.9— [En_OvLd]
10 No.10— [En_REF_S1]
This is the logic setting used to enable zero-sequence differential protection of side 1.
11 No.11— [En_REF_S2]
This is the logic setting used to enable zero-sequence differential protection of side 3.
12 No.12— [En_REF_S3]
This is the logic setting used to enable zero-sequence differential protection of side 3.
This protection equipment is applied for protection of differential kinds of transformer, including
main transformer, step-down transformer, and start-up/standby transformer protection. Here three
different setting principles are introduced below, and user can select the setting principle of your
actual application for the reference.
When the equipment is used to protect main transformer, side 1 is called HV side and side 2 and 3
are called branch side. Therefore the configuring principles of side 2 and 3 are similar.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_Pkp_PcntDiff]
This is a pickup setting of percentage current differential protection, which is also the setting of
fault detector of percent differential protection. It should be higher than maximum unbalanced
current of the transformer during normal rated load, i.e.
I cdqd K rel ( K er U m) I e
Where:
I cdqd represents the setting [I_Pkp_PcntDiff].
Ie is secondary calculated rated current of transformer (please see details in section );
Krel is reliability coefficient (generally K rel = 1.3 ~1.5);
Ker is the ratio error of CT (=0.03X2, for class 10P; =0.01X2, for class 5P and class TP);
U is the maximum deviation (in percentage of rated voltage) due to tap change;
m is the error caused by the difference between ratios of CT at all side, 0.05 is recommended.
For practical engineering application, Icdqd =(0.3 ~0.5) I e is reasonable and unbalanced current
2 No.2— [I_InstDiff]
Setting of unrestrained instantaneous differential protection, which is used to clear serious internal
fault quickly and prevent operation delay caused by CT saturation. The setting I cdsd (ie.
[I_InstDiff ]) should be higher than inrush current and maximum unbalanced current due to external
fault or asynchronous closing, generally
I cdsd K I e
Where:
K is a multiple depending on capacity of transformer and the system reactance. 5~ 6 is
recommended for main transformer, 6~8 is recommended for startup/standby transformer and
plant transformer.
I e is secondary calculated rated current of transformer.
calculated according to the phase-to-phase solid short circuit fault in normal operation condition at
3 No.3— [Slope1_PcntDiff]
K bl1 K er
Where:
K er is the error of current ratio of CT, no more than 0.1. K bl 1 is 0.10-0.20 generally.
Where:
I k. max is the periodic component (secondary value) of maximum through fault current of
K ap is the coefficient of aperiodic component. K ap = 1.0 if CT at both sides are class TP, or
I unb .max K ap K cc K er I k .max U h I k.h .max mI I k .I .max mII I k. II .max
Where:
Definition of K er , K cc and K ap have been mentioned above;
U h is the relative error (to rated voltage Un) of HV side due to tap changing, it is
recommended to adopt the maximum value of deviations to the rated value (in
percentage of rated voltage).
I k .max is the periodic component (secondary value) of maximum short current flowing through
CT close to the fault point when external fault occurred at the LV side.
I k.h . max is the periodic component (secondary value) of current flowing through CT of voltage
changeable side when calculating fault current of external fault at LV side.
I k .I . max and I k .II .max are the periodic components of secondary currents flowing through CT at
mI and mII are errors caused by difference between ratios of CT (auxiliary CT included if any)
at relevant sides.
The sensitivity coefficient K sen should be calculated according to phase-to-phase short circuit on
outlet of transformer protected by the differential relay in minimum operation mode. From the
calculated minimum short circuit current I k .min and relevant restraint current I res , corresponding
pickup current I op will be found in the operation characteristic curve of percent differential relay,
K sen I k. min / I op
K sen ≥ 2 is required.
4 No.4— [Slope2_PcntDiff]
Where:
Definition of I unb . max* , I cdqd * and I k .max* are almost same to Iunb .max , I cdqd and
I k. max mentioned above, and the only difference is they are per unit values. I e (secondary
k bl 2 =0.70 is recommended.
5 No.5— [k_2ndH_PcntDiff]
Restraint coefficient of second harmonic. This parameter is the blocking threshold of second
harmonic involving in differential current to against inrush current when the transformer is
energized. The differential protection will be blocked when the percentage of second harmonics
reaches the threshold because the percentage of second harmonics is high in inrush current but
low in fault current. In general, the parameter is set to be 15% ~20% and 15% is recommended.
6 No.6— [I_Alm_Diff]
Setting of differential current abnormality alarm. It should be higher than maximum differential
current due to tap changing of the transformer being not in the middle position or other possible
conditions during operation.
7 No.7— [TrpLog_Diff]
Tripping output logic setting of differential protection. Mentioned below are used to specify which
breaker or breakers will be tripped by the protection. This setting comprises following 13 binary
bits and is displayed by a hexadecimal number of 4 digi ts from 0000H to 1FFFH. The tripping
output logic setting of RCS-985TS is defined below.
Bits Function
0 Protection enabled
1 TrpOutp1
2 TrpOutp2
3 TrpOutp3
4 TrpOutp4
5 TrpOutp5
6 TrpOutp6
7 TrpOutp7
8 TrpOutp8
9 TrpOutp9
10 TrpOutp10
11 TrpOutp11
12 TrpOutp12
13-15 No definition
“TrpOutput 1”means to drive the 1st group of tripping output relays to operate.
Set bit “0”as 1 means this protection element will trip breaker or breakers. The bit corresponding
to the breaker to be tripped shall be set as“1”and other bits shall be “0”. For example, if
differential protection is defined to “Trpoutp 5”(the 5th group of tripping output relays), the “0”bit
and “5”bit shall be set as “1”and other bits “0”. Then a hexadecimal number 0021H is formed as
the tripping output logic setting.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
All the tripping logic settings mentioned below is defined as same as this one.
NOTE Tripping output logic settings have to be set on basis of application -specific
8 No.8— [En_InstDiff]
This is the logic setting used to enable unrestrained instantaneous differential protection.
9 No.9— [En_PcntDiff]
10 No.10— [En_CTSBlkDiff]
This is the logic setting used to select operating characteristic of percent differential protection
“0”: means percent differential protection is not blocked when differential CT circuit failure.
“1”: means percent differential protection is blocked when differential CT circuit failure.
All settings of transformer system parameters are accessible in the following path:
Restricted earth fault protection is also called zero-sequence differential protection. There are
three restricted earth fault protection elements of side 1, side 2 and side 3 and the each element is
independent to another side but with the same protection theory and scheme logic. Here take the
protection of side 1 as an example to give detailed settings explanation.
NOTE: Symbol of the parameters listed in above tables is used for communication,
NOTE: To configure the settings of zero-sequence percent differential protection, you can
follow the method provided in section 7.4.1.1 calculation of percent differential protection,
where U shall be taken as 0. Polarity of each CT for zero-sequence differential
protection at various sides is same as shown in Figure 1.1-1 ~ Figure 1.1-4. Positive
polarity of three-phase CT is at busbar side and that of zero-sequence CT is at neutral
point side.
1 No.1--[I_Pkp_PcntREF_S1]
This is pickup setting of zero-sequence percent differential element of restricted earth fault
protection, which is also the setting of fault detector of that element.
Calculation of this setting is based on rated secondary current of the transformer. If a setting got
from calculation is together with its unit Ampere, this setting shall be divided by rated secondary
current of this side of the CT, to get per unit value. The setting of zero - sequence differential
protection shall be greater than the maximum imbalanced current while transformer operates on
normal rated load, i.e.
Where:
Ker is the ratio errors of CT (for type 10P, Ker = 0.03×2; for class 5P and class TP, Ker =0.01X2);
m is the error caused by the difference between ratios of CT at all sides, 0.05 is recommended.
For practical engineering calculation, I ocdqd =(0.3 - 0.5)I e is reasonable and unbalanced current
Sensitivity of restricted earth fault protection shall be checked with the solid earth fault in its
In solid earthed system, distribution of zero sequence current for single-phase-to-earth fault
depends on the configuration of zero sequence network of power system. Magnitude of the
single-phase-to-earth fault current depends on not only zero sequence impedance of system but
also the positive and negative sequence impedances. That means different operation modes of
power system also have influence on the current. When power system is in maintenance status,
in order to remain the zero sequence impedance of the system network unchanged and increase
sensitivity for earth fault protection, the 220 kV power system is generally compensated by
properly changing earth mode of the transformer. Therefore, sensitivity of zero sequence
differential protection shall be checked in minimum operation mode for 220 kV power system.
2 No.2--[I_InstREF_S1]
3 No.3--[Slope_PcntREF_S1]
4 No.4--[TrpLog_REF_S1]
Tripping output logic setting of restricted earth fault protection which is used to specify which
breaker or breakers will be tripped by the protection.
5 No.5--[En_InstREF_S1]
6 No.6--[En_PcntREF_S1]
Logic setting of enabling zero-sequence percent differential protection element of restricted earth
fault protection.
Settings of restricted earth fault protection of side 1, side 2 and side 3 accessible in the following
path respectively:
Main Menu -> SETTING -> PROT SETTINGS -> S1 REF PROT
Main Menu -> SETTING -> PROT SETTINGS -> S2 REF PROT
Main Menu -> SETTING -> PROT SETTINGS -> S3 REF PROT
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [V_NegOV_VCE_S1]
Setting of negative sequence voltage control element of side 1. Setting and displayed value of
negative sequence voltage are U2.
The setting should be higher than the unbalance voltage during transformer normal operation,
which is derived through practical metering.
Where:
U
K sen k .2. min
U op.2
Where:
U k.2 .min is minimum secondary negative sequence voltage at location of the protection equipment
K sen ≥2.0 is required for near backup protection and K sen ≥1.5 for remote backup protection.
NOTE:When sensitivity coefficient is checked for current element and voltage element,
unfavorable normal system operation condition and unfavorable type of short circuit fault
shall be adopted.
2 No.2— [Vpp_UV_VCE_S1]
i) When Voltage for undervoltage relay is taken from LV side (Logic setting [En_S2.VCE_OC_S1]
or [En_S3.VCE_OC_S1] is set as “1”), undervoltage setting should be higher than the lowest
voltage during starting process of largest motor connected with the LV busbar.
Umin
U op
Krel
Kr
Where:
U min is the possible lowest phase-to-phase voltage during transformer normal operation and
0.9Un (Un is rated secondary phase-to-phase voltage) is recommended.
ii) When voltage for undervoltage relay is taken from local side busbar (Logic setting
[En_S1.VCE_OC_S1] is set as “1”), following criterion is needed to be satisfied.
U op 0.7U n
iii)When voltage for undervoltage relay is taken from VT of generator (Logic setting
[En_S2.VCE_OC_S1] or [En_S3.VCE_OC_S1] is set as “1”), the setting should be higher than
the possible lowest voltage during generator operating in loss excitation condition.
U op (0.5 0.6)U n
(2)Sensitivity check
U
K sen op
U c. max
Where:
U c max is the maximum secondary residual voltage at the location of the protection equipment,
when a phase-to-phase metallic short circuit fault occurs where sensitivey coefficient is checked.
K sen ≥1.5 is required for local backup protection and K sen ≥1.2 for remote backup protection.
NOTE:When sensitivity coefficient is checked for current element and voltage element,
unfavorable normal system operation condition and unfavorable type of short circuit fault
shall be adopted. If sensitivity coefficient of undervoltage element is not high enough,
function of composite voltage on LV side initiation can be enabled.
3 No.3— [I_OC1_S1]
When the sensitivity of overcurrent protection is not high enough, voltage controlled overcurrent
protection is needed to adopt to improve the sensitivity. Inputs of voltage control element are
usually from voltage transformer of low voltage side of transformer.
K
I op rel I e
Kr
Where:
I ( 2)
K sen k . min
I op
Where:
( 2)
I k .min is minimal fault current through location of the protection equipment during phase-to-phase
metallic short circuit on end of backup protected section.
K sen ≥ 1.3 is required for near backup protection and K sen ≥ 1.2 for remote backup protection.
NOTE :When sensitivity coefficient is checked for current element and voltage element,
unfavorable normal system operation condition and unfavorable type of short circuit fault
shall be adopted.
4 No.4— [t_OC1_S1]
5 No.5— [I_OC2_S1]
Setting of stage 2 of overcurrent protection of side 1. The configuring principle of the setting of
stage 2 is same to that of stage 1.
6 No.6— [t_OC2_S1]
7 No.7— [I_OC3_S1]
Setting of stage 3 of overcurrent protection of side 1. The configuring principle of the setting of
stage 2 is same to that of stage 1.
8 No.8— [t_OC3_S1]
9 No.9— [TrpLog_OC1_S1]
Tripping output logic setting of stage 1 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
10 No.10— [TrpLog_OC2_S1]
Tripping output logic setting of stage 2 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
11 No.11— [TrpLog_OC3_S1]
Tripping output logic setting of stage 3 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
12 No.12— [En_VCE_OC1_S1]
This is the logic setting used to enable stage 1 of overcurrent protection of side 1 is controlled by
voltage control element of local or other side.
13 No.13— [En_VCE_OC2_S1]
This is the logic setting used to enable stage 2 of overcurrent protection of side 1 is controlled by
voltage control element of local or other side.
14 No.14— [En_S1.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of local side.
15 No.15— [En_S2.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of side 2.
16 No.16— [En_S3.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of side 3.
(1) No.12 and NO.13 settings are configured first to decide whether OC protection is
controlled by voltage control element. No.12-No.13 settings are multioption, which means
any stage of OC protection can be controlled by voltage control elelment.
(2) If No.12 or No 13 is set as “1”, then No.14-No.16 settings are needed to be configured
to decide which side voltage control element OC is controlled by. No.14 -No.16 settings
are multioption, which means voltage control element of any side can controls OC
protection.
17 No.17— [Opt_VTS_OC_S1]
This is the logic setting used to select operating performance of OC protection of side 1 during VT
circuit failure.
“1”: when VT circuit failure on side 1 is detected, voltage control element of the side can not pick
up.
“0”: when VT circuit failure on side 1 is detected, voltage control element will pick up and the
voltage-controlled overcurrent element will become a pure overcurrent relay.
18 No.18— [En_Mem_Curr]
The setting is set as 1 when protection equipment is used to protect self-excitation generator.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: Same symbol except postfix in this section has similar meaning to that appears in
section 7.4.1.2 and the configuring principle is also similar, so please refer to that section
for the details.
