SECTION 15410 Plumbing Fixtures Rev 0
SECTION 15410 Plumbing Fixtures Rev 0
SECTION 15410 Plumbing Fixtures Rev 0
0 . ~I
~~_. \\ W\J~)U ~~\~\~\W~\yJ\
SECTION 15410:
KINGDOM
OFSAUDIARABIA ~~~I 4J.~1~I
forJubail&Yanbu
RoyalCommission ~4 W ~144fJ1
SECTION 15410
PLUMBING FIXTURES
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.03 REFERENCES..................................................................................................... 2
1.04 SUBMITTALS....................................................................................................... 3
2.02 LAVATORIES....................................................................................................... 7
2.03 SINKS................................................................................................................. 10
2.06 URINALS............................................................................................................ 21
3.04 INSTALLATION.................................................................................................. 29
3.10 TESTING............................................................................................................ 35
PART 1 GENERAL
A. This Section covers the furnishing and installation of all plumbing fixtures and trims
including all carriers, supports, anchors and accessories, in the location and
quantities shown on the Contract Drawings.
A. Lavatories
B. Sinks
C. Bidets
D. Water Closets
E. Urinals
H. Level Drains
I. Fixture Supports
A. Furnishing, installation, testing and bringing systems into full satisfactory operational
conditions of the plumbing fixtures and trims.
B. The Contractor shall furnish all labor, materials, tools and equipment required to
make the work complete and ready.
C. The Contractor shall provide all services, storage tanks, fill and refill mediums,
chemicals and all whatever other materials required for testing, commissioning and
start ups.
D. This Section shall be read in conjunction with SECTIONS 15051 and 15055.
1.05 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials, products and workmanship. In case of conflict between these
standards and the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment, materials and
processes conforming to one group of codes and standards.
2. Chapter 2 Environmental
4. Chapter 6 Mechanical
7. ANSI A112.19.5 Trim for Water Closet Bowls, Tanks and Urinals
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
1. Product Data
2. Samples
a) Submit 3 color samples, where other than white fixtures are proposed.
3. Shop Drawings showing the proposed method of installation for all fixtures.
4. Manufacturer's Instructions
5. Maintenance Data
6. Warranty
A. The Contractor shall be responsible for the quality of Work and shall develop and
propose programs and methods of construction and testing such as to achieve the
specified quality to the approval of the Royal Commission in accordance with
SECTION 01450.
B. Quality Assurance
1. Manufacturer’s Qualifications
C. Regulatory Requirements
D. Mock-Up
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
3. Store all fixtures in an upright position, above ground and in a dry place.
4. Trim and accessories shall also be stored above ground in a dry place.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
C. All fixtures shall be of manufacturer's standard, selected from the top half of the
product line and shall not be "factory close-out," "end of the product model," or
otherwise discontinued models.
D. Each fixture and device shall have indelibly product name marked on it.
E. Vitreous ware for the fixtures shall be first-quality, non-absorbent china, of even color
and unwrapped.
F. Enamel ware shall be constructed of smooth, sound, iron castings, properly finished
and provided with first-quality high-temperature enamel.
G. Provide all products from a single manufacturer, where feasible and unless otherwise
noted.
H. All dimensions given here below are tentative and approximate nominal.
J. Although this part is structured for easy selection of fixtures, it will nevertheless be
necessary to refer to the manufacturer's printed catalog (or CD-ROM equivalent) for
exact, dimensions, shapes and colors other than white.
M. All fixtures color shall be white, unless otherwise noted. All matching color shall be
selected by the Royal Commission.
N. All fixtures shall be provided complete with faucets, water supplies, drains, fittings,
accessories and necessaries for complete, operational installation.
O. Fittings for fixtures shall be of heavy red brass castings, properly finished and
chrome plated.
Q. All exposed piping and tubing, when applicable, shall be of red brass, chrome plated.
2.02 LAVATORIES
A. General
b) Vitreous china.
b) Vitreous china.
d) Self-closing faucets.
e) Faucets shall be chromium plated brass with red and blue indicators for
hot and cold water or single lever type.
3. Accessories
4. Maximum Flow
a) All faucets shall have maximum flow rate of 9.5 L/m (2.5 gallons per
minute) flow.
b) All lavatory faucets in public facilities shall have a maximum flow rate of
5 L/m.
1. Features
b) Soap depression.
c) Faucet ledge.
2. Product Specifications
3. Faucets
a) Features
1) Combination lavatory faucet.