NOTE: The settings of phase-to-phase fault protection of side 2 and those of side 3 are
1 No.1— [V_NegOV_VCE_S2]
Setting of negative sequence voltage control element of side 2. Setting and displayed value of
negative sequence voltage are U2.
2 No.2— [Vpp_UV_VCE_S2]
3 No.3— [I_OC1_S2]
4 No.4— [t_OC1_S2]
5 No.5— [I_OC2_S2]
6 No.6— [t_OC2_S2]
7 No.7— [TrpLog_OC1_S2]
Tripping output logic setting of stage 1 of overcurrent protection of side2. Refer to section 7.4.1.1.2
for more information about it.
8 No.8— [TrpLog_OC2_S2]
Tripping output logic setting of stage 2 of overcurrent protection of side 2. Refer to section
7.4.1.1.2 for more information about it.
9 No.9— [En_VCE_OC1_S2]
This is the logic setting used to enable stage 1 of overcurrent protection of side 2 is controlled by
voltage control element of local or other side.
10 No.10— [En_VCE_OC2_S2]
This is the logic setting used to enable stage 2 of overcurrent protection of side 2 is controlled by
voltage control element of local or other side.
11 No.11— [En_OC2_SOTF_S2]
This is the logic setting used to enable accelerating trip function of state 2 of OC protection of side
2 when switching one to fault.
12 No.12— [Opt_VTS_OC_S2]
This is the logic setting used to select operating performance of OC protection of side 2during VT
circuit failure.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_ROC1_S1]
(1) The setting shall be coordinated with unrestrained instantaneous differential protection or
stage1 or 2 of residual overcurrent protection of adjacent power line.
Where:
K brI is branch coefficient of zero sequence current which is equal to ratio of zero sequence
current passing through this protection equipment and passing through the faulty line during
ground fault at the end of protected section of stage 1 of residual over current protection of the
power line. Maximum value among various operation conditions being taken;
3I
K sen k .o .min
I op .o
Where:
3 I k .o. min is minimal secondary zero sequence current passing through location of the protection
2 No.2— [t_ROC1_S1]
3 No.3— [I_ROC2_S1]
(1) The setting shall coordinate with backup stage of residual overcurrent protection of adjacent
power line.
Where:
K brII is branch coefficient of zero sequence current which is ratio of zero sequence current
passing through this protection equipment and passing through the faulty line during ground fault
at end of protected section of backup zone of residual overcurrent protection of the power line.
Maximum value for various operation conditions being taken.
I op .o .1II is setting of backup zone of coordinating residual overcurrent protection of the power line
(secondary current).
(2) Sensitivity check: criterion is same to that of stage 2 of zero sequence overcurrent protection.
4 No.4— [t_ROC2_S1]
5 No.5— [TrpLog_ROC1_S1]
Tripping output logic setting of stage 1 of zero sequence overcurrent protection of side 1. Refer to
section 7.4.1.1.2 for more information about it.
6 No.6— [TrpLog_ROC2_S1]
Tripping output logic setting of stage 2 of zero sequence overcurrent protection of side 1. Refer to
section 7.4.1.1.2 for more information about it.
7 No.7— [Opt_3I0_ROC_S1]
This is the logic setting used to select where zero sequence current is derived.
“0”means zero sequence current is derived from zero-sequence CT installed at neutral point.
8 No.8— [En_Dir_ROC1_S1]
This is the logic setting used to select whether stage 1 of zero sequence overcurrent of side 1
controlled by zero-sequence direction element.
9 No.9— [En_Dir_ROC2_S1]
This is the logic setting used to select whether stage 2 of zero sequence overcurrent of side 1
controlled by zero-sequence direction element.
10 No.10— [Opt_VTS_ROC_S1]
This is the logic setting used to select operating performance of zero sequence overcurrent
protection of side 1 during VT circuit failure.
“1”: when VT circuit failure on side 1 is detected, zero-sequence voltage element of the side can
not pick up.
“0”: when VT circuit failure on side 1 is detected, the element will pick up and the
voltage-controlled zero-sequence overcurrent element will become a pure zero-sequence
overcurrent relay.
11 No.11— [Opt_Dir_ROC_S1]
Logic setting [Opt_Dir_ROC_S1] is used to select the direction of every stage of zero sequence
overcurrent protection. If this logic setting is set as “1”, the direction is transformer and reach angle
is 225º. If this logic setting is set as “0”, the direction is power system and reach angle is 75º..
This is the logic setting used to select the direction of zero-sequence overcurrent protection.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: LV side (i.e. side 2 and side 3) winding of main transformer are delta connected, so
the settings of earth fault protection of side 2 and side 3 are not needed to be
configured.
NOTE: The settings of earth fault protection of side 2 and those of side 3 are similar, so
only setting descriptions of the settings of side 2 are given below as an example.
1 No.1— [I_ROC1_S2]
2 No.2— [t_ROC1_S2]
3 No.3— [I_ROC2_S2]
4 No.4— [t_ROC2_S2]
5 No.5— [TrpLog_ROC1_S2]
Tripping output logic setting of stage 1 of zero sequence overcurrent protection of side 2 Refer to
section 7.4.1.1.2 for more information about it.
6 No.6— [TrpLog_ROC2_S2]
Tripping output logic setting of stage 2 of zero sequence overcurrent protection of side 2. Refer to
section 7.4.1.1.2 for more information about it.
All settings of transformer system parameters are accessible in the following path:
This submenu is used for configuration of gap earth fault protection for transformer which neutral
point is not earthed or earthed through air gap.
For transformer whose neutral point is grounded through gap, residual voltage protection and
residual overcurrent protection reflecting zero sequence voltage and discharge current through
gap shall be equipped.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_ROC1_Gap]
Setting of residual overcurrent protection in gap circuit depends on zero sequence impedance of
transformer and arc resistance of discharge through the gap, etc. Primary current setting can be
taken as 100 A generally.
2 No.2— [t_ROC11_Gap]
3 No.3— [t_ROC12_Gap]
4 No.4— [V_ROV1_Gap]
5 No.5— [t_ROV11_Gap]
6 No.6— [t_ROV12_Gap]
7 No.7— [V_Alm_ROV]
8 No.8— [V_Alm_ROV]
9 No.9— [TrpLog_ROC11_Gap]
Tripping output logic setting of delay 1 of stage 1 of gap zero sequence overcurrent protection.
Please refer to section 7.4.1.1.2 for more information about it.
10 No.10— [TrpLog_ROC12_Gap]
Tripping output logic setting of delay 2 of stage 1 of gap zero sequence overcurrent protection.
Please refer to section 7.4.1.1.2 for more information about it.
11 No.11— [TrpLog_ROV11_Gap]
Tripping output logic setting of delay 1 of stage 1 of gap zero sequence overvoltge protection.
Please refer to section 7.4.1.1.2 for more information about it.
12 No.12— [TrpLog_ROV12_Gap]
Tripping output logic setting of delay 2 of stage 1 of gap zero sequence overvoltge protection.
Please refer to section 7.4.1.1.2 for more information about it.
13 No.13— [En_Alm_ROV]
All settings of transformer system parameters are accessible in the following path:
This submenu is used for configuration the parameters for overload protection. Parameter cell
[En_OvLd] should be set as “1”to enable overload protection.
In addition, first of all, zero-sequence CT should be selected for overload protection. Please refer
to setting [Cfg_CT_OvLd] in section 7.2.2
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_Alm_OvLd]
Current setting for overload alarm. When actual secondary current is larger than this setting value
and the predefined time delay has elapsed, alarm information of overload will be issued.
2 No.2— [t_Alm_OvLd]
3 No.3— [I_InitCool_OvLd]
Current setting for initiating air cooling mechanism when the transformer is overloaded.
4 No.4— [t_InitCool_OvLd]
Time delay of initiating air cooling mechanism when the transformer is overloaded.
5 No.5— [I_Blk_OLTC_OvLd]
Current setting for blocking on-load tap changing when the transformer is overloaded.
6 No.6— [t_Blk_OLTC_OvLd]
Time delay of blocking on-load tap changing when the transformer is over overloaded load.
7 No.7— [I_CCE]
Current setting for current control element. If the actual current is larger than the current setting,
equipment will output binary output contacts and tripping output contacts to trip other circuit
breakers depending on setting No.8.
8 No.8— [TrpLog_CCE]
Tripping output logic setting of current control element. Refer to section 7.4.1.1.2 for more
information about it.
9 No.9— [En_Alm_OvLd]
10 No.10— [En_InitCool_OvLd]
This is the logic setting used to enable air cooling mechanism initiation function when the
transformer is overloaded.
11 No.11— [En_Blk_OLTC_OvLd]
This is the logic setting used to enable blocking on-load tap changing function when the
transformer is overloaded.
12 No.12— [En_BO_CCE]
This is the logic setting used to enable equipment to output contacts when current control element
picks up.
All settings of transformer system parameters are accessible in the following path:
When the equipment is used to protect start-up/standby transformer, side 1 is called HV side and
side 2 and 3 are called branch side. Therefore the configuring principles of side 2 and 3 are
similar.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_Pkp_PcntDiff]
This is a pickup setting of percentage current differential protection, which is also the setting of
fault detector of percent differential protection. It should be higher than maximum unbalanced
current of the transformer during normal rated load, i.e.
I cdqd K rel ( K er U m) I e
Where:
I cdqd represents the setting [I_Pkp_PcntDiff ].
Ie is secondary calculated rated current of transformer (please see details in section );
Krel is reliability coefficient (generally K rel = 1.3 ~1.5);
Ker is the ratio error of CT (=0.03X2, for class 10P; =0.01X2, for class 5P and class TP);
U is the maximum deviation (in percentage of rated voltage) due to tap changing;
m is the error caused by the difference between ratios of CT at all side, 0.05 is recommended.
For practical engineering application, Icdqd =(0.3 ~0.5) I e is reasonable and unbalanced current
2 No.2— [I_InstDiff]
Setting of unrestrained instantaneous differential protection, which is used to clear serious internal
fault quickly and prevent operation delay caused by CT saturation. The setting I cdsd (ie.
[I_InstDiff ]) should be higher than inrush current and maximum unbalanced current due to external
fault or asynchronous closing, generally
I cdsd K I e
Where:
K is a multiple depending on capacity of transformer and the system reactance. 5~ 6 is
recommended for main transformer, 6~8 is recommended for startup/standby transformer and
plant transformer.
I e is secondary calculated rated current of transformer.
calculated according to the phase-to-phase solid short circuit fault in normal operation condition at
3 No.3— [Slope1_PcntDiff]
K er is the error of current ratio of CT, no more than 0.1. K bl 1 is 0.10-0.20 generally.
Where:
I k. max is the periodic component (secondary value) of maximum through fault current of
K ap is the coefficient of aperiodic component. K ap = 1.0 if CT at both sides are class TP, or
I unb .max K ap K cc K er I k .max U h I k.h .max mI I k .I .max mII I k. II .max
Where:
Definition of K er , K cc and K ap have been mentioned above;
U h is the relative error (to rated voltage Un) of HV side due to tap changing, it is
recommended to adopt the maximum value of deviations to the rated value (in
percentage of rated voltage).
I k .max is the periodic component (secondary value) of maximum short current flowing through
CT close to the fault point when external fault occurred at the LV side.
I k.h . max is the periodic component (secondary value) of current flowing through CT of voltage
changeable side when calculating fault current of external fault at LV side.
I k .I . max and I k .II .max are the periodic components of secondary currents flowing through CT at
mI and mII are errors caused by difference between ratios of CT (auxiliary CT included if any)
at relevant sides.
The sensitivity coefficient K sen should be calculated according to phase-to-phase short circuit on
outlet of transformer protected by the differential relay in minimum operation mode. From the
calculated minimum short circuit current I k .min and relevant restraint current I res , corresponding
pickup current I op will be found in the operation characteristic curve of percent differential relay,
K sen I k. min / I op
K sen ≥ 2 is required.
4 No.4— [Slope2_PcntDiff]
Where:
Definition of I unb . max* , I cdqd * and I k .max* are almost same to Iunb .max , I cdqd and
I k. max mentioned above, and the only difference is they are per unit values. I e (secondary
k bl 2 =0.70 is recommended.
5 No.5— [k_2ndH_PcntDiff]
Restraint coefficient of second harmonic. This parameter is the blocking threshold of second
harmonic involving in differential current to against inrush current when the transformer is
energized. The differential protection will be blocked when the percentage of second harmonics
reaches the threshold because the percentage of second harmonics is high in inrush current but
low in fault current. In general, the parameter is set to be 15% ~20% and 15% is recommended.
6 No.6— [I_Alm_Diff]
Setting of differential current abnormality alarm. It should be higher than maximum differential
current due to tap changing of the transformer being not in the middle position or other possible
conditions during operation.
7 No.7— [TrpLog_Diff]
Tripping output logic setting of differential protection. Mentioned below are used to specify which
breaker or breakers will be tripped by the protection. This setting comprises following 16 binary
bits and is displayed by a hexadecimal number of 4 digits from 0000H to 0FFFH.
The tripping output logic setting of RCS-985TS is defined below.
Bits Function
0 Protection enabled
1 TrpOutp1
2 TrpOutp2
3 TrpOutp3
4 TrpOutp4
5 TrpOutp5
6 TrpOutp6
7 TrpOutp7
8 TrpOutp8
9 TrpOutp9
10 TrpOutp10
11 TrpOutp11
12 TrpOutp12
13-15 No definition
“TrpOutput 1”means to drive the 1st group of tripping output relays to operate.
Set bit “0”as 1 means this protection element will trip breaker or breakers. The bit corresponding
to the breaker to be tripped shall be set as“1”and other bits shall be “0”. For example, if
differential protection is defined to “Trpoutp 5”(the 5th group of tripping output relays), the “0”bit
and “5”bit shall be set as “1”and other bits “0”. Then a hexadecimal number 0021H is formed as
the tripping output logic setting.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
All the tripping logic settings mentioned below is defined as same as this one.
NOTE Tripping output logic settings have to be set on basis of application -specific
8 No.8— [En_InstDiff]
This it the logic setting used to enable unrestrained instantaneous differential protection.
9 No.9— [En_PcntDiff]
10 No.10— [En_CTSBlkDiff]
Logic setting used to select operating characteristic of percent differential protection when
differential CT circuit failure.
“0”: means percent differential protection is not blocked when differential CT circuit failure.
“1”: means percent differential protection is blocked when differential CT circuit failure.
All settings of transformer system parameters are accessible in the following path:
Restricted earth fault protection is also called zero-sequence differential protection. There are
three restricted earth fault protection elements of side 1, side 2 and side 3 and the each element is
independent to another side but with the same protection theory and scheme logic. Here take the
protection of side 1 as an example to give detailed settings explanation.
NOTE: Symbol of the parameters listed in above tables is used for communication,
NOTE: To configure the settings of zero-sequence percent differential protection, you can
follow the method provided in section 7.4.2.1 calculation of percent differential protection,
where U shall be taken as 0. Polarity of each CT for zero-sequence differential
protection at various sides is same as shown in Figure 1.1-1 ~ Figure 1.1-4. Positive
polarity of three-phase CT is at busbar side and that of zero-sequence CT is at neutral
point side.
1 No.1--[I_Pkp_PcntREF_S1]
This is pickup setting of zero-sequence percent differential element of restricted earth fault
protection, which is also the setting of fault detector of that element.
Calculation of this setting is based on rated secondary current of the transformer. If a setting got
from calculation is together with its unit Ampere, this setting shall be divided by rated secondary
current of this side of the CT, to get per unit value. The setting of zero - sequence differential
protection shall be greater than the maximum imbalanced current while transformer operates on
normal rated load, i.e.
Where:
Ker is the ratio errors of CT (for type 10P, Ker = 0.03×2; for class 5P and class TP, Ker =0.01X2);
m is the error caused by the difference between ratios of CT at all sides, 0.05 is recommended.
For practical engineering calculation, I ocdqd =(0.3 - 0.5)I e is reasonable and unbalanced current
Sensitivity of restricted earth fault protection shall be checked with the solid earth fault in its
In solid earthed system, distribution of zero sequence current for single-phase-to-earth fault
depends on the configuration of zero sequence network of power system. Magnitude of the
single-phase-to-earth fault current depends on not only zero sequence impedance of system but
also the positive and negative sequence impedances. That means different operation modes of
power system also have influence on the current. When power system is in maintenance status,
in order to remain the zero sequence impedance of the system network unchanged and increase
sensitivity for earth fault protection, the 220 kV power system is generally compensated by
properly changing earth mode of the transformer. Therefore, sensitivity of zero sequence
differential protection shall be checked in minimum operation mode for 220 kV power system.
2 No.2--[I_InstREF_S1]
3 No.3--[Slope_PcntREF_S1]
4 No.4--[TrpLog_REF_S1]
Tripping output logic setting of restricted earth fault protection which is used to specify which
breaker or breakers will be tripped by the protection.
5 No.5--[En_InstREF_S1]
6 No.6--[En_PcntREF_S1]
Logic setting of enabling zero-sequence percent differential protection element of restricted earth
fault protection.
Settings of restricted earth fault protection of side 1, side 2 and side 3 accessible in the following
path respectively:
Main Menu -> SETTING -> PROT SETTINGS -> S1 REF PROT
Main Menu -> SETTING -> PROT SETTINGS -> S2 REF PROT
Main Menu -> SETTING -> PROT SETTINGS -> S3 REF PROT
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [V_NegOV_VCE_S1]
Setting of negative sequence voltage control element of side 1. Setting and displayed value of
negative sequence voltage are U2.
(1) Configuring principle – voltage control element
Negative sequence voltage is taken from LV side usually. The operating negative sequence
voltage shall be higher than maximal unbalance voltage. Generally, U 2.op (0.06 0.08)U N is
U2
U2
Ksen 1.5
nTV U 2OP
Where:
transformer, when two-phase short circuit fault occurs on the end of line.
2 No.2— [Vpp_UV_VCE_S1]
U op (0.55 0.6)U n .
UOP
U
Ksen 1.5
nTV U1
Where:
3 No.3— [I_OC1_S1]
I K(3).max
IOPI Krel
nTA
1 S
K .max
I (3) B
X max X T 3U B
Where:
I k(3.max
)
is the maximum secondary current passing through HV side when three phase fault occurs
X max is per unit value of system reactance, which base value is S B , when HV side of the
4 No.4— [t_OC1_S1]
5 No.5— [I_OC2_S1]
K I
IOPII rel N
Kr nTA
Where:
U LN 1
I opII K CO ( I opII ( L ) nTAL I10 a )
U HN nTA
Where:
I opII (L) is the secondary operating current of stage 2 of overcurrent protection of LV side branch of
nTAL is the current ratio of CT used by overcurrent protection of the LV side branch;
Generally, when voltage control element for stage 2 of overcurrent protection is enabled, the first
configuring principle is adopted. However, if secondary principle is adopted, voltage control
element for stage 2 is selectable.
(3) Sensitivity check – voltage controlled overcurrent protection
I K (2)
Ksen I 1.3
nTA IOPII
Where:
I K (2) is short -circuit current flowing through HV side of the transformer when two-phase short
6 No.6— [t_OC2_S1]
The setting shall coordinate with stage 2 of overcurrent protection of LV side branch of the
startup/standby transformer. It can be taken as t 2 t 2' t t usually, where t 2' is delay of
stage 2 of LV side branch, t is the step difference. Since this delay is longer than oscillation
period, so even if stage 2 of overcurrent element operates due to HV side voltage drop during
system oscillation, stage 2 of overcurrent protection will not operate incorrectly.
7 No.7— [I_OC3_S1]
8 No.8— [t_OC3_S1]
9 No.9— [TrpLog_OC1_S1]
Tripping output logic setting of stage 1 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
10 No.10— [TrpLog_OC2_S1]
Tripping output logic setting of stage 2 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
11 No.11— [TrpLog_OC3_S1]
Tripping output logic setting of stage 3 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
12 No.12— [En_VCE_OC1_S1]
This is the logic setting used to enable stage 1 of overcurrent protection of side 1 is controlled by
voltage control element of local or other side.
13 No.13— [En_VCE_OC2_S1]
This is the logic setting used to enable stage 2 of overcurrent protection of side 1 is controlled by
voltage control element of local or other side.
14 No.14— [En_S1.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of local side.
15 No.15— [En_S2.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of side 2.
16 No.16— [En_S3.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of side 3.
(1) No.12 and NO.13 settings are configured first to decide whether OC protection is
controlled by voltage control element. No.12-No.13 settings are multioption, which means
any stage of OC protection can be controlled by voltage control elelment.
(2) If No.12 or No 13 is set as “1”, then No.14-No.16 settings are needed to be configured
to decide which side voltage control element OC is controlled by. No.14 -No.16 settings
are multioption, which means voltage control element of any side can controls OC
protection.
17 No.17— [Opt_VTS_OC_S1]
This is the logic setting used to select operating performance of OC protection of side 1 during VT
circuit failure.
“1”: when VT circuit failure on side 1 is detected, voltage control element of the side can not pick
up.
“0”: when VT circuit failure on side 1 is detected, voltage control element will pick up and the
voltage-controlled overcurrent element will become a pure overcurrent relay.
18 No.18— [En_Mem_Curr]
The setting is set as 1 when protection equipment is used to protect self-excitation generator.
All settings of transformer system parameters are accessible in the following path:
7 TrpLog_OC1_S2 0000-1FFF
8 TrpLog_OC2_S2 0000-1FFF 1: enable ; 0: disable
9 En_VCE_OC1_S2 0/1 1 1: enable ; 0: disable
10 En_VCE_OC2_S2 0/1 1 1: enable ; 0: disable
11 En_OC2_SOTF_S2 0/1 1 1: enable ; 0: disable
12 Opt_VTS_OC_S2 0/1 1
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: Same symbol except postfix in this section has similar meaning to that appears in
section 7.4.2.2, so please refer to that section for details. However configuring principle is
different.
NOTE: The settings of phase-to-phase fault protection of side 2 and those of side 3 are
1 No.1— [V_NegOV_VCE_S2]
Setting of negative sequence voltage control element of side 2. Setting and displayed value of
negative sequence voltage are U2.
2 No.2— [Vpp_UV_VCE_S2]
Calculation of setting of low-voltage voltage relay is the same as that of phase-to-phase fault
protection of side 1, so please refer to section 7.4.2.3.2 for details.
3 No.3— [I_OC1_S2]
(1) The setting of stage 1 shall coordinate with insensitive of instantaneous overcurrent protection
of largest motor connected with HV power plant busbar:
PN 1
I opI ( L ) K co K rel K st
3U N cos n TA
Where:
PN is the power of the largest motor (pump for water supply) connected with the HV power plant
busbar,
cos is the power coefficient of the motor and 0.75 is recommended generally;
(2)
I
Ksen K 1.3
nTA IOPI ( L )
Where:
I (K2 ) is short circuit current of overcurrent protection when two-phase short circuit fault occurs on
HV power plant busbar in minimum mode of operation of start-up/standby transformer.
4 No.4— [t_OC1_S2]
The delay shall coordinate with delay of instantaneous overcurrent protection on outlet of HV
power plant busbar.
5 No.5— [I_OC2_S2]
K I
I opII rel N
K r nTA
Where:
Both stage1 and 2 can be controlled by voltage control element by configuring corresponding
logic settings, and it is recommended that stage 2 is controlled by voltage control element.
6 No.6— [t_OC2_S2]
The delay shall coordinate with delay of outlet of HV power plant busbar.
7 No.7— [TrpLog_OC1_S2]
Tripping output logic setting of stage 1 of overcurrent protection of side2. Refer to section 7.4.1.1.2
8 No.8— [TrpLog_OC2_S2]
Tripping output logic setting of stage 2 of overcurrent protection of side 2. Refer to section
7.4.1.1.2 for more information about it.
9 No.9— [En_VCE_OC1_S2]
This is the logic setting used to enable stage 1 of overcurrent protection of side 2 is controlled by
voltage control element of local or other side.
10 No.10— [En_VCE_OC2_S2]
This is the logic setting used to enable stage 2 of overcurrent protection of side 2 is controlled by
voltage control element of local or other side.
11 No.11— [En_OC2_SOTF_S2]
This is the logic setting used to enable accelerating trip function of state 2 of OC protection of side
2 when switching one to fault.
12 No.12— [Opt_VTS_OC_S2]
This is the logic setting used to select operating performance of OC protection of side 2during VT
circuit failure.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_ROC1_S1]
There are two kinds of protection configuring schemes for zero-sequence overcurrent protection.
One is two-stage zero-sequence overcurrent protection without direction element and each stage
is equipped with two delays. The other is stage 1 of zero-sequence overcurrent protection is
equipped with direction element, but stage 2 is not. The difference between the following two
schemes is that in first scheme stage 1 can be used as backup protection for internal and external
earth fault of start-up/standby; in second scheme stage 1 only used as backup protection for
internal earth fault with short delay. However, configuring principles of stage 2 in above two
schemes are same.
The setting of stage 1 shall coordinate with cooperating stage (stage 1 or 2) of zero-sequence
overcurrent protection for HV side outlet:
3I0 OP
3 I0 OPI Kco Co
nTA
Where:
(3I 0 )op is maximum zero-sequence operating current (primary value) of cooperating stage of
C0 is distribution coefficient of zero sequence current which is ratio of zero sequence current
flowing through the protection equipment to that flowing through line and maximum value in
different operation modes is recommended;
(3I 0 ) min 1
(3I 0 )OPI K rel
C 0 nTA
Where:
(3I o ) min is the minimum operating current of backup stage of zero-sequence overcurrent
C0 is the distribution coefficient of zero sequence current which is equal to maximal ratio of
residual current of remote end to that of near end when ground fault occurs on HV side outlet of
the startup/standby transformer;
3I
K sen k .o .min
I op .o
Where:
3 I k .o. min is minimal secondary zero sequence current passing through location of the protection
2 No.2— [t_ROC1_S1]
The delay of stage 1 shall coordinate with delay of cooperating stage (stage 1 or 2) of
zero-sequence overcurrent protection for outline of HV side.
The delay of stage 1 shall coordinate with the longest delay of backup stage of zero-sequence
overcurrent protection for outline of HV side.
When ground fault occurs on near end of HV side outlet of startup/standby transformer, it is
protected by zero-sequence overcurrent protection stage 2 of remote end, so its delay is
t t II t
Where: t II is delay of residual protection stage 2 of remote end, and t is the step difference of
delay.
3 No.3— [I_ROC2_S1]
(1)Configuring principle
The setting shall coordinate with operating current of residual current protection of HV side outlet
for remote end ground fault:
(3I 0 ) op
(3I 0 )OPII K c 0 C0'
nTA
Where:
(3I o )OP is the primary operating current of backup stage of zero sequence overcurrent protection
'
C0 is the distribution coefficient of zero sequence current which is equal to the ratio of residual
current passing through the protection equipment to that passing through the power line when fault
occurs on the end of protective zone of backup stage of residual overcurrent protection of line, and
maximum value in different operation modes is recommended.
(2) Sensitivity check: criterion is same to that of stage 2 of zero sequence overcurrent protection.
4 No.4— [t_ROC2_S1]
Delay of stage 2 shall coordinate with the longest delay of backup stage of residual overcurrent
protection of HV side outlet.
5 No.5— [TrpLog_ROC1_S1]
Tripping output logic setting of stage 1 of zero sequence overcurrent protection of side 1. Refer to
section 7.4.1.1.2 for more information about it.
6 No.6— [TrpLog_ROC2_S1]
Tripping output logic setting of stage 2 of zero sequence overcurrent protection of side 1. Refer to
section 7.4.1.1.2 for more information about it.
7 No.7— [Opt_3I0_ROC_S1]
This is the logic setting used to select where zero sequence current is derived.
“0”means zero sequence current is derived from zero-sequence CT installed at neutral point.
8 No.8— [En_Dir_ROC1_S1]
This is the logic setting used to select whether stage 1 of zero sequence overcurrent of side 1
controlled by zero-sequence direction element.
9 No.9— [En_Dir_ROC2_S1]
This is the logic setting used to select whether stage 2 of zero sequence overcurrent of side 1
controlled by zero-sequence direction element.
10 No.10— [Opt_VTS_ROC_S1]
This is the logic setting used to select operating performance of zero sequence overcurrent
protection of side 1 during VT circuit failure.
“1”: when VT circuit failure on side 1 is detected, zero-sequence voltage element of the side can
not pick up.
“0”: when VT circuit failure on side 1 is detected, the element will pick up and the
voltage-controlled zero-sequence overcurrent element will become a pure zero-sequence
overcurrent relay.