2) Washerless ceramic disc valve cartridge.
3) One piece body.
4) Water aerator.
5) Indexed handles.
b) Product Specifications
1) Configuration: Center-set or single-hole.
2) Base Material: Brass.
3) Finish Appearance Type: Metallic.
4) Finish Material: Chrome.
4. Accessories
C. Lavatory, Countertop
1. Features
2. Product Specifications
3. Faucets
a) Features
1) Combination lavatory faucet.
2) One piece body.
3) Water aerator.
4) Indexed handles.
b) Product Specifications
1) Configuration: Center-set or single-hole.
2) Base Material: Brass.
3) Finish Appearance Type: Metallic.
4) Finish Material: Chrome.
5) Generic Finish: Polished.
6) Handle Type: Knob or round.
7) No. of Handles: 2 or 1.
8) Spout Type: Standard.
9) Meets Standards: Dimensions and hydraulic performance meet or
exceed ANSI A112.18.1 requirements.
10) Parts Included: Spout, handles, pop-up drain and valve.
4. Accessories
2.03 SINKS
1. Features
a) Double Bowl.
e) Underside undercoated.
h) One bowl made for use with food waste disposers, where applicable,
and the other bowl recessed and pierced for a basket strainer.
2. Product Specifications
g) No. of Bowls: 2.
3. Faucets
a) Features
1) Combination lavatory faucet.
2) Wall or sink mounted.
3) One piece body.
4) Widespread, swivel spout.
b) Product Specifications
1) Configuration: Center-set or single-hole.
2) Base Material: Brass.
3) Finish Appearance Type: Metallic.
4. Accessories
1. Same as residential kitchen, but sink shall be 68 L (34 L each) water capacity.
1. Features
e) 254 mm (10 in.) backsplash, includes 25 mm upturn and tile edge; and
rolled rims top.
2. Product Specifications
h) No. of Bowls: 3.
3. Faucets
a) Features
1) Combination lavatory faucet.
2) Extra heavy duty faucet.
3) One piece body.
4) Wall or sink mounted.
5) Widespread, swivel spout minimum 250 mm long swing spout
aerator tip.
b) Product Specifications
1) Base Material: Brass.
2) Finish Appearance Type: Metallic.
3) Finish Material: Chrome.
4) Generic Finish: Polished.
5) Configuration: Widespread.
6) Handle Type: Lever type.
7) Spout Type: High arc.
8) Meets Standards: ANSI A112.18.1M.
4. Accessories
a) Supply Assemblies
1) All chrome plated.
2) 13 mm (½ in.) angle stop valve and handle, 13 mm male threaded
inlet tube.
3) 13 mm flexible tube riser.
4) Inlet escutcheon.
b) Sink Drain
1) Perforated open strainer.
2) 38 mm (1½ in) chrome plated cast brass P-trap with bottom
cleanout and plug.
3) 38 mm (1½ in.) chrome finish tubing to wall.
4) Chrome finished nuts.
5) Escutcheon plate.
D. Service Sink
1. Features
b) Single compartment.
2. Product Specifications
3. Faucets
a) Features
1) Single spout, with pail hook and hose end, and top wall brace.
2) Short spout. Assembly shall project maximum of 125 mm from
face of wall.
3) With vacuum breaker.
4) Integrated stops.
5) 13 mm (½ in) female union eccentric coupling inlet and 19 mm
(¾ in) male hose threads outlet.
b) Product Specifications
1) Configuration: Backsplash or wall mounted.
2) Base Material: Brass.
3) Finish Material: Rough chrome plated.
4) Spout Type: Standard.
5) Handle Type: Lever or cross.
6) No. of Handles: 2.
7) Meets Standards: Dimensions and hydraulic performance meet or
exceed ASME/ANSI A112.18.1M requirements.
8) Parts Included: Spout, handles, wall brace and service stop.
4. Accessories
1. Features
a) One piece.
b) Single compartment.
2. Product Specifications
3. Faucets
a) Features
1) Same as service sink faucet but wall-mounted and spout to match
mop sink size.
4. Accessories
2.04 BIDETS
1. Features
2. Product Specifications
d) Configuration: One-piece.
3. Faucets
a) Features
1) Horizontal bidet faucet.
b) Product Specifications
1. General
2. Features
d) Quiet flush.
3. Product Specifications
e) Configuration: Two-piece.
h) Gallons Per Flush (GPF): Maximum 3.5 gallons (13.2 L) per flush.