11 No.11— [Opt_Dir_ROC_S1]
Logic setting [Opt_Dir_ROC_S1] is used to select the direction of every stage of zero sequence
overcurrent protection. If this logic setting is set as “1”, the direction is transformer and reach angle
is 225º. If this logic setting is set as “0”, the direction is power system and reach angle is 75º..
This is the logic setting used to select the direction of zero-sequence overcurrent protection.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: The settings of earth fault protection of side 2 and those of side 3 are similar, so
only setting descriptions of the settings of side 2 are given below as an example.
1 No.1— [I_ROC1_S2]
Setting of stage 1 of zero sequence overcurrent protection of side 2. Please note side 2 and 3 are
called branches of start-up/standby transformer.
Two stages with one delay are usually provided for residual overcurrent protection of branch of
startup/standby transformer. Stage 1 will operate to trip circuit breaker of the branch and stage 2
will operate to trip both circuit breakers of HV and LV sides.
(3 I )
(3I 0 )OPI K c(0n 1) 0 set
nTA 0
(3I o ) set is the primary operating current of maximum level of zero sequence overcurrent
3I
K sen k .o .min
I op .o
Where:
3 I k .o. min is minimal secondary zero sequence current passing through location of the protection
2 No.2— [t_ROC1_S2]
3 No.3— [I_ROC2_S2]
Where:
(2) Sensitivity check: criterion is same to that of stage 2 of zero sequence overcurrent protection.
4 No.4— [t_ROC2_S2]
The delay shall coordinate with stage 1 of residual overcurrent protection of side 2.
5 No.5— [TrpLog_ROC1_S2]
Tripping output logic setting of stage 1 of zero sequence overcurrent protection of side 2 Refer to
section 7.4.1.1.2 for more information about it.
6 No.6— [TrpLog_ROC2_S2]
Tripping output logic setting of stage 2 of zero sequence overcurrent protection of side 2. Refer to
section 7.4.1.1.2 for more information about it.
All settings of transformer system parameters are accessible in the following path:
This submenu is used for configuration of gap earth fault protection for transformer which neutral
point is not earthed or earthed through air gap.
During transformer operation, transformer neutral point probably is earthed or not earthed
according to dispatching center requirement. When neutral point probably is earthed through air
gap or not earthed, gap earth fault protection including zero-sequence overvoltage and gap
zero-sequence overcurrent protections should be enabled.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_ROC1_Gap]
100
I OP (A)
nTA
Where:
nTA is ratio of zero-sequence current transformer used for gap zero-sequence overcurrent
protection, which is installed in series between air gap and earth.
2 No.2— [t_ROC11_Gap]
The delay should longer than the duration of transient process and 0.3-0.5 s is recommended.
3 No.3— [t_ROC12_Gap]
4 No.4— [V_ROV1_Gap]
The setting is of gap zero-sequence overvoltage protection, which is derived from open-delta side
of voltage transformer.
Where:
(3U0 ) max is maximum residual voltage of open-delta side of voltage transformer for residual
overvoltage protection when fault occurs on the HV side busbar in part earthed power system.
(3U0 )w is open-delta voltage when voltage of transformer neutral point is equal to U w withstand
3 U K [0]
(3U0 )max
2 nTA 0
3U
(3U0 )w Krel w
1.8nTA 0
nTA0 is ratio of primary phase voltage of voltage transformer to one third of open-delta voltage.
Considering U K [0] is equal to primary rated voltage of VT approximately, above equation can be
changed to:
3
(3U0 ) max 100
2
Operating equation is changed to:
3 3U
100 (3U0 ) OP 0.5 w
2 nTA0
Where:
If part earthed system is changed to unearthed system, residual overvoltage protection must
operate when single-phase earth fault occurs. At this time , (3U 0 ) max 300 V is derived
220
Ksen 1.29
170
5 No.5— [t_ROV11_Gap]
6 No.6— [t_ROV12_Gap]
7 No.7— [V_Alm_ROV]
8 No.8— [V_Alm_ROV]
9 No.7— [TrpLog_ROC11_Gap]
Tripping output logic setting of delay 1 of stage 1 of gap zero sequence overcurrent protection.
Please refer to section 7.4.1.1.2 for more information about it.
10 No.8— [TrpLog_ROC12_Gap]
Tripping output logic setting of delay 2 of stage 1 of gap zero sequence overcurrent protection.
Please refer to section 7.4.1.1.2 for more information about it.
11 No.9— [TrpLog_ROV11_Gap]
Tripping output logic setting of delay 1 of stage 1 of gap zero sequence overvoltge protection.
Please refer to section 7.4.1.1.2 for more information about it.
12 No.10— [TrpLog_ROV12_Gap]
Tripping output logic setting of delay 2 of stage 1 of gap zero sequence overvoltge protection.
Please refer to section 7.4.1.1.2 for more information about it.
13 No.13— [En_Alm_ROV]
All settings of transformer system parameters are accessible in the following path:
This submenu is used for configuration the parameters for overload protection. Parameter cell
[En_OvLd] should be set as “1”to enable overload protection.
In addition, first of all, zero-sequence CT should be selected for overload protection. Please refer
to setting [Cfg_CT_OvLd] in section 7.2.2
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_Alm_OvLd]
Current setting for overload alarm. When actual secondary current is larger than this setting value
and the predefined time delay has elapsed, alarm information of overload will be issued.
2 No.2— [t_Alm_OvLd]
3 No.3— [I_InitCool_OvLd]
Current setting for initiating air cooling mechanism when the transformer is overloaded.
4 No.4— [t_InitCool_OvLd]
Time delay of initiating air cooling mechanism when the transformer is overloaded.
5 No.5— [I_Blk_OLTC_OvLd]
Current setting for blocking on-load tap changing when the transformer is overloaded.
6 No.6— [t_Blk_OLTC_OvLd]
Time delay of blocking on-load tap changing when the transformer is over overloaded load.
7 No.7— [I_CCE]
Current setting for current control element. If the actual current is larger than the current setting,
equipment will output binary output contacts and tripping output contacts to trip other circuit
breakers depending on setting No.8.
8 No.8— [TrpLog_CCE]
Tripping output logic setting of current control element. Refer to section 7.4.1.1.2 for more
information about it.
9 No.9— [En_Alm_OvLd]
10 No.10— [En_InitCool_OvLd]
This is the logic setting used to enable air cooling mechanism initiation function when the
transformer is overloaded.
11 No.11— [En_Blk_OLTC_OvLd]
This is the logic setting used to enable blocking on-load tap changing function when the
transformer is overloaded.
12 No.12— [En_BO_CCE]
This is the logic setting used to enable equipment to output contacts when current control element
picks up.
All settings of transformer system parameters are accessible in the following path:
When the equipment is used to protect step-down transformer, side 1 is called HV side and side 2
and 3 are called branch side. Therefore the configuring principles of side 2 and 3 are similar.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_Pkp_PcntDiff]
This is a pickup setting of percentage current differential protection, which is also the setting of
fault detector of percent differential protection. It should be higher than maximum unbalanced
current of the transformer during normal rated load, i.e.
I cdqd K rel ( K er U m) I e
Where:
I cdqd represents the setting [I_Pkp_PcntDiff];
Ie is secondary calculated rated current of transformer;
Krel is reliability coefficient (generally K rel = 1.3 ~1.5);
Ker is the ratio error of CT (=0.03X2, for class 10P; =0.01X2, for class 5P and class TP);
U is the maximum deviation (in percentage of rated voltage) due to tap changing;
m is the error caused by the difference between ratios of CT at all side, 0.05 is recommended.
For practical engineering application, Icdqd =(0.3 ~0.5) I e is reasonable and unbalanced current
2 No.2— [I_InstDiff]
Setting of unrestrained instantaneous differential protection, which is used to clear serious internal
fault quickly and prevent operation delay caused by CT saturation. The setting I cdsd (ie.
[I_InstDiff ]) should be higher than inrush current and maximum unbalanced current due to external
fault or asynchronous closing, generally
I cdsd K I e
Where:
K is a multiple depending on capacity of transformer and the system reactance. 5~ 6 is
recommended for main transformer, 6~8 is recommended for startup/standby transformer and
plant transformer.
I e is secondary calculated rated current of transformer.
calculated according to the phase-to-phase solid short circuit fault in normal operation condition at
3 No.3— [Slope1_PcntDiff]
K er is the error of current ratio of CT, no more than 0.1. K bl 1 is 0.10-0.20 generally.
Where:
I k. max is the periodic component (secondary value) of maximum through fault current of
K ap is the coefficient of aperiodic component. K ap = 1.0 if CT at both sides are class TP, or
I unb .max K ap K cc K er I k .max U h I k.h .max mI I k .I .max mII I k. II .max
Where:
Definition of K er , K cc and K ap have been mentioned above;
U h is the relative error (to rated voltage Un) of HV side due to tap changing, it is
recommended to adopt the maximum value of deviations to the rated value (in
percentage of rated voltage).
I k .max is the periodic component (secondary value) of maximum short current flowing through
CT close to the fault point when external fault occurred at the LV side.
I k.h . max is the periodic component (secondary value) of current flowing through CT of voltage
changeable side when calculating fault current of external fault at LV side.
I k .I . max and I k .II .max are the periodic components of secondary currents flowing through CT at
mI and mII are errors caused by difference between ratios of CT (auxiliary CT included if any)
at relevant sides.
The sensitivity coefficient K sen should be calculated according to phase-to-phase short circuit on
outlet of transformer protected by the differential relay in minimum operation mode. From the
calculated minimum short circuit current I k .min and relevant restraint current I res , corresponding
pickup current I op will be found in the operation characteristic curve of percent differential relay,
K sen I k. min / I op
K sen ≥ 2 is required.
4 No.4— [Slope2_PcntDiff]
Where:
Definition of I unb . max* , I cdqd * and I k .max* are almost same to Iunb .max , I cdqd and
I k. max mentioned above, and the only difference is they are per unit values. I e (secondary
k bl 2 =0.70 is recommended.
5 No.5— [k_2ndH_PcntDiff]
Restraint coefficient of second harmonic. This parameter is the blocking threshold of second
harmonic involving in differential current to against inrush current when the transformer is
energized. The differential protection will be blocked when the percentage of second harmonics
reaches the threshold because the percentage of second harmonics is high in inrush current but
low in fault current. In general, the parameter is set to be 15% ~20% and 15% is recommended.
6 No.6— [I_Alm_Diff]
Setting of differential current abnormality alarm. It should be higher than maximum differential
current due to tap changing of the transformer being not in the middle position or other possible
conditions during operation.
7 No.7— [TrpLog_Diff]
Tripping output logic setting of differential protection. Mentioned below are used to specify which
breaker or breakers will be tripped by the protection. This setting comprises following 16 binary
bits and is displayed by a hexadecimal number of 4 digits from 0000H to 0FFFH.
The tripping output logic setting of RCS-985TS is defined below.
Bits Function
0 Protection enabled
1 TrpOutp1
2 TrpOutp2
3 TrpOutp3
4 TrpOutp4
5 TrpOutp5
6 TrpOutp6
7 TrpOutp7
8 TrpOutp8
9 TrpOutp9
10 TrpOutp10
11 TrpOutp11
12 TrpOutp12
13-15 No definition
“TrpOutput 1”means to drive the 1st group of tripping output relays to operate.
Set bit “0”as 1 means this protection element will trip breaker or breakers. The bit corresponding
to the breaker to be tripped shall be set as“1”and other bits shall be “0”. For example, if
differential protection is defined to “Trpoutp 5”(the 5th group of tripping output relays), the “0”bit
and “5”bit shall be set as “1”and other bits “0”. Then a hexadecimal number 0021H is formed as
the tripping output logic setting.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
All the tripping logic settings mentioned below is defined as same as this one.
NOTE Tripping output logic settings have to be set on basis of application -specific
8 No.8— [En_InstDiff]
This it the logic setting used to enable unrestrained instantaneous differential protection.
9 No.9— [En_PcntDiff]
10 No.10— [En_CTSBlkDiff]
This it the logic setting used to select operating characteristic of percent differential protection
when differential CT circuit failure.
“0”: means percent differential protection is not blocked when differential CT circuit failure.
“1”: means percent differential protection is blocked when differential CT circuit failure.
All settings of transformer system parameters are accessible in the following path:
Restricted earth fault protection is also called zero-sequence differential protection. There are
three restricted earth fault protection elements of side 1, side 2 and side 3 and the each element is
independent to another side but with the same protection theory and scheme logic. Here take the
NOTE: Symbol of the parameters listed in above tables is used for communication,
NOTE: To configure the settings of zero-sequence percent differential protection, you can
follow the method provided in section 7.4.3.1 calculation of percent differential protection,
where U shall be taken as 0. Polarity of each CT for zero-sequence differential
protection at various sides is same as shown in Figure 1.1-1 ~ Figure 1.1-4. Positive
polarity of three-phase CT is at busbar side and that of zero-sequence CT is at neutral
point side.
1 No.1--[I_Pkp_PcntREF_S1]
This is pickup setting of zero-sequence percent differential element of restricted earth fault
protection, which is also the setting of fault detector of that element.
Calculation of this setting is based on rated secondary current of the transformer. If a setting got
from calculation is together with its unit Ampere, this setting shall be divided by rated secondary
current of this side of the CT, to get per unit value. The setting of zero - sequence differential
protection shall be greater than the maximum imbalanced current while transformer operates on
normal rated load, i.e.
Where:
Ker is the ratio errors of CT (for type 10P, Ker = 0.03×2; for class 5P and class TP, Ker =0.01X2);
m is the error caused by the difference between ratios of CT at all sides, 0.05 is recommended.
For practical engineering calculation, I ocdqd =(0.3 - 0.5)I e is reasonable and unbalanced current
Sensitivity of restricted earth fault protection shall be checked with the solid earth fault in its
In solid earthed system, distribution of zero sequence current for single-phase-to-earth fault
depends on the configuration of zero sequence network of power system. Magnitude of the
single-phase-to-earth fault current depends on not only zero sequence impedance of system but
also the positive and negative sequence impedances. That means different operation modes of
power system also have influence on the current. When power system is in maintenance status,
in order to remain the zero sequence impedance of the system network unchanged and increase
sensitivity for earth fault protection, the 220 kV power system is generally compensated by
properly changing earth mode of the transformer. Therefore, sensitivity of zero sequence
differential protection shall be checked in minimum operation mode for 220 kV power system.