4. Tanks
5. Accessories
a) Seat
1) Heavy duty.
2) Injection molded high impact solid plastic.
3) Stain and chemical resistant.
4) Integrally molded permanent color-match bumpers.
5) Elongated or round open front model.
B. Eastern Type
1. Acid resisting porcelain enameled finish interior and top or white vitreous
china.
4. Water conserving flush type with sealable integral flat bottom anchor and
support flange.
5. Bonded combination integral squatting floor plate with non-skid foot threads
and anti-splash flushing rim with 32 mm back spud inlet connection.
7. Toilet shall be supplied with cast iron low-profile hub inlet P-trap with porcelain
enameled interior finish and 50 mm seal. P-trap shall also have vent
connection and compression gasket shall be supplied with trap for installation.
a) Tank
1) High-level wall mounted; vitreous china, plastic or other approved
material complete with float assembly, pull chain, flush pipe and
connector. The plastic flush pipe shall be protected against
damage.
b) Perineal spray faucet shall be same as for western type water closet,
except that the mounting height above floor shall be 400 mm.
2.06 URINALS
1. Features
2. Specifications
3. Flush Valves
a) Features
1) Quiet, exposed urinal flushometer.
2) No leak handle feature.
3) Dual seal diaphragm with a clog resistant by-pass.
4) 19 mm (¾ in.) screwdriver back-check angle stop.
b) Product Specifications
1) Valve Type: Diaphragm-type flushometer valve.
2) Base Material: Brass.
3) Finish Material: Chrome plated.
4) Generic Finish: Polished exterior.
5) Handle Type: Oscillating, non-hold-open handle.
6) Installation Type: Wall mounted.
7) Meets Standards: Dimensions and hydraulic performance meet or
exceed ANSI A112.18.1M requirements.
8) Parts Included: Wall flange, spud coupling and flange for top spud
connection, cover tube, cast set screw and sweat solder adaptor.
A. Bathtubs
1. General
2. Features
3. Product Specifications
g) Shape: Rectangular.
4. Accessories
B. Shower Pans
1. Features
a) Non-slip surface.
2. Product Specifications
e) Shape: Square.
f) Configuration: One-piece.
i) Parts Included: Integral 3-sided, double tiling edge with water retention
flange; shower drain with stainless steel drain plate.
a) Features
1) Adjustable showerhead, with cast brass arm and flange.
2) Diverter tub spout.
3) Metal lever handle.
4) Brass wall escutcheon, polished chrome finish.
b) Product Specifications
1) Showerhead Arm and Flange: Cast brass, chrome plated finish.
2) Wall Escutcheon: Brass, chrome plated finish.
3) Handle: Metal indexed lever.
4) Spout: Cast brass, chrome plated finish.
5) Base Material: Brass.
6) Finish Appearance Type: Metallic.
7) Finish Material: Chrome.
8) Generic Finish: Polished.
9) Handle Type: Lever handle, ergonomic handle or as selected by
the Royal Commission.
10) No. of Handles: 2 or 1.
11) Spout Type: Diverter tub spout.
12) Meets Standards: Dimensions and hydraulic performance meet or
exceed ANSI A112.18.1M requirements.
a) Features
1) Pressure balancing valve type.
b) Product Specifications
1) Valve Body: Cast brass.
2) Valve Cartridge: Ceramic disc.
3) Connection Type: Female thread or direct sweat inlets/outlets.
4) Codes and Standards: Products meet or exceed
ANSI A112.18.1M.
A. Features
1. Wall-mounted.
B. Product Specifications
A. Floor Drains
2. Floor drains shall be 2-piece cast iron body with seepage flange, reversible
clamping collar, positioning set screws and adjustable polished brass strainer.
3. All floor drains connected to the sanitary system shall be provided with traps.
B. Roof Drains
2. Roof drains shall be cast iron with medium sump and flange, bottom outlet,
removable beehive dome and bolted flashing clamp device integral with gravel
stop.
A. All wall hung plumbing fixtures shall be furnished with the fixture manufacturer's
standard chair carriers or wall hangers furnished with the fixtures.
B. The Contractor shall furnish all necessary bolts and fittings required for a complete
installation.
A. Features
3. High capacity.
4. Compressor cooling capacity shall be 64 L/hr (17 gallon per hour) from 32.2 to
10°C (90 to 50°F) in a maximum ambient temperature of 32.2°C (90°F)
(indoor) and 48.9°C (120°F)(outdoor) installation.
B. Cooler Specifications
1. Cabinet
2. Bubbler
b) Anti-squirt design.
3. Cooling Package
4. Refrigeration System
5. Electrical Connections
6. Controls
a) All stainless steel tank, with stainless steel immersion coil evaporator,
tested at 1724 KPa (250 psi) for 862 KPa (125 psi) working pressure.
b) 7.5 L (2 gallon) storage to meet peak demand and to ensure long cycle
and long life machine operation.
PART 3 EXECUTION
3.01 GENERAL
A. All fixtures shall be free from imperfections, true as to line, angles, curves and color;
smooth, watertight, complete in every respect.
A. Check that fixtures are complete with trim, faucets, fittings and other specified
components.
B. Inspect installed fixtures for damage. Replace damaged fixtures and components.
C. Test installed fixtures after water systems are pressurized and demonstrate proper
operation.
A. Inspection
1. Verify that walls and floor finishes are prepared and ready for installation of
fixtures.
2. Verify that piping, rough-ins and wiring are installed and in the right location.
4. Confirm that millwork is constructed with adequate provision for the installation
of counter top lavatories and sinks.
B. Preparation
3.04 INSTALLATION
A. Supports
3. Furnish and set all hangers, supports, brackets, etc., for proper installation of
all fixtures and equipment.
4. The Contractor shall be responsible for stability of all fixtures and furnishing all
chair carriers or other materials necessary to accomplish this.
9. If not factory primed or coated, prime all concealed supports with 1 coat of
rust-resistant primer.
B. Fixtures
1. All fixtures and equipment shall be mounted level, plumb, sure, rigid and flush
with wall or floor as appropriate.
2. Provide required trim including chrome plated rigid or flexible supplies, loose-
keyed stops, reducers, wastes, traps and floor and wall escutcheon plates.
5. Exception
7. Install each fixture with trap, easily removable for servicing and cleaning. Omit
traps on fixtures having integral traps. Omit traps on indirect wastes, except
where otherwise noted.
10. All fixtures shall be left thoroughly clean and free from all marks and foreign
substances.
11. The Contractor shall replace all leaky faucets and valves prior to initial
acceptance.
13. All trim shall be permanently stamped with manufacturer's identification visible
after installation.
14. Caulk around all fixtures and adjacent wall and floor surfaces with a white, or
color to match fixture, silicone sealant fungicidal type.
15. Set shower receptors and mop basins in leveling bed of cement grout.
16. Solidly attach water closets to floor with lag screws. Lead flashing is not
intended to hold fixture in place.
1. The unit shall be provided with a shut-off stop valve and a minimum 32 mm
P-trap with cleanout for through the wall discharge. It shall be indirectly
connected to the drainage line with vent.
2. Electrical Connections
A. Shut off valves shall be supplied for each fixture, at entrances of buildings and to all
equipment and controls.
C. Install unions on one side of all valves, equipment connections and elsewhere as
shown or required for ease of service and/or installation, unless flanges are
indicated.
E. Caulk around all plumbing fixtures with white silicone epoxy type, non-hardening
compound, where fixtures meet floor or wall as required to present a finish
appearance. See SECTIONS 07910 and 07920.
F. Set shower receptors and janitor receptors in a leveling bed of cement grout and lead
pan.
A. General
1. Unless otherwise noted, install fixtures to heights above finished floor and
sizes as indicated.
B. Fixture Heights
1. Water Closet
2. Urinal
3. Lavatory
4. Drinking Fountain
5. Shower Heads
7. Wash Fountains
c) Vent: 50 mm (2 in.).
c) Vent: 50 mm (2 in.).
3. Bidet
b) Waste: 50 mm (2 in.).
b) Waste: 50 mm (2 in.).
6. Lavatory
7. Sink
8. Service Sink
c) Waste: 50 mm (2 in.).
c) Waste: 80 mm (3 in.).
11. Bathtub
12. Shower
2. Confirm location and size of fixtures and openings before rough-in and
installation.
B. Accessibility
C. Rough-Ins
D. Adjusting
1. Operate and adjust faucets, controls and any other equipment, as applicable.
5. Adjust intended water flow rate to comply with manufacturer’s rating of the
fixture, without splashing, noise or overflow.
6. Adjust all flush valves, where applicable, for quiet operation, minimum
pressure required to cleanse bowls and period of flush.
E. Equipment Grounding
3.10 TESTING