2 No.2--[I_InstREF_S1]
3 No.3--[Slope_PcntREF_S1]
4 No.4--[TrpLog_REF_S1]
Tripping output logic setting of restricted earth fault protection which is used to specify which
breaker or breakers will be tripped by the protection.
5 No.5--[En_InstREF_S1]
6 No.6--[En_PcntREF_S1]
Logic setting of enabling zero-sequence percent differential protection element of restricted earth
fault protection.
Settings of restricted earth fault protection of side 1, side 2 and side 3 accessible in the following
path respectively:
Main Menu -> SETTING -> PROT SETTINGS -> S1 REF PROT
Main Menu -> SETTING -> PROT SETTINGS -> S2 REF PROT
Main Menu -> SETTING -> PROT SETTINGS -> S3 REF PROT
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [V_NegOV_VCE_S1]
Setting of negative sequence voltage control element of side 1. Setting and displayed value of
negative sequence voltage are U2.
Negative sequence voltage is taken from LV side usually. The operating negative sequence
voltage shall be higher than maximal unbalance voltage. Generally, U 2.op (0.06 0.08)U N is
U2
U2
Ksen 1.5
nTV U 2OP
Where:
U 2 is negative sequence voltage (phase voltage) of LV side busbar of the step-down transformer,
2 No.2— [Vpp_UV_VCE_S1]
Phase-to-phase voltage is taken from LV side usually. The setting shall be higher than the lowest
voltage during starting process of the largest motor connected with the LV busbar.
U op (0.55 0.6)U n .
UOP
U
Ksen 1.5
nTV U1
Where:
3 No.3— [I_OC1_S1]
There are two kinds of configuring phase-to-phase fault protection of HV side. One is overcurrent
protection without voltage control, which operating current should be higher than the starting
current of motor. Therefore operating current is relatively high, which disadvantage is that it can
not provide full backup protection for HV side plant system such as fault occurring on the end of
long cable.
The other is voltage controlled overcurrent protection, which operating current is relatively low, so
it can provide full backup protection for HV side plant system. However If voltage of LV side busbar
of step-down transformer is adopted for voltage control element, following disadvantage exists.
During generator starting up and increasing voltage or power supply having been not switched to
step-down transformer, if short-circuit fault occurs in step-down transformer or fault occurs
between circuit breaker of branch and LV side, the protection will no operate. Therefore, it is
recommended that voltage of LV side (if there is VT between LV side of step-down transformer and
circuit breaker of branch) is adopted for voltage control element to eliminate the disadvantage.
Operating current I OPI should be higher than the operating current of stage 1 of LV side branch,
K I n
I OPI co OP ( L/ ) TA
K T nTA
(K I n I10a )
I OPI co OP ( L ) TA
/
K T nTA
Where:
IOPI ( L ) is operating current of one branch of LV side,I_OC1_S2] or [I_OC1_S3], and please refer to
the corresponding setting configuration. Please note the setting should be higher than the
maximum load current of LV side branch.
I (2)
Ksen ' K min 1.5
n TA IOPI
Where:
( 2)
I k .min is fault current through step-down transformer during phase-to-phase short circuit fault
occurs on outlet of LV side of the transformer.
Operating current of stage1 shall be higher than maximal current passing through the protection
equipment during three phase fault on LV side outlet of the startup/standby transformer:
I K(3).max
IOPI Krel
nTA
1 S
K .max
I (3) B
X max X T 3U B
Where:
I k(3.max
)
is the maximum secondary current passing through HV side when three phase fault occurs
X max is per unit value of system reactance, which base value is S B , when HV side of the
4 No.4— [t_OC1_S1]
No.1 setting [I_OC1_S1] is unaffected by increase of load current of the transformer when the HV
side voltage drops down due to system oscillation, so delay of this protection shall coordinate with
main protection only without considering oscillation period. [t_OC1_S1]=0.5 s is recommended
generally.
5 No.5— [I_OC2_S1]
The setting is equal to operating current of stage 1 of overcurrent protection of side 1, which is
[I_OC1_S1].
There are the following two configuring principles for the settings of voltage controlled overcurrent
protection.
(2) Configuring Principle 1 – voltage controlled overcurrent protection
The setting shall be based the condition that the protection can return reliably when rated current
passes through HV side:
K I
IOPII rel N
Kr nTA
Where:
U LN 1
I opII K CO ( I opII ( L ) nTAL I10 a )
U HN nTA
Where:
I opII (L) is the secondary operating current of stage 2 of overcurrent protection of LV side branch of
nTAL is the current ratio of CT used by overcurrent protection of the LV side branch;
Generally, when voltage control element for stage 2 of overcurrent protection is enabled, the first
configuring principle is adopted. However, if secondary principle is adopted, voltage control
element for stage 2 is selectable.
(4) Sensitivity check – voltage controlled overcurrent protection
I (2)
Ksen I K 1.3
nTA IOPII
Where:
I K (2) is short -circuit current flowing through HV side of the transformer when two-phase short
6 No.6— [t_OC2_S1]
The delay should coordinate with stage 2 of overcurrent protection of branch of LV side or be set
as the value of No.3 setting [I_OC1_S1].
The setting shall coordinate with stage 2 of overcurrent pr otection of LV side branch of the
transformer. It can be taken as t 2 t '2 t t usually, where t 2' is delay of stage 2 of LV
side branch, t is the step difference. Since this delay is longer than oscillation period, so even
if stage 2 of overcurrent element operates due to HV side voltage drop during system oscillation,
stage 2 of overcurrent protection will not operate incorrectly.
7 No.7— [I_OC3_S1]
8 No.8— [t_OC3_S1]
9 No.9— [TrpLog_OC1_S1]
Tripping output logic setting of stage 1 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
10 No.10— [TrpLog_OC2_S1]
Tripping output logic setting of stage 2 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
11 No.11— [TrpLog_OC3_S1]
Tripping output logic setting of stage 3 of overcurrent protection of side1. Refer to section 7.4.1.1.2
for more information about it.
12 No.12— [En_VCE_OC1_S1]
This is the logic setting used to enable stage 1 of overcurrent protection of side 1 is controlled by
voltage control element of local or other side.
13 No.13— [En_VCE_OC2_S1]
This is the logic setting used to enable stage 2 of overcurrent protection of side 1 is controlled by
voltage control element of local or other side.
14 No.14— [En_S1.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of local side.
15 No.15— [En_S2.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of side 2.
16 No.16— [En_S3.VCE_OC_S1]
This is the logic setting used to enable overcurrent protection of side 1 is controlled by voltage
control element of side 3.
(1) No.12 and NO.13 settings are configured first to decide whether OC protection is
controlled by voltage control element. No.12-No.13 settings are multioption, which means
any stage of OC protection can be controlled by voltage control elelment.
(2) If No.12 or No 13 is set as “1”, then No.14-No.16 settings are needed to be configured
to decide which side voltage control element OC is controlled by. No.14 -No.16 settings
are multioption, which means voltage control element of any side can controls OC
protection.
17 No.17— [Opt_VTS_OC_S1]
This is the logic setting used to select operating performance of OC protection of side 1 during VT
circuit failure.
“1”: when VT circuit failure on side 1 is detected, voltage control element of the side can not pick
up.
“0”: when VT circuit failure on side 1 is detected, voltage control element will pick up and the
voltage-controlled overcurrent element will become a pure overcurrent relay.
18 No.18— [En_Mem_Curr]
The setting is set as 1 when protection equipment is used to protect self-excitation generator.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: Same symbol in this section has similar meaning to that appears in section 7.4.3.2
and the configuring principle is also similar, so please refer to that section for details.
NOTE: The settings of phase-to-phase fault protection of side 2 and those of side 3 are
1 No.1— [V_NegOV_VCE_S2]
Setting of negative sequence voltage control element of side 2. Setting and displayed value of
negative sequence voltage are U2.
2 No.2— [Vpp_UV_VCE_S2]
Calculation of setting of low-voltage voltage relay is the same as that of phase-to-phase fault
protection of side 1, so please refer to section 7.4.2.3.2 for details.
3 No.3— [I_OC1_S2]
(1) The setting of stage 1 shall coordinate with insensitive of instantaneous overcurrent protection
of largest motor connected with HV power plant busbar:
PN 1
I opI ( L ) K co K rel K st
3U N cos n TA
Where:
PN is the power of the largest motor (pump for water supply) connected with the HV power plant
busbar,
cos is the power coefficient of the motor and 0.75 is recommended generally;
(2)
I
Ksen K 1.3
nTA IOPI ( L )
Where:
I (K2 ) is short circuit current of overcurrent protection when two-phase short circuit fault occurs on
HV power plant busbar in minimum mode of operation of start-up/standby transformer.
4 No.4— [t_OC1_S2]
The delay shall coordinate with delay of instantaneous overcurrent protection on outlet of HV
power plant busbar.
5 No.5— [I_OC2_S2]
K I
I opII rel N
K r nTA
Where:
Both stage1 and 2 can be controlled by voltage control element by configuring corresponding
logic settings, and it is recommended that stage 2 is controlled by voltage control element.
6 No.6— [t_OC2_S2]
The delay shall coordinate with delay of outlet of HV power plant busbar.
7 No.7— [TrpLog_OC1_S2]
Tripping output logic setting of stage 1 of overcurrent protection of side2. Refer to section 7.4.1.1.2
for more information about it.
8 No.8— [TrpLog_OC2_S2]
Tripping output logic setting of stage 2 of overcurrent protection of side 2. Refer to section
7.4.1.1.2 for more information about it.
9 No.9— [En_VCE_OC1_S2]
This is the logic setting used to enable stage 1 of overcurrent protection of side 2 is controlled by
voltage control element of local or other side.
10 No.10— [En_VCE_OC2_S2]
This is the logic setting used to enable stage 2 of overcurrent protection of side 2 is controlled by
voltage control element of local or other side.
11 No.11— [En_OC2_SOTF_S2]
This is the logic setting used to enable accelerating trip function of state 2 of OC protection of side
2 when switching one to fault.
12 No.12— [Opt_VTS_OC_S2]
This is the logic setting used to select operating performance of OC protection of side 2 during VT
circuit failure.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: HV side (i.e. side 1) winding of step-down transformer is delta connected, so the
1 No.1— [I_ROC1_S1]
2 No.2— [t_ROC1_S1]
3 No.3— [I_ROC2_S1]
4 No.4— [t_ROC2_S1]
Delay of stage 2 shall coordinate with the longest delay of backup stage of residual overcurrent
protection of HV side outlet.
5 No.15— [TrpLog_ROC1_S1]
Tripping output logic setting of stage 1 of zero sequence overcurrent protection of side 1. Refer to
section 7.4.1.1.2 for more information about it.
6 No.16— [TrpLog_ROC2_S1]
Tripping output logic setting of stage 2 of zero sequence overcurrent protection of side 1. Refer to
section 7.4.1.1.2 for more information about it.
7 No.21— [Opt_3I0_ROC_S1]
This is the logic setting used to select where zero sequence current is derived.
“0”means zero sequence current is derived from zero-sequence CT installed at neutral point.
8 No.22— [En_Dir_ROC1_S1]
This is the logic setting used to select whether stage 1 of zero sequence overcurrent of side 1
controlled by zero-sequence direction element.
9 No.23— [En_Dir_ROC2_S1]
This is the logic setting used to select whether stage 2 of zero sequence overcurrent of side 1
controlled by zero-sequence direction element.
10 No.24— [Opt_VTS_ROC_S1]
This is the logic setting used to select operating performance of zero sequence overcurrent
protection of side 1 during VT circuit failure.
“1”: when VT circuit failure on side 1 is detected, zero-sequence voltage element of the side can
not pick up.
“0”: when VT circuit failure on side 1 is detected, the element will pick up and the
voltage-controlled zero-sequence overcurrent element will become a pure zero-sequence
overcurrent relay.
11 No.25— [Opt_Dir_ROC_S1]
Logic setting [Opt_Dir_ROC_S1] is used to select the direction of every stage of zero sequence
overcurrent protection. If this logic setting is set as “1”, the direction is transformer and reach angle
is 225º. If this logic setting is set as “0”, the direction is power system and reach angle is 75º..
This is the logic setting used to select the direction of zero-sequence overcurrent protection.
All settings of transformer system parameters are accessible in the following path:
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: The settings of earth fault protection of side 2 and those of side 3 are similar, so
only setting descriptions of the settings of side 2 are given below as an example.
1 No.1— [I_ROC1_S2]
Setting of stage 1 of zero sequence overcurrent protection of side 2. Please note side 2 and 3 are
called branches of start-up/standby transformer.
Two stages with one delay are usually provided for residual overcurrent protection of branch of
startup/standby transformer. Stage 1 will operate to trip circuit breaker of the branch and stage 2
will operate to trip both circuit breakers of HV and LV sides.
(3 I )
(3I 0 )OPI K c(0n 1) 0 set
nTA 0
(3I o ) set is the primary operating current of maximum level of zero sequence overcurrent
3I
K sen k .o .min
I op .o
Where:
3 I k .o. min is minimal secondary zero sequence current passing through location of the protection
2 No.2— [t_ROC1_S2]
3 No.3— [I_ROC2_S2]
Where:
(2) Sensitivity check: criterion is same to that of stage 2 of zero sequence overcurrent protection.
4 No.4— [t_ROC2_S2]
The delay shall coordinate with stage 1 of residual overcurrent protection of side 2.
5 No.5— [TrpLog_ROC1_S2]
Tripping output logic setting of stage 1 of zero sequence overcurrent protection of side 2 Refer to
section 7.4.1.1.2 for more information about it.
6 No.6— [TrpLog_ROC2_S2]
Tripping output logic setting of stage 2 of zero sequence overcurrent protection of side 2. Refer to
section 7.4.1.1.2 for more information about it.
All settings of transformer system parameters are accessible in the following path:
This submenu is used for configuration of gap earth fault protection for transformer which neutral
point is not earthed or earthed through air gap.
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
NOTE: HV side (i.e. side 1) winding of step-down transformer is usually delta connected,
so the settings of gap earth fault protection of side 1 are not needed to be configured.
However zero-sequence overvoltage alarm element can be configured according to
the actual requirement.
1 No.1— [I_ROC1_Gap]
2 No.2— [t_ROC11_Gap]
3 No.3— [t_ROC12_Gap]
4 No.4— [V_ROV_Gap]
5 No.5— [t_ROV11_Gap]
6 No.6— [t_ROV12_Gap]
7 No.7— [V_Alm_ROV]
8 No.8— [V_Alm_ROV]
9 No.9— [TrpLog_ROC11_Gap]
Tripping output logic setting of delay 1 of stage 1 of gap zero sequence overcurrent protection.
Please refer to section 7.4.1.1.2 for more information about it.
10 No.10— [TrpLog_ROC12_Gap]
Tripping output logic setting of delay 2 of stage 1 of gap zero sequence overcurrent protection.
11 No.9— [TrpLog_ROV11_Gap]
Tripping output logic setting of delay 1 of stage 1 of gap zero sequence overvoltge protection.
Please refer to section 7.4.1.1.2 for more information about it.
12 No.10— [TrpLog_ROV12_Gap]
Tripping output logic setting of delay 2 of stage 1 of gap zero sequence overvoltge protection.
Please refer to section 7.4.1.1.2 for more information about it.
All settings of transformer system parameters are accessible in the following path:
This submenu is used for configuration the parameters for overload protection. Parameter cell
[En_OvLd] should be set as “1”to enable overload protection.
In addition, first of all, zero-sequence CT should be selected for overload protection. Please refer
to setting [Cfg_CT_OvLd] in section 7.2.2
NOTE: The parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1— [I_Alm_OvLd]
Current setting for overload alarm. When actual secondary current is larger than this setting value
and the predefined time delay has elapsed, alarm information of overload will be issued.
2 No.2— [t_Alm_OvLd]
3 No.3— [I_InitCool_OvLd]
Current setting for initiating air cooling mechanism when the transformer is overloaded.
4 No.4— [t_InitCool_OvLd]
Time delay of initiating air cooling mechanism when the transformer is overloaded.
5 No.5— [I_Blk_OLTC_OvLd]
Current setting for blocking on-load tap changing when the transformer is overloaded.
6 No.6— [t_Blk_OLTC_OvLd]
Time delay of blocking on-load tap changing when the transformer is over overloaded load.
7 No.7— [I_CCE]
Current setting for current control element. If the actual current is larger than the current setting,
equipment will output binary output contacts and tripping output contacts to trip other circuit
breakers depending on setting No.8.
8 No.8— [TrpLog_CCE]
Tripping output logic setting of current control element. Refer to section 7.4.1.1.2 for more
information about it.
9 No.9— [En_Alm_OvLd]
10 No.10— [En_InitCool_OvLd]
This is the logic setting used to enable air cooling mechanism initiation function when the
transformer is overloaded.
11 No.11— [En_Blk_OLTC_OvLd]
This is the logic setting used to enable blocking on-load tap changing function when the
transformer is overloaded.
12 No.12— [En_BO_CCE]
This is the logic setting used to enable equipment to output contacts when current control element
picks up.
All settings of transformer system parameters are accessible in the following path:
Furthermore, all above functions can be realized in a remote terminal with SAS software through a
communication bus via a RS-485 port or Ethernet port.
This chapter will describe human machine interface (HMI), menu tree and LCD display of the
equipment. In addition, how to input settings using keypad is described in detail.
8.1.1 Design
The human-machine interface consists of a human-machine interface (HMI) module which allows a
communication as simple as possible for the user. The HMI module includes:
A 160×80-dot matrix backlight LCD visible in dim lighting conditions for monitoring status, fault
diagnostics and setting, etc.
Three LED indicators on the front panel of the RCS-985TS for denoting the status of this
protection operation.
A 9-key keypad on the front panel of the device for full access to the device.
8.1.2 Functionality
The HMI module helps to draw your attention to something that has occurred which may activate
a LED or a report display on the LCD.
You as the operator may have own interest to view a certain data.
Use menus navigate through menu commands and to locate the data of interest.
The keypad and keys on the front panel of the equipment provide convenience to the operator to
view a certain data or change the device’
s setting.
The keypad contains nine keys, and each key has different function to the other one. Figure 8.1-2
shows the keypad and keys.
WARNING: Never press key “RST”when the relay is in service, otherwise an uncertain accident
maybe occur.
NOTE:
alarm signal can be reset and “ALARM”LED can be extinguished only when the
failure is removed and one of the following three actions is taken: pressing key “ENT”,
energizing binary input [BI_RstTarg] or receiving reset message from SAS or RTU.
The “TRIP”LED is extinguished once any protection element operates and remains
lit even after the trip command goes off. “TRIP”LED and corresponding latched
binary outputs can be reset by pressing key “ENT”, energizing binary input [BI_RstTarg]
or receiving reset message from SAS or RTU.
8.2.1 OVERVIEW
In this part, the main layout of the menu which is shown on the LCD of the local human-machine
interface (HMI) will be described in detail.
Under normal operating condition, the default display (please refer to section 8.3) is always on
LCD. Press key “▲ ”to enter the main menu of the device, which is shown as bellow. If the
current display is the latest report display or self-supervision report, please do as same as above.
Press key “▲ ”or “▼ ”to move the cursor and locate the desired item and then press “ENT”to enter
its submenu. If operator wants to exit, please press key “ESC”or menu EXIT to return to upper
level menu.
1.SETTINGS
2.VALUES
3.PRINT
4.CLOCK
5.REPORT
6.CLR REPORT
7.TRIG OSCLLOG
8.VERSION
0.EXIT
The following figure shows the menu tree structure of this equipment.
8.2.2 SETTINGS
The menu is used to view and modify the settings of active setting group.
8.2.3 VALUES
This menu is used to view the measured value including current, voltage, phase angle, binary
input state and other calculated quantities.
8.2.4 PRINT
8.2.5 CLOCK
The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified. The detailed
operating steps of adjusting time please see 8.8.6.
8.2.6 REPORT
This menu is used to view all kinds of report including trip report, alarm report and so on.
8.2.9 VERSION
This menu is used to check program version of the equipment.
8.2.10 EXIT
This menu is used to exit the main menu and return to default display.
The LCD has default display after equipment is energized. If there is no keypad activity for 2
minutes and 5 seconds in main menu or any submenu, the LCD backlight will be turned off. The
default display on the LCD is shown in the Figure 8.3-1.
NOTE:
The first line shows the current date and time of the equipment and the format is:
YY-MM-DD HH:MM:SS.
The value of voltage or current which is displayed on the LCD is the secondary value of
the primary VT and CT equipments.
NOTE: In case more than one protection element has operated, the relevant report will
The tripping report will keep being displayed on LCD until an acknowledgement by pressing the
key “ENT”or resetting the equipment. Then default display then appears on LCD and “TRIP”LED
is extinguished.
Protection element
No. Description
and tripping relay
1 Op_FD At least one of the fault detectors operates.
2 Op_InstDiff Operation element of instantaneous unrestrained differential protection.
3 Op_PcntDiff Percent differential protection operates.
4 Op_OC1_S1 Stage 1 of overcurrent element of side 1 operates.
5 Op_OC2_S1 Stage 2 of overcurrent element of side 1 operates.
6 Op_OC3_S1 Stage 3 of overcurrent element of side 1 operates.
7 Op_OC1_S2 Stage 1 of overcurrent element of side 2 operates.
8 Op_OC2_S2 Stage 2 of overcurrent element of side 2 operates.
9 Op_OC1_S3 Stage 1 of overcurrent element of side 3 operates.
10 Op_OC2_S3 Stage 2 of overcurrent element of side 3 operates.
11 Op_ROC1_S1 Stage 1 of zero-sequence overcurrent element of side 1 operates.
12 Op_ROC2_S1 Stage 2 z of zero-sequence overcurrent element of side 1 operates.
13 Op_ROC1_S2 Stage 1 of zero-sequence overcurrent element of side 2 operates.
14 Op_ROC2_S2 Stage 2 of zero-sequence overcurrent element of side 2 operates.
15 Op_ROC1_S3 Stage 1 of zero-sequence overcurrent element of side 3 operates.
16 Op_ROC2_S3 Stage 2 of zero-sequence overcurrent element of side 3 operates.
17 Op_ROV11Gap Time delay 1 of gap zero-sequence overvoltage operates.
18 Op_ROV12Gap Time delay 2 of gap zero-sequence overvoltage operates.
19 Op_ROC11Gap Time delay 1 of gap zero-sequence overcurrent operates.
20 Op_ROC12Gap Time delay 2 1of gap zero-sequence overcurrent operates.
21 Op_InstREF_S1 Instantaneous zero-sequence differential protection of side 1 operates.
22 Op_PcntREF_S1 Percent zero-sequence differential protection of side 1 operates.
23 Op_InstREF_S2 Instantaneous zero-sequence differential protection of side 2 operates.
24 Op_PcntREF_S2 Percent zero-sequence differential protection of side 2 operates.
25 Op_InstREF_S3 Instantaneous zero-sequence differential protection of side 3 operates.
26 Op_PcntREF_S3 Percent zero-sequence differential protection of side 3 operates.
Protection element
No. Description
and tripping relay
27 Op_CCE Current control element operates.
28 TrpOutp1 The 1st group of tripping output relays is driven to operate.
29 TrpOutp2 The 2nd group of tripping output relays is driven to operate.
30 TrpOutp3 The 3rd group of tripping output relays is driven to operate.
31 TrpOutp4 The 4th group of tripping output relays is driven to operate.
32 TrpOutp5 The 5th group of tripping output relays is driven to operate.
33 TrpOutp6 The 6th group of tripping output relays is driven to operate.
34 TrpOutp7 The 7th group of tripping output relays is driven to operate.
35 TrpOutp8 The 8th group of tripping output relays is driven to operate.
36 TrpOutp9 The 9th group of tripping output relays is driven to operate.
37 TrpOutp10 The 10th group of tripping output relays is driven to operate.
38 TrpOutp11 The 11th group of tripping output relays is driven to operate.
39 TrpOutp12 The 12th group of tripping output relays is driven to operate.
If there is any abnormality in the operating or firmware error detected by equipment self-diagnostic,
alarm report will be displayed instantaneously on the LCD. Therefore, default display will be
replaced by the alarm report.
In case there is more than one alarm has occurred, the information will be displayed alternately on
the LCD.
There are two types of alarm: operation alarm and equipment alarm.
Equipment Alarm:
Alarm occurs due to some hardware error detected by equipment self-diagnostic. Under this
condition, the “HEALTHY”LED will be turned off and all protection functions will be blocked.
Please refer to Table 4.2-1 for all the self-check alarm elements.
Operation Alarm:
Alarm occurs due to some abnormities during system operating. Under this condition, the
“ALARM”LED will be lit.
Please refer to Table 4.2-2 for all the self-check alarm elements.
If user makes any changes to the equipment, a brief report will be recorded in “CTRL REPORT”
menu.
Here take viewing settings of differential protection as an example to introduce the operating steps
of viewing setting for operators.
Operating steps:
Press key “▲ ”or “▼ ”to select “SETTINGS”by scrolling the cursor upward or downward.
Press key “▲ ”or “▼ ”to select “PROT SETTINGS”by scrolling the cursor upward or downward.
Press key “▲ ”or “▼ ”to select “DIFF SETTINGS”by scrolling the cursor upward or downward.
Press key “ENT”to display the setting symbol and parameters of the submenu.
If you want to view more setting parameters, please press key “▲ ”or “▼ ”to locate the setting you
are interested in by moving the cursor.
Metering data means AC sampled data and phase angles in the submenu CPU VALUES or MON
VALUES.
Take viewing AC sampled data of “S1 PPF PROT”of “CPU VALUES”as an example.
Operating steps:
Press key “▲ ”or “▼ ”to select “VALUES”item by scrolling the cursor upward or downward.
Press key “▲ ” or “▼ ” to select “CPU METERING” item by scrolling the cursor upward or
downward. Press key “ENT”to enter the submenu.
Press key “▲ ”or “▼ ”to select “S1 PPF PROT”item by scrolling the cursor upward or downward.
Press key “ENT”to view the values.
A cursor is at the head of the second line, press key “▲ ”or “▼ ”to move the cursor up or down
to see other measured values.
Sample quantity’
s and phase angles are list in detail in sections 5.2.
Operating steps:
Press key “▲ ”or “▼ ”to select “VALUES”item by scrolling the cursor upward or downward.
Press key “▲ ”or “▼ ”to select “BI STATE”item by scrolling the cursor upward or downward. Press
key “ENT”to view the state of binary input.
Press key “▲ ”or “▼ ”to move the cursor upward or downward to view the state of particular binary
input.
Refer to section Table 5.3-1 to see more information about the binary input.
The equipment program has three parts consisting of CPU MON, and HMI module programs.
There are totally independent.
Operating steps:
Press key “▲ ”or “▼ ”to select “VERSION”item by scrolling the cursor upward or downward.
Press key “ENT”to enter the submenu.
Press key “▲ ”or “▼ ”to select “CPU VERSION”item by scrolling the cursor upward or downward.
Press key “ENT”to enter the submenu.
NOTE: What above figure shows is just an example to introduce the meaning of LCD
Event recording
Events are recorded in form of report and can be viewed through LCD or by printing report.
Self-supervision report, equipment operation report, control report (i.e user operating report)
and binary input change report belong to event record.
Disturbance recording
Fault is recorded in form of both report and waveform, so report can be display on LCD or by
printing. However waveform must to be printed or displayed with special software.
Present recording
Present recording is recorded in form of waveform and can be viewed only by printing.
If you want to see event recording report and fault recording report through LCD, please follow the
operating steps.
Operating steps
First, please go in to the main menu by pressing key “▲ ”. Press key “▲ ” or “▼ ”to select
“REPORT”item by scrolling the cursor upward or downward.
Then press key “▲ ” or “▼ ”to select “TRIP REPORT”, “OPR REPORT”, “BI CHG REPORT”,
“CTRL REPORT”or “ALARM REPORT”by scrolling the cursor upward or downward. Press key
“ENT”to display the report selected.
The latest report will be displayed first. Press key “▲ ”or “▼ ”to view the next or last report.
If the report cannot be completely displayed by one screen, they will scroll from right to left one by
one.
If you want to see event recording report or fault recording report and waveform by printing, please
follow the operating steps.
Operating steps
First, please go in to the main menu by pressing key “▲ ”. Press key “▲ ”or “▼ ”to select “PRINT”
item by scrolling the cursor upward or downward.
Press key “▲ ”or “▼ ” to select “TRP RECORD”, “ALM REPORT”or “BI CHG REPORT” by
scrolling the cursor upward or downward. Please select the report to be printed. Then press key
“ENT”to print the report displayed on LCD via a printer.
In order to return to the upper level submenu, simply press key “ESC”.
Operating steps
First, please go in to the main menu by pressing key “▲ ”. Press key “▲ ”or “▼ ”to select “TRIG
OSCILLOG”item by scrolling the cursor upward or downward.
Press key “ENT”and password input interface will appear, enter the password and press “ENT”to
trigger a waveform.
Then, please return to the main menu by pressing key “▲ ”. Press key “▲ ”or “▼ ” to select
“PRINT”item by scrolling the cursor upward or downward.
Then press key ▲ or ▼ to select “PRESENT WAVE”by scrolling the cursor upward or downward.
Press key “ENT”to enter the lower level submenu.
Please select the required item in the submenu by scrolling cursor and then press key “ENT”to
print the waveform.
The menu structure contains two levels of access. The level of access is enabled determines what
users can do by entry of password. The levels of access are summarized in the following table:
The password are 3 digits and the factory default password is 001. Password is user-changeable
once it has been correctly entered. Entry of the password is achieved either by a prompt when a
setting change or deleting records is attempted.
The access level enabled by the password entry will be invalid once user exits current operation
interface.
NOTE: It is necessary for user to change the password before the relay being put into
service, and keep the changed password commendably. If the passwords are lost an
emergency password can be supplied – contact NARI-RELAYS with the relay’s serial
number and the equipment current data and time.
Please locate the setting you want to change by operating the keypad as described in section 8.4.
Then go on to operate as following steps.
Press key “+”or “–”invoke the password input interface and enter your password.
If the password inputted is wrong, prompt information will appear and return latter on.
If the password inputted is right, it will return to the setting operator wants to modify directly.
Press key “◄ ”or “► ”to move the cursor to the digit to be modified. Pressing key “+”and “–”to
change the digit. Press key “+”once to add 1 to the digit and press key “–“once to subtract 1 from
the digit.
Press key “ESC”to cancel the modification and return to upper level submenu.
Press key “ENT”to confirm the modification of settings. At the same time, the LED “HEALTHY”will
be turned off and all protection functions will be blocked.
After accomplishment of modification, press key “RST”to restart the equipment and the new
settings will be valid.
NOTE: In order to certify the entered settings are all correct, it is recommended to print
Modify the group number as the method described above and press “ENT”to confirm it. At
this time, the LED “HEALTHY”will be turned off and all protection functions have been
blocked.
Here records include report and waveform and please refer to section 8.7.3 for details.
If you want to delete the content of fault records or event records, you can follow the operating
steps.
NOTE: You cannot select which kind of records or which one record to be deleted but
Operating steps:
Then press key ▲ or ▼ to select “CLR REPORT”by scrolling the cursor upward or downward.
Press key “ENT”and enter your password and press key “ENT”again. After few moment
prompt information will appear to tell you all reports stored in the equipment have been
cleared except the present operation of clearing report, which will be logged as an event
belonging to “CTRL REPORT”.
Select the item “CLOCK”and press key “ENT”, the following will be displayed on the LCD.
Press keys “▲ ”, “▼ ”, “◄ ”and “► ”to select the digit to be modified. Press key “+”and “–“to modify
data. Pressing key “+”once will add 1 to the digit and pressing key “–“once will subtract 1 from
the digit.
Press key “ENT”to confirm the modification and return to the main menu.
Hardware circuit and operation condition of the equipment are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.
A common abnormality may block a certain number of protection functions while other functions
can still work.
However, if serious hardware failure or abnormality were detected, all protection functions will be
blocked and the LED “HEALTHY”will be turned off.
When hardware failure is detected, all protection functions will be blocked and corresponding
alarm signal will be issued. The equipment then cannot work normally in this case and manual
maintenance is required to fix the failure.
NOTE: If the equipment is blocked or alarm signal is issued during operation, do please
find out its reason by help of “ALARM RERORT”(referring to section 4.2.11). If the
reason can not be found on site, please inform the factory NARI-RELAYS. Please do not
simply press key press key “RST”on the protection front panel or energize binary input
[BI_RstTarg] or re-power on the equipment.
Chapter 9 Communications
9.1 General
This section outlines the remote data communication interfaces of the RCS-985TS relay. The relay
can supports IEC60870-5-103 and MODBUS protocols.
The two rear EIA RS-485 standardized interfaces are isolated, as well as the two/three Ethernet
interfaces, and are suitable for permanent connection whichever protocol is selected. The
advantage of this type of connection is that up to 32 relays can be “daisy chained”together using a
simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
This relay provides two rear RS-485 communication ports, and each port has three terminals (A ,B
and SHLD) in the 12-terminal screw connector located on the back of the relay. SHLD terminal is
ground terminal for the earth shield of the communication cable. The rear ports provide RS-485
serial data communication and are intended for use with a permanently wired connection to a
remote control center.
The protocol provided by the relay is indicated in the relay submenu in the “EQUIP SETUP”
column. Using the keypad and LCD, set the parameters [COM1_Protocol] and [COM2_Protocol]
as “1”or “2”, the corresponding protocol will be selected.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’
s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (see Figure 9.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in wh ich case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
EIA RS-485
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’
s chassis. This is for both safety and noise reasons.
9.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receiving mode and the master is slow to turn from receiving mode to
transmitting mode. This may be because the master purposefully waits in receiving mode, or even
in a high impedance state, until it has something to transmit. Jabber causes the receiving device(s)
to miss the first bits of the first character in the packet, which results in the slave rejecting the
message and consequentially not responding. Symptoms of these are poor response times (due
to retries), increasing message error counters, erratic communications, and even a complete
failure to communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
NOTE:
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NARI-RELAYS cannot assume
responsibility for any damage that may occur to a device connected to the network as a result
of incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs)
as this may cause noise to be passed to the communication network.
A brief explanation of IP and network submask is made as bellow. There are four sections for an IP
address.
Where:
Equipment address has above relationship described as an equation with section 1 and section 0
of IP address.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each equipment is connected to an exchanger via communication cable and thereby to form a star
The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission
Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform
communication with protection equipment. The standard configuration for the IEC60870 -5-103
protocol is to use a twisted pair EIA RS-485 connection over distances up to 500m. It also supports
to use an Ethernet connection. The relay operates as a slave in the system, responding to
commands from a master station.
Standard: Modicon Modbus Protocol Reference Guide, PI-MBUS-300 Rev.E is also supported by
the equipment through EIA RS-485 interface.
To use the rear port with MODBUS communication, the relay’ s relevant settings must be
configured. To do this use the keypad and LCD user interface. In the submenu “EQUIP SETUP”,
set the parameter [COM1_Protocol] or [COM2_Protocol] as “2”, then set the baud rate of each
rear port.
The IEC60870-5-103 interface over serial port is a master/slave interface with the relay as the
slave device. It is properly developed by NARI-RELAYS.
Initialization (reset)
Time synchronization
General interrogation
Disturbance records
Physical Layer Setup:RS-485, 1 start bit, 8 data bits, even parity, 1 stop bit.
Two EIA RS-485 standardized ports are available for IEC60870-5-103 in this relay. The
transmission speed is optional: 4800 bit/s, 9600 bit/s, 19200 bit/s or 38400 bit/s.
The link layer strictly abides by the rules defined in the IEC60870-5-103.
9.3.2 Initialization
Whenever the relay has been powered up, or if the communication parameters have been
changed, a reset command is required to initialize the communications. The relay will respond to
either of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU
will clear any unsent messages in the relay’
s transmit buffer.
The relay will respond to the reset command with an identification message ASDU 5, the COT
(Cause Of Transmission) of this response will be either Reset CU or Reset FCB depending on the
nature of the reset command.
In addition to the above identification message, if the relay has been powered up it will also
produce a power up event.
The relay time and date can be set using the time synchronization feature of the IEC60870 -5-103
protocol. The relay will correct for the transmission delay as specified in IEC60870-5-103. If the
time synchronization message is sent as a send/confirm message then the relay will respond with
a confirmation. Whether the time-synchronization message is sent as a send confirmation or a
broadcast (send/no reply) message, a time synchronization Class 1 event will be
generated/produced.
If the relay clock is synchronized using the IRIG-B input then it will not be possible to set the relay
time using the IEC60870-5-103 interface. An attempt to set the time via the interface will cause the
relay to create an event with the current date and time taken from the IRIG-B synchronized internal
clock.
The following tables contain a complete listing of all events produced by the relay.
Alarm reports consist of self-check alarm report and equipment operation alarm reports, which are
sent by ASDU1 (time-tagged message).
The GI can be used to read the status of the relay, the function numbers, and information numbers
that will be returned during the GI cycle. The GI cycle strictly abides by the rules defined in the
IEC60870-5-103.
The relay will respond to this GI command with an ASDU 44 message, the cause of transmission
(COT) of this response is 9.
Referring the IEC60870-5-103 standard can get the enough details about general interrogation.
This relay can store up to eight disturbance records in its memory. A pickup of the fault detector or
an operation of the relay can make the relay store the disturbance records.
The generic functions can be used to read the setting and protection measurement of the relay,
and modify the setting. Two supported type identifications are ASDU 21 and ASDU 10. For more
details about generic functions, see the IEC60870-5-103 standard.
INF Semantics
240 Read headings of all defined groups
241 Read values or attributes of all entries in one group
243 Read directory of a single entry
244 Read value or attribute of a single entry
245 General interrogation of generic data
248 Write entry
249 Write entry with confirmation
250 Write entry with execution
251 Write entry abort
INF Semantics
240 Read headings of all defined groups
The IEC60870-5-103 interface over Ethernet is a master/slave interface with the relay as the slave
device. It is properly developed by NARI-RELAYS too. All the service of this relay is based on
generic functions of the IEC60870-5-103. The following table lists all the group number of this relay.
And this relay will send all the relevant information about group caption to the SAS or RTU after
establishing a successful communication link.
Two or three unattached Ethernet ports are available for IEC60870-5-103 in this relay. The
transmission speed is 100M/s.
See Section 9.3.7 “Generic Functions” for more details about the generic functions in
IEC60870-5-103.
9.5.1 Overview
The Modbus protocol is a master/slaver communication protocol, and this device is severed as a
slaver in this system. The detailed information about the Modbus protocol, see the “Modbus
Protocol Reference Guide (PI-MBUS-300 Rev.J)”.
Linker layer configuration: RTU communication mode, ASCII code not supported.
The binary state includes protection element state, device operation state, alarm information state
and binary input state.
The functional code is 04H (Read Input Registers). The analog data include differential protection
measurement, backup protection measurement, restricted earth fault protection measurement and
phase angles.
The functional code is 03H (Read Holding Registers). The settings include equipment settings,
system settings and protection settings.
1) Protection Configuration
2) System Settings
5) S1 EF Prot Settings
6) S2 EF Prot Settings
7) S3 EF Prot Settings
0xb102 I_InstREF_S3 In
0xb103 Slope_PcntREF_S3
0xb104 TrpLog_REF_S3
Bit0: En_InstREF_S3
0xb105 Logic setting
Bit1: En_PcntREF_S3
If this device receives an unidentified message, this device will reply an abnormal information
message to the master device.
The listing below shows the exception codes supported by the equipment.
Chapter 10 Installation
10.1 General
The equipment must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.
Modules and units may only be replaced by correspondingly trained personnel. Always observe
the basic precautions to avoid damage due to electrostatic discharge when handling the
equipment.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
DANGER: Only insert or withdraw the PWR module while the power supply is switched
off. To this end, disconnect the power supply cable that connects with the PWR module.
WARNING: Only insert or withdraw the other boards while the power supply is switched
off.
WARNING: The modules of the RCS-985TS may only be inserted in the slots designated
WARNING: Industry packs and ribbon cables may only be replaced or the positions of
Only hold electronic boards at the edges, taking care not to touch the components.
Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Check that the consignment is complete immediately upon receipt. Notify the nearest
NARI-RELAYS Company or agent, should departures from the delivery note, the shipping papers
or the order be found.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NARI-RELAYS
Company or agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity should not exceed 90% at a
maximum temperature of +55°C; the permissible storage temperature range in dry air is -40°C to
+70°C.
The necessary mounting kits will be provided, including screws, pincers and assembly
instructions.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if RCS-985TS is mounted in cubicles).
The place of installation should permit easy access especially to front of the device, i.e. to the
human-machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1) The location should not be exposed to excessive air pollution (dust, aggressive substances).
2) Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.
The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
WARNING: Excessively high temperature can appreciably reduce the operating life of
the RCS-985TS
The RCS-985TS is made of a single layer 6U height 6”chassis with 6 connectors on its rear panel
(See Figure 5.2). Figure 10.6-1 shows the dimensions of RCS-985TS for reference in mounting.
GR P
ES C
Figure 10.6-1 Dimensions of the RCS-985TS and the cut-out in the cubicle (unit: mm)
NOTE: It is necessary to leave enough space top and bottom of the cut-out in the cubicle
As mentioned former (Chapter 6 “Hardware Description”), five modules are installed in the
enclosure of the RCS-985TS, and these modules must be plugged into the proper slots of the
RCS-985TS respectively. The safety instructions must be abided by when installing the boards,
see 10.2 “Safety Instructions”. Figure 10.6-2 shows the installation way that a module is being
plugged into a corresponding slot.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
NOTE: All these precautions can only be effective if the station ground is of good quality.
The cubicle must be designed and fitted out such that the impedance for RF interference of the
ground path from the electronic device to the cubicle ground terminal is as low as possible.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTE: If the above conditions are not fulfilled, there is a possibility of the cubicle or parts
of it forming a resonant circuit at certain frequencies that would amplify the transmission
of interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 10.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTE: For metallic connections please observe the voltage difference of both materials
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
There is a ground terminal on the rear panel (see Figure 10.7-2), and the ground braided copper
strip can be connected with it. Take care that the grounding strip is always as short as possible.
The main thing is that the device is only grounded at one point. Grounding loops from unit to unit
are not allowed.
There are some ground terminals on some connectors of the RCS-985TS, and the sign is “GND”.
All the ground terminals are connected in the cabinet of this relay. So, the ground terminal on the
rear panel (see Figure 10.7-2) is the only ground terminal of this device.
High frequency currents are produced by interfer ence in the ground connections and because of
skin effect at these frequencies, only the surface region of the grounding strips is of consequence.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
A female connector is used for connecting the wires with it, and then a female connector plugs into
a corresponding male connector that is in the front of one board. For further details about the pin
defines of these connectors, see Chapter 6 “Hardware Description”.
The following figure shows the glancing demo about the wiring for the electrical cables.
01 02
03 04
Tighten 05 06
07 08
09 10
11 12
01
13 14
15 16
17 18
19 20
21 22
23 24
Figure 10.7-4 Glancing demo about the wiring for electrical cables
WARNING: Never allow the current transformer (CT) secondary circuit connected to this
equipment to be opened while the primary system is live. Opening the CT circuit will
produce a dangerously high voltage.
Chapter 11 Commissioning
11.1 General
This relay is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employ a high degree of self-checking and in the unlikely event of
a failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipment’s rating label.
WARNING: Hazardous voltages are present in this electrical equipment during operation.
Non-observance of the safety rules can result in severe personal injury or property
damage.
WARNING: Only qualified personnel shall work on and around this equipment after
becoming thoroughly familiar with all warnings and safety notices of this manual as well
as with the applicable safety regulations.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
The limit values stated in the technical data (Chapter 2) must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
maybe also close commands to the circuit breakers and other primary switches are
DANGER: Current transformer secondary circuits must have been short-circuited before
WARNING: Primary test may only be carried out by qualified personnel, who are familiar
with the commissioning of protection system, the operation of the plant and safety rules
and regulations (switching, earthing, etc.)
Multifunctional dynamic current and voltage injection test set with interval timer
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V
respectively.
NOTE: Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for
insulation resistance test when required);
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
When commissioning a RCS-985TS relay for the first time, sufficient time should be allowed to
become familiar with the method by which the settings are applied. The Chapter 8 contains a
detailed description of the menu structure of this relay.
With the front cover in place all keys are accessible. All menu cells can be read. LED indicators
and alarms can be reset. Protection or configuration settings can be changed, or fault and event
records cleared. However, menu cells will require the appropriate password to be entered before
changes can be made.
These product checks cover all aspects of the relay which should be checked to ensure that it has
not been physically damaged prior to commissioning, is functioning correctly and all input quantity
measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the relay itself via printer or manually creating a setting record.
The RCS-985TS serial feeder protection is fully numerical and the hardware is continuously
monitored. Commissioning tests can be kept to a minimum and need only include hardware tests
and conjunctive tests. The function tests are carried out according to user’
s correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software-based. Tests of
the protection schemes and fault locator require a dynamic test set.
Timers test
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other
external equipment.
On load test
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. Following items listed is
necessary.
Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct
for the particular installation.
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
meeting the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them t o be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
To unplug all the terminals sockets of this relay, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection
In general, the jumpers of the relay have been set correctly before sent to user. While, checking
the jumpers is a good habit before the relay is brought to service. Setting method of the jumpers is
explained in Chapter 6 detailedly.
Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
The relay can be operated from either 110/125Vdc or 220/250Vdc auxiliary supply depending on
the relay’s nominal supply rating. The incoming voltage must be within the operating range
specified in the following table, before energizing the relay, measure the auxiliary supply to ensure
it within the operating range.
It should be noted that the relay can withstand an AC ripple of up to 15% of the upper rated voltage
on the DC auxiliary supply.
WARNING: Energize the relay only if the auxiliary supply is within the specified operating
ranges.
The following groups of checks verify that the relay hardware and software is functioning correctly
and should be carried out with the auxiliary supply applied to the relay.
The current and voltage transformer connections must remain isolated from the relay for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item ”CLOCK”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore when the auxiliary supply is restored the time and date will be correct
and not need to set again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY”should have illuminated and stayed on indicating that
the relay is healthy.
The relay has latched signal relays which remember the state of the trip when the relay was last
energized from an auxiliary supply. Therefore these indicators may also illuminate when the
auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision or current transformer supervison
will not reset at this stage.
Apply the rated DC Power supply and check that the “HEALTHY”LED is lighting in green. We
need to emphasize that the “HEALTHY”LED is always lighting in operation course except that the
equipment find serious errors in it.
Produce one of the abnormal conditions listed in Chapter 4, the “ALARM”LED will light in yellow.
The “TRIP”LED can be tested by initiating a manual circuit breaker trip from the relay. However
the “TRIP” LED will operate during the setting checks (performed later). Therefore no further
testing of the “TRIP”LED is required at this stage.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply current equal to the line current transformer secondary winding rating to each current
transformer input of the corresponding rating in turn, see the following table or external connection
diagram for appropriate terminal numbers, checking its magnitude using a multimeter/test set
readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the relay is 2.5 % or 0.02In,. However an additional allowance must
be made for the accuracy of the test equipment being used.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the relay is 2.5% or 0.1V. However an additional allowance must be
made for the accuracy of the test equipment being used.
This test checks that all the binary inputs on the relay are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using menu item “BI STATE”. Sign “1”denotes an
energized input and sign “0”denotes a de-energized input.
The setting checks ensure that the entire application-specific relay, for the particular installation,
has been correctly applied to the relay.
NOTE: The trip circuit should remain isolated during these checks to prevent accidental
The above tests have already demonstrated that the protection is within calibration, thus the
purpose of these tests is as follows:
To verify the corresponding operating contacts, issued trip reports and LED indicators lit are
correct when a protection element operates.
NOTE: Before each protective function test, its tripping logic setting should be configured
a) Go to Settings menu and check the settings. Make sure that [En_PcntDiff] is “1”.
b) Connect the test set for injection of three-phase current to the current terminals of any
two sides, e.g. side 1 and side 2.
c) Increase the current in any phase until the protection function operates, and at the same
time record the operating current.
d) When protection operates, corresponding signal contacts and tripping contacts (by
configuring trip logic setting [TrpLog_Diff]) can be tested.
NOTE: In order to be transformed into per unit value, the current compensation should be
above the pickup value measured in point 3 above. Repeat test with current injection in
phases B and C respectively.
b) Increase the current in any phase until the protection function operates, and at the same
time record the operating current.
b) Add three phases rated currents at any two sides and cut off any phase current, then
[Alm_CTS_Diff] will be issued. When [Opt_CTS_PcntDiff] is “1”, percent differential
protection will be blocked, otherwise it will operate.
c) The [Alm_CTS_Diff] signal can disappear only by removing all currents and resetting the
equipment.
There are three restricted earth fault protection (also called zero-sequence differential protection)
elements of each side are equipped according to hardware configuration, and they have the
similar logics with the independent settings. Here zero-sequence differential protection of side 1 is
taken as an example.
DANGER: Before restricted earth fault protection of some side is put into operation on
site, polarity of zero-sequence current transformers (CT) on neutral point of the side must
have been checked right by an energizing test of the side of a transformer or a test of
simulating an external fault of the side in primary system. Otherwise a maloperation may
occur during an external earth fault.
WARNING: Before test, please check the hardware configuration and designing scheme
a) Go to Settings menu and check the settings. Make sure that [En_PcntREF_S1] is “1”.
b) Connect the test set for injection of three-phase current to the three-phase current
terminals of side 1 and zero sequence current to the zero sequence CT 3 input terminals.
c) Increase the current in any phase until the protection function operates, and at the same
time record the operating current.
d) When protection operates, corresponding signal contacts and tripping contacts (by
configuring trip logic setting [TrpLog_REF_S1]) can be tested.
NOTE: In order to be transformed into per unit value, the current compensation should be
1
2
3
4
5
c) Check the settings and make sure [En_InstREF] is “1”and instantaneous differential
protection contact is closed.
d) Increase the current in any phase until the protection function operates, and at the same
time record the operating current.
DANGER: Before restricted earth fault protection of some side is put into operation on
site, polarity of zero-sequence current transformers (CT) on neutral point of the side must
have been checked right by an energizing test of the side of transformer or a test of
simulating an external fault of the side in primary system. Otherwise m aloperation may
occur during an external earth fault.
a) Check the settings and make sure [En_PPF_S1] is “1” and phase-to-phase fault
protection contact of side 1 is closed.
c) Increase the current in any phase until the protection function operates, and at the same
time record the operating current.
a) Check the settings and make sure [En_PPF_S1] is “1” and phase-to-phase fault
protection contact of side 1 is closed
c) Make sure the current in any phase is higher than stage 1 of overcurrent setting.
Decrease the phase to phase voltage or increase negative sequence votage of side 2
until the protection function operates and note the operating voltage.
Earth fault protection of side 1, 2 and 3 are almost same, except that direction element is
configured for side 1.
Preparation: Engergize the binary input [EBI_EF_S1].
(1) All stages and delay time of zero sequence overcurrent protection
a) Check the settings and make sure [En_EF_S1] is “1”and disable direction elements of
zero-sequence overcurrent protection of side 1.
b) Increase the current in any phase until the protection function operates, and at the same
time record the operating current.
[Opt_Dir_ROC_S1] is “1”.
c) Make sure the current in any phase is higher than stage 1 of zero-sequence overcurrent
setting. Decrease or increase angle between zero sequence current and zero sequence
voltage until the protection function operates and pay attention to the operating phase.
Phase-to-phase fault protections of side 2 and 3 are similar with similar settings cells. Here
function test of side 2 is taken as an example.
Preparation: Energize the binary input [EBI_PPF_S2].
(1) All stages and delay time of overcurrent protection
a) Check the settings and make sure [En_PPF_S2] is “1” and phase-to-phase fault
protection of side 2 contact is closed.
c) Increase the current in any phase until the protection function operates, and at the same
time record the operating current.
WARNING: Before test, please check the hardware configuration and designing scheme
to ensure earth fault protection of side 3 is equipped in your protection equipment. If this
protective function is not equipped, this test is needed not to be done, otherwise damage
to your equipment maybe occur.
Earth fault protections of side 2 and 3 are similar with similar settings cells. Here function test of
side 2 is taken as an example.
Preparation: Energize the binary input [EBI_EF_S2].
(1) All stages and delay time of zero sequence overcurrent protection
a) Check the setting and make sure [En_CT3_ROC] is “1”. Please note this step checking is
only for earth fault protection of side 3.
d) Increase the current in any phase until the protection function operates and note the
operating current.
c) Increase the zero sequence current via terminal 121-122 until the protection function
operates and pay attention to operating current.
WARNING: Before test, please check the hardware configuration and designing scheme
c) Check the settings and make sure [En_Gap_EF] is “1”and earth fault protection contact
is closed.
d) Increase the zero sequence voltage via terminal 123-124 until the protection function
operates and note the operating voltage.
(1) Configure the logic setting [Cfg_CT_OvLd] to select which side three-phase current channel is
used for the function. If [Cfg_CT_OvLd] is set as “3”, the function is equipped at side 3.
(3) When the current of side 3 is lower than breaker capacity limit setting [I_CCE], CB (circuit
breaker) of side 3 will be tripped with time delay 20 ms. But if the current is higher than the setting,
the relay will trip other breakers according to configured trip logic. Until the current value is below
than 0.85 times breaker capacity limit setting, the CB of side 3 will be tripped.
11.5.3.10 Overload, initiating cooling and on-load tap change blocking tests
(1) Configure the logic setting [Cfg_CT_OvLd] to select which side three-phase current channel is
used for the function. If [Cfg_CT_OvLd] is set as “3”, the function is equipped at side 3.
(3) Check the protections settings and modify them (if needed).
(1) Check the protections settings and modify them (if needed).
(1) Check the protections settings and modify them (if needed).
Check the “RESET”bottom on panel. Please push the “RESET”button to reset “TRIP”LED.
Check whether there are any kinds of reports displayed on LCD of equipment during function test.
Check printing function. Connect printer provided to equipment and push the “PRINT”button to
print last tripping report. Use keypad to select other kinds of reports to print.
In order to acquire the details of protection operation, it is convenient to print the fault report of
protection device. For further details, see section 8.7.3.
1. Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the protection in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and voltage
transformer wiring.
After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the protection in order to perform the
wiring verification tests, it should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’
s has been reset before leaving the protection.
Chapter 12 Maintenance
This relays are self-supervised and so require less maintenance than earlier designs of relay. Most
problems will result in an alarm so that remedial action can be taken. However, some periodic
tests should be done to ensure that the relay is functioning correctly and the external wiring is
intact.
The relay is almost completely self-supervised. The circuits which can not be supervised are
binary input, output circuits and human machine interfaces. Therefore regular testing can be
minimized to checking the unsupervised circuits.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the alarm record.
Failures detected by supervision are traced by checking the “ALM REPORT”screen on the LCD.
See section 8.3.3 “Display under Abnormal Condition”for the details of the alarm events.
If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, CPU, BO) and
hardware type-form as the removed module. Furthermore, the CPU module replaced should have
the same software version. And the AI and PWR module replaced should have the same ratings.
WARNING: Units and modules may only be replaced while the supply is switched off and
only by appropriately trained and qualified personnel. Strictly observe the basic
precautions to guard against electrostatic discharge.
WARNING: When handling a module, take anti -static measures such as wearing an
earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many
of the electronic components could suffer damage. After replacing the CPU module,
check the settings.
DANGER: After replacing modules, be sure to check that the same configuration is set as
before the replacement. If this is not the case, there is a danger of the unintended
operation of switchgear taking place or of protections not functioning correctly. Persons
may also be put in danger.
13.1 Decommissioning
To switch off the RCS-985TS, switch off the external miniature circuit breaker of the power supply.
DANGER: Before disconnecting the power supply cables that connected with the PWR
module of the RCS-985TS, make sure that the external miniature circuit breaker of the
power supply is switched off.
DANGER: Before disconnecting the cables that are used to connect analog input module
with the primary CTs and VTs, make sure that the circuit breaker for the primary CTs and
VTs is switched off.
13.1.3 Dismantling
The RCS-985TS rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
DANGER: When the station is in operation, make sure that there is an adequate safety
13.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
NOTE: Strictly observe all local and national regulations when disposing of the device.
Software Manual
Source Documentation
Version Version
RCS-985TS
V 1.00 V0.99 RCS-985TS_Instruction_Manual_Standard_V1.00.doc
V 2.10
RCS-985TS_B V1.01 V1.00 RCS-985TS_Instruction_Manual_Standard_V1.01.doc
V2.10-080716 V1.02 V1.01 RCS-985TS_Instruction_Manual_Standard_V1.02.doc
Manual
Section Page No. Description of change Note
Version
Manual
Section Page No. Description of change Note
Version